Documentos de Académico
Documentos de Profesional
Documentos de Cultura
T-124-1A(m)
Limite de
m
aproximacion
Table 124-1
segura de acuerdo
Clearances from live parts
PART ALow, medium, and high voltages (based on BIL factors) al NESC-2007
Column 1
Column C
Column 2
Column 3
Column 4
Maximum design
voltage between
phases
Basic impulse
insulation level t
(BIL)
Vertical clearance of
unguarded parts q
Horizontal
clearance of
unguarded parts q
Clearance guard
to live parts q
kV
kV
mm
0.3
Not specified
Not specified
Not specified
0.6
2.64
1.02
50
2.4
2.67
1.02
76
7.2
95
2.69
1.02
101
15
95
2.69
1.02
101
15
110
2.74
1.07
152
25
125
2.77
1.09
177
25
150
2.82
1.14
228
35
200
2.90
1.22
304
48
250
3.00
1.32
406
72.5
250
3.00
1.32
406
72.5
350
3.18
1.50
584
121
350
3.18
1.50
584
121
550
3.53
1.85
939
145
350
3.18
1.50
584
145
550
3.53
1.85
939
145
650
3.71
2.03
1117
169
550
3.53
1.85
939
169
650
3.71
2.03
1117
169
750
3.91
2.24
1320
242
550
3.53
1.85
939
242
650
3.71
2.03
1117
242
750
3.91
2.24
1320
242
900
4.19
2.51
1600
242
1050
4.52
2.84
1930
43
T-124-1D(ft)
125A2
ft
Column 1
Column A
Column B
Column 2
Column 3
Column 4
Maximum
design voltage
conductor to
ground
Transient
overvoltage
per unit r
Transient
overvoltage
line to grnd r
Vertical
clearance of
unguarded
parts q
Horizontal
clearance of
unguarded
parts q
Clearance
guard to live
partsq
kV
ft
in
ft
in
ft
in
kV
600
1.5 or below
900
20
10
15
12
600
1.6
960
22
16
13
600
1.7
1020
23
17
11
14
11
600
1.8
1080
24
10
19
16
750
1.5 or below
1125
25
11
20
17
750
1.6
1200
27
22
19
750
1.7
1275
29
24
21
750
1.8
1350
31
11
26
23
q Interpolate for intermediate values. The clearances in column 4 of this table are solely for guidance in installing
guards without definite engineering design and are not to be considered as a requirement for such engineering
design. For example, the clearances in the tables above are not intended to refer to the clearances between live
parts and the walls of the cells, compartments, or similar enclosing structures. They do not apply to the clearances
between bus bars and supporting structures nor to clearances between the blade of a disconnecting switch and its
base. However, where surge-protective devices are applied to protect the live parts, the vertical clearances,
column 2 of Table 124-1 Part A may be reduced provided the clearance is not less than 8.5 ft plus the electrical
clearance between energized parts and ground as limited by the surge-protective devices.
wClearances shall satisfy either switching-surge or BIL duty requirements, whichever are greater.
e Switching-surge factoran expression of the maximum switching-surge crest voltage in terms of the maximum
operating line-to-neutral crest voltage of the power system.
r The values of columns A, B, and C are power system design factors that shall correlate with selected clearances.
Adequate data to support these design factors should be available.
t The selection of station BIL shall be coordinated with surge-protective devices when BIL is used to determine
clearance. BILbasic impulse insulation levelfor definition and application, see IEEE Std 1313-1993.
Clear spaces
Working space required by this section shall not be used for storage. When normally enclosed
energized parts are exposed for inspection or servicing, the working space, if in a passageway
or general open space, shall be guarded.
2.
51
125A3
127
3.
Working space
The working space in the direction of access to energized parts operating at 600 V or less that
require examination, adjustment, servicing, or maintenance while energized shall be not less
than indicated in Table 125-1. In addition to the dimensions shown in Table 125-1, the working
space shall be not less than 750 mm (30 in) wide in front of the electric equipment. Distances
shall be measured from the energized parts if such are exposed or from the enclosure front or
opening if such are enclosed. Concrete, brick, or tile walls shall be considered grounded.
4.
5.
B.
Voltage to ground
Condition 1
Condition 2
Condition 3
mm
ft
mm
ft
mm
ft
0150
900
900
900
151600
900
1070
3-1/2
1200
aproximacion
seguro de acuerdo
al NESC-2007
When it is necessary for personnel to move themselves, material, or tools within the guard zone of
unguarded energized parts, protective equipment shall be provided.
This protective equipment shall be periodically inspected, tested, and kept in a safe condition.
Protective equipment shall be rated for not less than the voltage involved. Refer to Section 3 for a
list of specifications for equipment.