Está en la página 1de 9

CENTUM VP FAST/TOOLS Graphic Converter

Instruction book

Revision 0.1
Abstract
This document describes the how to use the Graphic converter of Centum VP to FAST/TOOLS.

Date: 31 October, 2012

Rev.

Date

Description

Written by

Reviewed by

Approved by

17/02/2012

Initial Version

N.Yoshima

R.Sugiyama

0.1

31/10/2012

Link Parts

N.Yoshima

R.Sugiyama

Yokogawa Electric Corporation


Document number: GSC-T-20120217-01

Graphic converter instruction book

Table of contents
1. Introduction ........................................................................................................................................... 2
2. Preparation............................................................................................................................................ 3
3.Conversion Command............................................................................................................................ 5
4. Active on FAST/TOOLS ........................................................................................................................ 7
5. Restriction ............................................................................................................................................. 8

Page 1 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

Introduction

This book explain how to use graphic converter of Centum VP to FAST/TOOLS graphic.
The version of FAST/TOOLS is needed R9.04 or later. The version of Centum VP is required 5.01.
Next shows the example of conversion by this converter.
Centum Graphic

FAST/TOOLS Graphic

Page 2 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

Preparation
2.1 CENTUM VP
To convert CENTUM graphic to FAST/TOOLS graphic, next data file is required.
-

CentumVP graphic file

Mapping file of VP tag to FT item

The File path of CENTUM graphic is below. Those graphic is automatically saved in this file
path when graphic is generated in standard graphic builder.

Page 3 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

The format of Mapping file VP tag to FT item is CSV text file. Contents should be same
style as bellow like Centum TAG, data type, and FAST/TOOLS Item.
TI002H.PV
TI002M.PV
TI002L.PV
TI002.PV
LI002.PV
FLOW001.PV
TANK001.PV
TANK001.PL
TANK001PH
PUMP-A1.PV
TANK002.PV
TANK002.PL
TANK002PH

real
real
real
real
real
real
real
real
real
Boolean
real
real
real

INST-1.UNIT-1.TI002H_PV
INST-1.UNIT-1.TI002M_PV
INST-1.UNIT-1.TI002L_PV
INST-1.UNIT-1.TI002_PV
INST-1.UNIT-1.LI002_PV
INST-1.UNIT-1.FLOW001_PV
INST-1.UNIT-1.TANK001_PV
INST-1.UNIT-1.TANK001_PL
INST-1.UNIT-1.FLOW001_PH
INST-1.UNIT-1.PUMP-A1_PV
INST-1.UNIT-1.TANK002_PV
INST-1.UNIT-1.TANK002_PL
INST-1.UNIT-1.TANK002_PV

2.2 FAST/TOOLS
For the preparation of FAST/TOOLS, the items on Mapping file VP tag to FT item should be
generated in FAST/TOOLS. To do this, FAST/TOOLS engineering module is required to use.
Next is display of FAST/TOOLS engineering module.

TI002H.PV
TI002M.PV
TI002L.PV
TI002.PV
LI002.PV
FLOW001.PV
TANK001.PV
TANK001.PL
TANK001PH
PUMP-A1.PV
TANK002.PV
TANK002.PL
TANK002PH

real
real
real
real
real
real
real
real
real
Boolean
real
real
real

INST-1.UNIT-1.TI002H_PV
INST-1.UNIT-1.TI002M_PV
INST-1.UNIT-1.TI002L_PV
INST-1.UNIT-1.TI002_PV
INST-1.UNIT-1.LI002_PV
INST-1.UNIT-1.FLOW001_PV
INST-1.UNIT-1.TANK001_PV
INST-1.UNIT-1.TANK001_PL
INST-1.UNIT-1.FLOW001_PH
INST-1.UNIT-1.PUMP-A1_PV
INST-1.UNIT-1.TANK002_PV
INST-1.UNIT-1.TANK002_PL
INST-1.UNIT-1.TANK002_PV

Mapping file VP tag to FT item

Page 4 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

Conversion command
3.1 Installation conversion program
Copy the next conversion program on the any file directory.

3.2 Execute the conversion command


Execute the conversion command from DOS prompt like bellow on same directory with the
place of conversion programs. Conversion command should be executed one by one with
Centum graphics.
>FTGraphicConverter s Source File d Destination Folder l Mapping File
Next is the example.
>FTGraphicConverter -s
C:CENTUMVPengBKProjectYO1-1HIS0164WINDOWYOTES001.edf
-d "C:Documents and Settings00110817source"
-l "C:Documents and Settings00110817sourcemapping.csv"
After executed conversion command, conversion result (.xml file & image file) will be
generated on destination folder. The result folder has 2 folders. One is Displays for xml file.
And other is Icons for image file.
If some error is happened, the log file is generated on same file folder of graphic command
programs. If some error message is shown on DOS display, please refer log file.

Page 5 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

3.3 Copy the conversion graphic to FAST/TOOLS


To use result of conversion on the FAST/TOOLS, it is needed to copy graphic file (.xml) and
image file to FAST/TOOLS directory correctly.
Next is the file directory of graphic converter destination and FAST/TOOLS graphics.

Copy

C:UsersPublicYokogawatlswap
cfgoperatorInterfacesDEPLYdisplays

Copy

C:UsersPublicYokogawa
tlswapcfgicons

Page 6 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

Activate on FAST/TOOLS
To activate the conversion graphic on FAST/TOOLS, validation is required on FAST/TOOLS
graphic editor. Next display shows the validation button on FAST/TOOLS graphic editor.
(Tools->Validate)

Validate Button

If linkage error is showed on editor, it is required to modify the graphic manually on the
editor.

Page 7 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

Graphic converter instruction book

Restriction
5.1 Restriction function
On the next table, Future Implementation and Not Possible column shows the restriction
of current conversion tool.

5.2 Link parts


If the graphic have link parts, it is required to removing the group property to all link parts
on Centum graphic builder.

Remove the group property

Page 8 of 9
Yokogawa Electric Corporation
Document number: GSC-T-20120106-01

También podría gustarte