Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Extract Pages From V265 en M A012-1
Extract Pages From V265 en M A012-1
5.
5 Protection functions
Protection functions
Each protection stage can independently be enabled or disabled
according to the requirements of the intended application.
5.1.
5.2.
46
IEC symbol
Function name
Overcurrent protection
Differential overcurrent protection
Current unbalance protection
Thermal overload protection
Earth fault protection
Second harmonic O/C stage
Fifth harmonic O/C stage
Circuit-breaker failure protection
Programmable stages
Optional arc fault protection
V265/EN M/A012
5 Protection functions
5.6.
K1
I2
IN
t
=
K1 =
I2
=
IN
K2
=
=
, where
2
2
Operation time
Delay multiplier
Measured and calculated negative sequence phase
current of fundamental frequency.
Rated current
Pick-up setting I2> in pu. The maximum allowed degree
of unbalance.
Example:
K1 = 15 s
I2
= 22.9 % = 0.229 xIN
K2 = 5 % = 0.05 xIN
15
2
0.229
2
0.05
1
300.4
V265/EN M/A012
61
5 Protection functions
Setting groups
There are two settings groups available. Switching between
setting groups can be controlled by digital inputs, virtual inputs
(mimic display, communication, logic) and manually.
Figure 5.6-1. Inverse operation delay of current unbalance stage I2>. The
longest delay is limited to 1000 seconds (=16min 40s).
62
V265/EN M/A012
5.8.
5 Protection functions
t ln
I IP
I 2 a2
Alarm:
Trip:
a k k I MODE
Release time:
I
t C ln 2 P 2
a I
Trip release:
a 0.95 k I MODE
Start release:
ln
I
=
=
=
=
Operation time
Thermal time constant tau (Setting value)
Natural logarithm function
Measured rms phase current (the max. value of three
phase currents)
Ip
Imode
C
=
=
70
V265/EN M/A012
5 Protection functions
I MAX k k I N
The value of ambient temperature compensation factor k
depends on the ambient temperature AMB and settings IMAX40 and
IMAX70. See Figure 5.8-1. Ambient temperature is not in use when
k = 1. This is true when
IMAX40 is 1.0
Samb is n/a (no ambient temperature sensor)
TAMB is +40 C.
V265/EN M/A012
71
5 Protection functions
72
V265/EN M/A012
7 Measurement functions
7.2.
THD
h
i 2
h1
2
i
, where
h1
= Fundamental value
h2...15 = Harmonics
Example
h1
= 100 A
h3
= 10 A
h7
=3A
h11
=8A
THD
10 2 32 8 2
13.2%
100
7.3.
RMS values
RMS currents
Relay calculates the RMS value of each phase current. The
minimum and the maximum of RMS values are recorded and
stored.
I rms I f 1 I f 2 ... I f 15
2
V265/EN M/A012
125
10 Applications
10.
Applications
10.1.
V265/EN M/A012
159
10.2.
10 Applications
160
V265/EN M/A012
10 Applications
10.2.1.
CT Requirements
Any difference between the CTs will give a misleading residual
current signal to the relay. Especially during heavy through faults
(i.e. the fault is outside the protected zone) the dissimilar
saturation of the CTs should not yield to a REF trip. On the other
hand a very high fault current causing an unselective earth fault
start or trip is not a fatal error.
Class X CT
In restricted earth fault protection the high and low side CTs
should give similar responses even for high over currents.
Class X CTs will fulfil this requirement. Their performance is
defined in terms of a knee-point voltage (VKP), the magnetizing
current at the knee point voltage and the resistance of the
secondary winding at +75 C.
Knee point voltage (VKP) is the secondary voltage at which a 50 %
increase of primary current is needed to increase the secondary
voltage by 10 %.
V265/EN M/A012
161
10 Applications
10.3.
10.3.1.
VS I MAXT
IMAXT
CTSEC
CTPRI
RCT
RW
CTSEC
RCT RW
CTPRIM
=
=
=
=
=
RS
VS
I Set
Selecting a low value helps to achieve more sensitivity and helps to avoid the
usage of a voltage limiting VDR. An unselective earth fault pick-up/trip is not
always a problem if a fast overcurrent stage will clear the fault anyway.
162
V265/EN M/A012
10 Applications
10.3.2.
Voltage limitation
During heavy inside faults the voltage in the secondary circuit may
rise to several kilovolts depending on the fault currents, CT
properties and the stabilizing resistor RS. If the secondary voltage
would exceed 2 kV it should be limited using a voltage dependent
resistor (VDR).
The peak voltage according a linear CT model is:
Equation 10.3.2-1
Vp I MAXF
CTSEC
BCT RW RS
CTPRIM
IMAXF
CTSEC
CTPRI
RCT
RW
RS
=
=
=
=
=
VP
10.3.3.
V265/EN M/A012
163
10.3.4.
10 Applications
Example
CT
IMAXT
IREF
= 2000/1
= 16 kA = 8 x In
= 5 % = 50 mA
VKP = 100 V
Setting value scaled to secondary
level
RCT
= 6
RW
= 0.4
IMAXF = 25 kA
Maximum secondary voltage during a through fault (Equation
10.3.1-1):
1
VS 16000
6 0.4 51.2 V
2000
Conclusion: The knee point voltage of 100 V is acceptable being
about twice the VS.
Serial resistance for the relay input (Equation 10.3.1-2):
512
.
RS
1024 1000
0.05
Maximum peak voltage during inside fault using a linear model for
CT (Equation 10.3.2-1):
1
Vp 25000
(6 0.4 1000) 12.6 kV
2000
Approximation of peak voltage during inside fault using a nonlinear model for a saturating CT (Equation 10.3.2-2):
164
V265/EN M/A012
10 Applications
10.4.
10.4.1.
Composite error C
Composite error is the difference between the ideal secondary
current and the actual secondary current under steady-state
conditions. It includes amplitude and phase errors and also the
effects of any possible harmonics in the exciting current.
Equation 10.4.1-1
T
1
( K N i S i P ) 2 dt
T 0
C
T
KN
iS
iP
IP
V265/EN M/A012
IP
=
=
=
=
=
100%
Cycle time
Rated transformation ratio INPrimary/INsecondary
Instantaneous secondary current
Instantaneous primary current
Rms value of primary current
165
10 Applications
NOTE: All current based protection functions of VAMP relays, except arc
protection, thermal protection and 2nd harmonic blocking functions, are
using the fundamental frequency component of the measured current.
The IEC formula includes an RMS value of the current. That is why the
composite error defined by IEC 60044-1 is not ideal for VAMP relays.
However the difference is not big enough to prevent rough estimation.
Amplitude error
at rated primary
current
(%)
Phase displacement
at rated primary
current
()
5P
10P
1
3
1
-
Composite error
C at rated
accuracy limit
primary current
(%)
5
10
Marking:
The accuracy class of a CT is written after the rated power.
E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20
Accuracy limit current IAL
Current transformers for protection must retain a reasonable
accuracy up to the largest relevant fault current. Rated accuracy
limit current is the value of primary current up to which the CT will
comply with the requirements for composite error C.
Accuracy limit factor kALF
The ratio of the accuracy limit current to the rated primary current.
Equation 10.4.1-2
K ALF
I AL
IN
The standard accuracy limit factors are 5, 10, 15, 20 and 30.
166
V265/EN M/A012
10 Applications
Marking:
Accuracy limit factor is written after the accuracy class.
E.g. 10 VA 5P10, 15 VA 10P10, 30 VA 5P20.
The actual accuracy limit factor kA depends on the actual burden.
Equation 10.4.1-3.
k A k ALF
kALF
Si
=
=
SN
SA
=
=
Si S N
Si S A
Accuracy limit factor at rated current and rated burden
Internal secondary burden. (Winding resistance RCT in Figure
10.4.1-1)
Rated burden
Actual burden including wiring and the load.
V265/EN M/A012
167
10.4.2.
10 Applications
kA c I
SET
c
ISET
INTra
INCT
=
=
=
=
I NTra
I NCT
Safety factor
Relative setting of the non-stabilized differential current stage
Rated current of the transformer (primary side or secondary side)
Rated primary current of the CT (primary side or secondary side)
Using slightly smaller safety factor than indicated in the table will
increase the setting inaccuracy.
Protection application
Overcurrent
Earth-fault, cable transformer
Earth-fault overcurrent, sum of three phase currents
Transformer differential, -winding or unearthed Ywinding
Transformer differential, earthed Y-winding
Generator differential
Safety factor c
2
3
6
3
4
3
168
V265/EN M/A012
10 Applications
k A k ALF
RCT RN
RCT RW RL
=
=
=
=
=
cI I
2
S N SET NTra RCT RW RL RCT I NCT
sec
k ALF I NCT
V265/EN M/A012
169
10 Applications
Example 1
Transformer:
16 MVA YNd11 Zk = 10%
110 kV / 21 kV (84 A / 440 A)
CTs on HW side:
100/5 5P10
Winding resistance RCT = 0.07
(RCT depends on the CT type, INCT and power rating. Let's say that the
selected CT type, 100 A and an initial guess of 15 VA yields to 0.07 .)
Safety factor c = 4.
(Transformer differential, earthed Y.)
CTs on LV side:
500/5 5P10
(Max. Short circuit curent is 4400 A = 8.8 x 500 A)
Safety factor c = 3.
(Transformer differential, .)
Differential current setting of the non-stabilized stage I>>: ISET = 9
x IN
RL
RWHV
RWLV
SN
0.07 0.138 0.008 0.07 5 2 14.6 VA
10 100
SN
0.28 0.086 0.008 0.28 5 2 15.2 VA
10 500
170
V265/EN M/A012