PSM-ME-RS232/RS485-P

Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

1. Short Description
The PSM-ME-RS232/RS485-P rail-mountable and
compact interface converters have been designed
especially for industrial use in the switch cabinet or
switch box. They convert the RS-232 interface signals
bidirectionally to the RS-485 2-/4-wire and RS-422
standard.
The devices are simply snapped onto standard EN
mounting rails and supplied with 24 V DC or AC.
Their particular feature is the multifunctional
application:
RS-232 master interface in RS-485 bus systems
Networking RS-232 equipment
RS-232 range increase to 1000 m as interferencefree and fast point-to-point connection
RS-232 interface adaptation to RS-422 and RS-485
systems
The following features of the interface converter are
particularly outstanding:
3 operating modi can be configured
- RS-232 RS-485-2-wire
- RS-232 RS-485-4-wire
- RS-232 RS-422
Can be used universally in all common bus systems
with UART/NRZ data format and 10/11 bits character
length
Transmission rate can be set between 4.8 kbit/s and
115.2 Mbit/s
Automatic transmit/receive changeover
High-quality 3-way isolation
(VCC // RS-232 // RS-485)
Integrated surge voltage protection with transient
discharge to the mounting rail
Supply voltage of 24 V DC or AC to suit the switch
cabinet
Minimal current consumption/power dissipation

If you have any technical questions, please contact us at:


PSM-HOTLINE:+49/(0)52 35/3-19890
FAX:+49/(0)52 35/3-19899
e-mail: interface-service@phoenixcontact.com

Headquarters: Phoenix Contact GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg Germany
Phone +49-(0) 52 35-3-00 Fax +49-(0) 52 35-3-4 12 00 http://www.phoenixcontact.com

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

1.1. Sample applications


RS-232
1

6
2

7
3

8
4

9
5

RS232

RS485

D(A) D(B) T(A) T(B)


6

GND

Fig. 2a
RS-232

6
2

7
3

8
4

PSMMERS232/RS485P
Ord.-No.: 27 44416

RS-485
PSMMERS232/RS485P
Ord.-No.: 27 44416

RS-232

RS232

RS232

RS485

RS485

D(A) D(B) T(A) T(B)


GND

D(A) D(B) T(A) T(B)

GND

Fig. 2b
1

PSMMERS232/RS485P
Ord.-No.: 27 44416

The RS-485 standard is specified for applications


with multipoint connections. We distinguish between
2-wire bus systems with half-duplex transmission and
4-wire bus systems with full-duplex transmission:
RS-232 master adaptation (fig. 2a)
Programming /and parameterizing connection
(fig. 2a)
Networking RS-232 stations (the software must
guarantee that the stations can be addressed;
(fig. 2b)

RS-485
PSMMERS232/RS485P
Ord.-No.: 27 44416

1.1.1. RS-232 // RS-485 interface converter

6
2

7
3

8
4

9
5

RS232

RS485

D(A) D(B) T(A) T(B)


6

PSMMERS232/RS485P
Ord.-No.: 27 44416

GND

6
2

7
3

8
4

9
5

RS232

RS485

D(A) D(B) T(A) T(B)


6

6
2

7
3

8
4

9
5

PSMMERS232/RS485P
Ord.-No.: 27 44416

GND

RS232

RS485

D(A) D(B) T(A) T(B)


GND

max. 31 stations

1.1.2. RS-232 // RS-422 interface converter

6
2

7
3

8
4

9
5

PSMMERS232/RS485P
Ord.-No.: 27 44416

RS-422

The RS-422 interface is a balanced to earth interface


for point-to-point connections. The logical states are
represented by a differential voltage between two lines.
Areas of application are:
Interface adaptation to RS-422 devices
(fig. 3a).
Interference-free and fast point-to-point connection
up to 1000 m (fig. 3b)

RS-232

Fig. 2

RS232

RS485

D(A) D(B) T(A) T(B)


6

GND

fig. 3a

RS-232

5
RS232

PSMMERS232/RS485P
Ord.-No.: 27 44416

RS-422

PSMMERS232/RS485P
Ord.-No.: 27 44416

RS-232

RS232

RS485

RS485

D(A) D(B) T(A) T(B)


GND

D(A) D(B) T(A) T(B)


GND

Fig. 3b

Fig. 3

PHOENIX CONTACT page 2 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

Type

2. Order data
Interface converter, for the conversion of
RS-232 to RS-485 2-/4-wire or RS-422,
with electrical 3-way isolation, rail-mountable

Order No.

Pcs.
Pkt.

PSM-ME-RS232/RS485-P

27 44 41 6

MCR-PS 230 AC/24 DC/650


MCR-PS 120 AC/24 DC/650

28 11 95 4
28 11 96 7

1
1

SUB-D9/SUB-D9
(socket/socket)

PSM-KA-9SUB 9/BB/2METER

27 99 47 4

SUB-D9/SUB-D25
(socket/socket)

PSM-KA-9SUB 25/BB/2METER

27 61 06 2

socket
pin

SUBCON 9/F-SH
SUBCON 9/M-SH

27 61 49 9
27 61 50 9

1
1

2.1. Accessories
Compact power supply, primary switchedmode, 24 V DC, 650 mA, rail-mountable
RS-232 cable, 2m, to connect the
PSM-ME converter
to a 9-pos. device interface
RS-232 cable, 2m, to connect the
PSM-ME converter
to a 25-pos. device interface
SUB-D plug, 9-pos., with screw
connection for free assembly of an
RS-232 cable

230 V AC
120 V AC

2.2. Technical Data


Supply voltage
Frequency
Rated current consumption
Connection
LED operational availability

24 V AC/DC 20 %
DC-60 Hz
typ. 85 mA
pluggable COMBICON screw terminal block
LED green

RS-232 interface
Type of transmission
Coding option
Data indicator

acc. to DIN 66 259 T1, CCITT V.28


transparent to protocol
DTE/DCE switchover via DIP switch
LED green (RD) RS-232 receive data (dynamic)
LED yellow (TD) RS-232 transmit data (dynamic)
4.8; 9.6; 19.2; 38.4; 57.6; 75; 93.75; 115.2
0...15 m shielded (recommended from 38.4 kbit/s, max.
5 m in industrial applications)
9-pos. SUB-D pin strip

Transmission rates in kbit/s


Transmission length
Connection

acc. to DIN 66 259-4


RS-485 2-wire, half duplex,
RS-485 4-wire, full duplex,
RS-422,
full duplex, can be configured via DIP switch
UART/NRZ1),
10/11 bit
11.5 bit after start bit edge
corresponding to the RS-232 interface
0...1200 m, twisted pair, shielded
either automatic control or control via RS-232 RTS/CTS
RTS/CTS 3V, transmit in direction of RS-485
Inversion possible via DIP switch
switchable, 390 pull up/down, 150 terminating resistance
pluggable COMBICON screw terminal block /shield connector

RS-485/RS-422 interface
Interface standards

Data format/coding
Character length
Tri-State
Transmission rates in kbit/s
Transmission length
Data direction switching

Terminating resistances
Connection

data/shield

3. General data
Protection circuit
Transient discharge
Electrical 3-way isolation
Test voltage
Resistance to vibration
Ambient temperature range
Protection type
Housing:

Material
Dimensions (W / H / D)
Connection data (conductor cross section)
- COMBICON plug connectors
Weight
Approval

Y-capacitors,
suppressor diodes, gas-filled surge arresters
via metal foot on EN mounting rail
power supply // RS-232 // RS-485/RS-422
2 kVrms, 50 Hz, 1 min.
5 g in acc. with IEC 68-2-6
0 C to + 55 C
IP 20
PA-V0
(99 / 22.5 / 118.6) mm
0.2 - 2.5 mm2 (AWG 24-12)
approx. 120 g

1) NRZ: Non Return To Zero


PHOENIX CONTACT page 3 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

Complies with EMC guideline 89/336/EEC

EMC (electromagnetic compatibility)


Immunity to interference in acc. with EN 50082-2
Electrostatic discharge (ESD)

EN 61000-4-2

Criterion B
8 kV discharge in air
6 kV contact discharge

Electromagnetic HF field:
Amplitude modulation:
Pulse modulation:

EN 61000-4-3

Criterion A
10 V/m
10 V/m

Fast transients (Burst)


Signal:
Supply:

EN 61000-4-4

Criterion B
2 kV/5 kHz
4kV/5 kHz

Surge voltage capacities (Surge)


Signal:
Supply:

EN 61000-4-5

Criterion B
2 kV/12
0.5 kV/2

Conducted disturbance

EN 61000-4-6

Criterion A
10 V

EN 55011

Class A

Noise emission in acc. with EN 50081-2

EN 61000 corresponds to IEC 1000


EN 55011 corresponds to CISPR11
Criterion A: Normal operating behavior within the defined limits.
Criterion B: Temporary impairment of operational behavior that the device corrects itself.
Class A: Area of application: industry, without special installation measures.

22,5

118,6

99

Fig. 4

PHOENIX CONTACT page 4 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

Function elements (fig. 5)


1 Supply voltage 24 V AC/DC

2 LED Supply voltage (VCC)

48

5-

3 LED-RS-232 receive data (RD)

3 2

32

/R

5 RS-232 interface connection

Or SM
d.Nr. -M
:2 E
74 44 R
16 S
2

4 LED-RS-232 transmit data (TD)

RS
23
RS
5

A)

48

T(
B)
D( ND
A) G

D(

6 RS-485/RS-422 interface connection

B)
T( 6

7 Shield connector

D
(A
)

-P

85

S4

D
(B
)

T
(B
)

Device-Typ
RS232

/R
32
S2 1 6
-R 4 4
ME 4
M- : 27
PS -Nr.
t.
r
A
DTE

8 Snap-on foot for mounting rails in acc. with


DIN EN 50 022

T
(A
)

ON

ON

RS422

RS485 4-WIRE

RTS/CTS INVERS

RTS/CTS-CONTROLLED

OFF

RS485

RS485 2-WIRE

RTS/CTS STANDARD

SELF-CONTROLLED

N /
NE N
IO E
AT ION
OB AT
PR OB
APPPR
A

DIP-Switch
3
2

OFF OFF
ON
ON
4,8
ON
OFF ON
ON
9,6
OFF
OFF ON
ON
19,2
OFF OFF ON
ON
38,4
OFF OFF OFF
ON
57,6
ON
ON
OFF ON
75
OFF
ON
OFF ON
93,75
OFF ON
OFF ON
115,2

FUNC.
5

SPEED
(kbit/s)

DCE

OFF

Terminate
RS485/RS422

G
N
D

S
AL S
OV AL
PR OV
APPPR
A

8
Fig. 5

4. Operational Diagram

24V
24V
OV
OV

RS - 232

DCE
DTE
TxD

RxD

RTS

CTS

GND

DSR

DTR

2 Wire
O FF
DIP 7
gn

DIP 6

O N (RTS / CTS)
O FF (RTS / CTS)

ON
4 Wire

ye
ON

D(A)
D(B)
DIP 8

O FF (RS 485)
O N (RS 422)

O FF
DATA

DIP 5

+5V
T(A)
T(B)

Bus - Management

2 Wire / 4 Wire

gn

RS - 485
RS - 422

+5V (Port A)

390 150 390

+5V (Port B)
390 150 390

VCC

+5V

+5V

SUB - D 9
pole
Steckbare Schraubklemme
Screw terminal block
Bloc de jonction a`vis
Borne de tornillo

RATE
GND

Shield

Fig. 6

PHOENIX CONTACT page 5 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

5. Notes on connection

24 V

5.1. Connections (fig. 7)

0V

1 Plug connector power supply


Connect 24 V AC/DC 20 % via the COMBICON
plug connector (PIN 1 and 3). Operational availability
is signaled via the VCC LED 2.

7
3

8
4

9
5

4 RS-485/RS-422 interface
pluggable COMBICON screw terminal block

3 RS-232 interface
9-pos. SUB-D pin strip

PSMMERS232/RS485P
Ord.-No.: 27 44416

RS232

RS485

D(A) D(B) T(A) T(B)


6

GND

4
Fig. 7

Or SM
d.Nr. -M
:2 E
74 44 R
16 S
2

32

/R

48

5-

5.2. Mounting in the switch cabinet (fig. 8)


P

Mounting (on 35 mm mounting rails in acc. with


DIN EN 50 022):
Hinge the device into the upper edge of the mounting
rail and snap it in with a downward motion.

RS
23
RS
5

A)

48

T(
B)
D( ND
A) G

D(

B)
T( 6

D
(A
)

-P

85

D
(B
)

T(A
)

DTE

ON

Note: The mounting rail must be


connected to ground potential. This is the
only way to guarantee that the integrated
surge voltage protection functions and
that the shield of the bus conductor
makes contact effectively.

SPEED
(kbit/s)

DCE

G
N
D

6
7
8

ON

RS422

RS485 4-WIRE

RTS/CTS INVERS

RTS/CTS-CONTROLLED

DIP-Switch
3
2

FUNC.
5
SELF-CONTROLLED

OFF OFF
ON
ON
4,8
ON
OFF ON
ON
9,6
OFF
OFF ON
ON
19,2
OFF OFF ON
ON
38,4
OFF OFF OFF
ON
57,6
ON
ON
OFF ON
75
OFF
ON
OFF ON
93,75
OFF ON
OFF ON
115,2

OFF

Terminate
RS485/RS422
RS485

RS485 2-WIRE

OFF

S
AL
OV LS
PR VA
AP PRO
/
P
N / A
E
N
IO EN
AT N
OB TIO
PR BA
AP PRO
AP
RTS/CTS STANDARD

Dismantling:
Pull back the metal disassembling lever 1 with the
aid of a screwdriver and remove the device from the
top.

Device-Typ
RS232

S4
/R
32
S2 41 6
E-R 44
M-M: 27
PS.-Nr.
rt
A

T(B
)

1
Fig. 8

PHOENIX CONTACT page 6 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

6. The RS-232 interface


peripherals side

PSM-ME-RS232...

Designation

SUB-D 9-pos.

Transmit data
Receive data
Clear to send
Request to send
Functional ground
DEE data terminal ready
Data set ready
Ground

TXD
RXD
CTS
RTS
GND
DTR
DSR
6

(pin)
PIN 3
PIN 2
PIN 8
PIN 7
PIN 5
PIN 4
PIN 6
Shield

SUB-D 9-pos.
(pin)

SUB D
25
9

Max.
15 m

TxD
RxD
CTS
RTS
DTR
DSR
GND
6

3
2
8
7
4
6
5

3
2
8
7
4
6
5

TxD
RxD
CTS
RTS
DTR
DSR
GND

2
3
5
4
20
6
7

6.1. Interface coupling


Make a 1-to-1 connection between the PSM module
and the peripheral device as shown in Fig. 9.

Fig. 9

48

5-

Note: For a minimum configuration, you need to


connect TXD, RXD and GND (software handshake)!
Connect the 9-pos. SUB-D plug to the module
(fig.10).

S
OOrrd M
d.-.-N Nr.r.: M
: 227 E
7 444 -R
4 441 S
166 2

32

/R

6.2. Data indicator

RS
23
RS
48

A
T(
B)
D( ND
A) G

D(
)

Two diagnostic LEDs indicate the RS-232 interface


modes
Yellow: Transmit data (TD), dynamic
Green: Receive data (RD), dynamic

B)
T( 6
-P

D
(A
)

85

D
(B
)

T
(A
)

S4
/R
32
S2 41 6
E-R 44
M-M: 27
PS.-Nr.
Art

T
(B
)

Device-Typ
RS232

DTE

ON
SPEED
(kbit/s)

DCE

7
8
RS422
RS485

RS485 2-WIRE

OFF

RTS/CTS STANDARD

SELF-CONTROLLED

ON

RS485 4-WIRE

RTS/CTS INVERS

RTS/CTS-CONTROLLED

DIP-Switch
3
2

N
NE N
IO NE
ATTIO
OBBA
PRRO
APPP
A

FUNC.
5

OFF OFF
ON
ON
4,8
ON
OFF ON
ON
9,6
OFF
OFF ON
ON
19,2
OFF OFF ON
ON
38,4
OFF OFF OFF
ON
57,6
ON
ON
OFF ON
75
OFF
ON
OFF ON
93,75
OFF ON
OFF ON
115,2

OFF

Terminate
RS485/RS422

G
N
D

S
ALLS
OVVA
PRRO
APPP
A

Fig. 10
6.3. Configuration

S2

32

/R

74

44

16

E-R

Or

d.-

PS

M
M-

:2

Nr.

For configuration, release the top of the housing on


both sides 1. Pull the p.c.b. out of the housing as far
as possible 2 (fig. 11).

RS

Static charges can damage electronic


devices.
Discharge the electrical charge from your
body before opening and configuring the
device.
To do so, touch a grounded surface, e.g.
the metal housing of the switch cabinet.

23
RS
48

A
T(
B)
D( ND
A) G

D(
)

B)
T( 6

D
(A
)

D
(B
)

T(
A
)

T(
B
)

ON

OFF

Terminate
RS485/RS422

G
N
D

FUNC.
5
6
7
8

ON

RS422

RS485 4-WIRE

RTS/CTS INVERS

RTS/CTS-CONTROLLED

OFF

RS485

RS485 2-WIRE

RTS/CTS STANDARD

SELF-CONTROLLED

IO
AT
OB TIO
PR BA
AP PRO
P

Fig. 11

PHOENIX CONTACT page 7 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

6.4. DTE/DCE switchover (fig. 12)


DTE/DCE
The DTE/DCE slide switches can be used to cross
the cables TXD and RXD as well as RTS and CTS
internally so that an adaptation to DTE or DCE
interfaces can be performed easily.

ON
DTE

For the connection to:


Data terminal equipment (DTE) switch to position
DTE.
(Standard setting for most applications)

ON 10
9
8
7
6
5

PSM-ME-RS232/RS485-P
Art.-Nr.: 27 44 41 6

DCE

Device-Typ
RS232

DTE

OFF

Terminate
RS485/RS422

ON

1
2
3

OFF

DIP-Switch

(kbit/s)

SPEED

OFF

ON
OFF
ON
OFF

ON

RTS/CTS STANDARD

SELF-CONTROLLED

ON

RS485

RS485 2-WIRE

ON
OFF
ON

ON
OFF

RTS/CTS-CONTROLLED

ON
ON
OFF
OFF
ON
ON
OFF

RTS/CTS INVERS

OFF
OFF
OFF
OFF
ON
ON
ON

RS422

RS485 4-WIRE

ON
ON
ON
ON
OFF
OFF
OFF

4,8
9,6
19,2
38,4
57,6
75
93,75
115,2

6
7
8

FUNC.

If the connected interface type is unknown, you can


determine the right configuration by trial and error
(DTE/DCE switch).

ON

Data communication equipment (DCE) switch to


position DCE.

ON 410
3
2 9
1
8
7
6
5
4
3
2
1

APPROBATIONEN / APPROVALS

Fig. 12
6.5. CTS/RTS support (DIP switch 5)
In normal operating mode, no control lines (RTS/
CTS) are required for data direction switching (switch
position DIP 5 "OFF").
The data direction switching can alternatively be
controlled through the RTS/CTS lines. Set the DIP
switch 5 to the "ON" position.

6.6. RTS/CTS inversion (DIP switch 6)


In uncommon applications, the control lines must be
inverted. Set the DIP switch 6 to the "ON" position
(default: "OFF"). The signal position in inverse mode is
then as follows:

RS - 232

Function:
RTS/CTS 3 V to 15 V = RS-485 receive mode
RTS/CTS +3 V to +15 V = RS-485 transmit mode

DCE
DTE
TxD

RxD

RTS

CTS

GND

DSR

DTR

RTS/CTS +3 V to +15 V = RS-485 receive mode


RTS/CTS -3 V to -15 V = RS-485 transmit mode

PHOENIX CONTACT page 8 of 12

DIP 6

DATA

S1

O N (RTS / CTS)
O FF (RTS / CTS)

Bus - Man

RATE

Fig. 13

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

7. The RS-485/RS-422 interface

D(A)
D(B)
GND

Pin configuration
Designation

COMBICON

Data line (+)


Data line ()
Signal ground
Ground/shielded connection

D(B)
D(A)
GND
6

PSM-ME-RS-485

7.1. Operation as RS-485 2-wire interface

(pin)

PSM-ME-RS-485

1
2
6
6

1
2
6
6

PIN 2
PIN 1
PIN 6
PIN 8

D(A)
D(B)
GND

Shield

COMBICON

Fig. 14

Settings:
1) As described in the section "RS-232 interface", set the operating mode of the RS-232
interface with DIP switch 5 and 6 and
the type of interface with the DTE/DCE
switchover switch.

DTE/DCE

RS-485 Terminate

ON
DTE

Note: If automatic operating mode


is selected, no control lines from the
RS-232 interface are required.

ON 10
9
8
7
6
5

ON 410
3
2 9
1
8
7
6
5
4
3
2
1

PSM-ME-RS232/RS485-P
Art.-Nr.: 27 44 41 6

DCE

Device-Typ
RS232

DTE

OFF

Terminate
RS485/RS422

ON

ON

ON

ON

OFF

DIP-Switch

(kbit/s)

SPEED

Fig. 15

ON
ON
OFF
OFF
ON
ON
OFF

RTS/CTS

SELF-CO

RS485 2-

OFF
OFF
OFF
OFF
ON
ON
ON

ON

RS422

RTS/CTS-CONTROLLED

RTS/CTS INVERS

RS485 4-WIRE

ON
ON
ON
ON
OFF
OFF
OFF

6
7
8

FUNC.
5

4,8
9,6
19,2
38,4
57,6
75
93,75
115,2

2) If the automatic operating mode was selected,


set the transmission rate with the aid of DIPswitches S1-S4 (fig. 15) and the table
below.
All PSM converters and bus stations must
be set to the same transmission rate!

RS

T(
)
(B D
GN

A)

48

B)
T( 6

The interface converters only convert an electric


signal.

D
(A
)

D
(B
)

T
(A
)

3) Set DIP switch 8 to position "OFF" to activate the


RS-485 operating mode.

T
(B
)

ON

4) Set DIP switch 7 to "OFF" to activate the 2-wire


mode.

7
ON

RS48

RTS/CT

Use shielded twisted pair cables.


Connect the cable shield to both sides of
the transmission path!

OFF

The data cables are shielded using a shield terminal


block that is fixed in the 6 terminal block (fig. 16). The 6
terminal block is connected capacitively to the
mounting rail contact on the underside of the device.
The shield connector is included in the scope of
delivery.

RTS/CTS-C

Fig. 16
SPEED
(kbit/s)
4,8

Shielding the data cables

115,2

6) To couple two RS-485 interfaces, connect the


connections acc. to fig. 14. (1 = twisted pair)
GND connection is recommended, but is not
essential.

FUNC.
5

5) If necessary, activate the terminating resistors


fig. 15 (Please observe the section 8 on
"Terminating resistor for the RS-485/RS-422
interface", page 12).

OFF

Terminate
RS485/RS422

G
N
D

DIP
1

ON

ON

OFF

OFF

9.6

ON

OFF

ON

ON

19.2

ON

OFF

ON

OFF

38.4

ON

OFF

OFF

ON

57.6

ON

OFF

OFF

OFF

75

OFF

ON

ON

ON

93.75

OFF

ON

ON

OFF

OFF

ON

OFF

ON

115.2
FUNC.
DIP

ON

OFF

RTS/CTS-CONTROLLED

SELF-CONTROLLED

RTS/CTS INVERS

RTS/CTS STANDARD

RS485 4-WIRE

RS485 2-WIRE

RS422

RS485

PHOENIX CONTACT page 9 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

7.2. Operation as RS-485 4-wire interface


PSM-ME-RS-485

Pin configuration
Designation

COMBICON

Receive data (+)


Receive data ()
Transmit data (+)
Transmit data ()
Signal ground
Ground/shielded connection

D(B)
D(A)
T(B)
T(A)
GND
6

(pin)

D(B)
D(A)
T(B)
T(A)
GND

PIN 2
PIN 1
PIN 4
PIN 3
PIN 6
PIN 8

PSM-ME-RS-485

2
1
4
3
6

2
1
4
3
6
6

D(B)
D(A)
T(B)
T(A)
GND

Shield
COMBICON

Settings:

Fig. 17

1) Set as described in the section "RS-232 interface" the operating mode of the RS-232
interface using DIP switch 5 and 6 and
the type of interface with the DTE/DCE
switchover switch.

DTE/DCE

RS-485 Terminate

ON
DTE

Note: If automatic operating mode


is selected, no control lines from the
RS-232 interface are required.

ON 10
9
8
7
6
5

2) If the automatic operating mode was selected,


set the transmission rate with the aid
of DIP-switches S1-S4 (fig. 18) and the table
below.

PSM-ME-RS232/RS485-P
Art.-Nr.: 27 44 41 6

DCE

Device-Typ
RS232

DTE

OFF

Terminate
RS485/RS422

ON

ON

ON

ON

OFF

DIP-Switch

(kbit/s)

SPEED

Fig. 18

ON
ON
OFF
OFF
ON
ON
OFF

RTS/CTS

SELF-CO

RS485 2-

OFF
OFF
OFF
OFF
ON
ON
ON

ON

RS422

RTS/CTS-CONTROLLED

RTS/CTS INVERS

RS485 4-WIRE

ON
ON
ON
ON
OFF
OFF
OFF

6
7
8

4,8
9,6
19,2
38,4
57,6
75
93,75
115,2

FUNC.
5

All PSM converters and bus stations must


be set to the same transmission rate!

ON 410
3
2 9
1
8
7
6
5
4
3
2
1

B)
T( 6

D
(A
)

D
(B
)

T
(A
)

3) Set DIP switch 8 to position "OFF" to activate the


RS-485 operating mode.

T
(B
)

P
A

ON

4) Set DIP switch 7 to "ON" to activate the 4-wire


mode.

93,75
115,2

7
ON

ON

RS

RS485 4-WIR

RTS/CTS INVE

OFF

RTS/CTS-CONTR

Use shielded twisted pair cables.


Connect the cable shield to both sides of
the transmission path!

The data cables are shielded using a shield terminal


block that is fixed in the 6 terminal block (fig. 19).
The 6 terminal block is connected capacitively to the
mounting rail contact on the underside of the device.
The shield connector is included in the scope of
delivery.

FUNC.
5

Shielding the data cables

OFF

Terminate
RS485/RS422

G
N
D

5) If necessary, activate the terminating


resistors fig.18 (Please observe the section 8 on
"Terminating resistor for the RS-485/RS-422
interface", page 12).
6) To couple two RS-48 interfaces, connect the
connections acc. to fig. 17. (1 = twisted pair)
When connecting the device, take into account
that it is necessary to cross transmitted and
received data.
GND connection is recommended, but is not
essential.

The interface converters only convert an electric


signal.

Fig. 19
SPEED
(kbit/s)
4,8

DIP
1

ON

ON

OFF

OFF

9.6

ON

OFF

ON

ON

19.2

ON

OFF

ON

OFF

38.4

ON

OFF

OFF

ON

57.6

ON

OFF

OFF

OFF

75

OFF

ON

ON

ON

93.75

OFF

ON

ON

OFF

OFF

ON

OFF

ON

115.2
FUNC.
DIP

ON

OFF

RTS/CTS-CONTROLLED

SELF-CONTROLLED

RTS/CTS INVERSE

RTS/CTS STANDARD

RS485 4-WIRE

RS485 2-WIRE

RS422

RS485

PHOENIX CONTACT page 10 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

7.3. Operation as RS 422 interface


Pin configuration
Designation

COMBICON

(pin)

PSM-ME-RS-422

Receive data (+)


Receive data ()
Transmit data (+)
Transmit data ()
Signal ground
Ground/shielded connection

D(B)
D(A)
T(B)
T(A)
GND
6

PIN 2
PIN 1
PIN 4
PIN 3
PIN 6
PIN 8

D(B)
D(A)
T(B)
T(A)
GND

PSM-ME-RS-422

2
1
4
3
6

D(B)
D(A)
T(B)
T(A)
GND

2
1
4
3
6
6

Settings:

Shield
COMBICON

1) Set the DIP switch 8 to position.


"ON" to activate the RS-422 operating mode
(fig. 21).
2) Set as described in the section "RS-232 interface" the interface type of the RS-232 interface
with the DTE/DCE switchover switch.
Note: In this operating mode, no
control lines from the RS-232 interface are
required and none are transmitted.

Fig. 20
RS-422 Terminate "ON"
DTE/DCE

3) Switch the line terminating resistor on both sides


of the RS422 transmission link on. Put
"Terminate" slide switch to "ON".

ON
DTE

4) To couple two RS-422 interfaces, connect the


connections acc. to fig. 20. (1 = twisted pair)
When connecting the device, take into account
that it is necessary to cross transmitted and
received data.
GND connection is recommended, but is not
essential.

ON 10
9
8
7
6
5

DIP 8

ON 410
3
2 9
1
8
7
6
5
4
3
2
1

PSM-ME-RS232/RS485-P
Art.-Nr.: 27 44 41 6

DCE

Device-Typ
RS232

DTE

OFF

Terminate
RS485/RS422

ON

ON

1
2
3

OFF

DIP-Switch

(kbit/s)

SPEED

OFF

ON
OFF
ON
OFF

ON

RTS/CTS STANDARD

SELF-CONTROLLED

ON

RS485

RS485 2-WIRE

ON
OFF
ON

ON
OFF

RTS/CTS-CONTROLLED

ON
ON
OFF
OFF
ON
ON
OFF

RTS/CTS INVERS

OFF
OFF
OFF
OFF
ON
ON
ON

RS422

RS485 4-WIRE

ON
ON
ON
ON
OFF
OFF
OFF

4,8
9,6
19,2
38,4
57,6
75
93,75
115,2

6
7
8

FUNC.

APPROBATIONEN / APPROVALS

Fig. 21

RS

Shielding the data cables

23
RS
48

A
T(
B)
D( ND
A) G

D(
)

B)
T( 6

D
(A
)

D
(B
)

T
(A
)

M
MPS.-N
t
Ar

T
(B
)

ON

The data cables are shielded using a shield terminal


block that is fixed in the 6 terminal block (fig. 22). The
6 terminal block is connected capacitively to the
mounting rail contact on the underside of the device.
The shield connector is included in the scope of
delivery.

57,6
75
93,75
115,2

6
7
8

ON

RS422

RS485 4-WIRE

RTS/CTS INVERS

RTS/CTS-CONTROLLED

OFF

RS485

RS485 2-WIRE

RTS/CTS STANDARD

SELF-CONTROLLED

OFF OFF OFF


ON
ON
ON
OFF ON
OFF
ON
OFF ON
OFF ON
OFF ON

FUNC.
5

Use shielded twisted pair cables.


Connect the cable shield to both sides of
the transmission path!

OFF

Terminate
RS485/RS422

G
N
D

/
N /
NE N
IO E
AT ION
B
O AT

Fig. 22
PHOENIX CONTACT page 11 of 12

PSM-ME-RS232/RS485-P
Interface converter for RS-232 to RS-485 2-/4-wire or RS-422

PSMMERS232/RS485P
Ord.-No.: 27 44416

A connectable line terminating resistor is integrated


in the converter and it must be switched on or off,
depending on the application.

PSMMERS232/RS485P
Ord.-No.: 27 44416

8. Set the line terminating resistor


correctly in RS-485 and RS-422 mode.

RS232

RS232

RS485

RS485

D(A) D(B) T(A) T(B)

D(A) D(B) T(A) T(B)

GND

GND

6
2

7
3

8
4

9
5

RS-485 is the standard for a multi-point-capable


connection (up to 32 terminals).
The RS-485 bus line may only be terminated at the
two most distant bus ends.
"Terminate" slide switch to "ON"
at the beginning and end of the bus line
(fig. 23).

PSMMERS232/RS485P
Ord.-No.: 27 44416

8.1. In RS-485 mode (2/4-wire)


RS232

RS485

D(A) D(B) T(A) T(B)


6

GND

= Bus terminating resistor "ON"

Fig. 23

RS232

RS485

RS485

D(A) D(B) T(A) T(B)

GND

= Terminating resistor "ON"

Fig. 24

http://www.phoenixcontact.com

GND

RS 485/RS 422 Terminate

ON
DTE

ON
DTE

DTE
Device-Typ
RS232
DCE

OFF

Terminate
RS485/RS422

ON

TNR: 5104422-01

PSM-ME-RS232/RS485-P
Art.-Nr.: 27 44 41 6

ON 10
9
8
7
6
5
4
3
2
1

FU

Fig. 25

PHOENIX CONTACT page 12 of 12

30.07.99

D(A) D(B) T(A) T(B)

PHOENIX CONTACT

PSMMERS232/RS485P
Ord.-No.: 27 44416

6
RS232

RS-422 is the standard for a point-to-point connection between two devices. The line terminating resistor
on both sides of the RS-422 transmission link must be
switched on.
"Terminate" slide switch always in "ON" position
(fig. 24).

PSMMERS232/RS485P
Ord.-No.: 27 44416

8.2. In RS-422 mode