Air cooled water chillers


Air cooled motocondensing unit
ALZ HA 011.1 033.2
ALP HA 011.1 033.2
Cooling capacity from 38,5 to 104,9 kW
50Hz Refrigerant: HFC 407C
Scroll Compressors

New McQuay Air cooled chillers and motocondensing unit ALZ/ALP HA

McQuay International introduces their newest air cooled chillers ALZ HA equipped with scroll compressors and
electronic control system. McQuay have once again succeded in developing a high quality product with
extraordinary performance which is able to satisfy HVAC applications.
McQuay units are completely factory assembled, piped, wired and charged with refrigerant and shipped ready for
the installation.
Each unit consists of scroll compressors, condenser coils with independent subcooler circuits, multiple propeller
type direct drive condenser fans with independent fan motors, heavy-gauge weatherproof casing and weatherproof
electrical control centre containing all necessary and operating controls and motor starting equipment.
ALZ / ALP HA units are high thermodynamic engineering products, studied with high accuracy in balancing
compressors, condensers and evaporators in order to offer high performances and wide safety margins. The
choose of the materials and the equipments adopted for the products has been made without any compromises,
taking care of quality and long life purposes. The products meet ISO 9001 requirements, an assurance, beyond
any doubts, of the high producing standards followed by McQuay.

Code requirements
All units are designed and manufactured in accordance with applicable selections of the following which are
equivalent to American Air-conditioning industry applicable codes:
Rating of chillers: UNI 9018.
Construction of pressure vessel: TUV Standards (optional).
Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes.
Safety Codes: CEI-EN 602041 Codes.
Manufacturing Quality Stds: ISO 9001.

Highly flexible design


The ALZ / ALP HA units are available in sizes covering a range from 38,5 to 104,9 kW nominal cooling capacity.
Availability of many accessories, and the applications of high tech control and safety devices, give to these
products high flexibility for their installation in commercial, residential and industrial environments.

Refrigerant
As the HCFC phase out will occur more quickly than currently legislated, the designers, owners and operators
should only evaluate equipment using chlorine free refrigerants. ALZ / ALP HA units are supplied with ecological
refrigerant HFC 407C. Studied and used by McQuay for several years, it offers the same garancies of
performance, costs and reliability of refrigerant HCFC 22.

Low installation costs


The complete assembly of the units and fuction testing at the factory reduces the cost of installation on site. A rigid
steel base distributes the weight of the unit to the support points and allows simple installation by an easy access
to the lifting points. The units are designed with a single point 400/3/50 + NEUTRAL. The ALZ HA units can also
include a pumping set consisting of one or more water circulation pumps and buffer tank.

Low maintenence costs


The microprocessor safety and control system allows the trouble shooting of any type of functional anomaly,
enabling simpler, safer and timely intervention by the unit maintenance personnel. The oil heater on each
compressor and a complete set of controls and safety devices protect the unit from abnormal operating conditions.
The design of the ALZ HA unit, with two independent refrigerant circuits, increases the redudancy of the unit and
allows maintenance while the other circuit is still running.

Factory testing
Each unit is pressure tested, vacuum tested, evacuated and charged with refrigerant requested. It is then tested at
the factorys test bench under the design conditions specified by the customer. Upon request, a second series of
tests can be carried out witnessed by the customer. Before shipment, each unit is re-checked for pressure and
refrigerant charge control.

305 B 00/09 B page 2

General characteristics
Cabinet and structure
The cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. The unit base
frame has holes to lift the unit with ropes for an easy installation. The weight is uniformly distributed along the
profiles of the base and this facilitates the arrangement of the units bases and the support structures. The
electrical and control equipment is located inside a panel which can be accessed by key locked doors complete
with door interlocking on the power cabinet.
The unit cabinet can be sound insulated (as an option) in order to reduce the noise of the compressors.

Scroll compressors
The scroll compressors achieve a high volumetric efficiency, due to constant contact with the sides of the scroll
spirals and the total absence of discharge and suction valves. This compressor is not only extremely reliable
thanks to the reduced number of moving parts, but has an exceptionally low noise level because of the absence of
suction and discharge valves and hence of the reduced pulsations of the discharge gas. The reduction in moving
parts means a very low level of vibration. Each compressor is equipped with a check valve on the discharge to
mantain the pump-down condition and hence avoid the migration of the refrigerating gas from the condenser to the
evaporator.

Evaporator (only ALZ HA units)


The evaporator is a compact, efficient, dual circuit plate to plate type heat exchanger consisting of stainless steel
brazed plates.
The evaporator is wrapped with closed cell heat insulation and equipped with an heater for protection against
freezing down to 29C.

Condenser coils
ALZ HA condenser coils are constructed with internally enhanced seamless copper tubes arranged in a staggered
row pattern and mechanically expanded into McQuay lanced and rippled aluminium condenser fins with full fin
collars.

Condenser coil fans


The condenser fans are of the axial helical type with wing-profile blades to achieve a better performance. The
direct coupling with the electrical motor eliminates any problems as regards the application of transmission devices
and reduces the vibrations caused by the functioning. The motors are supplied as standard with IP54 protection
and are of the mono-phase external rotor type; they are protected against overload and short circuits by circuit
breakers located inside the electrical control panel.

Electrical control panel and control devices


The electrical components for both the power and the control are split into two sections on the main panel. The
panel is manufactured to ensure protection in all weather conditions (IP 54). The power panel is fitted with a door
interlocked mains isolator to prevent access. The electrical control panel complies with IEC204-1 safety norms.
The power section includes: compressors contactors and fuses, fans contactors and fuses. Additional space is
provided for the installation of the various optional accessories provided to enhance the capabilities of the ALZ HA
units.
The control section includes the microprocessor regulator of the water temperature (ALZ HA) which carries out the
following functions:
-

access password to prevent unauthorised access


water temperature control
regulation of temperature set points
start-up sequence delay device
compressor on-off control
fan on-off control
antifreeze control
antifreeze heater functioning
general alarm

305 B 00/09 A pag. 3

differential pressure switch or pump failure alarm (opt.)

The multifunctional microprocessor control device has contacts for remote on/off control and remote signal of
general failure.
On request, remote programming radio-control and remote PC board are available as option.

Refrigerant circuit
The ALZ HA units are equipped with a complete refrigerant charge. The ALP HA units are equipped only by a
holding charge to keep the circuit in pression and to avoid moisture infiltration.
The ALZ HA circuits consist of insulated copper pipes on the suction line and is complete with suction shut-off
valves, filter driers, moisture indicators, liquid sight glass, thermostatic expansion valves and drain valves.
ALP HA motocondensing units are not equipped by liquid and suction lines. Customer will have to provide:
antivibration isolators, filter driers, solenoid valves, moisture indicators, thermostatic expansion valves.

Accessories and Options


100% total heat recovery (R) (only for ALZ HA units) - Produced with plate heat exchangers to produce hot water
up to +50C. The heat exchangers are mounted on the refrigerant circuits parallel to the condenser coils to remove
all the heat rejection.
Desuperheaters (D) (only for ALZ HA units) - Produced with plate heat exchangers installed between the
compressor discharge and the condenser coil. These allow hot water to be produced up to a maximum
temperature of +55C.
Compressor thermal overload relays Safety devices against compressor motor overload.
Fans thermal overload relays Safety devices against fans motor overload.
Condenser power factor correction - Installed on the electrical control panel to ensure the conformance to the
local rules.
Condenser coil guards - Metal protection guards fixed on all the external surface of the condenser coils.
Cu-Cu condensing coils - To give better protection against corrosion by aggressive environments.
Alucoat condensing coils - Fins are protected by a special epoxy paint with a high resistance to corrosion.
Suction line shut off valve Standard.
Discharge line shut off valve Standard.
Inertial tank (factory unit mounted) - Cooled water buffer tank to give to the hydraulic plant inertia and reduce
excessive compressor starts and stops. The tank, supplied with one or two pumps has a 180 l capacity. The tank
is complete with: automatic filling module, manual vent valve, drain tap and 150 W antifreeze heater. The tank is
heat insulated with 20-mm thick PU and wrapped with PVC.
Water circulation pump (factory unit mounted) - Pump unit, assembled and wired, consists of a water
circulation pump (max. working pressure 6 bar) complete with safety valve and 8 litre expansion tank. The pump
motor is protected by a circuit breaker.
Two water circulation pumps (factory unit mounted) - Pump unit, assembled and wired, consisting of two
water circulation pumps (max. working pressure 6 bars) complete with shut off valve, check valves, safety valve
and 8 litre expansion tank. The pump motors are protected by circuit breakers and controlled by a two-position
switch.

NOTE: one and two pumps options always include inertial tank.
Microprocessor program remote infrared-control Infrared-control to remote program data.
Wooden box packing - Self-supporting wooden box internally insulated and suitable for shipment by sea.
Open Cage packing - Protection with polythene and wooden cage for transport and protection before the
installation.
Rubber type antivibration mounts - Supplied separately, these will be positioned under the base of the unit
during installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring type antivibration mounts - Supplied separately, these will be positioned under the base of the unit
during installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
Low noise version For this version internal side of the steel cabinet is covered by soundproof material to allow
compressor sound insulation.

305 B 00/09 B page 4

Table 1 - Operating limits


ALZ
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2

Entering evaporator
water temperature
Min (C)
Max (C)
8
8
8
8
8
8
8
8

Leaving evap. water


temp.(without glycol)
Min (C)
Max (C)

20
20
20
20
20
20
15
15

4
4
4
4
4
4
4
4

Evaporator water t

Ambient temperature

Min (C)

Max (C)

Min (C)

4
4
4
4
4
4
4
4

8
8
8
8
8
8
8
8

10
10
10
10
10
10
10
10

15
15
14
12
15
13
12
10

Max (C)
50
49
49
48
50
48
47
47

Table 2 - Altitude correction factor


Elevation above sea level (m)
Barometric pressure (mbar)
Cooling capacity correction factor

0
1013
1,000

300
977
0,991

600
942
0,981

900
908
0,972

1200
875
0,962

1500
843
0,953

1800
812
0,943

Table 3 - Ethylene glycol and low ambient temperature correction factors


Air ambient temperature C
% of ethylene glycol correction factor
Cooling capacity correction factor
Flow rate correction factor
Water pressure drops correction factor

-3
10
0,986
1,023
1,061

-8
20
0,980
1,054
1,114

-15
30
0,973
1,092
1,190

-23
40
0,966
1,140
1,244

-35
50
0,960
1,200
1,310

Table 4 - Low temperature operation performance factors


Ethylene glycol/water leaving temperature C
Cooling capacity correction factor
Power input compressors correction factor
Min % of ethylene glycol
Max air ambient temperature C

2
0,942
0,950
10
40

0
0.783
0,934
20
40

-2
0,725
0,918
20
38

-6
0,615
0,870
30
34

-8
0,562
0,845
30
32

Table 5 - Fouling factor


Fouling factor
m2 C / kW

Cooling capacity
correction factor

0,044
0,132
0,308

1,000
0,986
0,939

Water content in cooling circuits


The cooled water distribution circuits should have a minimum water content to avoid excessive compressors start
and stop.
In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressors sump and
simultaneously there is a rise in the temperature of the compressor motors stator due to the inrush current during
the start-up. To prevent damage to the compressors, McQuay has envisaged the application of a device to limit
frequent stops and restarts.
During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore
ensure that the overall water content allows a more constant functioning of the unit and consequently greater
environmental comfort. The minimum installation water content envisaged should be calculated with a certain
approximation using this formula:

(1)

Q=

Pxp
25

305 B 00/09 A pag. 5

where:
Q = minimum content of the plant expressed in litres.
P = cooling capacity of the plant expressed in W
p = minimum unloading capacity percentage
For a more accurate determination of the quantity of water, it is advisable to contact the designer of the plant.
When the sum of the water content of the evaporator, the pipes of the hydraulic circuit and the terminals (coils,
exchangers, etc.) is lower than the value obtained, it would be better to opt for a ALZ/ALP HA McQuay cooling unit
equipped with inertial tank (optional).

Installation notes
Handling
All moving and handling may damage the unit if some conditions are not scrupulously observed. The units should
be lifted with a crane using long ropes anchored to the holes on the frame of the units base and by using the
upper spacer bars to prevent the ropes from damaging the condenser coils.

Location
The ALZ/ALP HA units are produced for outside installation on roofs, floors or below ground level on condition that
the area is free from obstacles for the passage of the condensation air. The unit should be positioned on solid
foundations and perfectly level; in the case of installation on roofs or floors, it may be advisable to arrange the use
of suitable weight distribution beams. When the units are installed on the ground, a concrete base at least 250 mm
wider and longer than the units footprint should be laid. Furthermore, this base should be sufficiently robust to
withstand the unit weight mentioned in the technical data table. When the units are positioned in areas which are
easily accessible by persons or animals, it is advisable to fit guards (option) to protect the condenser and the
compressors.

305 B 00/09 B page 6

Space requirements
The ALZ/ALP HA units are air-cooled, hence it is important to observe the minimum distances which guarantee the
best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions
in cooling capacity, and increase in electricity consumption. The fans do not allow the use of ducts which have
high flow resistance, hence is should be ensured that the output air cannot recycle itself inside the condenser
coils. The units should be positioned such that there is sufficient distance between the coils and any obstacles to
improve ventilation and also to facilitate inspection (fig.1).
When two or more units are positioned side by side it is recommended that the condenser coils are at least 2500
mm distance from one another (fig. 2). Smaller distances could cause the recirculation of hot air. If the units are
positioned in places surrounded by walls or obstacles of the same height as the units, the units should be at least
2000 mm from said obstacles (fig. 3). In the event the obstacles are higher than the units, the units should be at
least 2500 mm from the obstacle (fig. 4). For other installation solutions, consult McQuay technicians.

Acoustic protection
The low noise levels of the ALZ/ALP HA units means that they meet most of the most restrictive regulations. When
the noise level must meet special requirements it will be necessary to pay the maximum attention to ensure the
perfect insulation of the unit from the support base by applying appropriate vibration-dampening devices, applying
vibration-dampening mounts on the water pipes and on the electrical connections (by the customer).

Nomenclature
ALZ HA 025 . 2 407

ALZ
ALP

Air cooled chiller


Air cooled motocondensing unit

High ambient temperature

011033

Unit size

1
2

N of tandem scroll

407

Refrigerant HFC 407C

305 B 00/09 A pag. 7

Physical data HFC 407C units


ALZ HA unit size
Cooling capacity (1)
kW
Power input (1)
kW
Cooling cap. in heat rec. condition (2)
kW
Heating capacity (2)
kW
Power input heat recovery cond. (2)
kW
Desuperheaters heating capacity (3)
kW
Desuperheaters pressure drops (3)
kPa
Scroll compressors
No. of compressors / No of circuits
Oil charge
l
No. of reduction steps
Refrigerant charge
kg
Plate heat exchangers
Water volume
l
Max. water pressure
bar
Condenser fans
No. of fans / Diameter
mm
Motor power / rotation regime
Kw / rpm
Dimensions and weights
Unit length
mm
Unit width
mm
Unit height
mm
Standard unit shipping weight
kg
Unit with two pumps and tank weight
kg
ALZ HA unit size
Cooling capacity (1)
kW
Power input (1)
kW
Cooling cap. in heat rec. condition (2)
kW
Heating capacity (2)
kW
Power input heat recovery cond. (2)
kW
Desuperheaters heating capacity (3)
kW
Desuperheaters pressure drops (3)
kPa
Scroll compressors
No. of compressors / No of circuits
Oil charge
l
No. of reduction steps
Refrigerant charge
kg
Plate heat exchange
Water volume
l
Max. water pressure
bar
Condenser fans
No. of fans / Diameter
mm
Motor power / rotation regime
Kw / rpm
Dimensions and weights
Unit length
mm
Unit width
mm
Unit height
mm
Standard unit shipping weight
kg
Unit with two pumps and tank weight
kg
Notes:

011.1

013.1

017.1

020.1

38,5
17,2
46,6
57,7
12,5
11,0
14

43,8
20,8
54,5
68,1
15,1
12,8
18

54,3
26,3
65,6
83,5
20,0
15,7
15

65,2
31,8
82,4
104,1
24,1
17,1
20

1 Tandem / 1
6,5
2
5,5

1 Tandem / 1
6,5
2
6

1 Tandem / 1
10,4
2
7

1 Tandem / 1
13,2
2
8,5

2,6
30

2,9
30

3,6
30

4,4
30

2 / 630
1,9 / 1360

2 / 630
1,9 / 1360

2 / 630
1,9 / 1360

2 / 630
1,9 / 1360

2780
1200
1400
400
662

2780
1200
1400
520
676

2780
1200
1400
530
740

2780
1200
1400
560
804

022.2

025.2

029.2

033.2

76,1
35,2
91,6
115,7
26,9
21,4
18

85,9
42,9
106,5
135,2
32,1
24,4
20

98,8
47,9
125,1
157,2
36,5
28,1
19

105,9
54,9
134,9
171,5
41,7
30,0
24

2 Tandem / 2
6,5+6,5
2
11

2 Tandem / 2
6,5+6,5
2
13

2 Tandem / 2
6,5+10,4
2
16

2 Tandem / 2
10,4+10,4
2
18

5,2
30

5,8
30

6,8
30

7,6
30

3 / 630
1,9 / 1360

3 / 630
1,9 / 1360

3 / 630
1,9 / 1360

3 / 630
1,9 / 1360

3530
1200
1400
630
834

3530
1200
1400
750
958

3530
1200
1400
760
992

3530
1200
1400
940
1040

(1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
46C ambient temperature;
(2) Nominal cooling capacity, power input and heating capacity are based on: 12/7 C entering/leaving evaporator
water temperature; 45C leaving HR water temperature.
(3) Desuperheaters heating capacity and pressure drops are based on: 12/7C entering/leaving evaporator water
temperature; 40/45C entering/leaving desuperheater water temperature; 46C ambient temperature.

305 B 00/09 B page 8

Electrical data
ALZ / ALP HA Unit size
Standard voltage (1)
Max tandem 1 absorbed current
Max tandem 1 absorbed current
Max total compressors abs. current
Max fans absorbed current
Max unit absorbed current
Max inrush current (2)

A
A
A
A
A
A

011.1

013.1

017.1 020.1 022.2 025.2


400 V - 3f 50 Hz + NEUTRAL

029.2

033.2

37,0
37,0
6,8
43,8
134,5

42,4
42,4
6,8
49,2
148,2

52,0
52,0
6,8
58,8
185,0

52,0
42,4
94,4
10,2
104,6
227,4

52,0
52,0
104,0
10,2
114,2
237,0

64,0
64,0
6,8
70,8
224,0

37,0
37,0
74,0
10,2
84,2
171,5

42,4
42,4
84,8
10,2
95,0
190,6

Note: (1) Allowed voltage tolerance 10%.


Note: (2) 1 Tandem units: absorbed current of compressor n1 at full load + inrush current of the second compressor.
2 tandem units: absorbed current of Tandem n1 at full load + full load of compressor n1 (of the second Tandem) + inrush
current of the last compressor.

Sound pressure level ALZ / ALP HA


Unit size
ALZ / ALP HA
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2

63 Hz
75,0
75,0
75,0
75,0
77,0
77,0
77,0
77,0

Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )
125 Hz
250 Hz
500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
75,0
75,0
75,0
75,0
76,5
76,5
76,5
76,5

72,0
72,0
72,0
72,0
73,5
73,5
73,5
73,5

71,5
71,5
71,5
71,5
73,0
73,0
73,0
73,0

71,0
71,0
71,0
71,0
72,5
72,5
72,5
72,5

65,5
65,5
65,5
65,5
67,0
67,0
67,0
67,0

58,0
58,0
58,0
58,0
59,5
59,5
59,5
59,5

50,5
50,5
50,5
50,5
52,0
52,0
52,0
52,0

dBA
74,5
74,5
74,5
74,5
76,0
76,0
76,0
76,0

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Sound pressure level ALZ / ALP HA with soundproof cabinet


Unit size
ALZ / ALP HA
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2

63 Hz
72,5
72,5
72,5
72,5
74,5
74,5
74,5
74,5

Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )
125 Hz
250 Hz
500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
72,5
72,5
72,5
72,5
74,0
74,0
74,0
74,0

69,5
69,5
69,5
69,5
71,0
71,0
71,0
71,0

69,0
69,0
69,0
69,0
70,5
70,5
70,5
70,5

68,5
68,5
68,5
68,5
70,0
70,0
70,0
70,0

63,0
63,0
63,0
63,0
64,5
64,5
64,5
64,5

55,5
55,5
55,5
55,5
57,0
57,0
57,0
57,0

48,0
48,0
48,0
48,0
49,5
49,5
49,5
49,5

dBA
72,0
72,0
72,0
72,0
73,5
73,5
73,5
73,5

Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.

Table 6 Sound pressure level correction factor for different distances


ALZ /ALP HA 011.1 020.1
Distance (mt)
dBA

1
0

5
-9

10
-14,1

15
-17,3

20
-19,7

25
-21,5

5
-8,7

10
-13,8

15
-16,9

20
-19,3

25
-21,1

ALZ /ALP HA 022.2 033.2


Distance (mt)
dBA

1
0

305 B 00/09 A pag. 9

ALZ HA
unit
size
HFC
407C

011.1

013.1

017.1

020.1

022.2

025.2

029.2

033.2

Evaporator
leaving
temp. (C)

Standard ratings ALZ HA HFC 407C

4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10

AMBIENT TEMPERATURE - C
30

35

40

43

46

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

41,7
43,0
44,3
45,7
47,0
48,4
49,8
47,8
49,2
50,7
52,2
53,8
55,1
56,9
59,6
61,3
63,1
65,0
66,9
68,8
70,7
71,2
73,3
75,5
77,7
80,0
82,1
84,4
83,0
85,5
88,1
90,8
93,5
96,1
98,9
94,2
96,9
99,8
102,7
105,7
108,7
111,6
108,0
111,3
114,7
118,1
121,6
125,1
128,6
116,8
120,3
123,8
127,3
130,9
134,7
138,4

12,1
12,2
12,3
12,5
12,6
12,5
12,6
14,6
14,7
14,9
15,0
15,1
15,2
15,3
18,6
18,7
18,9
19,1
19,1
19,3
19,6
22,7
23,0
23,2
23,4
23,6
23,8
23,9
25,1
25,3
25,5
25,7
25,9
26,0
26,2
30,2
30,5
30,7
31,0
31,3
31,5
31,8
34,2
34,5
34,8
35,0
35,3
35,6
35,8
39,1
39,3
39,7
40,1
40,4
40,8
41,2

40,2
41,5
42,8
44,1
45,4
46,7
48,1
46,0
47,4
48,8
50,3
51,8
53,2
54,8
57,3
59,0
60,8
62,6
64,4
66,3
68,1
68,5
70,6
72,7
74,8
77,0
79,1
81,3
79,9
82,4
84,9
87,5
90,1
92,7
95,4
90,5
93,2
96,0
98,8
101,7
104,6
107,5
103,8
107,0
110,3
113,6
116,9
120,3
123,7
112,1
115,5
118,9
122,3
125,8
129,4
133,0

13,2
13,3
13,4
13,5
13,6
13,6
13,7
15,9
16,0
16,2
16,3
16,4
16,5
16,6
20,2
20,3
20,5
20,7
20,8
21,0
21,2
24,6
24,9
25,1
25,3
25,5
25,7
25,9
27,2
27,4
27,6
27,8
28,0
28,2
28,4
32,9
33,2
33,4
33,7
34,0
34,2
34,5
37,1
37,4
37,7
38,0
38,3
38,6
38,9
42,4
42,7
43,1
43,5
43,9
44,3
44,7

38,0
39,2
40,5
41,7
43,0
44,2
45,5
43,3
44,7
46,0
47,4
48,8
50,3
51,7
53,9
55,6
57,3
59,0
60,7
62,5
64,2
64,5
66,5
68,5
70,5
72,5
74,6
76,7
75,3
77,7
80,1
82,6
85,0
87,6
90,1
85,0
87,7
90,3
93,0
95,7
98,5
101,3
97,5
100,6
103,7
106,8
109,9
113,1
116,4
105,1
108,3
111,5
114,8
118,1
121,5
124,9

14,8
14,9
15,0
15,0
15,1
15,2
15,3
17,9
18,0
18,1
18,2
18,3
18,5
18,6
22,6
22,7
22,9
23,1
23,3
23,5
23,6
27,5
27,7
27,9
28,2
28,4
28,6
28,9
30,4
30,6
30,8
31,0
31,2
31,5
31,7
36,9
37,2
37,5
37,7
38,0
38,3
38,6
41,5
41,8
42,1
42,5
42,8
43,1
43,5
47,4
47,8
48,2
48,6
49,1
49,5
49,9

36,6
37,8
38,9
40,1
41,4
42,6
43,9
41,6
42,9
44,2
45,5
46,9
48,3
49,7
51,7
53,3
55,0
56,6
58,3
60,0
61,7
61,9
63,8
65,7
67,7
69,6
71,7
73,7
72,4
74,6
77,0
79,4
81,8
84,2
86,7
81,5
84,1
86,6
89,2
91,9
94,5
97,2
93,4
96,3
99,3
102,4
105,4
108,5
111,6
100,5
103,6
106,7
109,9
113,1
116,3
119,6

15,8
15,9
16,0
16,1
16,2
16,3
16,4
19,2
19,3
19,4
19,5
19,6
19,8
19,9
24,2
24,4
24,5
24,7
24,9
25,1
25,3
29,4
29,6
29,8
30,1
30,3
30,6
30,9
32,6
32,8
33,0
33,2
33,4
33,7
33,9
39,6
39,9
40,2
40,5
40,7
41,0
41,3
44,5
44,8
45,2
45,5
45,9
46,2
46,6
50,8
51,2
51,6
52,1
52,5
53,0
53,4

35,1
36,3
37,4
38,5
39,7
40,9
42,2
39,9
41,2
42,5
43,8
45,2
46,5
47,8
49,6
51,1
52,7
54,3
56,0
57,6
59,3
59,5
61,4
63,3
65,2
67,1
69,1
71,0
69,3
71,5
73,8
76,1
78,4
80,8
83,2
78,4
80,9
83,4
85,9
88,5
91,1
93,6
90,1
92,9
95,8
98,8
101,8
104,7
107,7
96,8
99,7
102,8
105,9
109,0
112,2
115,3

16,9
17,0
17,1
17,2
17,3
17,4
17,5
20,4
20,6
20,7
20,8
20,9
21,1
21,2
25,8
26,0
26,1
26,3
26,5
26,7
26,9
31,0
31,3
31,5
31,8
32,0
32,3
32,6
34,8
35,0
35,2
35,5
35,7
35,9
36,1
42,0
42,3
42,6
42,9
43,1
43,4
43,7
46,9
47,2
47,6
47,9
48,3
48,6
49,0
53,5
53,9
54,4
54,9
55,3
55,8
56,3

Notes: (1) Rating based on: evaporator fouling factor of 0,044 m C/ kW, evaporator temperature drop of 5C and sea level altitude.
(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.
(3) The power input values are referred to compressor only.
(4) To know the units functioning maximum air ambient temperature consult the operating limits table.

305 B 00/09 B page 10

ALZ HA
unit
size
HFC
407C

011.1

013.1

017.1

020.1

022.2

025.2

029.2

033.2

Evaporator
leaving
temp. (C)

Total heat recovery ratings ALZ HA HFC 407C

4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10

LEAVING HEAT RECOVERY CONDENSER WATER TEMPERATURE


40

45

50

Cooling
capacity
(kW)

Power
input
(kW)

Heating
capacity
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Heating
capacity
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Heating
capacity
(kW)

46,8
48,2
49,8
52,4
54,2
56,5
58,3
54,5
56,2
57,4
59,1
60,8
64,4
66,0
65,2
67,3
69,5
71,3
73,3
75,7
77,6
77,7
80,2
82,5
85,0
87,4
89,8
92,3
90,1
93,0
95,6
96,0
98,6
99,0
101,6
100,2
103,4
106,4
109,5
113,8
115,9
117,2
121,6
125,4
126,1
129,4
129,9
133,6
147,5
131,6
135,4
136,0
139,9
146,5
154,6
159,0

12,3
12,3
12,3
12,2
12,3
12,3
12,2
14,6
14,6
14,5
14,6
14,6
14,6
14,6
18,4
18,4
18,5
18,6
18,8
19,0
19,0
22,2
22,3
22,3
22,6
22,5
22,6
22,6
25,0
25,2
25,4
25,5
25,7
25,7
25,8
32,2
32,2
32,5
32,4
32,5
32,6
32,5
34,6
34,7
35,1
35,4
36,0
36,3
36,7
39,5
39,8
40,1
40,7
41,0
41,6
42,0

57,7
59,2
60,6
63,1
64,9
67,2
68,5
67,2
69,0
70,4
72,1
73,3
76,9
78,7
81,5
83,7
85,7
87,6
89,8
92,2
96,3
97,5
100,0
102,5
105,1
106,7
109,4
112,1
112,3
115,2
117,9
118,7
120,9
121,9
124,1
129,1
132,3
135,4
138,6
142,3
145,2
145,9
152,3
156,2
158,8
160,3
162,5
164,4
178,6
166,8
170,9
173,8
175,3
184,3
190,0
194,5

44,0
45,3
46,3
46,6
47,7
48,9
52,4
49,9
51,5
53,0
54,5
56,2
59,0
60,5
60,0
62,0
63,7
65,6
68,7
70,9
72,7
76,1
78,5
80,7
82,4
84,8
87,1
89,5
83,8
86,4
88,8
91,6
96,4
95,1
97,6
96,2
100,5
103,4
106,5
108,1
110,1
111,3
113,3
116,7
120,4
125,1
126,0
129,6
137,4
122,5
126,1
129,9
134,9
138,8
144,1
148,2

12,3
12,4
12,6
12,5
12,6
12,8
12,8
14,8
14,9
15,1
15,1
15,1
15,3
15,3
19,6
19,7
19,8
20,0
20,2
20,3
20,3
23,5
23,7
23,8
24,1
24,0
24,2
24,2
26,4
26,6
26,8
26,9
27,1
27,4
27,6
31,6
31,9
32,1
32,1
32,3
32,2
32,5
36,0
36,2
36,1
36,5
36,7
36,6
36,7
41,3
41,5
41,5
41,7
41,9
41,7
42,1

55,0
56,4
57,4
57,7
58,9
60,3
63,3
63,0
64,9
66,6
68,1
69,2
72,3
74,0
77,6
79,7
81,4
83,5
86,7
88,8
92,7
97,2
99,7
102,2
104,1
105,6
108,3
110,9
107,4
110,1
112,7
115,7
120,2
119,7
121,9
124,6
129,1
132,2
135,2
136,6
139,1
140,2
145,5
149,1
154,2
157,2
159,5
160,8
168,8
159,7
163,4
169,1
171,5
177,6
179,9
184,2

41,1
42,4
43,7
44,9
47,3
48,8
50,0
47,1
49,0
52,9
53,1
54,6
54,8
56,2
57,1
59,0
60,7
62,5
64,2
67,6
69,3
71,7
76,2
78,5
77,3
79,5
81,8
85,6
78,9
81,4
83,7
86,3
90,9
89,9
92,3
89,0
93,0
95,7
99,6
99,1
101,1
104,2
106,9
112,4
116,0
119,3
120,1
120,2
128,4
115,7
119,2
125,1
128,9
132,4
135,0
138,7

13,1
13,1
13,1
13,0
13,0
13,1
13,1
16,0
16,1
16,1
16,3
16,2
16,3
16,5
20,6
20,8
20,9
21,0
21,1
21,2
21,3
24,7
24,9
25,1
25,9
25,0
25,3
24,9
27,7
28,0
28,2
28,3
28,2
28,5
28,7
33,3
33,5
33,5
33,7
33,7
33,9
33,9
37,9
38,1
38,5
38,5
38,7
38,6
39,0
43,4
43,7
44,0
44,1
44,4
44,4
44,8

52,9
54,3
55,4
56,6
58,9
60,5
61,3
61,5
63,6
67,5
67,8
68,8
69,1
70,9
75,8
77,8
79,5
81,4
83,1
86,4
90,2
94,1
98,7
101,3
100,9
101,4
104,1
107,8
104,0
106,6
109,0
111,9
115,9
115,7
117,9
119,2
123,4
126,0
130,1
129,3
131,9
134,6
141,2
146,7
152,2
153,4
155,7
153,6
162,4
155,2
158,8
166,9
167,9
173,8
173,7
177,5

305 B 00/09 A pag. 11

Standard ratings motocondensing units ALP HA HFC 407C

011.1

013.1

017.1

020.1

022.2

025.2

029.2

033.2

AMBIENT TEMPERATURE - C
35
40
43

Evaporation
temperature
C

Unit
Size
ALP
HA
HFC
407C

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

Cooling
capacity
(kW)

Power
input
(kW)

0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10

42,3
45,0
47,8
50,8
53,9
56,8
47,9
50,9
54,1
57,5
61,1
64,4
60,0
63,8
67,8
72,0
76,1
80,3
71,3
76,3
81,0
86,1
91,2
96,3
83,1
88,9
94,5
100,0
105,5
111,3
93,9
100,4
106,7
112,9
119,5
126,0
108,2
115,6
122,9
130,5
136,5
143,3
116,8
124,8
132,7
140,6
149,1
156,5

13,3
13,7
14,2
14,7
15,1
15,5
15,9
16,4
17,0
17,5
18,1
18,8
20,3
20,9
21,6
22,3
23,0
23,8
24,9
25,7
26,5
27,4
28,2
29,2
27,3
28,2
29,1
30,2
31,1
32,2
33,1
34,2
35,3
36,7
37,8
39,1
37,4
38,6
39,9
41,2
42,2
43,0
43,0
44,4
45,8
47,3
48,6
50,1

39,4
41,9
44,5
47,4
50,4
53,2
44,7
47,6
50,5
53,7
57,1
60,4
55,9
59,4
63,1
67,2
71,2
75,2
66,4
71,0
75,4
80,4
85,2
90,3
77,4
82,8
88,0
93,3
98,7
104,1
87,4
93,4
99,3
105,4
111,7
118,0
100,7
107,7
114,4
121,8
129,0
136,7
108,7
116,2
123,5
131,2
138,9
146,9

13,7
14,2
14,6
15,2
15,6
16,1
16,5
17,0
17,6
18,2
18,8
19,5
20,9
21,6
22,3
23,1
23,9
24,7
25,7
26,5
27,4
28,3
29,3
30,3
28,5
29,4
30,4
31,5
32,7
33,8
34,6
35,7
36,9
38,4
39,6
41,0
39,2
40,4
41,8
43,2
43,9
44,6
44,9
46,4
47,9
49,5
50,4
51,3

37,6
39,9
42,4
45,3
48,4
51,1
42,9
45,6
48,5
51,5
54,8
58,0
53,2
56,5
60,1
64,2
68,2
72,4
63,2
67,6
71,8
76,8
81,7
86,8
72,9
78,0
82,9
88,0
92,9
98,1
82,3
88,0
93,6
99,3
105,2
111,1
94,9
101,5
107,9
114,8
121,2
127,3
102,5
109,6
116,5
123,7
131,5
136,3

14,1
14,5
15,0
15,6
16,0
16,5
16,9
17,5
18,0
18,6
19,2
20,0
21,5
22,2
22,9
23,7
24,5
25,3
26,4
27,2
28,1
29,1
30,0
31,1
29,2
30,2
31,2
32,3
33,5
34,6
35,5
36,6
37,8
39,4
40,6
42,0
40,2
41,5
42,8
44,2
45,0
45,7
46,1
47,6
49,1
50,8
51,7
52,6

36,3
38,6
41,0
43,9
47,2
49,9
41,7
44,4
47,2
50,1
53,3
56,5
51,4
54,7
58,1
62,3
66,4
70,7
61,1
65,3
69,4
74,4
79,5
84,7
69,7
74,5
79,2
84,2
88,7
93,8
78,8
84,2
89,5
95,0
100,6
106,1
90,8
97,1
103,2
109,8
115,5
120,3
98,1
104,9
111,5
118,4
126,3
128,3

14,4
14,9
15,4
16,0
16,4
16,9
17,3
17,9
18,5
19,1
19,7
20,5
22,0
22,7
23,5
24,3
25,2
25,9
27,0
27,9
28,8
29,8
30,8
31,9
30,0
30,9
32,0
33,1
34,3
35,5
36,4
37,6
38,8
40,4
41,6
43,1
41,2
42,5
43,9
45,4
46,1
46,9
47,2
48,8
50,4
52,0
53,0
53,9

35,1
37,3
39,7
42,5
46,0
48,7
43,0
45,7
48,6
50,2
51,9
55,0
49,7
52,8
56,2
60,4
64,6
69,0
59,0
63,1
67,1
72,2
77,4
82,6
66,7
71,3
75,7
80,6
84,6
89,7
75,4
80,6
85,6
90,8
96,1
101,4
86,9
92,9
98,7
105,1
110,2
113,8
93,9
100,4
106,7
113,3
121,4
120,9

14,8
15,3
15,8
16,4
16,8
17,3
17,8
18,4
19,0
19,6
20,2
21,0
22,6
23,3
24,1
24,9
25,8
26,6
27,7
28,6
29,5
30,6
31,6
32,7
30,7
31,7
32,8
34,0
35,2
36,4
37,3
38,5
39,8
41,4
42,7
44,2
42,2
43,6
45,0
46,5
47,3
48,1
48,4
50,0
51,7
53,4
54,4
55,2

30

305 B 00/09 B page 12

46

Evaporator Pressure drops

ALZ HA 011.1 - 020.1 HFC 407C


011.1
Flow rate
Pressure
(l/s)
drop (kPa)

013.1
Flow rate
Pressure
(l/s)
drop (kPa)

017.1
Flow rate
Pressure
(l/s)
drop (kPa)

020.1
Flow rate
Pressure
(l/s)
drop (kPa)

1,02

10

1,18

10

1,44

10

1,71

10

1,31
1,72

15
28

1,45
1,75

15
21

1,61
2,03

14
20

2,02
2,42

14
20

2,02
2,51
2,94

36
52
74

2,12
2,71
3,20

30
47
72

2,51
3,23
4,00

31
50
78

3,10
3,83
4,50

34
49
70

3,24

100

3,74

100

4,56

100

5,42

100

ALZ HA 022.2 - 033.2 HFC 407C


022.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,13
2,62
3,21
3,83
5,06
6,02
6,72

10
15
2
32
54
78
100

025.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,38
2,81
3,23
4,11
5,12
6,42
7,51

10
14
18
30
45
72
100

029.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,94
3,42
4,13
5,09
6,23
7,65
9,28

10
14
19
29
44
68
100

033.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,94
3,41
4,12
5,02
6,21
7,62
9,28

10
14
19
29
44
68
100

305 B 00/09 A pag. 13

Water pump diagrams


Type A water pump
Standard voltage 400/3/50 Motor power 0,75 kW Absorbed current 2,3 A IP 55

200

Hydraulic lift (kPa)

190
180
170
160
150
140
130
120
110
100
0,50

1,00

1,50

2,00

2,50

3,00

3,50

4,00

4,50

Water flow (l/s)

Type B water pump

Hydraulic lift (kPa)

Standard voltage 400/3/50 Motor power 1,5 kW Absorbed current 4,3 A IP 55

190
180
170
160
150
140
130
120
110
100
90
80
70
60
3,00

4,00

5,00

6,00

7,00

8,00

9,00

Water flow (l/s)

N.B. In order to get the net hydraulic lift, subtract the evaporator pressure drop from diagram value.
When you order the unit with the water pump and tank, you must specify the selected type: A or B.

305 B 00/09 B page 14

10,00

ALZ/ALP HA Unit dimensions

Fans Arrangement

ALZ /ALP HA 011.1 020.1

ALZ /ALP HA 022.2 033.2

305 B 00/09 A pag. 15

We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.

McQuay Italia S.P.A.


S.S. Nettunense, km 12+300 00040 Cecchina (Roma) Italia Tel. (06) 937311 Fax (06) 9374014 E-mail: mcquay.italia@pcg.telpress.it Tlx 611349 MCQUAY I