Está en la página 1de 68

Installation Instructions

DeviceNet Modules
Catalog Numbers 1756-DNB, 1769-ADN, 1769-SDN
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Allen-Bradley, Compact I/O, CompactLogix, ControlLogix, FlexLogix, Logix5000, MicroLogix, Rockwell Automation, Rockwell Software, RSLinx, RSLinx Classic, RSLogix 5000, RSNetWorx for DeviceNet, and
TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 3
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Topic Page
Added new warnings for USB cable usage 19
4 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Summary of Changes
Notes:
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 5
Table of Contents
Preface Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Install a 1756 DeviceNet
Communication Module
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Determine Module Slot Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Set the Communication Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Set the Rotary Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Use RSNetWorx for DeviceNet Software. . . . . . . . . . . . . . . . . . . . . . . 13
Set the Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Set the Rotary Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Use RSNetWorx for DeviceNet Software. . . . . . . . . . . . . . . . . . . . . . . 15
Restore the Factory Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Connect the Module to a DeviceNet Network. . . . . . . . . . . . . . . . . . . . . . 17
Download the Add-on Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Connect to the Module via the USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Configure the Module via the USB Port . . . . . . . . . . . . . . . . . . . . . . . . 19
Load Firmware through a USB Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . . . . 23
Install or Remove the Module Under Power . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 2
Install a 1769 DeviceNet
Communication Module
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Minimum Spacing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
System Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Panel Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Panel Mounting Using the Dimensional Drawing . . . . . . . . . . . . . . . 29
Panel Mounting Procedure Using Modules as a Template. . . . . . . . 30
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Connect the Module to a DeviceNet Network. . . . . . . . . . . . . . . . . . . . . . 31
Set the Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Set the Node Address of a 1769-ADN Module. . . . . . . . . . . . . . . . . . 32
Set the Node Address of a 1769-SDN Module . . . . . . . . . . . . . . . . . . 33
Download the Add-on Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . . . . 36
Replace a Module within a System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Table of Contents
Chapter 3
Configure a Workstation to
Operate on a DeviceNet
Network
Connect a Computer to the DeviceNet Network. . . . . . . . . . . . . . . . . . . . 40
Configure a Driver for a Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Verify that the Driver Works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Appendix A
1756 DeviceNet Status
Indicators and Data Structures
1756-DNB DeviceNet Scanner Status Indicators. . . . . . . . . . . . . . . . . . . . 45
1756-DNB DeviceNet Scanner Alphanumeric Display . . . . . . . . . . . . . . 47
Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
1756-DNB DeviceNet Scanner Data Structures. . . . . . . . . . . . . . . . . . . . . 51
Input Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Output Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Module Command Register Bit Definitions. . . . . . . . . . . . . . . . . . . . . 52
Module Status Register Bit Definitions . . . . . . . . . . . . . . . . . . . . . . . . . 53
Status Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Appendix B
1769 DeviceNet Modules Status
Indicators and Data Structures
1769-ADN Adapter Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
1769-ADN Adapter Data Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Input Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Output Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
1769-SDN Scanner Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
1769-SDN Scanner Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
1769-SDN Scanner Data Structures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Input Data Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Output Data Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
CompactLogix Status Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 7
Preface
This manual describes how to install and start DeviceNet module systems with
Logix5000 controllers.
Use this manual if you program applications that use an EtherNet/IP network
with one of these Logix5000 controllers:
CompactLogix controller
ControlLogix

controller
You should also understand the following:
Networking concepts
How to use RSLogix

5000 software
How to use RSLinx

Classic programming software
Additional Resources
For more information on the products included in this publication, use the
publications listed in this table.
Resource Description
DeviceNet Network Configuration User Manual,
publication DNET-UM004
Provides details about how to use DeviceNet
communication modules with Logix5000
controllers and communicate with other devices
on the DeviceNet network.
Compact I/O 1769-ADN DeviceNet Adapter User
Manual, publication 1769-UM001
Provides information about installing,
configuring, and troubleshooting the 1769-ADN
DeviceNet adapter.
Compact I/O DeviceNet Scanner Module User
Manual, publication 1769-UM009
Provides a quick start and describes how to
install, configure, operate, and troubleshoot the
1769-SDN scanner module.
DeviceNet Media Design Installation Guide,
publication DNET-UM072
Provides information about how to design,
install, and troubleshoot a DeviceNet cable
system.
8 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Preface
Notes:
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 9
Chapter 1
Install a 1756 DeviceNet Communication
Module
Topic Page
Installation Summary 11
Determine Module Slot Location 12
Set the Communication Rate 12
Set the Node Address 14
Restore the Factory Default Settings 15
Install the Module 16
Connect the Module to a DeviceNet Network 17
Download the Add-on Profile 18
Connect to the Module via the USB Port 18
Apply Chassis Power and Check Status Indicators 23
Install or Remove the Module Under Power 24
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-
metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure type ratings that are required to comply with
certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by
enclosures
10 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
North American Hazardous Location Approval
The following information applies when operating this equipment
in hazardous locations.
Informations sur lutilisation de cet quipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with markings on the rating
nameplate indicating the hazardous location temperature code. When
combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature
code of the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une
utilisation en environnements de Classe I Division 2 Groupes A, B, C, D
dangereux et non dangereux. Chaque produit est livr avec des marquages
sur sa plaque d'identification qui indiquent le code de temprature pour les
environnements dangereux. Lorsque plusieurs produits sont combins dans
un systme, le code de temprature le plus dfavorable (code de
temprature le plus faible) peut tre utilis pour dterminer le code de
temprature global du systme. Les combinaisons d'quipements dans le
systme sont sujettes inspection par les autorits locales qualifies au
moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other means
provided with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
AVERTISSEMENT: RISQUE DEXPLOSION
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher l'quipement.
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher les connecteurs. Fixer
tous les connecteurs externes relis cet
quipement l'aide de vis, loquets
coulissants, connecteurs filets ou autres
moyens fournis avec ce produit.
La substitution de composants peut rendre
cet quipement inadapt une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est class non
dangereux avant de changer les piles.
WARNING: If you connect or disconnect the communication cable with power applied to this module or any device
on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
European Hazardous Location Approval
The following applies when the product bears the Ex Marking:
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply
with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
WARNING:
This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%
when applied in Zone 2 environments.
This equipment must be used only with ATEX certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or
other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 11
Install a 1756 DeviceNet Communication Module Chapter 1
Installation Summary
To install a communication module in a 1756 ControlLogix chassis, complete
these steps.
1. Determine Module Slot Location.
2. Set the Communication Rate.
3. Set the Node Address.
4. Install the Module.
5. Connect the Module to a DeviceNet Network.
6. Download the Add-on Profile.
7. Connect to the Module via the USB Port.
8. Apply Chassis Power and Check Status Indicators.
Grounding Considerations
Refer to these publications for grounding guidelines:
DeviceNet Media Design and Installation Guide, publication
DNET-UM072
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
12 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
Determine Module Slot
Location
Install the communication module in any slot in the ControlLogix chassis. You
can install multiple communication modules in the same chassis. This example
shows chassis slot numbering in a 4-slot chassis. Slot 0 is the first slot and is always
the leftmost slot in the rack.
Set the Communication
Rate
The 1756-DNB scanner module supports the following DeviceNet network
communication rates:
125 Kbps (default)
250 Kbps
500 Kbps
Change the communication rate by setting the rotary switch or commissioning
the 1756-DNB scanner module in RSNetWorx for DeviceNet software.
Use the switch to select a specific communication rate. When the switch is set to
39 (except for 888), you can configure the communication rate with
RSNetWorx for DeviceNet software. When all three switches are set to 8, the
1756-DNB scanner module will reset to factory default settings at powerup.
1
4
5
6
2
20806
3 Item Description
1 Power supply
2 Chassis
3 Slot 0
4 Slot 1
5 Slot 2
6 Slot 3
ATTENTION: Do not change the communication rate on an active
network. Unpredictable operation may result. In addition, the new
communication rate does not take effect until you cycle power to the
1756-DNB scanner module.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 13
Install a 1756 DeviceNet Communication Module Chapter 1
Figure 1 - Communication Rate Rotary Switch
Set the Rotary Switch
Use the communication (data) rate rotary switch to change the communication
rate.
1. If the module is removed from the chassis, be sure that power is removed or
the area is nonhazardous before proceeding.
2. Move the rotary switch to the desired position.
3. If necessary, reinstall the module into the chassis.
Use RSNetWorx for DeviceNet Software
Follow this procedure to use RSNetWorx for DeviceNet software to set the
communication rate.
1. In RSNetWorx for DeviceNet software, select the 1756-DNB scanner
module.
2. From the Tools menu, choose Node Commissioning.
3. Browse to the DeviceNet network for the 1756-DNB scanner module you
want to commission.
4. Select the 1756-DNB scanner module you want to commission.
Table 1 - Switch Settings and Communication Rate
Switch Setting Communication Rate
0 125 Kbps
1 250 Kbps
2 500 Kbps
8 When all three switches are set to 8, this resets the 1756-DNB
scanner module to factory default settings.
Do not use for normal operation.
All other values Select the communication rate with RSNetWorx for DeviceNet
software.
Front of
Module
Top of Module
Communication (data) Rate
Rotary Switch
14 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
5. From the Data Rate pull-down menu, choose the communication (data)
rate.
6. Click Apply.
7. Cycle power to the 1756-DNB scanner module.
Set the Node Address
The 1756-DNB scanner module supports DeviceNet node addresses 0063.
The factory default setting is node address 63.
Change the node address by setting the rotary switches or commissioning the
1756-DNB scanner module in RSNetWorx for DeviceNet software.
Use the switches to select any network address from 0063. When the switches
are set outside of this range (except for 888), you can configure the node address
with RSNetWorx for DeviceNet software. When all 3 switches are set to 8, the
1756-DNB scanner module will reset to factory default settings at powerup.
Figure 2 - Node Address Rotary Switch
Set the Rotary Switches
Use the node address rotary switches to change the DeviceNet node address for
the 1756-DNB scanner module.
1. If the module is removed from the chassis, be sure that power is removed or
the area is nonhazardous before proceeding.
2. Move the rotary switches to the desired position.
3. If necessary, reinstall the module into the chassis.
Table 2 - Switch Settings
Switch Setting Node Address
063 The DeviceNet node address is 0063.
888 When all 3 switches are set to 8, this resets the 1756-DNB scanner module
to factory default settings. Do not use for normal operation.
All other values Select the node address with RSNetWorx for DeviceNet software.
Front of
Module
Top of Module
Least Significant
Digit Switch
Most Significant
Digit Switch
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 15
Install a 1756 DeviceNet Communication Module Chapter 1
Use RSNetWorx for DeviceNet Software
Follow this procedure to use RSNetWorx for DeviceNet software to set the node
address.
1. In RSNetWorx for DeviceNet software, select the 1756-DNB scanner
module.
2. From the Tools menu, choose Node Commissioning.
3. Browse to the DeviceNet network for the 1756-DNB scanner module you
want to commission.
4. Select the 1756-DNB scanner module you want to commission.
5. From the Address pull-down menu, choose the node address.
6. Click Apply.
Restore the Factory Default
Settings
The out-of-box reset will clear the scan list, including ADR configuration
recovery files, and return all software setting attributes to their default values.
Follow this procedure to restore the factory-default communication rate and
node address.
1. Set the switches to 888.
2. Restore power to the module.
When the out-of-box reset is complete, the module status display
repeatedly scrolls the message Reset Complete - Change Switch Settings.
During this time, the module does not respond to communication from
any port, including the backplane, DeviceNet connector, or USB port.
3. After the module resets, perform these steps.
a. Set the switches to the desired position.
b. Restore power to the module.
IMPORTANT Do not use the 888 switch setting during normal module
operation.
16 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
Install the Module
To install the module, follow this procedure.
1. Align the circuit board with top and bottom guides in the chassis.
2. Slide the module into the chassis, making sure the module backplane
connector properly connects to the chassis backplane and noting that the
module is properly installed when it is flush with the power supply or other
installed modules.
WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
31588-M
31589-M
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 17
Install a 1756 DeviceNet Communication Module Chapter 1
Connect the Module to a
DeviceNet Network
Use an open-style 5- or 10-position linear plug to connect to the DeviceNet
network. An open-style 10-position linear plug is provided with your module.
Wire the connector according to the following illustrations.
Attach the connector to the modules DeviceNet port as shown below. Tighten
the screws on the connector as needed.
IMPORTANT For detailed DeviceNet connection information, see the DeviceNet Media
Design and Installation Guide, publication DNET-UM072.
Also see the Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
WARNING: If you connect or disconnect the DeviceNet connector with
power applied to this module or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Red Dot
Black Dot
Blue Dot
White Dot
10-position Plug 5-position Plug
D
D
D
D
D
Linear Plug
10-position
Drop Line or
DeviceNet
Trunk Cable
Red
White
Bare
Blue
Black
10-position Linear Plug
DeviceNet Port
DeviceNet Drop Line
or Trunk Connector
USB Port
18 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
Download the Add-on
Profile
If you are using a later firmware revision for the communication module than
recognized in the most current version of RSLogix 5000 software, you may need
to download the Add-on Profile (AOP) for the communication module so it can
be recognized in the Controller Organizer.
1. Locate the module AOP at http://www.rockwellautomation.com/
support/controlflash/LogixProfiler.
2. Click the file to download it.
3. Enter your RSLogix 5000 software serial number and click Qualify for
Update.
4. Download and extract the zipped files to a temporary directory.
5. Shut down any instances of RSLogix 5000 software that are currently
running.
6. In the temporary directory, double-click the MPSetup.exe file and follow
the onscreen instructions to install the AOP.
Connect to the Module
via the USB Port
The module has a USB device port that uses a series B receptacle. Connecting to
the module via the USB port requires these steps:
1. Set Up the Hardware.
2. Configure the Module via the USB Port.
3. Load Firmware through a USB Port.
IMPORTANT You need a Rockwell Automation MySupport account to
download the AOP. If you do not have one, follow the steps on the
MySupport website to obtain an account.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 19
Install a 1756 DeviceNet Communication Module Chapter 1
Set Up the Hardware
In this example, the controller in the local chassis produces a tag that the
Logix5000 controller in the remote chassis consumes. The local controller can
also send a MSG instruction to the remote controller.
Figure 3 - Sharing Data and Transferring Messages
Configure the Module via the USB Port
To use the modules USB port, you must have RSLinx Classic software, version
2.51 or later, installed on your computer. Use a USB cable to connect your
computer to the USB port. This connection lets you download programs to
controllers and configure other devices, which are accessible by the module,
directly from your computer.
Item Description
A Local chassis containing a Logix5000 controller and a communication module with a
USB port
B Remote chassis containing a Logix5000 controller with an EtherNet/IP connection
C Remote chassis containing a Logix5000 controller
WARNING: Do not use the USB port in hazardous locations.
ATTENTION: The USB port is intended for temporary local programming
purposes only and is not intended for permanent connection. The USB
cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
A
C
USB Connection
DeviceNet
B
20 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
To configure RSLinx Classic software to use a USB port, you need to first set up a
USB driver. To set up a USB driver, perform this procedure.
1. Connect your EtherNet/IP module to your computer by installing a USB
cable in your modules USB port.
The RSLinx Found New Hardware Wizard dialog box appears.
2. Click Install the Software Automatically.
3. Click Next.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 21
Install a 1756 DeviceNet Communication Module Chapter 1
These RSLinx dialog boxes appear consecutively.
4. Click Finish to set up your USB driver.
5. In RSLinx software, from the Communications pull-down menu, choose
RSWho.
22 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
The RSLinx Workstation organizer appears.
Your 1756-EN2T module appears under two different drivers, a virtual
chassis and the USB port.
Load Firmware through a USB Port

IMPORTANT Do not simultaneously load firmware for more than one module at a
time through a USB port. If you do, one or more of the firmware loads
may fail in the middle of the upgrade.
Virtual Chassis Driver
USB Port Driver
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 23
Install a 1756 DeviceNet Communication Module Chapter 1
Apply Chassis Power and
Check Status Indicators
Before you apply power, you must install and connect a ControlLogix chassis and
power supply.
To apply power, follow these steps.
1. Apply chassis power as shown.
2. Check the power supply and status indicators to determine that the power
supply and module are operating properly.
The module status display should cycle through the following states:
TEST - PASS - OK - REV x.x, where x.x is the modules firmware revision.
Power Supply indicator is green.
OK indicator is red during
self-test, then green.
Module Status Display
I/O
MOD/NET
24 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 1 Install a 1756 DeviceNet Communication Module
Install or Remove the
Module Under Power
You can install or remove this module while chassis power is applied.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance that can
affect module operation.
To remove or replace the module, use this procedure.
1. Push on the upper and lower module tabs to disengage them.
2. Slide the module out of the chassis.
WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.
IMPORTANT If you want to replace an existing module with an identical one, and you
want to resume identical system operation, you must install the new
module in the same slot.
31590-M
31591-M
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 25
Chapter 2
Install a 1769 DeviceNet Communication
Module
Topic Page
Installation Summary 27
System Assembly 28
Panel Mounting 29
DIN Rail Mounting 30
Connect the Module to a DeviceNet Network 31
Set the Node Address 31
Download the Add-on Profile 36
Apply Chassis Power and Check Status Indicators 36
Replace a Module within a System 36
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if
nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure type ratings that are required to comply with
certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation
requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by
enclosures
26 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
North American Hazardous Location Approval
The following information applies when operating this equipment
in hazardous locations.
Informations sur lutilisation de cet quipement en environnements
dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with markings on the rating
nameplate indicating the hazardous location temperature code. When
combining products within a system, the most adverse temperature code
(lowest "T" number) may be used to help determine the overall temperature
code of the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the time of
installation.
Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent qu' une
utilisation en environnements de Classe I Division 2 Groupes A, B, C, D
dangereux et non dangereux. Chaque produit est livr avec des marquages
sur sa plaque d'identification qui indiquent le code de temprature pour les
environnements dangereux. Lorsque plusieurs produits sont combins dans
un systme, le code de temprature le plus dfavorable (code de
temprature le plus faible) peut tre utilis pour dterminer le code de
temprature global du systme. Les combinaisons d'quipements dans le
systme sont sujettes inspection par les autorits locales qualifies au
moment de l'installation.
WARNING: EXPLOSION HAZARD
Do not disconnect equipment unless power
has been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed
or the area is known to be nonhazardous.
Secure any external connections that mate
to this equipment by using screws, sliding
latches, threaded connectors, or other means
provided with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
WARNING: RISQUE DEXPLOSION
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher l'quipement.
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher les connecteurs. Fixer
tous les connecteurs externes relis cet
quipement l'aide de vis, loquets
coulissants, connecteurs filets ou autres
moyens fournis avec ce produit.
La substitution de composants peut rendre
cet quipement inadapt une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est class non
dangereux avant de changer les piles.
WARNING: An electrical arc can occur if you do the following:
Insert or remove the module while backplane power is on
Connect or disconnect the communication cable with power applied to this module or any device on the network
Change switch settings while power is on
These actions could cause an explosion in hazardous location installations. Be sure that power is removed or the area is
nonhazardous before proceeding. Remove power before removing or inserting this module.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 27
Install a 1769 DeviceNet Communication Module Chapter 2
Installation Summary
To install a communication module in a 1769 ControlLogix chassis, complete
these steps.
1. System Assembly.
2. Panel Mounting.
or
DIN Rail Mounting.
3. Connect the Module to a DeviceNet Network.
4. Set the Node Address.
5. Download the Add-on Profile.
6. Apply Chassis Power and Check Status Indicators.
7. Apply Chassis Power and Check Status Indicators.
Grounding Considerations
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow
50 mm (2 in.) of space on all sides for adequate ventilation.
Allow at least 110 mm (4.33 in.) of enclosure depth to accommodate the module
and the DeviceNet connector.
ATTENTION:
The grounding screw on the front of the scanner must be connected to a suitable ground source when operating in
electrically noisy environments. Use a 2.08 mm
2
(14 AWG) wire to make this connection.
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure
proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately
every 200 mm (7.8 in.) and use end-anchors appropriately.
This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel. Additional
grounding connections from the scanner's mounting tabs or DIN rail (if used) are not required unless the mounting
surface cannot be grounded. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1,
for additional information.
Top
Side
Bottom
Side
Controller
C
o
m
p
a
c
t

I
/
O
C
o
m
p
a
c
t

I
/
O
C
o
m
p
a
c
t

I
/
O
C
o
m
p
a
c
t

I
/
O
C
o
m
p
a
c
t

I
/
O
E
n
d

C
a
p
28 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
System Assembly
The module can be attached to an adjacent controller, power supply, or I/O
module.
Follow these steps to assemble the Compact I/O system.
1. Disconnect power.
2. Check that the bus lever of the module (A) is in the unlocked (fully right)
position.
3. Use the upper and lower tongue-and-groove slots (B) to secure the
modules together.
4. Move the module back along the tongue-and-groove slots until the bus
connectors (C) line up with each other.
5. Use your fingers or a small screwdriver to push the bus lever back slightly to
clear the positioning tab (D).
6. Move the modules bus lever fully to the left (E) until it clicks.
Be sure it is locked firmly in place.
7. Attach an end cap terminator (F) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (G).
ATTENTION: When attaching I/O modules, it is very important
that the bus connectors are securely locked together to make a
proper electrical connection.
IMPORTANT A 1769-ECR or 1769-ECL right or left end cap must be used to
terminate the end of the serial communication bus.
G
F
E
D
B
A
B
C
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 29
Install a 1769 DeviceNet Communication Module Chapter 2
Panel Mounting
Mount the module to a panel by using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.
Panel Mounting Using the Dimensional Drawing
Hole spacing tolerance is 0.04 mm (0.016 in.).
Compact I/O Modules with CompactLogix Controller and Power Supply
Compact I/O Modules with MicroLogix 1500 Base Unit and Processor
ATTENTION: During panel or DIN rail mounting of all devices, be sure
that all debris, such as metal chips and wire strands, is kept from falling
into the module. Debris that falls into the module could cause damage on
powerup.
1
3
2

m
m


(
5
.
1
9

i
n
)
1
2
2
.
6

m
m


(
4
.
8
3

i
n
)
1
1
8

m
m


(
4
.
6
5

i
n
)
1
4
7
.
4

m
m


(
5
.
8
1

i
n
)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
28.5 mm
(1.12 in)
35 mm
(1.38 in)
70 mm
(2.76 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
50 mm
(1.97 in)
40 mm
(1.58 in)
5
9

m
m
(
2
.
3
2

i
n
)
5
9

m
m
(
2
.
3
2

i
n
)
DIN Rail Center Line
Mounting Hole Dimension
1
3
2

m
m


(
5
.
1
9

i
n
)
1
2
2
.
6

m
m


(
4
.
8
3

i
n
)
1
1
8

m
m


(
4
.
6
5

i
n
)
1
4
7
.
4

m
m


(
5
.
8
1

i
n
)
14.7 mm
(0.58 in)
35 mm
(1.38 in)
168 mm
(6.62 in)
147 mm
(5.79 in)
35 mm
(1.38 in)
13.5 mm
(0.53 in)
5
9

m
m
(
2
.
3
2

i
n
)
5
9

m
m
(
2
.
3
2

i
n
)
28.5 mm
(1.12 in)
DIN Rail Center Line
Mounting Hole Dimension
30 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
Panel Mounting Procedure Using Modules as a Template
This procedure lets you use the assembled modules as a template for drilling holes
in the panel. Due to module mounting hole tolerance, it is important to follow
these procedures.
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel by using the mounting screws.
7. Repeat these steps for any remaining modules.
DIN Rail Mounting
The module can be mounted by using the following DIN rails: 35 x 7.5 mm
(EN50022 - 35 x 7.5) or 35 x 15 mm (EN 50022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the
DIN rail mounting area of the module against the DIN rail. The latches will
momentarily open and lock into place. DIN rail mounting dimensions are shown
below.
A
B
C
Dimension Height
A 118 mm
(4.65 in.)
B 59 mm
(2.325 in.)
C 59 mm
(2.325 in.)
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 31
Install a 1769 DeviceNet Communication Module Chapter 2
Connect the Module to a
DeviceNet Network
Follow these steps to wire the DeviceNet connector.
1. Connect the DeviceNet cable to the removable connector as shown.
2. Insert the removable female connector into the mating male connector on
the DeviceNet scanner module.
3. Screw the removable connector to the scanner case with the upper and
lower mounting screws with a torque of 0.60.7 Nm (56 lbin).
Set the Node Address
Set the node address using one of these methods:
For the 1769-ADN, use the node address rotary switches as described in
Set the Node Address of a 1769-ADN Module.
For the 1769-SDN, use RSNetWorx for DeviceNet software as described
in Set the Node Address of a 1769-SDN Module. The 1769-SDN module
has no hardware mechanism to set its address.
DeviceNet Connector
Connect Wire
(1)
(1) DeviceNet cable colors are shown on
the wiring label on the front of the
scanner.
To
Red V+
White CAN High
Bare Shield
Blue CAN Low
Black V-
Grounding Screw
Use 2.08 mm
2
(14 AWG) wire
to connect to panel ground.
C
o
m
m

A
d
a
p
t
e
r
MS
IO
NS
DIAG
DeviceNet Connector
1769-ADN 1769-SDN
IMPORTANT If the 1769-SDN module is the first or last device connected to the
DeviceNet network trunkline, be sure to add a termination
resistor (120 1% W resistor, Allen-Bradley catalog number
1485A-C2) across the blue (CAN Low) and white (CAN High)
wires.
32 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
Set the Node Address of a 1769-ADN Module
The module supports DeviceNet node addresses 00...63. The factory default
setting is node address 63.
Set the node address by using the two rotary switches. Use a small, slotted
screwdriver to set the switches. The switch labeled MSD (Most Significant Digit)
sets the 10s while the switch labeled LSD (Least Significant Digit) sets the 1s.
Use the switches to select any network address from 0063. Switch settings from
0063 select node addresses 0063. Switch settings from 6499 instruct the
adapter to use the software programmed value for the network address.
Switch setting 95 is reserved for factory use in Series B adapters.
The software programmed value is set via the node commissioning tool available
in RSNetWorx for DeviceNet software and stored in nonvolatile memory on the
1769-ADN.
Figure 4 - Node Address Rotary Switches
Use the removable, write-on label to mark your I.D. tag and other markings with
permanent ink. Your markings are visible when the module door is closed.
TIP The baud rate for the adapter is set by way of the modules Autobaud
feature at powerup.
TIP Series B adapters that have their node address switches set to 95 start
up in a special factory mode that does not support I/O connections.
Series B adapters should not have their node address set to 95 for
normal use.
C
o
m
m

A
d
a
p
t
e
r
MS
IO
NS
DIAG
42127
Least Significant Digit Switch
Most Significant Digit Switch
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 33
Install a 1769 DeviceNet Communication Module Chapter 2
Set the Node Address of a 1769-SDN Module
You can use the following options to set the node address of DeviceNet devices:
Set the Node Address via Software on page 33
Set the Node Address via the DeviceNet Node Commissioning Tool on
page 34
Set the Node Address via Software
Complete the following steps to set a devices node address in your network
configuration file. This example uses an AC drive.
1. Start RSNetWorx for DeviceNet software and double-click the device.
2. Enter the DeviceNet address for the device.
3. Click OK to close the configuration window.
1
2
3
34 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
Set the Node Address via the DeviceNet Node Commissioning Tool
You can use the DeviceNet node commissioning tool available in RSNetWorx for
DeviceNet software to set the node addresses of devices on the DeviceNet
network. Remember the following when you decide to use the DeviceNet node
commissioning tool.
You can only use this tool with a DeviceNet network that is online.
You can only use this tool as you add new devices to the network that
either do not have hardware mechanisms to set their node address or have
their hardware mechanism set to a number higher than 63.
If you add a device to the network with a hardware mechanism setting the
node address to 63 or lower, this tool does not change the devices node
address.
You should complete the tasks described in this section each time a new
device is added to the network.
If you add more than one device to the online network before using the
DeviceNet node commissioning tool, you will experience duplicate node
address conflicts on the network because all new devices initially use node
address 63.
Keep track of the node addresses you set with the DeviceNet node
commissioning tool and verify they match the devices configuration in the
RSNetWorx for DeviceNet software configuration file.
Complete the following steps to use the DeviceNet node commissioning tool to
set a devices node address.
1. Verify that the network is online.
2. Connect a device to the DeviceNet network.
3. Choose Start>Programs>Rockwell Software>RSNetWorx for
DeviceNet>DeviceNet node commissioning tool.
or
From the Tools pull-down menu in RSNetWorx for DeviceNet software,
choose Node Commissioning.
4. Click Browse.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 35
Install a 1769 DeviceNet Communication Module Chapter 2
5. On the Device Selection dialog box, check the I want to input the address
for the device on the selected network box.
6. Browse to the DeviceNet network.
7. Type the current address for the device. Out of the box, devices use
address 63.
8. Click OK.
9. When you return to the Node Commissioning dialog box, enter the new
address for the device.
10. Click Apply.
11. Look for confirmation in the Messages area.
36 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
Download the Add-on
Profile
If you are using a later firmware revision for the communication module than
recognized in the most current version of RSLogix 5000 software, you may need
to download the Add-on Profile (AOP) for the communication module so it can
be recognized in the Controller Organizer.
1. Locate the module AOP at http://www.rockwellautomation.com/
support/controlflash/LogixProfiler.
2. Click the file to download it.
3. Enter your RSLogix 5000 software serial number and click Qualify for
Update.
4. Download and extract the zipped files to a temporary directory.
5. Shut down any instances of RSLogix 5000 software that are currently
running.
6. In the temporary directory, double-click the MPSetup.exe file and follow
the onscreen instructions to install the AOP.
Apply Chassis Power and
Check Status Indicators
Before you apply power, you must install and mount a CompactLogix controller
and Compact I/O power supply on the DIN rail.
To apply power, follow these steps.
1. Apply chassis power.
2. Check the power supply and status indicators to determine that the power
supply and module are operating properly.
Replace a Module within a
System
The module can be replaced while the system is mounted to a panel or DIN rail.
1. Remove power.
2. Remove the DeviceNet cable from the module by removing the DeviceNet
connector.
3. Remove the upper and lower mounting screws from the module or open
the DIN latches by using a screwdriver.
IMPORTANT You need a Rockwell Automation MySupport account to
download the AOP. If you do not have one, follow the steps on the
MySupport website to obtain an account.
ATTENTION: Do not remove or replace this module while power is
applied. Interruption of the backplane can result in unintentional operation
or machine motion.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 37
Install a 1769 DeviceNet Communication Module Chapter 2
4. On the module to be replaced and the right-side adjacent module (or end
cap if the module is the last module in the bank), move the bus levers to the
right (unlock) to disconnect the module from the adjacent modules.
5. Gently slide the disconnected module forward.
If you feel excessive resistance, be sure that you disconnected the module
from the bus and that you removed both mounting screws or opened the
DIN latches.
It may be necessary to rock the module slightly from front to back to
remove it. In a panel-mounted system, you might need to loosen the screws
of adjacent modules.
6. Before installing the replacement module, be sure that the bus lever on the
right-side adjacent module is in the unlocked (fully right) position.
7. Slide the replacement module into the open slot.
8. Connect the modules together by locking (fully left) the bus levers on the
replacement module and the right-side adjacent module or end cap.
9. Replace the mounting screws or snap the module onto the DIN rail.
10. Replace the DeviceNet cable by attaching the connector to the module.
11. Restore configuration by using RSNetWorx for DeviceNet software.
IMPORTANT Be sure that the new module has the same node address and
communication rate as the module that was replaced.
38 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 2 Install a 1769 DeviceNet Communication Module
Notes:
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 39
Chapter 3
Configure a Workstation to Operate on a
DeviceNet Network
You can connect a computer to the network before or after connecting devices to
the network. You can also connect a computer to the network before or after
configuring the network offline.
You must connect a computer to the network before configuring the network
online.
After you connect a computer to the system and configure a driver in RSLinx
Classic software, you can complete these tasks:
Configure the devices on the network.
Configure network parameters.
Upload, download, monitor, and program projects for Logix5000
controllers.
Some networks let you bridge to other networks in your system. This lets you
connect to one network and access devices or controllers on other networks.
Topic Page
Connect a Computer to the DeviceNet Network 40
Configure a Driver for a Network 41
40 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 3 Configure a Workstation to Operate on a DeviceNet Network
Connect a Computer to the
DeviceNet Network
To access the DeviceNet network, use one of these methods:
Connect directly to the network via a DeviceNet interface device. If you
connect directly to a DeviceNet network, you can access only the devices
on that network.
This graphic shows a computer connected directly to a DeviceNet
network by using a 1784-PCIDS Universal PCI Scanner Card.
Figure 5 - Connect Directly to a DeviceNet Network
Connect to a different network and bridge to the desired DeviceNet
network. This requires no additional programming.
This graphic shows a computer connected to a DeviceNet network
through an EtherNet/IP network used with a ControlLogix system.
Figure 6 - Connect to a DeviceNet Network through an EtherNet/IP Network
DeviceNet Network
Device Device Device Device Device
Device Device Device
EtherNet/IP
Module
ControlLogix
Controller
DeviceNet
Module
DeviceNet Network
EtherNet/IP Network
Computer
Device Device
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 41
Configure a Workstation to Operate on a DeviceNet Network Chapter 3
Depending on how you decide to connect your computer to the DeviceNet
network, do the following.
1. If you are connecting directly to the network, install the1784-PCD card,
1784-PCIDS card, or 1784-U2DN cable.
For more information on installing the 1784-PCD card, refer to the
DeviceNet Communication Card installation instructions, publication
1784-IN029.
For more information on installing the 1784-PCIDS card, refer to the
DeviceNet Universal PCI Scanner Card installation instructions,
publication 1784-IN004.
For more information on installing the 1784-U2DN cable, refer to the
USB-to-DeviceNet Cable installation instructions, publication
1784-IN046.
2. If you are connecting to a different network and bridging to the DeviceNet
network, install the required communication modules.
3. Connect the computer to the network with the correct cable.
Configure a Driver for a
Network
To communicate over a specific network, configure a driver in RSLinx Classic
software for the appropriate network.
Complete the following steps to configure a driver for the network.
1. In RSLinx Classic software, from the Communications pull-down menu,
choose Configure Drivers.
The Configure Drivers dialog box appears.
IMPORTANT If RSLinx Classic software, version 2.54 or later, is installed on the
computer, the device driver is already installed on the computer. Skip this
section.
42 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 3 Configure a Workstation to Operate on a DeviceNet Network
2. From the Available Driver Types pull-down menu, choose DeviceNet
Drivers.
3. Click Add New and name the new driver.
4. Click OK.
5. Configure the driver.
The configuration screens may differ for each driver.
Driver Configuration
If unused, use the default
Node Address of 62 and set
your Network Baud Rate.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 43
Configure a Workstation to Operate on a DeviceNet Network Chapter 3
Verify that the Driver Works
Complete these steps to verify that the driver works.
1. Open the Configure Drivers dialog box and verify that the driver is
running.
2. Close the Configure Drivers dialog box.
3. Open the RSWho dialog box.
4. Double-click the driver to see the network.
44 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Chapter 3 Configure a Workstation to Operate on a DeviceNet Network
Notes:
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 45
Appendix A
1756 DeviceNet Status Indicators and Data
Structures
1756-DNB DeviceNet
Scanner Status Indicators
The 1756-DNB scanner has three status indicators that provide information
about your network and its connections.
Topic Page
1756-DNB DeviceNet Scanner Status Indicators 45
1756-DNB DeviceNet Scanner Alphanumeric Display 47
1756-DNB DeviceNet Scanner Data Structures 51
Status Indicator Description
Module/Network (MOD/NET) Status A bicolor (green/red) status indicator that provides device
and communication status.
I/O Status A bicolor (green/red) status indicator that provides the
status of inputs and outputs, including the following:
Whether the device has outputs under its control
Whether any outputs or inputs are active or faulted
Mod/state of the inputs and outputs, but not
necessarily the On/Off condition of the I/O points
OK Status A bicolor (green/red) status indicator that reflects
whether the device has power and is operating properly.
DeviceNet TM
MOD/NET I/O OK
Module/Network
Status Indicator
I/O Status Indicator
OK Status Indicator
46 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix A 1756 DeviceNet Status Indicators and Data Structures
Table 3 - Module/Network Status (MOD/NET) Indicator
Status Description
Off One of the following conditions exists:
The device has not completed the Dup_MAC_ID test.
The device may not have power.
Either wait for the Dup_MAC_ID test to complete or make sure the device has
power.
Solid green The device is fully operational and is communicating with other devices on the
network:
For a Group 2 only device, this means the device is allocated to a master.
For a UCMM capable device, this means the device has one or more
established connections.
No action is necessary.
Flashing green
(1)
The device is fully operational and online. However, it is not communicating with
other devices on the network because of one of the following conditions:
The device has passed the Dup_MAC_ID test, is online, but has no
established connections to other nodes.
For a Group 2 only device, this means the device is not allocated to a master.
For a UCMM capable device, this means that the device has no established
connections.
The configuration is missing, incomplete, or incorrect.
No action is required until you need the device to communicate with other
devices. In that case, check your system configuration.
Flashing red
(1)
Either or both of the following conditions exist:
A recoverable fault has occurred.
Communication with at least one device has timed out.
Check the 4-character display to determine which device has timed out.
Solid red Any of the following conditions exist:
Another device is using the same address.
In this case, change the device address to a unique value.
Communication problems on the network (bus off condition).
In this case, make sure all devices are operating at the same communication
rate.
Device has an unrecoverable fault.
In this case, replace the scanner.
For more corrective actions, see status code 91 on page 50.
(1) The flash rate of the status indicator is approximately 1 flash per second. The status indicator should be on for
approximately 0.5 seconds and off for approximately 0.5 seconds.
Table 4 - I/O Status Indicator
Status Description
Off The scanner is not powered.
Apply chassis power, and verify the module is completely inserted into the
chassis.
Solid green The scanner is in Run mode, outputs are under control, and inputs are being
consumed.
No action is necessary.
Flashing green
(1)
The scanner is in Idle mode, outputs are not under control, and inputs are being
consumed.
To control output devices, place the scanner in Run mode.
(1) The flash rate of the status indicator is approximately 1 flash per second. The status indicator should be on for
approximately 0.5 seconds and off for approximately 0.5 seconds.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 47
1756 DeviceNet Status Indicators and Data Structures Appendix A
1756-DNB DeviceNet
Scanner Alphanumeric
Display
The 1756-DNB scanner has an alphanumeric display that provides diagnostic
information about your module through status messages and status codes. The
display flashes messages and codes at approximately one-second intervals.
Table 5 - OK Status Indicator
Status Description
Off The device is not powered.
Apply chassis power, and verify the module is completely inserted into the
chassis.
Solid green The device is operating normally and has at least one connection to it from a
controller.
No action is necessary.
Flashing green
(1)
The device is operating correctly, but no controller is controlling it.
Verify that the 1756-DNB scanner module is properly configured in the
controllers I/O configuration.
Solid red One of the following conditions exists:
The device is in Self-test mode.
In this case, wait until the test completes.
During powerup, the device has experienced an unrecoverable fault.
In this case, complete these steps.
1. Wait for the device to complete its power-up sequence.
2. If the device appears to have completed its power-up sequence and the
indicator remains solid red, cycle power.
3. If after cycling power the status indicator still remains solid red, replace the
device.
(1) The flash rate of the status indicator is approximately 1 flash per second. The status indicator should be on for
approximately 0.5 seconds and off for approximately 0.5 seconds.
DeviceNet TM
MOD/NET I/O OK
Alphanumeric Display
48 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix A 1756 DeviceNet Status Indicators and Data Structures
Status Messages
This table summarizes the DeviceNet status messages that appear on the
alphanumeric display.
Table 6 - Status Messages
Display Description
RUN The scanner is in Run mode.
IDLE The scanner is in Idle mode.
AUTO The AutoScan option is on, and the scanner is in Idle mode.
Flash In Progress ControlFLASH software is transferring an upgrade image to the scanner.
Duplicate Node Failure The node address of the scanner is in use by another device on the
DeviceNet network.
Bus Off Detected The scanner has detected errors on the DeviceNet network and is offline.
No Network Power The DeviceNet cable is not supplying power to the communication port.
Troubleshoot the system to determine why power is not supplied and turn
on power to the network.
NoRx Either or both of the following conditions exist:
The device does not have a scan list.
In this case, configure a scan list.
The device has not received communication from any other device.
In this case, check the system configuration to determine why
communication is not occurring.
NoTx Either or both of the following conditions exist:
The scanner has failed to transmit a message due to a network or device
issue.
The scanner is the only node on the network.
Reset Complete -
Change Switch
Settings
The factory default settings for the scanner have been restored.
Set the data rate and node address rotary switches to the desired position
and restore power to the scanner.
Network disabled The scanner is not enabled.
To enable the scanner, locate the O.CommandRegister.DisableNetwork bit
on the command register and turn it off.
A#xx Indicates the scanners DeviceNet node address where xx is the address.
N#xx Indicates there is a problem with another device on the network where xx
is the address of the device.
The status code for the device follows the address. Refer to Table 7 on
page 49 for more information about status codes.
E#xx Indicates a status code for a device with a problem where xx is the status
code for the device.
The address of the device comes before the status code. Refer to Table 7
on page 49 for more information about status codes.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 49
1756 DeviceNet Status Indicators and Data Structures Appendix A
Status Codes
This table summarizes the DeviceNet status codes that appear on the
alphanumeric display.
Table 7 - Status Codes
Status Code Description Recommended Action
063 Indicates the scanners DeviceNet node address. None.
65 The AutoScan option is on and the device is in Idle mode. None.
67 The scanner is the secondary scanner. None.
68 The primary scanner has detected no secondary scanner. Configure another scanner to be the secondary scanner.
69 The primary and secondary configurations are mismatched. Check configuration of the secondary scanner.
70 The address of the device is already in use by another device
on the network. The scanner failed the duplicate node address
check.
Change the address of the device to an unused address.
71 There is invalid data in the scan list. Use RSNetWorx for DeviceNet software to reconfigure the
scan list.
72 The slave device stopped communicating. If the slave device
does not recover communication during the next scan, the
status code changes to 78.
Verify the slave devices power and communication
connections.
If the slave device is polled, verify that the interscan delay
time is adequate for the device to return data.
73 The slave devices identity information does not match the
electronic key in the scanner.
Make sure that the correct device is connected at this
address.
Make sure that the device matches the specified electronic
key, such as vendor, product code, or product type.
74 The scanner detected a data overrun on the DeviceNet
communication port.
Modify your configuration and check for invalid data.
Check network communication traffic.
75 Either or both of the following may be true:
The device does not have a scan list.
The device has not received communication from any other
device.
Verify that the device has the following:
A configured scan list
A properly-wired connection to the network
76 There is no direct network traffic for the scanner. The scanner
hears other network communication but does not hear any
communication directed to it.
None.
77 During initialization, the data size expected by the device does
not match the scan list entry.
Use RSNetWorx for DeviceNet software to check the slave
device and the scan list for the correct input and output sizes
for the slave device.
78 The device is configured in the scan list, but not
communicating. The device has failed to communicate during
the scanners second scan, which followed the display of
status error code 72.
Verify devices power and communication connections.
If the device is polled, make sure the interscan delay is long
enough for the device to return its data.
If necessary, use RSNetWorx for DeviceNet software to do the
following:
Add the device to the DeviceNet network.
Delete the device from scanners scan list.
Inhibit the device in the scanners scan list.
79 The scanner has failed to transmit a message. The error status
usually displays after the duplicate node check completes and
power is applied to the module.
Make sure the scanner is connected to a valid network.
Check for disconnected cables.
Verify the network communication rate.
80 The scanner is in Idle mode. Put the controller in Run or Remote Run mode by using the
keyswitch on the controller or through RSLogix 5000
software.
Turn on the bit O.CommandRegister and run for the scanner.
50 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix A 1756 DeviceNet Status Indicators and Data Structures
81 The controller has set the scanner to the Faulted mode. The
Command bit also indicates a DeviceNet network fault state.
The Bit O.CommandRegister.Fault for the scanner is on.
Correct the condition that caused the controller to set this bit
and then turn this bit off.
82 An error was detected in a sequence of fragmented I/O
messages from the device.
Use RSNetWorx for DeviceNet software to do the following:
Check the scan list of the device to make sure that its input
and output data sizes are correct.
Check the configuration of the device.
83 The device returns error responses when the scanner attempts
to communicate with it.
Use RSNetWorx for DeviceNet software to do the following:
Check the accuracy of the scan list.
Check the configuration of the device. The device may be in
another scanners scan list.
Use the slave devices documentation to verify that the
device supports the message type used by the scanner.
If the devices message type does not match the scanners,
then use RSNetWorx for DeviceNet software to access the
scanners scan list and change the scanners message type
to one that is compatible with the slave device.
Cycle power to the device.
84 The scanner is initializing the DeviceNet network. None. This code clears itself once the scanner attempts to
initialize all the devices on the network.
85 During runtime, the data size sent by the slave device does not
match the size in the corresponding scan list entry.
Because variable length poll data is not supported, verify that
the slave device is functioning properly.
86 The device is in Idle mode, or not producing data, while the
scanner is in Run mode.
Check the configuration and status of the device.
If you set up an interlock between two scanners
(controllers), make sure both scanners are in Run mode.
87 The scanner cannot listen to shared inputs from the slave
device because the owning scanner has not established
communication with that slave device.
Verify the primary scanner connection and configuration.
Verify that the slave device is producing data.
88 The scanner cannot listen to shared inputs from the slave
device because I/O parameters, such as electronic key or data
size, for that slave device are configured differently between
this scanner and the owning scanner.
In this scanner, reconfigure the I/O parameters for the shared
inputs scan list entry so that they match those same
parameters in the owning scanner.
89 The scanner failed to configure a device using the Automatic
Device Recovery (ADR) parameters.
Make sure that you installed a compatible device.
If the offline configuration of the device does not match the
actual (online) configuration of the device, change the
offline configuration to match the online configuration.
90 The controller has set the scanner to Disabled mode. If desired, enable the scanner by locating the
O.CommandRegister.DisableNetwork bit on the command
register and turning it off.
91 Indicates a Bus-off condition likely due to cable or signal
errors.
Cycle power to the device.
Verify that all devices are set to the same communication
rate.
Check DeviceNet cabling to make sure no short circuits
exist between CAN (blue and white) wires and power or
shield (black, red, and shield) wires.
Check the media system for the following noise sources:
Close proximity to high-voltage power cable
Incorrect or no termination resistor
Improper grounding
Noise produced from another device on the network
Incorrect data for the network
Table 7 - Status Codes
Status Code Description Recommended Action
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 51
1756 DeviceNet Status Indicators and Data Structures Appendix A
1756-DNB DeviceNet
Scanner Data Structures
The 1756-DNB scanner module supports several sizes of input, output, and
status structures over the ControlLogix backplane. These I/O structures were
created to reduce the complexity of connecting DeviceNet I/O and status data
with ladder programs.
The module creates all three structures whether DeviceNet devices are
configured or online.
RSLogix 5000 software directs the controller to connect to these predefined
default I/O structures. The controller automatically performs periodic updates of
the structures on a cyclic basis.
RSNetWorx for DeviceNet software configures scan list map segments that are
used to copy specific portions of I/O data between the I/O structures and
DeviceNet network packets.
92 The DeviceNet cable is not supplying power to the devices
communication port.
Verify that the networks 24V DC power supply is operating
properly.
Verify the cable is in good condition.
Check the cable connections to the device.
95 A devices firmware is being updated or a configuration is
being downloaded.
None. Do not disconnect the device while the update is in
process because existing data in the device memory will be
lost.
96 The communication port is in Test mode. None.
97 The controller has placed the scanner in Halt mode. If the O.CommandRegister.HaltScanner bit is on, turn it off.
Then cycle scanner power.
98 General firmware error. Replace device.
99 System failure. Replace device.
Table 7 - Status Codes
Status Code Description Recommended Action
IMPORTANT Only one Logix controller at a time can send outputs to the 1756-DNB
scanner module.
52 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix A 1756 DeviceNet Status Indicators and Data Structures
Input Structure
The controller receives input I/O by reading input data from an input structure
in the 1756-DNB scanner module. The scanner module receives input data from
DeviceNet modules and delivers a copy of these values to the controller. The
input structure consists of one 32-bit status register and a variable size 32-bit array
of up to 124 words for input data. The 32-bit status register reflects the current
state of several key module-level operational parameters.
The input structure consists of these data elements.
Output Structure
The controller controls output I/O by writing output data to an output structure
in the 1756-DNB scanner module. The scanner module then delivers a copy of
these output values to modules on the DeviceNet network. The output structure
consists of a 32-bit command register and a variable size 32-bit array of up to 123
words for output data. The 32-bit command register consists of several bits that
affect the modules behavior on the network.
The output structure consists of these data elements.
Module Command Register Bit Definitions
The bits of the Module Command Register are defined as follows.
Input Structure Element Data Type
module status register 1 x 32-bit register
input_data 123 x 32-bit variable size data array
Output Structure Element Data Type
module command register 1 x 32-bit register
output_data 123 x 32-bit data array
Bit Name Description
0 Run 1 = Run mode
0 = Idle mode
1 Fault 1 = Fault network
2 DisableNetwork 1 = Disable network
3 HaltScanner 1 = Halt module
The 1756-DNB scanner module ceases all operation.
4 Reset 1 = Reset module (put back to 0 to resume operation)
531 Reserved Unused
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 53
1756 DeviceNet Status Indicators and Data Structures Appendix A
Module Status Register Bit Definitions
The Module Status Register bits are defined as follows.
IMPORTANT If the module is halted because the HaltScanner bit is set, power must be
physically cycled to restart the module.
Bit Name Description
0 Run 1 = in Run mode
0 = in Idle mode
1 Fault 1 = Network is faulted
2 DisableNetwork 1 = Network is disabled
3 DeviceFailure 1 = Device failure exists (examine the status structure for
causes)
4 AutoverifyFailure 1 = At least one device has failed to be initialized by the
scanner
5 CommFailure 1 = Communication failure exists
6 DupNodeFail 1 = Failure due to duplicate node address
7 DnetPowerDetect 1 = DeviceNet power failure
8 NetworkWarning 1 = Scanner has detected numerous receive and/or transmit
errorscheck the integrity of the DeviceNet network
931 Reserved Unused
54 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix A 1756 DeviceNet Status Indicators and Data Structures
Status Structure
The controller receives status information concerning the 1756-DNB scanner
modules ability to exchange DeviceNet messages with other nodes by reading
from the status structure in the 1756-DNB scanner module. The scanner module
periodically updates the contents of the status structure and copies its contents to
the controller. The status structure consists of several tables. The bit position of
each of the 64-bits that make up a given status table directly corresponds to the
node address of a device.
The status structure consists of these data elements.
Status Structure Element Description Data
Type
DINTS
ScanCounter Counter incremented each I/O scan 32-bit 10
DeviceFailureRegister Device failed bit table; 1 = failed 64-bit
AutoverifyFailureRegister Device I/O size does not match scanners
internal table; 1 = mismatch
64-bit
DeviceIdleRegister Device is idle bit table; 1 = idle 64-bit
ActiveNodeRegister Node online bit table; 1 = online 64-bit
StatusDisplay ASCII representation of scanner
alphanumeric display
4-byte
ScannerDeviceStatus Scanner device status 4-byte
binary
11
ScannerAddress DeviceNet address of1756- DNB scanner
module
8-bit
binary
ScannerStatus Status of 1756-DNB scanner module 8-bit
binary
ScrollingDeviceAddress Scrolls through DeviceNet nodes once
per second by address and status; 0 = no
faults
8-bit
binary
ScrollingDeviceStatus 8-bit
binary
ReservedArray Future expansion (20 bytes) 20 x 8-bit 16
DeviceStatus DeviceNet node status array, byte per
device
64 x 8-bit 24/32
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 55
Appendix B
1769 DeviceNet Modules Status Indicators
and Data Structures
1769-ADN Adapter Status
Indicators
The 1769-ADN adapter has four status indicators that provide information
about your network and its connections.
Topic Page
1769-ADN Adapter Status Indicators 55
1769-ADN Adapter Data Structures 58
1769-SDN Scanner Status Indicators 59
1769-SDN Scanner Status Codes 61
1769-SDN Scanner Data Structures 63
Status Indicator Description
Module Status Indicator A bicolor (green/red) status indicator that provides device
status.
I/O Status Indicator A bicolor (green/red) status indicator that provides the
status of inputs and outputs, including the following:
Whether the adapter has outputs under its control
Whether any outputs or inputs are active or faulted
Mod/state of the inputs and outputs, but not
necessarily the On/Off condition of the I/O points
Network Status Indicator A bicolor (green/red) status indicator that provides
communication status.
Diagnostic Status Indicator A bicolor (green/red) status indicator that provides the
status of diagnostic tests.
Diagnostic Status Indicator
Module Status Indicator
I/O Status Indicator
Network Status Indicator
56 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures
Table 8 - Module Status Indicator
Status Description
Off The adapter is not powered.
Verify that the adapter is installed correctly.
Flashing green The adapter is online, but the configuration is missing.
Configure the adapter.
Solid green The adapter is fully operational and is communicating with other
devices on the network.
No action is required.
Flashing red The adapter has experienced a recoverable fault due to one of these
conditions:
Configuration is incorrect.
Duplicate MAC ID check has failed.
Node address switch has changed.
Main program checksum has failed.
Configured I/O size is too large.
Solid red The adapter has experienced an unrecoverable fault due to one of
these conditions:
Terminator/end cap is missing.
Connector or cable between devices is missing or no longer
connected.
An issue with the configuration memory exists.
Watchdog has been tripped.
Table 9 - I/O Status (IO) Indicator
Status Description
Off The adapter is not powered.
Verify that the adapter is installed correctly.
Flashing green The adapter is in Idle mode, outputs are not under control, and inputs
are being consumed.
To control output devices, place the adapter in Run mode.
Solid green The adapter is in Run mode, outputs are under control, and inputs
are being consumed.
No action is required.
Flashing red The adapter has experienced a recoverable fault because one or
more of the I/O modules may be in Fault mode.
Check the I/O modules to determine which ones are in Fault mode
and remedy that issue.
Solid red The adapter has experienced an unrecoverable fault because one or
more of the I/O modules may be in Fault mode.
Check the I/O modules to determine which ones are in Fault mode
and remedy that issue. If you remedy the issue and the status
indicator remains solid red, replace the adapter.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 57
1769 DeviceNet Modules Status Indicators and Data Structures Appendix B
Table 10 - Network Status (NS) Indicator
Status Description
Off The network or the adapter is not powered.
Check power connections to the network and then verify that the
adapter is installed correctly.
Flashing green The device is fully operational but is not communicating with the
controller.
Make sure the scanner is correctly configured in the controllers I/O
configuration.
Solid green The device is fully operational and communicating with the
controller.
No action is required.
Flashing red One or both of these conditions exist:
A recoverable fault has occurred.
Communication with at least one device has timed out.
Check the 4-character display to determine which device has timed
out.
Solid red The adapter is powering up, or has fully powered up, and
experienced an unrecoverable fault.
1. If necessary, wait for the adapter to fully power up.
2. Cycle power to the adapter.
3. If after cycling power, the status indicator remains solid red,
replace the adapter.
Table 11 - Diagnostic Status (DIAG) Indicator
Status Description
Off The adapter is not powered or is running diagnostics.
Apply power to the adapter or wait for it to finish running
diagnostics.
Flashing amber The Main program detected an error.
Flashing green Diagnostic tests are in progress.
Wait for the tests to finish.
Flashing red Diagnostics found an error. The number of flashes indicates which
test failed:
One flashRAM test failed.
Two flashesBoot program checksum failed.
Three flashesMain program checksum failed.
Four flashesConfiguration checksum failed.
Five flashesAccess to program or configuration failed.
Six flashesBackplane power fault (series B only).
Solid red Watchdog has been tripped.
58 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures
1769-ADN Adapter Data
Structures
The scanner uses the input and output data images to transfer data, status, and
command information between the adapter and the scanner.
Input Data
This is the I/O data the 1769-ADN adapter sends to the DeviceNet master. All
inputs are in words.
Output Data
This is the I/O data the DeviceNet master sends to the 1769-ADN adapter. All
outputs are in words.
W
o
r
d
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 V16 V15 V14 V13 V12 V11 V10 V9 V8 V7 V6 V5 V4 V3 V2 V1
1 X NS V30 V29 V28 V27 V26 V25 V24 V23 V22 V21 V20 V19 V18 V17
2 Input data for slot 1
(1)
(1) The amount of input data for each module is based on the configuration of each I/O module done as part of the
1769-ADN configuration. Note that if an I/O module is configured to have 0 words of input data, then there are
no input data words for that module in the 1769-ADN adapters input image.
V1 = Data invalid from slot 1 (1 = invalid data)
V2 = Data invalid from slot 2
V3 = Data invalid from slot 3

V30 = Data invalid from slot 30 where 1 = data invalid or a module error is detected; 0 = data valid, no module error
NS = Node address switch changed where 1 = node address switch changed since power-up
X = Reserved
3

n Input data for slot 30
(1)
W
o
r
d
Bit Position
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Output data for slot 1
(1)
(1) The amount of output data for each module is based on the configuration of each I/O module done as part of the
1769-ADN configuration. Note that if an I/O module is configured to have 0 words of output data, then there are
no output data words for that module in the 1769-ADN adapters output image.
1

n Output data for slot 30
(1)
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 59
1769 DeviceNet Modules Status Indicators and Data Structures Appendix B
1769-SDN Scanner Status
Indicators
The 1769-SDN scanner has two status indicators that provide information about
the scanner and its network connection.
Status Indicator Description
Module Status Indicator A bicolor (green/red) status indicator that provides device status.
Network Status Indicator A bicolor (green/red) status indicator that provides
communication status.
Table 12 - Module Status Indicator
Indicator Condition Description
Off The scanner is not powered.
Apply power.
Flashing green No Bus Master (MicroLogix or CompactLogix controller) is
present.
Complete these steps to address this issue.
1. Verify that module connectors are properly seated.
2. If the connectors are properly seated, cycle power to the
controller.
3. If cycling power does not correct the issue, replace the
controller.
4. If replacing the controller does not correct the issue, replace
the scanner.
Solid green The scanner is fully operational and is communicating with other
devices on the network.
Flashing red The scanner has experienced a recoverable fault because one of
these conditions exists:
Memory has been erased.
Memory is being programmed.
Complete the update or start a new update.
Solid red The scanner has experienced an unrecoverable fault. Complete
these steps to address this issue.
1. Verify that the module connectors are properly seated.
2. If the connectors are properly seated, verify that the bus
terminator/end cap is installed.
3. If the bus terminator/end cap is installed, cycle power.
4. If, after cycling power, the status indicator is still solid red,
replace the scanner.
Module Status Indicator
Network Status Indicator
60 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures
Table 13 - Network Status Indicator
Indicator Condition Description
Off One of these conditions exists:
The scanner is not powered.
The network is not powered.
Communication is not occurring between the scannner and the
DeviceNet network. (This may be an acceptable condition.)
Complete these steps to change this state.
1. Verify that the scanner has power.
2. Check that the DeviceNet cable is securely connected and the
DeviceNet network is powered.
3. Verify that network power is adequate (1125V DC).
Flashing green The scanner is fully operational, but there are no connections
established with any of the devices on the network.
If the scannner should be controlling DeviceNet slaves, configure its
scan list.
Solid green The scanner is fully operational and communicating with the
controller.
Flashing red One or more of the devices that the scanner is communicating with is
in a timed-out state.
Monitor the status display to determine which slave device is offline.
Solid red A critical network failure has occurred because a duplicate DeviceNet
node address has been detected.
Reset the scannner and change the node address of either the
scanner or that of the conflicting device. If the failure continues,
replace the scanner.
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 61
1769 DeviceNet Modules Status Indicators and Data Structures Appendix B
1769-SDN Scanner Status
Codes
The 1769-SDN scanner has a 2-character numeric display that provides the
DeviceNet node address and diagnostic information about the status of the
module.
Numeric Display Description
063 Indicates the 1769-SDN modules DeviceNet node address.
7099 Indicates a status code for the displayed node address.
Alternating numbers 063Indicates the node number that has generated an
error.
7099Indicates the status code.
Numeric Display
Table 14 - Status Codes
Status Code Description Recommended Action
063 Indicates the scanners DeviceNet node address. None.
65 The AutoScan option is on and the device is in Idle mode. None.
67 The scanner is the secondary scanner. None.
68 The primary scanner has detected no secondary scanner. Configure another scanner to be the secondary scanner.
69 The primary and secondary configurations are mismatched. Check configuration of the secondary scanner.
70 The address of the device is already in use by another device
on the network. The scanner failed the duplicate node address
check.
Change the address of the device to an unused address.
71 There is invalid data in the scan list. Use RSNetWorx for DeviceNet software to reconfigure the
scan list.
72 The slave device stopped communicating. If the slave device
does not recover communication during the next scan, the
status code changes to 78.
Verify the slave devices power and communication
connections.
If the slave device is polled, verify that the interscan delay
time is adequate for the device to return data.
73 The slave devices identity information does not match the
electronic key in the scanner.
Make sure that the correct device is connected at this
address.
Make sure that the device matches the specified electronic
key, such as vendor, product code, or product type.
74 The scanner detected a data overrun on the DeviceNet
communication port.
Modify your configuration and check for invalid data.
Check network communication traffic.
75 Either or both of these may be true:
The device does not have a scan list.
The device has not received communication from any other
device.
Verify that the device has the following:
A configured scan list
A properly-wired connection to the network
76 There is no direct network traffic for the scanner. The scanner
hears other network communication but does not hear any
communication directed to it.
None.
62 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures
77 During initialization, the data size expected by the device does
not match the scan list entry.
Use RSNetWorx for DeviceNet software to check the slave
device and the scan list for the correct input and output sizes
for the slave device.
78 The device is configured in the scan list, but not
communicating. The device has failed to communicate during
the scanners second scan, which followed the display of
status error code 72.
Verify devices power and communication connections.
If the device is polled, make sure the interscan delay is long
enough for the device to return its data.
If necessary, use RSNetWorx for DeviceNet software to do the
following:
Add the device to the DeviceNet network.
Delete the device from scanners scan list.
Inhibit the device in the scanners scan list.
79 The scanner has failed to transmit a message. The error status
usually displays after the duplicate node check completes and
power is applied to the module.
Make sure the scanner is connected to a valid network.
Check for disconnected cables.
Verify the network communication rate.
80 The scanner is in Idle mode. To run the network, do these steps.
1. Put the controller in Run or Remote Run mode using the
keyswitch on the controller or through RSLogix5000
software.
2. Turn on the bit O.CommandRegister and run for the scanner.
81 The controller has set the scanner to the Faulted mode. The
Command bit also indicates a DeviceNet network fault state.
The Bit O.CommandRegister.Fault for the scanner is on.
Correct the condition that caused the controller to set this bit
and then turn this bit off.
82 An error was detected in a sequence of fragmented I/O
messages from the device.
Use RSNetWorx for DeviceNet software to do the following:
Check the scan list of the device to make sure that its input
and output data sizes are correct.
Check the configuration of the device.
83 The device returns error responses when the scanner attempts
to communicate with it.
Use RSNetWorx for DeviceNet software to do the following:
Check the accuracy of the scan list.
Check the configuration of the device. The device may be in
another scanners scan list.
Use the slave devices documentation to verify that the
device supports the message type used by the scanner.
If the devices message type does not match the scanners,
then use RSNetWorx for DeviceNet software to access the
scanners scan list and change the scanners message type
to one that is compatible with the slave device.
Cycle power to the device.
84 The scanner is initializing the DeviceNet network. None. This code clears itself once the scanner attempts to
initialize all the devices on the network.
85 During runtime, the data size sent by the slave device does not
match the size in the corresponding scan list entry.
Since variable length poll data is not supported, verify that the
slave device is functioning properly.
86 The device is in Idle mode, or not producing data, while the
scanner is in Run mode.
Check the configuration and status of the device.
If you set up an interlock between two scanners
(controllers), make sure both scanners are in Run mode.
87 The scanner cannot listen to shared inputs from the slave
device because the owning scanner has not established
communication with that slave device.
Verify the primary scanner connection and configuration.
Verify that the slave device is producing data.
88 The scanner cannot listen to shared inputs from the slave
device because I/O parameters, such as electronic key or data
size, for that slave device are configured differently between
this scanner and the owning scanner.
In this scanner, reconfigure the I/O parameters for the shared
inputs scan list entry so that they match those same
parameters in the owning scanner.
Table 14 - Status Codes
Status Code Description Recommended Action
Rockwell Automation Publication DNET-IN001B-EN-P - January 2012 63
1769 DeviceNet Modules Status Indicators and Data Structures Appendix B
1769-SDN Scanner Data
Structures
The scanner uses the input and output data images to transfer data, status, and
command information between the scanner and the controller.
Input Data Image
The input data image is transferred from the scanner module to the controller.
89 The scanner failed to configure a device by using the
Automatic Device Recovery (ADR) parameters.
Make sure that you installed a compatible device.
If the offline configuration of the device does not match the
actual (online) configuration of the device, change the
offline configuration to match the online configuration.
90 The controller has set the scanner to Disabled mode. If desired, enable the scanner by locating the
O.CommandRegister.DisableNetwork bit on the command
register and turning it off.
91 Indicates a Bus-off condition likely due to cable or signal
errors.
Cycle power to the device.
Verify that all devices are set to the same communication
rate.
Check DeviceNet cabling to make sure no short circuits
exist between CAN (blue and white) wires and power or
shield (black, red, and shield) wires.
Check the media system for these noise sources:
Close proximity to high-voltage power cable
Incorrect or no termination resistor
Improper grounding
Noise produced from another device on the network
Incorrect data for the network
92 The DeviceNet cable is not supplying power to the devices
communication port.
Verify that the networks 24V DC power supply is operating
properly.
Verify the cable is in good condition.
Check the cable connections to the device.
95 A devices firmware is being updated or a configuration is
being downloaded.
None. Do not disconnect the device while the update is in
process because existing data in the device memory will be
lost.
96 The communication port is in Test mode. None.
97 The controller has placed the scanner in Halt mode. If the O.CommandRegister.HaltScanner bit is on, turn it off.
Then cycle scanner power.
98 General firmware error. Replace device.
99 System failure. Replace device.
Table 14 - Status Codes
Status Code Description Recommended Action
Word Description Data Type
063 Status Structure 64-word array
64 and 65 Module Status Register 2 words
66245 Input Data Image 180-word array
64 Rockwell Automation Publication DNET-IN001B-EN-P - January 2012
Appendix B 1769 DeviceNet Modules Status Indicators and Data Structures
Output Data Image
The output data image is transferred from the controller to the scanner module.
The following table shows the bit descriptions for the modules command array.
CompactLogix Status Structure
The second area of the CompactLogix controller input image is the Status
Structure. The status structure consists of these data elements.
Word Description Data Type
0 and 1 Module Command Array 2-word array
2181 Output Data Image 180-word array
Word Bit Operating Mode
0 0 1 = Run, 0 = Idle
1 1 = Fault
2 1 = Disable Network
3 Reserved
(1)
(1) Do not manipulate reserved bits. Doing so may interfere with future compatibility.
4 1 = Reset
515 Reserved
(1)
1 015 Reserved
(1)
Description Data Type
I.Status.Scan Counter 2 words
I.Status.Device Failure Register 64-bit array
I.Status.Autoverify Failure Register 64-bit array
I.Status.Device Idle Register 64-bit array
I.Status.Active Node Register 64-bit array
I.Status.Status Display 8 bytes
I.Status.Scanner Address 1 byte
I.Status.Scanner Status 1 byte
I.Status.Scrolling Device Address 1 byte
I.Status.Scrolling Device Status 1 byte
I.Status.Device Status 64 bytes
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400
Publication DNET-IN001B-EN-P - January 2012 68
Supersedes DNET-IN001A-EN-P - March 2011 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
SM

support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
your local Rockwell Automation representative.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

También podría gustarte