JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.

Address: No. 5, West Huimin Road, Economic Development Zone, Rugao, Jiangsu Province, P.R.China.
Zip code: 226572
Tel: 0086-513-87303629
Fax: 0086-513-87530056
Email: Marketing@sieyuan.net
Http://www.sieyuan.net
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO.,LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

!
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. conducts research and development on
technically advanced and safe quality products on its own, including:
35-500 kV Oil Impregnated Inverted Current Transformers,
35-500 kV Sulfur Hexafluoride Gas Insulated Inverted Current Transformers,
35-500 kV Capacitor Voltage Transformers,
35-500 kV Sulfur Hexafluoride Gas Insulated Voltage Transformers for mounting in GIS,
35-220 kV Inductive Voltage Transformers,
10-220 kV Oil Impregnated Tank type Current Transformers,
35-110 kV Dry type Current Transformers and Dry Graded Wall Bushing, etc.
The products have obtained KEMA test certification in Holland, as well as inspection and examination
by national authorities.
Sieyuan Hertz leads the instrument transformer trade to a higher level at a sustained speed, with ardent
enthusiasm, prudent attitude
and customer orientation.
Jiangsu Sieyuan Hertz Instrument Transformer Co., Ltd. ( www.sieyuan.net ) covers the land
area of more than 100,000 square meters and the construction area of over 60,000 square
meters, which is within the factory area of more than 50,000 square meters. With a sealing &
purifying workshop up to 100,000 grade, it is regarded as a world-class instrument transformer
production base in China.
Sieyuan Hertz has a R&D and management team with the most competitive power, it now has
more than 400 employees, among the employees, the percent of engineering and technology
talents who got Ph. D or master degree or graduated from universities is 45%, and the
Company also invites foreign professionals to take charge of the technology and quality
management.
Sieyuan Hertz leads the instrument transformer trade to a
higher level at a sustained speed, with ardent enthusiasm,
prudent attitude and customer orientation.
Company Brief
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Comp any Brief
1 2
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Advanced Facilities
In order to realize the product design con-
cept and reduce the uncertainty brought by
manual operation, during the production
process, Siyuan Hertz adopts automatic pro-
duction equipments.
World Class Testing Condition
Secondary Coil Winding Machine Capacitance Graded Bushings Wind-
ing Machines
German Welding Robots
Sieyuan Hertz has the world-classy testing conditions and perfect testing equipments, including three
six-facet shielding high voltage testing laboratory with the rated voltage 1000 kilovolt, 600 kilovolt, 300
kilovolt and also an impulse voltage generator up to 3000 kilovolt with automatic measuring system.
In the profession field, the company introduces firstly the partial discharge test in power frequency
withstand voltage, which is more stringent than national and IEC standards, and ensures much more
reliance and safety for product running.
Transient Characteristics Tester for
Current Transformer
600kV Power Frequency Testing Trans-
former
300kV Power Frequency Testing Trans-
former
1000kV Power Frequency Testing
Transformer
3000kV Lightning Impulse Generator
High Frequency Capacitance and Stray
Capacitance Meter
Ferro-resonance Testing Analysis Sys-
tem for Capacitor Voltage Transformer
(CVT)
3 4
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Ger man Leybol d


Vacuum Treat ment
System
Capacitance Graded Bushings Winding
Machine for SF6 Gas Insulated Products
Assembly Shop for SF6 Gas Insulated
Current Transformer
German B&R Aptitude Coil Machine
Sieyuan Hertz promotes total quality management and strictly abiding by
ISO9000 quality management system, the regulation of technical re-
quirement is quite clear and uniform from parts inspection to routine test,
so as to ensure the whole production under control and the products can
be traced back. To ensure the product quality meeting international
standards, all major raw materials are imported from foreign countries,
such as: cable paper, semiconducting paper, aluminum foil, transformer
oil, insulating material for sulfur hexafluoride gas insulated products,
enameled wire and compacting material for product etc.
Sieyuan Hertz consistently follows the mission of "service creates value" by professional, speedy,
sincere and quality service. We endeavor to help lower our customer' operation costs while improving
their business efficiency and competitiveness.
Sieyuan Hertz is committed to offer our customers with products featuring "high-safety", "high-
reliance", "high-accuracy" and "high-standardization". Since our foundation, the company has gained
earnest support from users in all lines. At present, our sales network covers all the cities in China and
overseas markets. In north, east, south, and mid China, northwest and northeast China, sales offices
and after-sale service stations have been established. In addition, the company has established
perfect partnership with State Grid Corporation of China, and China Southern Power Grid Co., Ltd.,
Sieyuan Hertz has continuously won bids in major power station projects in Vietnam, Burma and
Nigeria, which marks that our products have known worldwide.
Reliable Products & Quality
ISO9000 Quality System Certificate (SGS)
General Customer Service
Hebei Electric Power
Corporation, China
Jiangsu Electric Power Corporation, China
500kV SF6 Gas Insulated Inverted Cur-
rent Transformers
Zhejiang Electric Power Corporation,
China 500kV Oil Impregnated Inverted
Current Transformers
Shanxi Electric Powr
Corporation, China
Jiangsu Electric Power
Corporation, China
Jilin Electric Power
Corporation, China
Ningxia Electric Power
Corporation, China
Nanjing Electric
Power
Corporation,
China
Shanxi Electric Power
Corporation, China
Guangdong Electric
Power Corporation,
China
5 6
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Symbol Explanation
LVB Series Oil Immersed Inverted Current Transformers
L V B (T)
Antipollution Class (W2, W3)
Voltage Grade (kV)
With Transient Protection
With Protection
Inverted
Current Transformer
LVB (T) series current transformer has an inverted structure with oil-immersed paper insulation (Please see the left figure).
It is connected in series with electric energy measurement, measuring, relay protection and transient protection functions.
Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal
current can be up to 63kA/3s (when primary coil is connected in series).
Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1and
0.2S grades.
Secondary coil is fixed in an aluminum shielded-case by casting organic materials; secondary measurement and
protection circuits cannot be damaged by insulation breakdown.
Optimal capacitor screen bushing is made of a complete piece of imported broadsheet cable paper; it is coiled by an
automatic wrapping machine which is controlled by a computer with high performance. It has a technological de-centrality
and an excellent insulation property. Partial discharge test is carried out under power frequency test voltage.
Use the automatic vacuum drying treatment system produced by LEYBOLD in Germany, carry out pressure-changing
vacuum drying treatment and oiling after a product is assembled completely, and all insulation materials are imported from
foreign countries. All these ensure that the dielectric dissipation factor of complete product tan_ is less than 0.3%.
External insulation uses a porcelain cover with high strength, optimal surface field intensity together with lower field
intensity of internal bushing make the porcelain cover avoid explosion.
Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement
of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; it
is more convenient for operations such as plug-in, pull-out and wiring etc.
Connection between components uses argon-arc welding, fill in high pressure nitrogen to detect leakage after assembly
is complete, so oil penetration and oil leakage caused by oil-immersed products are resolved at root.
Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and
nameplate etc do not rust forever.
It is light and handy with a small volume and light weight.
This product is free-maintenance.
Introduction to Structure
Stainless Steel Expander
Primary Terminal Plate on P1 Side
Bushing
Core and winding assembly
Porcelain Cover
Oil Drain Value
Nameplate
Secondary Terminal Box
Oil Level Observation Window
Primary Terminal Plate on P2 Side
7 8
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Technical Parameters of LVB (T) - 35


LVB-35W2/1X LVB-35W3/1X LVB(T)-35W2/2X LVB(T)-35W3/2X
Technical Parameters of LVB 66
LVB-66W2/1X LVB-66W3/1X LVB-66W2/2X LVB-66W3/2X
Type
LVB-66W2/1X LVB-66W3/2X
LVB-66W3/1X LVB-66W3/2X
Highest voltage for equipment kV 72.5
Rated frequency Hz 50/60
Rated power-frquency withstand voltage (rms) kV 160
Rated lightning impulse withstand voltage (full wave)(peak) kV 350
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403
Flashover distance mm 700
Creepage distance mm 1812/2250
Rated primary current (Maximum) A 4000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S;0.5S;5P;10P;TPU;TPS
Rated output VA 10-50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 63kA/3s (In series)
Dynamic current (Maximum) kA 160
Allowable mechanical load of transformer: Static N 3000
Allowable mechanical load of transformer: Dynamic N 5000
Net weight kg 200 450
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Type
LVB-35W2/1X LVB(T)-35W2/2X
LVB-35W3/1X LVB(T)-35W3/2X
Highest voltage for equipment kV 40.5
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 95
Rated lightning impulse withstand voltage(full wave)(peak)kV 200
Rated lightning impulse withstand voltage (Chopped wave) (Peak) kV 230
Flashover distance mm 500
Creepage distance mm 1015/1260
Rated primary current (Maximum) A 4000(8000)
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P;TPY;TPS
Rated output VA 10-50
Safety factor FS 5;10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 63kA/3s (In series)
Dynamic current (Maximum) kA 160
Allowable mechanical load of transformer (Static) N 3000
Allowable mechanical load of transformer (Dynamic) N 5000
Net weight kg 170 420
Outline and Dimensional Drawing Outline and Dimensional Drawing
9 10
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LVB-110(132)W2/1X
LVB-110(132)W3/1X
LVB-110(132)W2/2X
LVB-110(132)W3/2X
LVB-110(132)W2/3X
LVB-110(132)W3/3X
11 12
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Outline and Dimensional Drawing


Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Technical Parameters of LVB-110
Type
LVB-110W2/1X LVB-110W2/2X LVB-110W2/3X
LVB-110W3/1X LVB-110W3/2X LVB-110W3/3X
Highest voltage for equipment kV 126
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashover distance mm 1200
Creepage distance mm 3150/3910
Rated primary current (Maximum) A 4000
Rated secondary current A 1;5
Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 50kA/3s (In series)
Dynamic current (Maximum) kA 125
Allowable mechanical load of transformer (Static) N 3000
Allowable mechanical load of transformer (Dynamic) N 5000
Net weight kg 230 475 525
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Technical Parameters of LVB-132
Type
LVB-132W2/1X LVB-132W2/2X LVB-132W2/3X
LVB-132W3/1X LVB-132W3/2X LVB-132W3/3X
Highest voltage for equipment kV 145
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 275
Rated lightning impulse withstand voltage (full wave)(peak) kV 650
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 748
Flashover distance mm 1200
Creepage distance mm 3625/4495
Rated primary current (Maximum) A 4000
Rated secondary current A 1;5
Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 50kA/3s (In series)
Dynamic current (Maximum) kA 125
Allowable mechanical load of transformer (Static) N 3000
Allowable mechanical load of transformer (Dynamic) N 5000
Net weight kg 230 475 525
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Technical Parameters of LVB (T)-330500
Outline and dimensional drawings for
LVB(T)-330W2 Current Transformer
Outline and dimensional drawings for
LVB(T)-500W2 Current Transformer
Outline and Dimensional Drawing
Type LVB (T) -330W2 LVB (T) -500W2
Highest voltage for equipment kV 363 550
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 510 740
Rated lightning impulse withstand voltage (full wave)(peak) kV 1175 1675
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352 1930
Impulse withstand voltage (Wet Test) kV 950 1175
Flashover distance mm 2650 4000
Creepage distance mm 9100 13750
Rated primary current (Maximum) A 5000 5000
Rated secondary current A 5; 1 5; 1
Accuracy classes (they can be combined if necessary) 0.2S; 0.5S; 0.1; 0.2S; 0.5S; 0.1;
0.2; 0.5; 5P; 10P; TPY 0.2; 0.5; 5P; 10P; TPY
Rated output VA 10~50 10~50
Safety factor FS 5; 10 5; 10
Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40
Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30
TPY Parameter Operating cycle C-O-C-O
Output capacity VA 10, 15
Thermal current (Maximum) kA 63 kA / 3s ( in series )
Dynamic current (Maximum) kA 160 ( in series )
Weight of oil 280 432
Net weight 1000 2250
Gross weight 1300 3000
13 14
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LVB-220W2/1X LVB-220W3/1X LVB-220W2/2X LVB-220W3/2X


Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Technical Parameters of LVB (T)-220
Type
LVB-220W2/2X LVB (T)-220W2/3X
LVB-220W3/2X LVB (T)-220W3/3X
Highest voltage for equipment kV 252
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 460
Rated lightning impulse withstand voltage (full wave)(peak) kV 1050
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208
Flashover distance mm 2200
Creepage distance mm 6300/7900
Rated primary current (Maximum) A 4000
Rated secondary current A 15
Accuracy classes (they can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P; TPY; TPS
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 63kA/3s (In series)
Dynamic current (Maximum) kA 160
Allowable mechanical load of transformer: Static N 4000
Allowable mechanical load of transformer: Dynamic N 6000
Net weight kg 550 800
Outline and Dimensional Drawing

LVQB series current transformer has an inverted structure with SF6 gas insulation (Please see the figure). It is connected
in series with electric energy measurement, measuring, and relay protection functions.
Primary coil has a through-type conducting rod structure with good dynamic and thermal stability; its maximum thermal
current can be up to 63kA/3s (when primary coil is connected in series).
Primary coil passes through the center of secondary coil without flux leakage. Measurement precision can be up to 0.1
and 0.2S grades.
Secondary coil is fixed in an aluminum shielded-case by casting organic materials; measurement and protection circuits
cannot be damaged by insulation breakdown.
Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent
insulation property. Partial discharge test is carried out under power frequency test voltage.
There are two types of external insulation bushing for customers: they have excellent explosion-resistant and shock-
resistant behaviors.
External bushing uses silicon rubber umbrella type apron reinforced by glass fiber. Optimal external surface field makes
silicon rubber avoid electrical erosion.
Porcelain bushing shell with high-strength.
Secondary outlet box is a complete structure by casting the aluminum alloy; its sealing structure meets the requirement
of IP55, which is dust proof, water proof and air permeable; secondary terminal for wiring uses Phoenix special terminal; it
is more convenient for operations such as plug-in, pull-out and wiring etc.
Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great
temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.
Product performance keeps changeless after severe transporting test.
Use an aluminum alloy cast case, all components including the base, connection box, stainless steel expander, and
nameplate etc do not rust forever.
A density meter is installed on the base, this meter can show the gas pressure and density in the transformer (The show
value is turned to be the internal gas pressure at 20 automatically). A signal for refilling gas is sent out when the pressure
in the transformer drops down to the alarm pressure.
Introduction to Structure
Shell
Silicon Rubber Bushing
Secondary Lead Pipe
Outlet Box
Base
Nameplate
Electrode
Conducting Block
Main Body
Rupture Disc
15 16
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LVQB Series SF6 Gas-insulated Inverted Current Transformer


Antipollution Class (W2, W3)
Voltage Grade (kV)
With Transient protection
With Protection
SF6 Gas-insulation
Inverted
Current Transformer
L V Q B (T)
Symbol Explanation
17 18
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Fig. 2
Technical Parameters of LVQB-110
LVQB-110W2/1X LVQB-110W3/1X LVQB-110W2/2X LVQB-110W3/2X
Outline and Dimensional Drawing
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Type
LVQB-110W2/1X LVQB-110W2/2X
LVQB-110W3/1X LVQB-110W3/2X
Highest Voltage for Equipment kV 126
Rated Frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashover Distance mm 1100
Creepage Distance mm 3150, 3950
Rated Primary Current In (Maximum) A 2400 (1:2; 1:2:4 available)
Rated Secondary Current A 1; 5
Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated Output VA 10~50
Safety Factor FS 5; 10
Accuracy limit Factor ALF 10; 15; 20; 30
Thermal Current (Maximum) kA 50kA/3s
Dynamic Current (Maximum) kA 125
Air Pressure (Absolute value) MPa 0.5
Outline and Installation Dimensions Fig.2
Net Weight kg 490 565
Gross Weight kg 590 670
Technical Parameters of LVQB-66
Fig.1 LVQB-66W2
Type LVQB-66W2 LVQB-66W3
Highest voltage for Equipment kV 72.5
Rated Frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 160
Rated lightning impulse withstand voltage (full wave)(peak) kV 350
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 403
Flashover Distance mm 650
Creepage Distance mm 1812, 2250
Rated Primary Current In (Maximum) A 4000
Rated Secondary Current A 1; 5
Accuracy Classes (They can be combined if necessary) 0.1; 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated Output VA 10~50
Safety Factor FS 5; 10
Accuracy Limit Factor ALF 10; 15; 20; 30
Thermal Current (Maximum) kA 50kA/3s (In series)
Dynamic Current (Maximum) kA 125
Air Pressure (Absolute Value) MPa 0.5
Outline and Installation Dimensions Fig.1
Net Weight kg 400
Gross Weight kg 490
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Outline and Dimensional Drawing
19 20
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Outline and dimensional drawings for


LVQB(T)-330W3 Current Transformer
Outline and dimensional drawings for
LVQB(T)-500W3 Current Transformer
Technical Parameters of LVB (T)-330500
Outline and Dimensional Drawing
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Type LVQB(T)-330W3 LVQB(T) -500W3
Highest voltage for equipment kV 363 550
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 510/567 740
Rated lightning impulse withstand voltage (full wave)(peak) kV 1175/1305 1675
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1352/1501 1930
Impulse withstand voltage (Wet Test) kV 950/1156 1175
Flashover distance mm 2850 4220
Creepage distance mm 9080 17050
Rated primary current (Maximum) A 5000(2 2500) 5000(2 2500)
Rated secondary current A 5; 1 5; 1
Accuracy classes (they can be combined if necessary)
0.2S;0.5S;0.1;0.2; 0.2S;0.5S;0.1;0.2;
0.5;5P;10P;TPY 0.5;5P;10P;TPY
Rated output VA 10~50 10~50
Safety factor FS 5; 10 5; 10
Accuracy limit factor ALF 10; 15; 20; 30; 40 10; 15; 20; 30; 40
Times of symmetry short-circuit current Kssc 10, 15, 20, 25, 30
TPY Parameter Operating cycle C - O - C - O
Output capacity VA 10, 15
Thermal current (Maximum) kA 63 kA / 3s ( in series )
Dynamic current (Maximum) kA 160 ( in series )
Weight of oil 280 432
Net weight 1800 3000
Gross weight 2600 4000
Fig. 3 LVQB-220W2/1X LVQB-220W3/1X
Technical Parameters of LVQB-220
Outline and Dimensional Drawing
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
LVQB(T)-220W2/2X LVQB(T)-220W3/2X
Type
LVQB-220W2/1X LVQB(T)-220W2/2X
LVQB-220W3/1X LVQB(T)-220W3/2X
Highest voltage for equipment kV 252
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 460
Rated lightning impulse withstand voltage (full wave)(peak) kV 1050
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208
Flashover distance mm 2250
Creepage distance mm 6300, 7900
Rated primary current In (Maximum) A 4000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.1;0.2;0.5;0.2S;0.5S;5P;10P 0.1;0.2;0.5;0.2S;0.5S5P;10PTPY;TPS
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Thermal current (Maximum) kA 63kA/3s
Dynamic current (Maximum) kA 160
Rated gas pressure (Absolute value) MPa 0.5
Outline and installation dimensions Fig.3
Net weight kg 1050 1200
Gross weight kg 1350 1500
21 22
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

JDQXF Series SF6 Gas-insulated Voltage Transformer


Transformer cabinet is at the bottom of product, main body is in
it, there is a silicon rubber composite insulation bushing or high
strength porcelain bushing at the middle and primary terminals are
at top both sides of product.
A SF6 gas density controller is equipped on the transformer
cabinet; it can monitor the SF6 gas pressure in-line. There is a
pressure-relief device on the top; the rupture (relief) pressure is 0.
7 MPa without oil or explosion risk, and it is free-maintenance.
Main body is inside the cabinet, use the composite insulation of
polyester film and SF6 as interlayer insulation, so it has high
strength insulation. Coil uses single-staged tower structure, so it
has a good shock resistant performance.
Product shell is carried out hot galvanizing or uses cast aluminum
alloy, all components including stainless steel fasteners and name-
plate etc work in outdoor for long time without rust.
Primary terminal block uses cast aluminum part, the static test
load it can bear is no less than 3000N.
Secondary outlet box is a complete structure by casting the
aluminum alloy; its sealing structure meets the requirement of IP55,
which is dust proof, water proof and air permeable; secondary
terminal for wiring uses Phoenix special terminal; it is more conve-
Introduction to Structure
Symbol Explanation
Antipollution Class W2 or W3
Rated Voltage Grade
Measurement Coil and Pro-
tection Coil Being Separate
With Residual Voltage Coil
Gas-insulation
Single Phase
Voltage Transformer
nient for operations such as plug-in, pull-out and wiring etc.
Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an excellent
insulation property. Partial discharge test is carried out under power frequency test voltage.
Seal ring is made of imported fluorocarbon silicone rubber, it is suitable for using in the area where there is great
temperature change or the environmental temperature is extreme. The leakage rate per year is less than 0.5%.
High voltage coil is made of imported polyester film and conducting wires with high insulation strength and stable
performance; use imported automatic winding equipment to complete the wire winding and the wrapping of interlayer
insulation automatically according to entered instructions.
J D Q X F
Secondary Outlet Box
Cabinet
Main Body
Primary Conducting Pipe
Bushing Electrode
Silicon Rubber Insulated Bushing
Primary Terminal Block
Explosion Resistant Device
Technical Parameters
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 We also can provide with products which meet the requirement of IEC and ANSI.
Type JDQXF-110W2 / JDQXF-110W3
Highest voltage for equipment kV 126
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashover distance mm 1160
Creepage distance mm 3150 / 3950
Rated gas pressure (Absolute value) MPa 0.5
Rated voltage factor/time1.2/continual 1.5/30s
Accuracy class and rated output
Secondary coil 1 Secondary coil 2 Residual voltage coil
Accuracy class 0.2 0.5or3P 3P
Rated output VA
150 300
100 150 300
Thermal limit output VA 2000
Outline and installation dimensions See the figure
Net weight kg 450
Gross weight kg 550
JDQXF-110W2
It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four
coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.
Integrated design is reasonable; it shows capacitive character under certain voltage.
Outline and Dimensional Drawing
Technical Parameters
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 We also can provide with products which meet the requirement of IEC and ANSI.
Leading wire of secondary coil and leading wire of ground terminal of primary coil are connected with Phoenix special
terminal in the secondary terminal box via the terminal block cast as a whole with epoxy on the shell. It is more convenient
for operations such as plug-in, pull-out and wiring etc. The sealing performance meets the requirement of IP55.
The transformer can be installed horizontally or vertically.
Type JDQXF-110ZH
Highest voltage for equipment kV 126/145
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 230/275
Rated lightning impulse withstand voltage (full wave)(peak) kV 550/650
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633/748
Rated gas pressure (Absol ute value) MPa 0.5/0.6
Rated voltage factor/time 1.2/continual 1.5/30s
Accuracy class and rated output
Secondary coil 1 Secondary coil 2 Residual voltage coil
Accuracy class 0.2 0.5or3P 3P
Rated output VA
150 300
75 120 300
Thermal limit output VA 2000
Outline and installation dimensions See the figure
Net weight kg 400
Gross weight kg 500
Outline and Dimensional Drawing
23 24
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

GIS Gas-insulated Voltage Transformer


Voltage transformer matched with GIS is used for SF6
close combined apparatus; it is connected between the
phase and ground. It uses SF6 gas as main insulation, and
uses polyester film, which is used for interlayer insulation,
as additional insulation.
Main components of transformer
There are lifting blocks, a ground terminal, a nameplate,
an instruction plate and a secondary terminal box on the
metal shell. The shell body is formed by welding steel
plates and hot galvanizing, all connecting bolts uses stain-
less standard parts, they can work in outdoor place for long
time, and do not rust forever. A metal rupture disc is
installed on the base. If a high energy discharge occurs in
it, the rupture disc will break to relief pressure, so the safety
of product is improved.
Main body is installed in the shell, high voltage electrode
Introduction to Structure
J D Q X F
Supporting rack
Shell
Charging
Connection
Lifting Block
Grounding Base
Insulator
Conduit
Core and
Winding
Assembly
and low voltage shielded plate use aluminum plates, which are rotated and pressed to form and carried out polishing
treatment. Optimal Electrode shielded structure improves internal and external field distribution of the product. It has an
excellent insulation property. Partial discharge test is carried out under power frequency test voltage.
High voltage coil uses single-staged tower structure, so it has a good shock resistant performance. Use imported polyester
films and high strength enameled wires, so it has high insulation strength. Use imported automatic winding equipment to
complete the wire winding and the wrapping of interlayer insulation automatically according to entered instructions.
It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage coil) or four
coils (one primary coil, two secondary coils and one residual voltage coil) according to the requirement of customer.
Disc insulator is used as the partition between the gas chamber of transformer and that of composite apparatus.
Transformer and composite apparatus can have SF6 gas with different pressure. The connection between high voltage
conductor and high voltage electrode on main body uses elastic structure.
Rated Voltage
Measurement Coil and Protection Coil Being Separate
With Residual Voltage Coil
Gas-insulation
Dfor Single Phase; Sfor Three Phases
Voltage Transformer
Symbol Explanation
Secondary
Outlet Box
Explosion Re-
sistant Device
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Fig.1 Outline and Installation Dimensions of LB6-110 type Current Transformer (Primary Coil is in series)
Outline and Dimensional Drawing
Main technical Parameters
Type LB6-110(W2) LB6-110(W3) GY
Rated primary voltage kV 110
Highest Voltage for Equipment kV 126
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashover distance mm 1000
Creepage distance mm 3150, 3906
Rated primary current In (Maximum) A 2 50~2 1000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output (Maximum) VA 50 (Pigtail 30)
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (depend on the number of
31.5~45kA / 1s
turns of primary and secondary coils) kA
Dynamic current (Maximum) kA 80~115
Allowable mechanical load of transformer: Static 2000N
Outline and installation dimensions Fig.1
Net weight kg 690 730
Gross weight kg 750 780
25 26
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LB6-110 type Current Transformer


Symbol Explanation
L B 6 110

Voltage Grade, kV
Design No.
With Protection
Current Transformer

Except for the above basic symbol, suffix W2 means that it is
suitable for using in Grade area, suffix W3means that it is
suitable for using in Grade area, and suffix GYmeans that it
is suitable for using in plateau area.
Introduction to Structure
LB6-110 type current transformer has an oil-immersed fully-
sealed structure. The primary coil is U-shape, the main body is fixed
on the bracket, the main insulation uses capacitor type oilpaper, use
the high voltage cable paper to wrap the core of primary coil, and set
up several capacitor shields among it, the internal shield is con-
nected to high potential, and the external shield is connected to
ground reliably.
There is a porcelain bushing at the upper part of oil tank, and an
oil conservator is set up on top of porcelain bushing, primary outlet
terminal is on the oil conservator, series-parallel connection uses an
external switch device, i.e., the switching operation is carried out
outside the oil conservator.
Use a stainless steel expander as the oil compensation device to
ensure oil quality. Oil level is indicated by the pointer at the upper
window of expander.
A nameplate is set up on the oil tank to show the technical data. There are four lifting blocks for hoisting, an oil-discharge
valve and earthing bolts at the bottom of oil tank.
The product can have four to six secondary coils, the secondary measurement coil is made by microcrystalline alloy with
high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade. 2600A
or above current transformer has a pigtail at measurement secondary coil, in order to get two current ratios.
Use new technology and new materials such as hot galvanizing or stainless steel standard parts etc for outside of the
product to make complete equipment rustless.
Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and
durably.
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Outline and Dimensional Drawings for LB7-220 type Current Transformer
Outline and Dimensional Drawing
Technical Parameters of LB7-220
Type LB7-220
Highest Voltage for Equipment kV 252
Rated frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 460
Rated lightning impulse withstand voltage (full wave)(peak) kV 1050
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 1208
Flashover distance mm 2200
Creepage distance mm 6300W2)7900W3
Rated primary current (Maximum) A 2 6002 800
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (Maximum) kA 50kA/3s (In series)
Dynamic current (Maximum) kA 125
Allowable mechanical load of transformer (Static) N 3000
Net weight kg 1180
27 28
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Introduction to Product
This product has an oil-immersed fully-sealed structure. It con-
sists of metal expander, oil conservator, main body and other
accessories. The primary coil is U-shape, the main insulation uses
capacitor type oilpaper, use the high voltage cable paper to wrap
the core of primary coil, and set up several main shields among it.
The secondary coil is set up at the lower part of primary coil; the
whole main body is fixed in the oil tank. There is a bushing at upper
part of oil tank, and an oil conservator is set up on top of bushing, the
primary wire is lead out via the hole of oil conservator, the series-
parallel switching operation is carried out outside the oil conservator.
Use a stainless steel expander as the oil compensation device to
ensure oil quality. Oil level is indicated by the pointer at the upper window of expander.
A nameplate showing the technical data and a description plate showing the coils arrangement schematic diagram are set
up on the oil tank. There are four holes or lifting blocks on the under-frame for hoisting the product, and an oil-discharge valve
and earthing bolts at bottom of oil tank.
The product can have five or six secondary coils, the secondary measurement coil is made by microcrystalline alloy with
high magnetic conductivity, thus can ensure that the measurement precision reaches up to 0.2 grade or 0.2S grade.
The secondary terminal has limit and double sealing functions. The outlet box is made by stretching wholly; it is elaborate
and practical. The oil tank is carried out surface treatment; it is bright and durable.
Complete transformer is fully sealed. New technology and new materials such as hot galvanizing or stainless steel
standard parts etc are used for outside of the product to prevent from rustless and get long working life.
Reasonable and originative structure as well as advanced technology ensures that the product runs reliably, safely and
durably.
LB7-220 type Current Transformer
Symbol Explanation
L B 7 220
Voltage Grade, kV
Design No.
With Protection
Current Transformer
Except for the above basic symbol, suffixW2means that it is
suitable for using in Grade area, suffixW3means that it is
suitable for using in Grade area, and suffix GYmeans that it
is suitable for using in plateau area.
29 30
Rated primary voltage kV 35
Highest voltage for the equipment kV 40.5
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 95
Rated lightning impulse withstand voltage (full wave)(peak) 185
Flashover distance mm 450
Creepage distance mm 10501256
Rated primary current A 52000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 40. 2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output VA 10~40
Safety factor FS 10
Accuracy limit factor ALF 10; 15; 20; 30
Thermal current (Maximum) kA 40 kA/ 1s
Dynamic current (Maximum) kA 100
Type LAB6-35
Main Technical Parameters
Outline and Dimensional Drawing
Outline and Dimensional Drawing for LAB6-35 type Current Transformer with Expander
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LAB6-35 type Current Transformer


Symbol explanation
L A B 6 35
Voltage Grade, kV
Design No.
With Protection
Chain type
Current Transformer
Except for the above basic symbol, suffix W2means that it is suitable for using in Grade polluted area, suffix W3
means that it is suitable for using in Grade polluted area.
Introduction to product
LAB6-35 type current transformer uses oilpaper insulation for outdoor use, it is a fully sealed product. It is used as a current,
electric energy measurement and relay protective device for AC power system with highest voltage for the equipment of the
equipment 40.5 kV and rated frequency 50Hz.
The product can have three or four secondary coils, the magnetic core uses microcrystalline alloy with high magnetic
conductivity, the measurement precision of secondary coil can be up to 0.2 grade or 0.2S grade.
The oil conservator of this product is made of aluminum alloy. The oil tank is made by high-quality steel plate stretching
to form as a whole, in order to reduce welding seam leakage points; it has not exposed sealing structure, so it can lengthen
the aging period of seal ring, ensure that the sealing performance is reliable, improve the run quality of insulation oil, and
ensure that the run is safe and reliable.
Outline and Dimensional Drawing for LGBJ-35 type Current Transformer
Technical Parameters of LGBJ-35 Current Transformer
Outline and Dimensional Drawing
Highest voltage for the equipment kV 40.5
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 95
Rated lightning impulse withstand voltage (full wave)(peak)kV 200
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230
Flashover distance mm 380
Creepage distance mm 1020/1260
Rated primary current (Maximum) A 2000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (depend on the number of turns of 50kA/3s (In series)
primary and secondary coils) MaximumkA
Dynamic Current (Maximum) kA 125
Allowable mechanical load of transformer: Static 2000N
Outline and installation dimensions Fig.1
Net weight kg 100
Gross weight kg 120
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Type LGBJ-35W2 LGBJ-35W3
31 32
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

LGBJ type Current Transformer


Introduction to Product
This product uses the capacitor equalizing theory; it uses optimal
structural design by special electric field analysis and calculation; it
is light and handy, and it is convenient for installation.
The product is made of fire resistant and corrosion resistant
material without oil or porcelain. It not only can be used in the city
with high sanitary requirement, but also can be used in the area with
severe pollution.
This series product consists of primary coil, secondary coil, shell
and base plate etc components.
The secondary coil is set up at the bottom; it is covered by shell
completely to prevent from dust and outer matters entering, and
prevent from being corroded by sand blown by wind.
The end shield or ground shield is led out separately to be convenient for test, and it also has good humidity resistance.
The insulation resistance is stable and reliable.
The secondary terminal block uses cast as a whole.
This is a patented product of our company, and the patent No. is ZL 02 2 88478.5.
This product uses organic composite material as its main insulation, so it has a long working life, and can be up to 30 years.
No oil: there is not explosion risk, it is safe and does not leak forever.
No porcelain: small and light.
No gas: there is not possibility to pollute environment.
Non-epoxy cast: it is used in the open air, it is stable and reliable.
Advanced technology: use the optimal design concept with uniform voltage distribution; partial discharge is small and
dielectric loss factor is low.
Use special technology, carry out 1% NaCl water cooking test for 42 hours, the data do not change obviously before and
after the test.
The primary terminal uses copper or aluminium; it is led out horizontally, so it is convenient for wiring.
Symbol explanation
L G B J 110 GY W2
Antipollution Class
Tableland type
Voltage Class, kV
With High Insulation
With Protection
Dry type
Current Transformer
Technical Parameters of LGBJ-110 type Current Transformer
Outline and Dimensional Drawing for LGBJ-110 type Current Transformer
Outline and Dimensional Drawing
Type LGBJ -110W2 LGBJ -110W3
Highest voltage for the equipment kV 126
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashover distance mm 1000
Creepage distance mm 3150/3910
Rated primary current (Maximum) A 2000
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (depend on the number of turns of primary and 50kA/3s (In series)
secondary coils) (Maximum) kA
Dynamic current (Maximum) kA 125
Allowable mechanical load of transformer: Static N 2000N
Outline and installation dimensions Fig.3
Net weight kg 300
Gross weight kg 350
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
33 34
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Outline and Dimensional Drawing for LGBJ-66 type Current Transformer


Technical Parameters of LGBJ-66 type Current Transformer
Outline and Dimensional Drawing
Type LGBJ-66W2 LGBJ-66W3
Highest voltage for the equipment kV 72.5
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 140
Rated lightning impulse withstand voltage (full wave)(peak) kV 325
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 374
Flashover distance mm 700
Creepage distance mm 1820/2250
Rated primary current (Maximum) A 1250
Rated secondary current A 1; 5
Accuracy classes (they can be combined if necessary) 0.2; 0.5; 0.2S; 0.5S; 5P; 10P
Rated output VA 10~50
Safety factor FS 5; 10
Accuracy limit factor ALF 10; 15; 20; 30
Short-time thermal current (depend on the number of turns of primary 50kA/3s (In series)
and secondary coils) (Maximum) kA
Dynamic current (Maximum) kA 125
Allowable mechanical load of transformer: Static N 2000N
Net weight kg 220
Gross weight kg 230
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
Note: 1 We can supply the plateau type product which is suitable for altitude 3000m or above according to the requirement of customer,
its technical parameters are the same as that of the product with 31mm/kV ratio of creepage distance and the highest voltage for
equipment of the system;
2 We also can provide with products which meet the requirement of IEC and ANSI.
Type JDC6-110 JDCF-110
Highest voltage for equipment kV 126
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 200
Rated lightning impulse withstand voltage (full wave)(peak) kV 480
Flashover distance mm 552
Creepage distance mm 3150/3910
Rated voltage factor 1.2/ continual 1.5/ 30s 1.2/ continual 1.5/ 30s
Rated voltage ratio 110/ /0.1/ /0.1 110/ /0.1/ /0.1/ /0.1
Accuracy class 0.2(0.5, 3P)/3P 0.2/0.5/3P
Rated output VA 150(300,500)/300 100/250/300
Limit output VA 2000 2000
Oil weight kg 130/165 130/165
Total weight kg 675/695 675/695
Main Technical Parameters
3 3 3 3 3
Outline and Dimensional Drawing
35 36
JDCF-110 type Inductive Voltage Transformer
(Creepage Distance25mm/kV
JDCF-110 type Inductive Voltage Transformer
Creepage Distance31mm/kV
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

JDC6-110 and JDCF-110 type Inductive Voltage Transformers


Introduction to Product
JDC6 -110 and JDCF-110 type voltage transformers use electromagnetic oilpaper insulation for outdoor use; it is a fully
sealed product. It is used as a current, electric energy measurement and relay protective device for the system with effectively
earthed neutral with the highest voltage for equipment 126 kV and rated frequency 50Hz.
This product has a reliable design and low magnetic density, it can avoid ferroresonance over-voltage, the secondary coil
can separate measurement from protection; the measuring precision can be up to grade 0.2 to meet the different requirement
of customers and the high precision measuring requirement required by power departments.
This product uses a stainless steel expander; it is carried out advanced vacuum drying and vacuum oiling treatment
technology, so it has small dielectric loss and low partial discharge, and can ensure that the operation of product is safe and
reliable.
Symbol explanation
J D C 6 110 W
Anti Fouling
Rated Voltage, kV
Design Number
With Residual Voltage
Winding in Cascade Stage
Single Phase
Voltage Transformer
J D C F 110 W
Anti Fouling
Rated Voltage, kV
With Secondary Winding for
Measurement and Protection
respectively
With Residual Voltage
Winding in Cascade Stage
Single Phase
Voltage Transformer
37 38
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Outline and Dimensional Drawing of


JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.5/3P)
Outline and Dimensional Drawing of
JD6-35W3 Inductive Voltage Transformer
Main Technical Parameters
Outline and Dimensional Drawing
Type JD6-35 JDX6-35
Highest voltage for equipment kV 40.5
Rated frequency Hz 50
Rated power-frequency withstand voltage (rms) kV 95
Rated lightning impulse withstand voltage (full wave)(peak) kV 200
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230
Creepage distance 31
Rated voltage factor 1.2 continual 1.2 continual/ 1.98h
Rated voltage ratio 35/0.1
35/ /0.1/ /0.1/3
35/ /0.1/ /0.1/ /0.1/3
Accuracy class 0.2(0.5)
0.2(0.5)/3P
0.2/1.5/3P
Rated output VA 80(150)
80(150)/10
30/80/1000
Limit output VA 1000 1000
Oil weight kg 29 24
Total weight kg 135 127
3 3
3 3 3
Outline and Dimensional Drawing of
JDX6-35W3 Inductive Voltage Transformer(Accuracy Class 0.2/0.5/3P)
JD6-35 and JDX6-35 type Inductive Voltage Transformers
Symbol explanation
J D (X) 6 35 W
Anti Fouling
Rated Voltage, kV
Design Number
With Residual Voltage Winding
Single Phase
Voltage Transformer
Introduction to Product
JD6-35 and JDX6-35 type voltage transformers use oilpaper insulation for outdoor use; it is a fully sealed product. It is used
as a current, electric energy measurement and relay protective device for the system with the highest voltage for equipment
40.5 kV and rated frequency 50Hz.
JD6-35 type voltage transformer has a structure with single phase and double coils, it is suitable for connecting at the place
between the phase and phase in a system with ineffectively earthed neutral.
JDX6-35 type voltage transformer has a structure with single phase and triple coils; it is suitable for connecting at the place
between the phase and ground in a system with ineffectively earthed neutral.
The core of product uses high quality silicon steel sheets, the measuring precision can be up to grade 0.2; the oil tank has
a form structure, it is formed by stretching high quality steel plate wholly to reduce the number of welding seam leakage points.
The rubber ring uses double sealing to ensure that the operation of product is reliable.
JDX6-35 JD6-35
39 40
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

TYD110/220 type Capacitor Voltage Transformer


Symbol explanation
T YD 110/220 0.01 H
Anti Fouling
Rated Capacitance, F
Rated Phase Voltage
Capacitor Voltage Transformer
Integrated Equipment
Introduction to Product
Capacitor voltage transformer series products are suitable for current, electric energy measurement and relay protection
in a system with effectively earthed neutral with rated voltage 35kV, 66kV, 110kV or 220kV and rated frequency 50Hz. It can
also be used for carrier wave communication concurrently.
This product consists of capacitor voltage divider and electromagnetic unit the medium voltage terminal and low voltage
terminal of capacitor voltage divider are lead out into an oil tank equipped with electromagnetic unit. The electromagnetic unit
consists of middle transformer, a compensation reactor and a damper
The capacitor voltage divider consists of a bushing, a core and a metal expander. The core of capacitor is combined by
several film-paper composite media and serial parts which are made by coiling aluminum foils, it is carried out vacuum dipping
treatment, the porcelain bushing is filled with transformer oil, and it is equipped with the metal expander to compensate the
change of oil volume at different temperatures.
This series transformer has a quick saturation damping device with a quick transient response speed, and it also can damp
ferroresonance reliably.
There is a carrier wave communication terminal in the secondary outlet box, and it also has an over-voltage protection clearance.
There are an oil level gauge, an outlet box, a nameplate, an oil-discharge plug and an earthing base outside the oil tank.
The sealing structure of product is optimized, so it has a good sealing performance.
3
M
a
i
n

t
e
c
h
n
i
c
a
l

p
a
r
a
m
e
t
e
r
s
N
o
t
e
:
1

T
h
e

p
a
r
a
m
e
t
e
r
s

in

t
h
e

t
a
b
le

a
r
e

n
o
t

c
h
a
n
g
e
le
s
s
;

t
h
e

C
o
m
p
a
n
y

r
e
s
e
r
v
e
s

t
h
e

r
ig
h
t

t
o

c
h
a
n
g
e

t
h
e
m
.
2

W
h
e
n

t
h
e

p
a
r
a
m
e
t
e
r
s

r
e
q
u
ir
e
d

b
y

t
h
e

c
u
s
t
o
m
e
r

a
r
e

d
if
f
e
r
e
n
t

f
r
o
m

t
h
a
t

in

t
h
e

t
a
b
le
,

t
h
e
y

c
a
n

b
e

n
e
g
o
t
ia
t
e
d

a
c
c
o
r
d
in
g

t
o

t
h
e

r
e
q
u
ir
e
m
e
n
t

o
f

t
h
e

c
u
s
t
o
m
e
r
.
3

W
e

c
a
n

s
u
p
p
ly

t
h
e

p
r
o
d
u
c
t

w
it
h

3
1
m
m
/
k
V

r
a
t
io

o
f

c
r
e
e
p
a
g
e

d
is
t
a
n
c
e

a
n
d

h
ig
h
e
s
t

v
o
lt
a
g
e

f
o
r

e
q
u
ip
m
e
n
t

o
f

t
h
e

s
y
s
t
e
m
;
4

W
e

a
ls
o

c
a
n

p
r
o
v
id
e

w
it
h

p
r
o
d
u
c
t
s

w
h
ic
h

m
e
e
t

t
h
e

r
e
q
u
ir
e
m
e
n
t

o
f

I
E
C

a
n
d

A
N
S
I

3 3 3 3 3 3
1
T
Y
D
3
5
/





-
0
.
0
2
W
3
4
0
.
5
3
5
/
0
.
1
/
0
.
1
/
0
.
1
/
3
5
0

0
.
2

5
0

0
.
5

1
0
0

3
P

9
5
/
2
0
0
3
1
5
0
0
2
T
Y
D
6
6
/





-
0
.
0
2
W
3
7
2
.
5
6
6
/
0
.
1
/
0
.
1
/
0
.
1
/
3
1
0
0

0
.
2

1
0
0

0
.
5

1
0
0

3
P

1
4
0
/
3
2
5
3
1
5
0
0
3
T
Y
D
1
1
0
/





-
0
.
0
0
6
6
H
1
2
6
1
1
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
0
0
4
T
Y
D
1
1
0
/





-
0
.
0
0
7
H
1
2
6
1
1
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
0
0
5
T
Y
D
1
1
0
/





-
0
.
0
0
8
H
1
2
6
1
1
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
0
0
6
T
Y
D
1
1
0
/





-
0
.
0
1
H
1
2
6
1
1
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
0
0
7
T
Y
D
1
1
0
/




-
0
.
0
1
H
1
2
6
1
1
0
/
0
.
1
/
0
.
1
/
0
.
1
1
0
0
/
0
.
2
1
0
0
/
0
.
5
1
0
0
/
3
P
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
7
0
8
T
Y
D
1
1
0
/





-
0
.
0
1
5
H
1
2
6
1
1
0
/
0
.
1
/
0
.
1
/
0
.
1
1
0
0
/
0
.
2
1
0
0
/
0
.
5
1
0
0
/
3
P
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
5
7
0
9
T
Y
D
1
1
0
/





-
0
.
0
2
H
1
2
6
1
1
0
/
0
.
1
/
0
.
1
/
0
.
1
1
5
0
/
0
.
2
1
5
0
/
0
.
5
1
5
0
/
3
P
1
0
0
/
3
P
2
0
0
/
4
8
0
2
5
6
8
0
1
0
T
Y
D
2
2
0
/





-
0
.
0
0
3
3
H
2
5
2
2
2
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
7
5
0
1
1
T
Y
D
2
2
0
/





-
0
.
0
0
3
5
H
2
5
2
2
2
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
7
5
0
1
2
T
Y
D
2
2
0
/





-
0
.
0
0
4
H
2
5
2
2
2
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
7
5
0
1
3
T
Y
D
2
2
0
/





-
0
.
0
0
5
H
2
5
2
2
2
0
/
0
.
1
/

0
.
1
1
0
0
/
0
.
2
1
5
0
/
0
.
5
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
7
5
0
1
4
T
Y
D
2
2
0
/





-
0
.
0
0
5
H
2
5
2
2
2
0
/
0
.
1
/
0
.
1
/
0
.
1
1
0
0
/
0
.
2
1
0
0
/
0
.
5
1
0
0
/
3
P
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
8
2
0
1
5
T
Y
D
2
2
0
/





-
0
.
0
0
7
5
H
2
5
2
2
2
0
/
0
.
1
/
0
.
1
/
0
.
1
1
0
0
/
0
.
2
1
0
0
/
0
.
5
1
0
0
/
3
P
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
8
2
0
1
6
T
Y
D
2
2
0
/





-
0
.
0
1
H
2
5
2
2
2
0
/
0
.
1
/
0
.
1
/
0
.
1
1
5
0
/
0
.
2
1
5
0
/
0
.
5
1
5
0
/
3
P
1
0
0
/
3
P
3
9
5
/
9
5
0
2
5
9
1
0
H
ig
h
e
s
t
R
a
t
e
d

P
r
im
a
r
y
R
a
t
e
d

S
e
c
o
n
d
a
r
y
R
a
t
e
d

O
u
t
p
u
t

(
V
A
)
I
n
s
u
la
t
io
n
R
a
tio
o
f c
r
e
e
p
a
g
e
d
is
ta
n
c
e
S
/
N
T
y
p
e
V
o
lt
a
g
e
V
o
lt
a
g
e

V
o
lt
a
g
e
(
k
V
)
/

A
c
c
u
r
a
c
y

C
la
s
s
L
e
v
e
l(
k
V
)
a
n
d

H
ig
h
e
s
t

v
o
lt
a
g
e

f
o
r
W
e
ig
h
t
(
k
V
)
(
k
V
)
1
a
-
1
n
2
a
-
2
n
d
a
-
d
n
1
a
-
1
n
2
a
-
2
n
d
a
-
d
n
P
o
w
e
r F
re
q
u
e
n
c
y
/L
ig
h
tn
in
e
q
u
ip
m
e
n
t

(
m
m
/
k
V
)
(
k
g
)
3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3 3 3 3 3 3 3 3 3 3 3 3 3
3 3
3 3
3 3
3 3
41 42
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

CWG type Dry Wall Bushing


Symbol explanation
Introduction to Structure and Features
This product uses the capacitor equalizing theory; it uses optimal structural design by special electric field analysis and
calculation; it is light and handy, and it is convenient for installation.
The product is made of fire resistant and corrosion resistant material without oil or porcelain. It not only can be used in the
city with high sanitary requirement, but also can be used in the area with severe pollution.
This series product consists of primary coil, bushing flanges, and terminal block etc components.
The end shield or ground shield is lead out separately to be convenient for test, and it also has good humidity resistance.
The insulation resistance is stable and reliable.
The secondary terminal block is formed by casting as a whole, it can prevent from turning, so the insulation resistance is
stable and reliable.
C W G /
Whether used in plateau
Supplemental feature code
Installation mode
Rated current (A)
Rated voltage (kV)
With current transformer
Dry type
Outdoor bushing
Through the wall
Outline and Dimensional Drawing
Outline and dimensional drawing of
TYD-110 type voltage transformer
Outline and dimensional drawing of
TYD-220 type voltage transformer
TYD35/ -0.02W3 type Inductive Voltage Transformers TYD35/ -0.02W3 type Inductive Voltage Transformers 3 3
43 44
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Outline and Dimensional Drawings of CWG - L - 40.5 - CWG - L - 126


CWG-72.5/630 220 220
40 4-14
60
CWG-72.5/800 220 220 1815
65
CWG-72.5/1000 2470 770 220 770 220 1040 550 275 300 2250
CWG-72.5/1250 220 220 50 4-18 70
CWG-72.5/1600 220 220
6-18
75
CWG-126/630
1040
220
1040
220
1390 40 4-14
80
CWG-126/800 220 220 90
CWG-126/1000
3160 1040
220
1040
220
1390 700 350 350
3150
95
CWG-126/1250 220 220 50 4-18 3906
CWG-126/1600
1040
220
1040
220
1390
110
CWG-126/2000 220 220 120
Table 2 unit: mm
Outdoorside Indoor Side Earth Potential Installation Flange Terminal Block Cree- Wei-
Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Installation Distance Between Install- page ght
Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes ation dist- kg
L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance
CWG-L-40.5/630 180 180
40 4-14
50
CWG-L-40.5/800 55
CWG-L-40.5/1000 1910 220 220 101560
CWG-L-40.5/1250 470 220 470 220 970 450 500 200 50 4-18 1260
65
CWG-L-40.5/1600 220 220
CWG-L-40.5/3150 2070 220 220 60 8-18 70
CWG-L-40.5/4000 2070 220 220 60 8-18 70
CWG-L-72.5/630 220 220 40 4-14 65
CWG-L-72.5/800 220 220 6-18 1815
70
CWG-L-72.5/1000 2820 730 220 730 220 1400 970 670 300 2250
CWG-L-72.5/1250 220 220 50 4-18 75
CWG-L-72.5/1600 220 220 80
CWG-L-126/630
1100
220
1100
220
2070 40 4-14
80
CWG-L-126/800 220 220 90
CWG-L-126/1000 3560
1100
220
1100
220
2070 950 600 350
3150
95
CWG-L-126/1250 220 220
50 4-18
3906
CWG-L-126/1600
1100
220
1100
220
2070
110
CWG-L-126/2000 220 220 120
Main Technical Parameters
Type test items
Complete all test items according to the requirement of GB/T4109-1991.
Rated voltage is 12~126 kV, standard current values can be chosen from the following (Unit: A)
250, 400, 630, 800, 1000, 1250, 1600, 2000, 3150, 4000
Precision of attached current transformer:
1. Measurement coil: 0.1, 0.2, 0.5, 0.2S, 0.5S (Grade)
2. Accuracy grade of protection coil: 5P, 10P; Accuracy limit factor:10, 15, 20, 30
3. Secondary output capacity (VA): 20, 25, 30, 40 50
Antipollution grade and creepage distance
Outline and Dimensional Drawings of CWG-40.5-CWG-126
Insulation Level and Discharge Level (Voltage Unit: kV)
Rated Voltage Nominal Voltage Power-frequency Withstand Lightning Impulse Partial Discharge Level
Ur of the System Voltage (Dry or Wet) Withstand Voltage Measurement Voltage pC
40.5 35 95 200 35 10
72.5 66 147 325 63 10
126 110 230 550 109 10
Light, Medium 20 3.5
Severe 25 4.0
Special severe 31 4.0
Nominal Value of Minimum Ratio of Creepage Distance and Highest Voltage
for Equipment Relative to Ground mm/kV ( Highest Voltage for Equipment )
Ratio of Creepage Distance and Highest
Voltage for Equipment/ Flashover Distance
Antipollution
Grade
Table 1 unit: mm
Outdoorside Indoor Side Earth Potential Installation Flange Terminal Block Cree- Wei-
Type Total Insulation Maximum Insulation Maximum Total Total Indoor Diameter of Installation Distance Between Install- page ght
Length Distance External Insulation External Length Length L5 Installation Hole Hole the Center of Two Holes ation dist- kg
L1 Diameter L3 Diameter L4 L2 D1 a1 Hole ance
CWG-40.5/630
180 180 40 4-14
45
CWG-40.5/800 50
CWG-40.5/1000 1560 220 220 101555
CWG-40.5/1250
440
220
440
220
600 300 150 200 6-f18
50 4-18 1260 60
CWG-40.5/1600 220 220 60
CWG-40.5/3150
1720
220 220
60 8-18
65
CWG-40.5/4000 220 220 65
45
!"#$%&'()*
JIANGSU SIEYUAN HERTZ INSTRUMENT TRANSFORMER CO., LTD.
Sieyuan Sieyuan Sieyuan Sieyuan Sieyuan

Parameters of CWG-126 (CWG-L-126)


Type CWG-126/250~4000 CWG-L-126/250~4000
Highest Voltage for Equipment kV 126
Rated Frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashout Distance mm 1200
Creepage Distance mm 3150 or 3906
Rated Primary Current (Maximum) A 2000
Rated Secondary Current of Built-in Current Transformer A 15
Accuracy Classes of Built-in Current Transformer
0.10.20.50.2S; 0.5S; 5P; 10P
(They can be combined if necessary)
Rated Output of Built-in Current Transformer VA 10-50
Safety Factor of Built-in Current Transformer FS 5; 10
Accuracy Limit Factor of Built-in Current Transformer 10; 15; 20; 30
Short-time Thermal Current 25 times of rated current
Bending Load Withstand Test 2000N
Outline and Installation Dimensions See the corresponding drawings
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;
4 We also can provide with products which meet the requirement of IEC and ANSI.
CWG-126/2504000
CWG-L-126/2504000
126
50/60
230
550
633
1200
3150 or 3906
2000
15
0.10.20.50.2S; 0.5S; 5P; 10P
10-50
5; 10
10; 15; 20; 30
25 times of rated current
2000N
See the corresponding drawings
Note: 1 The parameters in the table are not changeless; the Company reserves the right to change them.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the requirement of the customer.
3 We can supply the product with 31mm/kV ratio of creepage distance and highest voltage for equipment of the system;
4 We also can provide with products which meet the requirement of IEC and ANSI.
Type
CWG-72.5/2504000
CWG-L-72.5/2504000
Highest Voltage for Equipment kV 126
Rated Frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 230
Rated lightning impulse withstand voltage (full wave)(peak) kV 550
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 633
Flashout Distance mm 1200
Creepage Distance mm 1815 or 2250
Rated Primary Current (Maximum) A 2000
Rated Secondary Current of Built-in Current Transformer A 15
Accuracy Classes of Built-in Current Transformer
0.10.20.50.2S;0.5S;5P;10P
(They can be combined if necessary)
Rated Output of Built-in Current Transformer VA 10-50
Safety Factor of Built-in Current Transformer FS 5;10
Accuracy Limit factor of Built-in Current Transformer 10; 15; 20; 30
Short-time Thermal Current 25 times of rated current
Bending Load Withstand Test 2000N
Outline and Installation Dimensions See the corresponding drawings
Parameters of CWG-72.5 (CWG-L-72.5)
Parameters of CWG-40.5 (CWG-L-40.5)
Type CWG-40.5/250~4000 CWG-L-40.5/250~4000
Highest Voltage for Equipment kV 40.5
Rated Frequency Hz 50/60
Rated power-frequency withstand voltage (rms) kV 95
Rated lightning impulse withstand voltage (full wave)(peak) kV 200
Rated lightning impulse withstand voltage (chopped wave)(peak) kV 230
Creepage Distance mm 1015 or 1260
Rated Primary Current (Maximum) A 4000
Rated Secondary Current of Built-in Current Transformer A 1, 5
Accuracy Classes of Built-in Current Transformer
0.2; 0.5; 0.2S; 0.5S; 5P; 10P
(They can be combined if necessary)
Rated Output VA 10-50
Safety Factor FS 5, 10
Accuracy limit Factor ALF 10; 15; 20; 30
Short-time Thermal Current 25 times of rated current
Bending Load Withstand Test 2000N
Outline and Installation Dimensions See the corresponding drawings
Note: 1 The Company reserves the right to change the parameters in the table.
2 When the parameters required by the customer are different from that in the table, they can be negotiated according to the
requirement of the customer.
3 There are several current ratios for one-time switch of the transformer.
4 We also can provide with products which meet the requirement of IEC and ANSI.
46