1. Check the foundation with regards to the general assembly drawing. 2. Maintain the foundation as even as possible 3. Mark the center lines. Description Remarks and Measured alues Static Parts 1. !ositioning of the "nlet cone 2. #ightening of fi$ing bolts on the ducts 3. #ightening of the fi$ing of static parts. %. Check alignment of base frame with precision level. #he permissible deviation is &.&% mm' meter (. Check the level) height and center of bearing pedastal. *. Maintain the center a$is of the shaft and casing as per +, drawing. -. Check tightness of Motor foundation bolts. Rotor Assembly 1. .nsure that inlet cone /s0 is placed along with the rotor 2. ,d1ust the thermal e$pansion clearances in free bearing 3. Check the alignment of impeller shaft with precision level. #he permissible deviation is &.&% mm 'meter %. Check the bearing alignment /ref vendor manual0 (. Check the alignment of fan motor coupling. *. Check the tightness of fi$ing bolts of impeller ' hub Coupli! Ali!met 1. Check the height level variation of coupling levels. 2. Maintain the gap between coupling halves as per dimension 3. Check the level and alignment of motor with respect to the fan shaft %. Check the alignment of motor with respect to the fan coupling. !age 1 of 2 EECC - THANE Pre Start C"ec#s 1. .nsure that the "mpeller handling matches with the fan casing 2. Check the mounting of the bearing housings and electric motor 3. Check that the coupling is tightened properly %. Check that the foundation bolts are tightened properly (. Check that the connecting flanges between the fan and ducting are good) and proper packing is provided *. Check that different components of the control system are correctly connected. -. Check that the inlet damper is fully closed. 2. Check the operation of fluid couplings /in case the fan is provided with fluid coupling 0 3. Check that no foreign material has been left anywhere inside the fan. 1&. Check that no water stays in the bottom of the casing and inlet bo$. 11. Check that specified guards have been fitted 12. Check that the inspection door on the casing and inlet bo$ are correctly shut. 13. Check that rotor can run freely without rubbing with any static parts. 1%. Check that the bearings have been correctly filled with bearing lubricant. 1(. Check the direction of rotation of motor in decoupled condition and ensure that direction of rotation is correct. /"f re4uired carryout further checks as per recommendation of manufacturer'as per 5 6 M manual0 !age 2 of 2