Upsilon STS
800A-900A1000A-1200A
Source prioritaire
UPS galaxy
salle 14
deuxime tage,
Source secours
UPS galaxy
salle
deuxime tage,
13
= 0
Q1
Q2BP
Q3
D E R
V I
O
R
T H E
U N
I N
T E
R
34003641FR/AA
- Page 1
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical applications.
The Upsilon STS range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features of your Upsilon STS.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Upsilon STS range, we invite
you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
Environment
MGE UPS SYSTEMS pays great attention to the environmental impact of its products throughout their life cycle by following
an eco-design process covering the design, use and recycling of the Upsilon STS.
Pictograms used
Document
Display
Important instructions
that must be followed
Up / down selection
Other selection
Visual indication
Confirm
Increase
Action
Details
Reduce
Audio indication
Scrolling menu
Save
LED off
Graphic display
Enter characters
LED flashing
Graphic display
Phase-to-neutral measurements
LED on green
Graphic display
Phase-to-phase measurements
LED on orange
LED on red
Earth cables
Other cables
88.8
8.88
E
S
C
D
E
L
VOLT
Digital display
17
mai
STOP
Transfer
Delete
Alarm
Access to measurements
Buzzer off
0101
1010
0101
Status conditions
Settings
Maintenance
Note: LEDs and switches are represented in their rest position. Transient conditions are indicated by dotted arrows.
34400847FR/AA
- Page 2
Contents
1.
2.
Presentation
1.1
1.2
1.3
1.4
1.5
Installation
2.1
Positioning ................................................................................................................................... 9
2.2
2.3
2.4
2.5
3.
Operation
3.1
Start-up ...................................................................................................................................... 16
3.2
Shutdown.................................................................................................................................... 17
3.3
4.
5.
3.4
3.5
3.6
Maintenance
4.1
Identification of anomalies........................................................................................................ 23
4.2
Environment
Environmental protection, end of life recycling and packing recycling......................................... 25
6.
Appendix
6.1
Technical specifications............................................................................................................ 26
6.2
Single-line diagrams.................................................................................................................. 27
6.3
Glossary ..................................................................................................................................... 28
34400847FR/AA
- Page 3
34400847FR/AA
- Page 4
1. Presentation
1.1 Cabinet dimensions and weights
Source prioritaire
UPS galaxy
salle 14
deuxime tage,
Source secours
UPS galaxy
salle 13
deuxime tage,
= 0
Q1
Q2BP
Q3
1900 mm
10 mm
825 mm
1015 mm
1015 mm
Left-hand cabinet
Right-hand cabinet
Weight:
384 kg
448 kg
Footprint:
0.83 m2
0.83 m2
34400847FR/AA
- Page 5
1. Presentation
1.2 Access to controls and connections
Q4
Q1
on
off
off
on
Q1BP
6
N L1 L2 L3
Q6
Q2
on
off
off
on
off
on
15
14
15
15
Q2BP
N L1 L2 L3
12
10
Q3
N L1 L2 L3
13
11
14
15
The two STS cabinets are shown from the front with their doors open and transparent covers removed.
34400847FR/AA
- Page 6
1. Presentation
1.3 Control panel and display
21
20
Menu
NORMAL OPERATION
I1
17 A
I2
9A
I3
UPS 1
preferred
U12 413 V
U23 414 V
U31 414 V
50.0
Hz
Source
prioritaire
synchro
UPS galaxy
deuxime tage, salle 14
22
2A
1 KW
6 KVA
Transfert
Alarme
Mesures PF 0.3
Etats
Historique
22
volt
UPS 2
22
U12 412 V
U23 415 V
U31 413 V
50.0 Hz
Source secours
22
UPS galaxy
deuxime tage, salle 13
= 0
23 24 25
26
27
28
Q1
Q2
30
32
Q1BP
29
31
33
Q3
34
35
Q2BP
36
load
37
charge
Upsilon STS
34400847FR/AA
- Page 7
1. Presentation
1.4 Relay communication card
40
40
42
43
43
43
43
41
41
1
BA
45
44
3 4
46
46
48
47
34400847FR/AA
- Page 8
2. Installation
2.1 Positioning
>400 mm
Source prioritaire
UPS galaxy
salle 14
deuxime tage,
Source secours
UPS galaxy
salle 13
deuxime tage,
= 0
Q1
Q2BP
Q3
15
16
15
15
16
Note: If access from the rear of the cabinets is impossible, they must be assembled before positioning. The two
cabinets can be moved together after assembly.
34400847FR/AA
- Page 9
2. Installation
2.2 Assembling the cabinets
DROE
Q2
Q1
Q4
Q6
N L1 L2 L3
Q1BP
XF32
XF31
XF30 d
XM30
XM31
XM32
Q2BP
Q3
800 mm
N L1 L2 L3
500 mm
14
N L1 L2 L3
14
34400847FR/AA
- Page 10
2. Installation
2.3 Power connections
See section 6.1 for information on sizing protection devices and cables (Appendix: Technical specifications).
The equipment is designed to allow connection to an IT system (as defined by standard EN 60950 / IEC 60950 or IEC
60364-3).
See section 1.2 for information on accessing the connections.
Connections by lugs to copper bars with 12 mm diameter holes.
Upsilon STS with inputs for 3 phases + PEN and outputs for 3 phases + PEN
Q4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
S1
14
14
S2
PEN
PEN
Upsilon STS with inputs for 3 phases + PEN and outputs for 3 phases + PE + Neutral
Q4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
S2
S1
14
14
PE
N PEN
Upsilon STS with inputs for 3 phases + PEN and outputs for 3 phases + PE
4
Q6
N L1 L2 L3
N L1 L2 L3
12
7
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
14
S2
S1
N PE
14
PEN
34400847FR/AA
- Page 11
2. Installation
Upsilon STS with inputs for 3 phases + PE + Neutral and outputs for 3 phases + PE + Neutral
4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
N L1 L2 L3
13
Q3
PE
S2
S1
14
14
PE PE
Upsilon STS with inputs for 3 phases + PE and outputs for 3 phases + PE
Q4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
N L1 L2 L3
13
Q3
PE
14
34400847FR/AA
- Page 12
S2
S1
14
PE PE
2. Installation
Connection via the top of the cabinets
Q1
Q2
Q4
Q6
Q1BP
Q2BP
Q3
34400847FR/AA
- Page 13
2. Installation
2.5 Connection of the communication cards
Tie the cables to the cable way on the door.
Do not run the control wires with the power
cables.
Two slots are available in the card
compartment (2) for optional additional
communication cards.
2
Q1
Q4
Q1BP
3
BUS
OD
BUS/M
8 7 6
RS232:
Pin 2: Rxd (or Txd)
Pin 3: Txd (or Rxd)
Pin 5: Earth
RS485:
Pin 4: RPin 5: TPin 8: R+
Pin 9: T+
For information on using the communication
card, see the J-BUS communication card
manual.
34400847FR/AA
- Page 14
2. Installation
Connection of the relay communication card
Before proceeding, disconnect all power sources connected to the card.
Do not mix SELV (Safety Extra Low Voltage) and non-SELV circuits on the card outputs.
44
BA
45
40
42
43
43
43
43
40
41
41
46
Overload status
STS fault
General alarm
(fault on one of the sources or on the STS)
Load-supply status
B A
34400847FR/AA
- Page 15
3. Operation
Make sure that the voltages and frequencies of the two sources S1 and S2 are identical.
Make sure that the voltages of the two sources S1 and S2 are the same as the rated voltage (380/400/415 V) of
Upsilon STS, otherwise see section 3.5 (Customization).
3.1 Start-up
Q4
on
Q1
Q6
on
on
off
off
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
1 - Check that all the switches and circuitbreakers are open and check that the two
sources are energized (voltage present).
2 - Set circuit breakers Q4 and Q6 to the ON
position (position 1).
3 - Turn switch Q1BP to the ON position
(position 1). LEDs (23), (32) and (37) go on.
The load is supplied by Source 1 via the
bypass.
4 - Set switches Q1 and Q3 to the ON position
(position 1). LEDs (28), (30), (33) and (34) go
on.
5 - Turn switch Q1BP back to the OFF
position (position 0). LED (32) goes off.
6 - Set switch Q2 to the ON position (position
1). LEDs (29) and (31) go on.
The load is supplied by Source 1.
S1
S2
23
28
24
25
Q1
Q2
33
32
35
Q3
Q2BP
34
37
34400847FR/AA
- Page 16
31
30
Q1BP
29
36
3. Operation
3.2 Shutdown
Q4
on
Q1
Q6
on
on
off
off
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
S1
S2
Q1
Q2
Q1BP
Q3
Q2BP
34400847FR/AA
- Page 17
3. Operation
3.3 Normal mode. Operation on preferred source S1
Operation on the preferred source
S1
23
28
S2
24
25
Q1
Q2
29
31
30
33
35
Q1BP
Q3
32
Q2BP
34
36
37
S1
23
28
S2
24
25
Q1
Q2
29
31
30
33
35
Q1BP
Q3
32
Q2BP
34
36
37
S1
24
Q1
Q2
33
32
35
Q3
34
37
34400847FR/AA
- Page 18
31
25
30
Q1BP
29
S2
23
28
Q2BP
36
3. Operation
Manual transfer to an out-of-phase alternate source
S1
23
28
24
25
Q1
Q2
33
32
29
31
30
Q1BP
S2
35
Q3
Q2BP
34
36
37
34400847FR/AA
- Page 19
3. Operation
3.4 Display organization
Initial screen
Main screen
DOWNGRADED MODE
I1
17 A
I2
9A
1 KW
I3
MAIN MENU
2A
Transfer
6 KVA
PF 0.3
UPS 1
V1 244 V
V2 230 V
V3 232 V
50.0 Hz
preferred
synchro
Alarms
UPS 2
V1 232 V
V2 229 V
V3 230 V
50.0 Hz
0 1 0 1
1 0 1 0
0 1 0 1
Status
VOLT
Measurements
E
S
C
Setup
Maintenance
= 64
Transfer
Alarms
ALARMS
MANUAL TRANSFERT
Transfer without break
Transfer with break
Retransfer without break
Status
STATUS
Measurements
CURRENT MEASUREMENTS
VOLTAGE MEASUREMENTS
Event log
FREQUENCY MEASUREMENTS
Statistics
POWER MEASUREMENTS
Setup
SETUP
Language
Date and time
Maintenance
Contrast adjust
Buzzer volume
Source names
Password change
Personalization
Dry contact settings
34400847FR/AA
- Page 20
MAINTENANCE
Display test
Unit on bypass
Start-up
3. Operation
3.5 Upsilon STS customization
1 - Press the menu button (26).
2 - Select "Setup", then "Customization" using the function buttons (22) or .
3 - Confirm the order by pressing the function button (22) .
4 - Enter the password.
The password is the factory setting.
Select "Setup", then "Password" to personalize the password.
The monitoring parameters must be identical
for the two sources.
These parameters depend on the tolerances
of the connected loads.
PERSONALIZATION
Current settings
Nominal voltage
Overvoltage threshold
Undervoltage threshold
Nominal frequency
Overfrequency threshold
Underfrequency threshold
Phase sync tolerance
Retransfer
400 V
10%
10%
50 Hz
5%
5%
15
YES
E
S
C
Factory setting
Customization
15
1 to 45 in 1 steps
400 V
Overvoltage threshold
Un +10%
Undervoltage threshold
Un -10%
50 Hz
50 / 60 Hz
Frequency tolerances
5%
Automatic
Manual / Automatic
34400847FR/AA
- Page 21
3. Operation
3.6 Customization of the relay communication card
Inputs
1.A
- Not affected.
1.B
- Not affected.
Outputs
34400847FR/AA
- Page 22
Factory setting
Factory setting
1.1
1.2
1.3
1.4
- Overload status.
1.5
1.6
4. Maintenance
4.1 Identification of problems
General-alarm
LED (21)
S1 (30) or S2
(31) LED
Static-switch LED
(33) or (35)
Buzzer
System output
LED (37)
Meaning
Beeps
Beeps
Source outside
tolerances, load still
supplied
Beeps
Beeps
Beeps
Overload
Beeps
Source outside
tolerances, no voltage.
The load cannot be
supplied by this source
Static-switch fault
34400847FR/AA
- Page 23
4. Maintenance
4.2 Transfer to the manual bypass
Q1
Q2
on
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
Q1
on
off
off
Q6
on
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
34400847FR/AA
- Page 24
Environment
This product has been designed to protect the environment
It does not contain CFCs or HCFCs.
It is manufactured on a production site certified ISO 14001.
Packing recycling
Packing materials must be recycled in compliance with all applicable regulations.
34400847FR/AA
- Page 25
Appendix
6.1 Technical specifications
Output currents and voltage
Rated output current:
800 A
900 A
1000 A
1200 A
Thermal characteristics
Heat losses (1):
3.3 kW
3.8 kW
4.7 kW
6.6 kW
Required ventilation:
2300 m3/hr
2300 m3/hr
2300 m3/hr
2300 m3/hr
(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.
Noise level
Noise (ISO 3746):
60 dB
60 dB
60 dB
60 dB
2 x 150 mm2
2 x 185 mm2
2 x 240 mm2
2 x 300 mm2
300 mm2
300 mm2
300 mm2
300 mm2
12 mm
12 mm
12 mm
12 mm
(2) The recommended cable sizes must be checked by calculations taking into account the specific characteristics of the
installation (cable lengths, installation method, ambient temperature, etc.) and any applicable local standards.
NS800H
NS800H
NS1000H
NS1000H
NS1250H
NS1250H
NS1250H
NS1250H
Trip unit(3):
Micrologic 2
Micrologic 2
Micrologic 2
Micrologic 2
Thermal setting:
1.05 In
1.05 In
1.05 In
1.05 In
Magnetic setting:
10 In
10 In
10 In
10 In
(3) The indicated products are taken from the Schneider Electric Low Voltage catalogue (Merlin Gerin brand).
32 In
16 In
8 In
4 In
2 In
In
0.01 s
t(s)
0.1 s
1s
10 s
100 s
1000 s
34400847FR/AA
- Page 26
6. Appendix
6.2 Single-line diagrams
Upsilon STS single-line diagram
Upsilon STS
S1
S2
Control /
Monitoring
Q2
Q1
Q1BP
Q3
Q2BP
Upsilon STS
Upsilon STS
Upsilon STS
34400847FR/AA
- Page 27
6. Appendix
6.3 Glossary
34400847FR/AA
Alternate source
J-BUS
communication card
Internal card implementing the J-BUS protocol on a serial link to supply the user with system
information.
Load
Manual bypass
Q1BP and Q2BP switches, accessible to the user, that may be used to directly supply the load
from Source S1 or S2. The bypass enables servicing on the equipment without interrupting the
supply of power to the load.
Normal mode
Operating mode during which the load is supplied by the preferred source.
Preferred source
Relay
communication card
Internal card implementing contacts to supply the user with system information.
Static switch
- Page 28
www.mgeups.com
Upsilon STS
800A-900A1000A-1200A
Manuel dinstallation et
dutilisation
Source prioritaire
UPS galaxy
salle 14
deuxime tage,
Source secours
UPS galaxy
salle 13
deuxime tage,
= 0
Q1
Q2BP
Q3
D E R
V I
O
R
T H E
U N
I N
T E
R
34003641FR/AA
- Page 1
Introduction
Nous vous remercions d'avoir choisi un produit MGE UPS SYSTEMS pour la scurit de vos applications.
La gamme Upsilon STS a t labore avec le plus grand soin.
Pour exploiter au mieux les performances de votre Upsilon STS, nous vous conseillons de prendre le temps de lire ce
manuel.
Nous vous invitons dcouvrir l'offre de MGE UPS SYSTEMS ainsi que les options de la gamme Upsilon STS en visitant
notre site WEB : www.mgeups.com, ou en contactant votre reprsentant MGE UPS SYSTEMS.
Respect de l'environnement
MGE UPS SYSTEMS se proccupe de l'impact de ses produits sur l'environnement en suivant une dmarche d'coconception pendant le cycle de vie de Upsilon STS: conception, utilisation et recyclage.
Pictogrammes utiliss
Document
Afficheur
Consignes suivre
imprativement
Slection verticale
Autres slections
Indication visuelle
Validation
Augmenter
Action
Dtail
Diminuer
Signalisation sonore
Menu circulant
Enregistrer
Voyant teint
Affichage graphique
Voyant clignotant
Affichage graphique
Affichage graphique
Cbles de terre
Autres cbles
88.8
8.88
E
S
C
D
E
L
VOLT
Affichage numrique
17
mai
STOP
Transfert
Effacer
Alarme
Arrt du buzzer
0101
1010
0101
Etats
Rglages
Maintenance
Nota : les voyants et interrupteurs sont reprsents en position de fonctionnement stable. Les passages transitoires sont reprsents par des
flches en pointill.
34400847FR/AA
- Page 2
Sommaire
1.
2.
Prsentation
1.1
1.2
1.3
1.4
1.5
Installation
2.1
2.2
2.3
2.4
2.5
3.
Utilisation
3.1
3.2
3.3
4.
5.
3.4
3.5
3.6
Maintenance
4.1
4.2
Environnement
Respect de lenvironnement, recyclage en fin de vie, recyclage de lemballage ......................... 25
6.
Annexes
6.1
Spcifications techniques......................................................................................................... 26
6.2
6.3
Glossaire .................................................................................................................................... 28
34400847FR/AA
- Page 3
34400847FR/AA
- Page 4
1. Prsentation
1.1 Caractristiques des cellules
Source prioritaire
UPS galaxy
salle
deuxime tage,
14
Source secours
UPS galaxy
salle 13
deuxime tage,
= 0
Q1
Q2BP
Q3
1900 mm
10 mm
825 mm
1015 mm
1015 mm
Cellule de gauche
Cellule de droite
Masse :
384 kg
448 kg
Surface au sol :
0,83 m2
0,83 m2
34400847FR/AA
- Page 5
1. Prsentation
1.2 Accs aux commandes et raccordements
Q4
Q1
on
off
off
on
Q1BP
6
N L1 L2 L3
Q6
Q2
on
off
off
on
off
on
15
14
15
15
Q2BP
N L1 L2 L3
12
10
Q3
N L1 L2 L3
13
11
14
15
Les faces avant des deux cellules de lappareil sont reprsentes portes ouvertes et capots de protection en
plastique transparent dmonts.
34400847FR/AA
- Page 6
1. Prsentation
1.3 Pupitre de commande et daffichage
21
20
Menu FONCTIONNEMENT NORMAL
I1
17 A
I2
9A
I3
SOURCE 1
preferred
U12 413 V
U23 414 V
U31 414 V
50.0
Hz
Source
prioritaire
synchro
UPS galaxy
deuxime tage, salle 14
22
2A
1 KW
6 KVA
Transfert
Alarme
Mesures FP 0.3
Etats
Historique
SOURCE 2
22
volt
22
U12 412 V
U23 415 V
U31 413 V
50.0 Hz
Source secours
22
UPS galaxy
deuxime tage, salle 13
= 0
23 24 25
26
27
28
Q1
Q2
30
32
Q1BP
29
31
33
Q3
34
35
Q2BP
36
37
load
charge
Upsilon STS
34400847FR/AA
- Page 7
1. Prsentation
1.4 Carte de communication relais
40
40
42
43
43
43
43
41
41
1
BA
45
44
3 4
46
46
48
47
34400847FR/AA
- Page 8
2. Installation
2.1 Mise en place
>400 mm
Source prioritaire
UPS galaxy
salle 14
deuxime tage,
Source secours
UPS galaxy
salle 13
deuxime tage,
= 0
Q1
Q2BP
Q3
15
16
15
15
16
34400847FR/AA
- Page 9
2. Installation
2.2 Assemblage des cellules
DROE
Q2
Q1
Q4
Q6
N L1 L2 L3
Q1BP
XF32
XF31
XF30 d
XM30
XM31
XM32
Q2BP
Q3
800 mm
N L1 L2 L3
500 mm
14
N L1 L2 L3
14
34400847FR/AA
- Page 10
2. Installation
2.3 Raccordements de puissance
La dtermination des protections et des cbles est donne au chapitre 6.1 (Annexes, spcifications techniques).
Le matriel a t conu pour permettre le raccordement selon un schma d'alimentation IT (dfini selon les normes
EN 60950 / CEI 60950 ou CEI 60364-3).
Pour accder aux raccordements, voir le paragraphe 1.2.
Raccordements par cosses sur barres de cuivre avec trous de diamtre 12 mm.
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
S1
14
14
S2
PEN
PEN
Q4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
S2
S1
14
14
PE
N PEN
Q6
N L1 L2 L3
N L1 L2 L3
12
7
Q2BP
Q1BP
L1 L2 L3
13
Q3
PEN
14
S2
S1
N PE
14
PEN
34400847FR/AA
- Page 11
2. Installation
Upsilon STS avec entres 3 phases + PE + Neutre, et sortie 3 phases + PE + Neutre
4
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
N L1 L2 L3
13
Q3
PE
S2
S1
14
14
PE PE
Q6
N L1 L2 L3
N L1 L2 L3
12
Q2BP
Q1BP
N L1 L2 L3
13
Q3
PE
14
34400847FR/AA
- Page 12
S2
S1
14
PE PE
2. Installation
Raccordements par le haut des cellules
Q1
Q2
Q4
Q6
Q1BP
Q2BP
Q3
34400847FR/AA
- Page 13
2. Installation
2.5 Raccordement des cartes de communication
Fretter les cbles sur le chemin de cbles
plac cet effet sur la porte.
Ne pas faire cheminer les fils fins avec les
cbles de puissance.
Deux emplacements sont disponibles dans
le coffret (2) pour des cartes de
communication complmentaires en option.
2
Q1
Q4
Q1BP
3
ODBU
/M
JBUS
8 7 6
RS232 :
Broche 2 : Rxd (ou Txd)
Broche 3 : Txd (ou Rxd)
Broche 5 : masse
RS485 :
Broche 4 : RBroche 5 : TBroche 8 : R+
Broche 9 : T+
Pour les dtails d'utilisation, voir le manuel de
la carte de communication J-BUS.
34400847FR/AA
- Page 14
2. Installation
Raccordement de la carte de communication relais
Condamner toutes les sources d'alimentation raccordes cette carte avant manipulation.
Ne pas mixer les circuits TBTS (trs basse tension de scurit) et non TBTS sur les sorties d'une mme carte.
44
BA
45
40
42
43
43
43
43
40
41
41
46
Surcharge
B A
34400847FR/AA
- Page 15
3. Utilisation
S'assurer que les tensions et frquences des deux sources S1 et S2 sont identiques.
S'assurer que la tension des deux sources S1 et S2 correspond la tension nominale 380/400/415V de Upsilon STS,
sinon voir chapitre 3.5 (personnalisation).
Q1
Q4
on
Q6
on
on
off
off
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
S1
S2
23
28
24
25
Q1
Q2
33
32
35
Q3
Q2BP
34
37
34400847FR/AA
- Page 16
31
30
Q1BP
29
36
3. Utilisation
3.2 Mise hors service
Q4
on
Q1
Q6
on
on
off
off
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
S1
S2
Q1
Q2
Q1BP
Q3
Q2BP
34400847FR/AA
- Page 17
3. Utilisation
3.3 Mode normal : fonctionnement sur source prioritaire S1
Fonctionnement sur source principale
S1
23
28
S2
24
25
Q1
Q2
29
31
30
33
35
Q1BP
Q3
32
Q2BP
34
36
37
S1
23
28
S2
24
25
Q1
Q2
29
31
30
33
35
Q1BP
Q3
32
Q2BP
34
36
37
S1
24
25
Q1
Q2
33
32
35
Q3
34
37
34400847FR/AA
- Page 18
29
31
30
Q1BP
S2
23
28
36
3. Utilisation
Transfert manuel sur source secondaire "hors phase"
S1
23
28
24
25
Q1
Q2
33
32
29
31
30
Q1BP
S2
35
Q3
Q2BP
34
36
37
34400847FR/AA
- Page 19
3. Utilisation
3.4 Organisation de l'afficheur
Ecran d'accueil
Ecran principal
FONCTIONNEMENT NORMAL
I1
17 A
I2
9A
1 KW
I3
MENU PRINCIPAL
2A
Transfert
6 KVA
FP 0.3
SOURCE 1
U12 413 V
U23 414 V
U31 414 V
50.0 Hz
Alarmes
preferred
SOURCE 2
synchro
U12 412 V
U23 415 V
U31 413 V
50.0 Hz
0 1 0 1
1 0 1 0
0 1 0 1
Etats
VOLT
Mesures
E
S
C
Rglages
Maintenance
Transfert
Alarmes
ALARMES
TRANSFERTS MANUELS
Transfert sans coupure
Transfert avec coupure
Retransfert sans coupure
Etats
ETATS
Mesures
Evnements horodats
Statistiques
Rglages
REGLAGES
Langue
Date et heure
Maintenance
Rglage du contraste
Volume du buzzer
Nom des sources
Changement du mot
de passe
Personnalisation
Programmation contacts secs
34400847FR/AA
- Page 20
MAINTENANCE
Auto-test
By-pass de lappareil
Mise en route
3. Utilisation
3.5 Personnalisation de Upsilon STS
1 - Appuyer sur la touche "menu" (26).
2 - Slectionner "rglages" puis "personnalisation" l'aide des touches de fonction (22) ou .
3 - Valider avec la touche de fonction (22) .
4 - Entrer le mot de passe.
Le mot de passe correspond la configuration usine.
Pour personnaliser le mot de passe, slectionner "rglages" puis "mot de passe".
Les paramtres lectriques de contrle sont
identiques sur les 2 sources.
Ces paramtres sont dfinis en fonction des
tolrances des quipements raccords.
PERSONNALISATION
Personnalisation active
Tension nominale
400 V
Seuil de surtensions
10%
Seuil de soustension
10%
Frquence nominale
50 Hz
Seuil de surfrquence
5%
Seuil de sousfrquence 5%
Dphasage tolr
15
Retransfert
OUI
E
S
C
Configuration usine
Personnalisation
15
de 1 45 par pas de 1
400 V
Un +10%
Un -10%
50 Hz
50 / 60 Hz
5%
Automatique
Manuel / Automatique
34400847FR/AA
- Page 21
3. Utilisation
3.6 Personnalisation de la carte de communication relais
Entres
1.A
- Non affect.
1.B
- Non affect.
Sorties
34400847FR/AA
- Page 22
Configuration usine
Configuration usine
1.1
1.2
1.3
1.4
- Etat surcharge.
1.5
1.6
4. Maintenance
4.1 Identification des anomalies
Voyant d'alarme
gnrale (21)
Voyant S1 (30)
ou S2 (31)
Voyant contacteur
statique (33) ou (35)
Buzzer
Voyant tat de
sortie (37)
Signification
Dfaut interne de
l'appareil
Bip
Bip
Bip
Bip
Bip
Surcharge des
quipements.
Bip
Equipements non
aliments
34400847FR/AA
- Page 23
4. Maintenance
4.2 Passage sur by-pass manuel
Q1
Q2
on
on
off
off
Q1BP
Q2BP
off
off
on
on
Q3
off
on
Q1
on
off
off
Q6
on
Q2
on
off
off
Q2BP
Q1BP
off
off
on
on
Q3
off
on
34400847FR/AA
- Page 24
Environnement
Ce produit est conu pour respecter lenvironnement
Il ne contient ni CFC ni HCFC.
Il est fabriqu sur un site certifi ISO 14001.
Recyclage de lemballage
Pour le recyclage de lemballage, conformez-vous aux exigences lgales en vigueur.
34400847FR/AA
- Page 25
Annexes
6.1 Spcifications techniques
Tensions et courants de sortie
Courant de sortie nominal :
800 A
900 A
1000 A
1200 A
Caractristiques thermiques
Pertes vacuer (1) :
3,3 kW
3,8 kW
4,7 kW
6,6 kW
2300 m3/h
2300 m3/h
2300 m3/h
2300 m3/h
(1) Ces caractristiques sont dfinies pour une tension de 400 V et un facteur de puissance de 0,8.
Emission acoustique
Bruit (ISO 3746) :
60 dB
60 dB
60 dB
60 dB
2 x 150 mm2
2 x 185 mm2
2 x 240 mm2
2 x 300 mm2
300 mm2
300 mm2
300 mm2
300 mm2
12 mm
12 mm
12 mm
12 mm
(2) Les sections de cbles prconises doivent tre valides par une tude prenant en compte les contraintes spcifiques de
l'installation (longueur des cbles, mode de pose, temprature ambiante,...) et les normes locales en vigueur.
NS800H
NS800H
NS1000H
NS1000H
NS1250H
NS1250H
NS1250H
NS1250H
Dclencheur (3) :
Micrologic 2
Micrologic 2
Micrologic 2
Micrologic 2
Rglage thermique :
1,05 In
1,05 In
1,05 In
1,05 In
Rglage magntique :
10 In
10 In
10 In
10 In
(3) Les rfrences cites sont issues du catalogue Basse Tension de Schneider Electric (marque Merlin Gerin).
32 In
16 In
8 In
4 In
2 In
In
0,01 s
t(s)
0,1 s
1s
10 s
100 s
1000 s
34400847FR/AA
- Page 26
6. Annexes
6.2 Schmas de principe
Schma de principe de l'appareil
Upsilon STS
S1
S2
Contrle /
Commande
Q2
Q1
Q1BP
Q3
Q2BP
Upsilon STS
Upsilon STS
Upsilon STS
34400847FR/AA
- Page 27
6. Annexes
6.3 Glossaire
34400847FR/AA
By-pass manuel
Interrupteurs Q1BP et Q2BP manoeuvrs par lutilisateur, permettant dalimenter directement les
quipements par la source S1 ou S2. Le passage en by-pass manuel permet la maintenance de
l'appareil sans interrompre l'alimentation lectrique vers les quipements connects.
Carte de
communication
relais
Carte interne dlivrant, sous forme de contacts, des informations destines l'utilisateur.
Carte de
communication
J-BUS
Carte interne dlivrant, sous forme de liaison srie utilisant le protocole J-BUS, des informations
destines l'utilisateur.
Contacteur statique
Equipements
Mode normal
Source prioritaire
Source secondaire
- Page 28
3440084700/AA
T H E
U N I N T E R R U P T I B L E
P O W E R
P R O V I D E R