N Document Technical specification Rev.00
Date:
Site:
12/03/2012
Montebello Vicentino (VI)
Issued by Checked by Authorized by
SZ RDN MP
Technical Specification
PVxx8M872NP
e PVxx8M872NN_ENG_rev01 2
All information provided on these pages is for information purpose only and not binding. Changes of the information are reserved at any time without prior notice.
Electrical data
Solargate Inverter PV8M872NP
Operative PV voltage UDC 480 -800 Vdc
Max system DC voltage UDC, max 1000 Vdc
Grid voltage UAC 300 Vac
Max Efficiency* 98,31 %
European efficiency* 98,26 %
CEC efficiency* 98,24 %
Short circuit current Isc A 1912 A
DC Voltage ripple UPP < 3%
Incoming overvoltage protection integrated
Grid frequency Hz 50/60
Harmonic current distortion AC THDIAC < 3%
Power factor cos 0,99 @Pac
Over voltage protection AC side optional
Protection degree IP 33
Environment operating temperature C
- 5 +45C (max 55C, from 45 to 55 C there is a current
and power derating of 1% each C)
Altitude above sea level 1000m. (Derating 1% for each 100m, max 3000m)
Relative humidity 10% 95% (non condensing)
User interface Graphic Display backlit (3 led, 20 keys)
Length mm 4000
Height: mm 2172
Depth: mm 600
Output @ 300Vac Input
Operative
Current
Operative
Power
Max
Power
Operative
Current
Operative
Power
Max PV
Power
I_ac P_ac Pm_ac I_dc P_dc PPV
Solargate Converter A kW kW A kW kW
PVxx8M872 3xSVGT420GEP 1738 903 993 1824 948 1042
* Efficiency calculated at 50C with Miro Function and at Minimum Voltage.
Input DC side Output AC side
e PVxx8M872NN_ENG_rev01 3
All information provided on these pages is for information purpose only and not binding. Changes of the information are reserved at any time without prior notice.
Inverter performance Efficiency Vs Load Inverter performance Efficiency Vs Voltage
Inverter performance Efficiency Vs Temperature
Miro Tool
In large photovoltaic plant where there are modular inverters, for example composed by two or more modules in
parallel, the conversion efficiency can be optimized using only the minimum number of modules needed to deliver
the power coming from the strings. The "Miro" toggles the modules and their line contactor to the output to be
delivered and requires no additional body (contactor DC).
Miro
Under conditions of low irradiance, the efficiency of each
inverter decreases sharply to values of less than about 25%
of its rated power. The voltage output characteristic of
photovoltaic cells, also exhibits a maximum which becomes
less pronounced with decreasing irradiation and reading of
the current string is gradually less accurate. These factors
reduce the efficiency of MPPT algorithm. It follows that from
the standpoint of efficiency, the division into sections is
most advantageous when the radiation decreases and
becomes instead more convenient configuration with a
single inverter.
Voltage
Power
PLow efficency
P
Highefficency
e PVxx8M872NN_ENG_rev01 4
All information provided on these pages is for information purpose only and not binding. Changes of the information are reserved at any time without prior notice.
Solargate inverter
A Built
Electrical equipment will be mounted in a steel plate cabinet, Silcoflex series with vertical structural profiles in sheet
thickness 30/10, hips and back doors of sheet thickness 15/10 with internal reinforcements. The sheet metal is welded
in and bolted.
Opening: front with lockable doors
Accessibility: front with lockable doors and side panels bolted
Closures: with rubber seals
Colour: external and internal RAL 7035 textured gray epoxy powder as per our standard
paint specification STD004 Rev. 02.
Incoming cables from below
Outgoing cables from below
Ingress Protection: IP33
Ventilation: Forced with electric fans.
Cooling. Through grilles, filters and fans
Handling: Eyebolts or lifting angle
Installation & connections Converters, the relevant organs of protection and control, and regulators are mounted on
panels in galvanized steel, white sendzmir thickness 25/10.
- - The wires, except those of power, are placed in PVC conduit with removable lid with
differentiation pathways for cables with different levels of power and signal
- - Conductors are identified by collars containing the numbers on plastic stand scratches
and tinned copper ferrule compression
- - The components are identified by tag made
- - Adjustment module cards suffer burn-in test
- - Electrical connections with cable meets IEC 20-22
- - The equipment will be realized according to the ns. STD003 in construction
specifications "Form 1" (according to the classification IEC 439-1, EN 60433-1).
Inverter general characteristics.
Solargate Inverter DC Section - PV Side AC Section - Grid Side
Version Converter
R
F
I
f
i
l
t
e
r
L
i
g
h
t
i
n
g
p
r
o
t
e
c
t
i
o
n
G
r
o
u
n
d
f
a
u
l
t
d
e
t
e
c
t
i
o
n
d
e
v
i
c
e
D
i
s
c
o
n
n
e
c
t
o
r
s
s
w
i
t
c
h
S
u
b
f
i
e
l
d
f
u
s
e
s
C
l
e
a
n
P
o
w
e
r
f
i
l
t
e
r
C
o
n
t
a
c
t
o
r
D
e
c
o
u
p
l
i
n
g
r
e
a
c
t
o
r
R
F
I
F
i
l
t
e
r
C
i
r
c
u
i
t
B
r
e
a
k
e
r
M
P
P
T
n
u
m
b
e
r
M
I
R
O
t
o
o
l
PVMS8M872NP 3 x SVGT420 3 1 1 3 3 couples 3 3 No 1 1 1 Yes
PVMP8M872NP 3 x SVGT420 3 3 3 3 3 couples 3 3 Yes 1 1 3 No
Auxiliary Circuits and accessories:
Single phase transformer fed by 400Vca and protection breakers for the following:
- 230 Vac, for contactors and auxiliary relays
- 400 Vac for converter fans
- 24 Vdc power supply for data logger
- Lamps for lighting the cubicles
- heating resistors with thermostat, fed at 230Vac.
Front doors:
- Warning lights
- Emergency pushbutton and alarm reset
- Monitoring panel with 8 alarms
- Handle for circuit breaker and auxiliary disconnector
- LCD panel for converter programming and parameter visualisation
e PVxx8M872NN_ENG_rev01 5
All information provided on these pages is for information purpose only and not binding. Changes of the information are reserved at any time without prior notice.
Auxiliary circuits power consumption and external supplies:
Inverter Fan (3ph) Aux, cubicle fans, heating resistances,.. Control
400Vac
Transformer supplies 400Vac
230/48 Vac - 24Vdc
230Vac 1f
from 400Vac
3x750W 1200VA 990VA
B Reference Standard
1. Quality Management System
Answer Drives Srl operates a Quality Management System conforming to ISO 9001:2008 by providing, upon
request, evidence of the production processes and quality records.
The company's Quality System was certified according to ISO 9001:2008 on December 20, 2007, the Institute
RINA Certificate No. 17318/07/S.
Answer Drives have the certificate IQNet, the same number.
2. Environmental Management System
Answer Drives Srl operates with an Environmental Management System conforming to ISO 14001:2004 and
may provide, on request, evidence of the processes on the system and the associated records.
The company's Environmental Management System was certified according to ISO 14001:2004 on 20
December 2007, the Institute RINA Certificate No. EMS-2026 / S.
Answer Drives have the certificate IQNet, the same number.
3 Main rule: IEC 60439-1
The equipment to be procured are in accordance with European Standard EN 50178 "Electronic equipment
for power systems." Compliance with the supplied equipment may be declared by the issuance of a
declaration of conformity.
4 Main rule: EN 50178
The equipment to be procured are in accordance with European Standard EN 50178 "Electronic equipment for
power systems." Compliance with the supplied equipment may be declared by the issuance of a declaration of
conformity.
5 Directive: "Low Voltage" Directive 2006/95/EC; "MD Machinery" 98/37/EC
The electrical equipment the subject of our offer conform to EU Directive "Low Voltage (LV)" 2006/95/EC
(which replaced Directive 73/23/EC, as amended by Directive 93/68/EC) on the material safety Low voltage
electrical.
This conformity is confirmed by entering the "CE mark" on all the equipment and the awarding of a
"Declaration of Conformity." The marking is based on the conformity of equipment products to the harmonized
European standards EN 60204-1.
As for the "Machinery Directive (MD)" 2006/42/EC (ex 98/37/EC, 89/392/EC ex), it is not applicable to the
goods supplied by us does not fall within the scope of Directive
6 Directive: "Electromagnetic Compatibility EMC" 2004/108/EC
Answer Drives Srl declares that the equipment conform to European Directive 2004/108/EC (formerly
89/336/EC, as amended by 93/68/EC) on the electromagnetic compatibility (EMC) "
7 Specific Certifications SOLARGATE
Italian ENEL DK
Low Voltage
The equipment to be procured are certified in accordance with ENEL DK 5940. Conformity is declared by
TUV N. CV-187248-001 of 04/11/2008.
Medium Voltage
The product has a protection interface complies with the requirements ENEL DK 5740 is used in
photovoltaic grid-connected medium voltage (TUV Certificate No. CV -187248-001 of 11/04/2008).
Answer Drives S.r.l.
Viale Sarca 336
I - 20126 Milano
Phone +39 02 6445 1
Fax +39 02 6445 4401
GERMANY
Ansaldo Sistemi Industriali GmbH
Im Teelbruch 104
D-45219 Essen - Kettwig
Phone +49 (0) 2054 104980
Fax +49 (0) 2054 1049811
MANUFACTURING FACILITY
S.S. 11 - Via C Sordis, 4
I-36054 Montebello Vicentino (VI)
Phone +39 0444 449 268
Fax +39 0444 449 276
www.answerdrives.com
ROMANIA
Ansaldo Sistemi Industriali RO
235b Darzei II St. - Crevedia, Jud. Dambovita
137180 Romania
Phone +40 374 00 33 54
Fax +40 757 71 02 04
CUSTOMER SERVICE AND SUPPORT
S.S. 11 - Via C Sordis, 4
I-36054 Montebello Vicentino (VI)
Phone +39 0444 449 226
Fax +39 0444 449 276
www.answerdrives.com
RUSSIA
AO Ansaldo - VEI
Krasnokazarmennaya Ul 12
111250 Moscow, Russia
Phone +7 495 3619163
Fax +7 495 2734391
REPRESENTATIVE OFFICE CHINA
Silver Tower Rm. 3208 No. 2
Dongsanhuan Beilu Chao Yang District
Beijing 100027
Phone +86 10 6410 6601
+86 10 6410 6602
Fax +86 10 6554 4493
THAILAND
Ansaldo Sistemi Industriali SpA Thailand Branch
Muang Thai-Phatra Office Tower II 24th Fl
252/119 Rachadaphisek Rd, Huaywang
Bangkok 10310 Thailand
Phone +66 2 6932930
Fax +66 2 6932934
ANSALDO SISTEMI INDUSTRIALI
INTERNATIONAL NETWORK
SUPPORTING ANSWER DRIVES
USA
Anselectric LLC
an Ansaldo Sistemi Industriali SpA Company
4900 Woodway Dr., Suite 680
Houston, Texas
77056 USA
Phone +1 832 214 4185
Fax +1 713 583 7775
CHINA
ASI Industrial Systems Beijing Co. Ltd.
(subsidiary of Ansaldo Sistemi Industriali S.p.A.)
Room 3206 3208 / Beijing Silver Tower
No. 2 Dong San Huan Bei Road-Chaoyang District
Beijing Peoples Republic of China
Phone +86 10 6554 4490/91/92
Fax +86 10 6554 4493
VIETNAM
ASI Industrial Systems - Representative Office of
Ansaldo
Sistemi Industriali S.p.A.
Room 702 Floor 7th No. 3 Mai Hac De street, Hai Ba
Trung district - Hanoi
Phone +84 4 394 47415
Fax +84 4 394 47415
FRANCE
Ansaldo Sistemi Industriali SA
Z.I. du Buisson, Rue de la Poudrire
F-42230 Roche-La-Molire
Phone +33 4 77907600
Fax +33 4 77907629
UAE
Anselectric LLC
an Ansaldo Sistemi Industriali SpA Company
P.O.Box 45265 - Abu Dhabi
Phone +971 2 6508023 - Fax +971 2 6740723
Mobile +971 50 6227095
For information on the sales office or sales
representative nearest you contact us at:
info@asiansaldo.com

También podría gustarte