SCOPE OF WORK
The Scope of Work shall include Design, Manufacture, Supply, Erection, Testing and Commissioning of 250 Kva , 415V DG Sets and accessories and AMF Logic Panel to comply with the local pollution control board norms for noise and air pollution. Supply, laying & termination of 1.1 KV grade, 12 core 2.5 sq. mm PVC copper stranded armoured cable from DG set to Inbuilt control panel. Higher size cable should be used if there is a signal drop due to increase in length. Qty will vary according to site condition. Providing and fixing of suitable painted MS angle iron/channel frame including grouting the same, minor civil works, bolts etc as required. Testing of the control panel for all its function in co-ordination with other agencies involved in presence of Consultant / Client. Providing proper fixing arrangement for Low fuel sensor as instructed by Engineer-incharge. Power and control cables between alternator and Main MV panel is included in the scope. The power cable shall be copper cable sufficient to withstand the fault level and current carrying capacity taking into account of derating factors and voltage drop. The cables shall be conforming to IS-1554. Control cables shall be stranded copper conductor, unarmored and sheathed. Minimum sizes of power and control cables are specified in the data sheet. The Cost shall include service kit for two B Check of engine.
PNP
RGCA
Engine and alternator shall be mounted on MS base frame structure. The base frame shall be treated for rust formation and shall be painted with one coat of primer and two quotes of heat resistance paint. The base frame shall be fixed over anti-vibration mounts with proper spacing such that the static and dynamic load of DG is uniformly distributed to the foundation.
ENGINE COOLING
The engine shall be water-cooled through radiator as specified in data sheet. The blower fan and cooling water circulation pump shall be engine driven. A separate fan of adequate CFM shall be designed and fixed inside the Acoustic for fresh air circulation inside acoustic enclosure. Supply and installation of all items associated with engine cooling system shall be in the scope of Vendor. Major components of the Engine shall be as below: Fly wheel with starter ring Electronic Governor V belt driven water circulation pump Lube oil cooler Oil bath type air cleaner Residential Exhaust silencer Fuel lift pump Belt tensioning unit Fuel filter (Pre & Micro) & lube oil filter 12/24V electric starting system with starter and battery Electrical start arrangement Hour Meter Engine control panel consisting of ON/OFF/ START Key, lube oil pressure gauge, ammeter, Water temp indicators Belt guard & coupling Radiator with expansion tank. Battery Dynamo Base frame for Mounting Engine and alternator
DAY TANK
The fuel oil day tank shall be of made of 2.0mm thick CRCA sheet on all sides, welded at all corners, properly treated for rust and grease removal and painted with one coat of primer and two coats of epoxy paint to match engine color. Structural base frame shall be provided such that the natural flow of fuel to the governor and does not affect its performance. Day tank shall be of 990 ltrs. Capacity. The Day tank shall be provided with the following features. 1. 2. 3. 4. 5. Diesel filling lid with pad lock and key arrangement Drain pipe with ball valve Silica gel breather Level gauge for level indication Fuel level sensor with wiring and terminal arrangement
PNP
RGCA
ALTERNATOR
The alternator shall be Self-ventilated, Screen protected & drip proof, Salient pole, Brush less & Revolving field type, Self-excited & Self-regulating type. The main and exciter winding shall be Class H insulated. The exciter shall be capable of forcing the field for 3 seconds (or duration as specified in the data sheet) in the event of short circuit fault at generator terminal. The rectifier shall have in built protection for over voltage and rate of rise of voltage. All other parameters shall be as specified in the data sheet and conforming to codes and standards specified in the data sheet or relevant standards. Majority (50%) of load fed by the alternator are non-linear thyrister loads. Significant other loads are of inductive nature, ie., compressor and fan motors. Alternator shall be capable of handling these loads safely without any change in performance, due to the heavy harmonics induced along with excess neutral currents. BUSDUCT box of suitable size shall be provided for termination.
The Vendor shall submit a clear description / specification of panel along with drawing considered in the offer. The Vendor shall provide the following.
Engine coolant pre heater by a resistor separator to the engine fixed on the frame including the temperature regulation sensor.
PNP
RGCA Primary fuel filter mounted upstream from standard filtration for the decantation of coolant at the engine fuel supply. Protective grids for engine hot parts. Electronic engine speed regulator including a logic controller, injection pump with actuator and speed measurement sensor mounted to the engine bell. Manual pump mounted on the engine allowing for easy drainage of the sump.
CABLING
All cabling between the alternator and the control panel is included in the scope of Vendor. The cables shall conform to IS codes and shall be with copper conductor. Suitable cable entry adopter boxes are to be fabricated and fitted to the alternator. Control cables between all instrumentation and control panel is included in the scope of Vendor. Cables shall be copper conductor of not less than 2.5sqmm, with proper shielding as required.
PIPING
The material of construction for 15Kg/sq.cm pressure class, corrosion allowance, piping C class etc. for interconnecting pipes, pipe fittings, exhaust pipe, bolts and nuts shall be as per relevant standards and suitable to withstand the temperature of the gas/liquid within the pipe and the environmental conditions. Exhaust pipe shall be cladded with rockwool insulation for 50mm thickness and covered with 24G aluminium sheet.
PAINTING
PNP
RGCA
Surface Primer Final Paint Final Paint Shade Minimum Paint Thickness : Pretreatment: Sand blasting / Chemical cleaning : Two coats of epoxy primer : Two coats of epoxy paint : 631 as per IS 5 : 100 microns.
HARDWARE
Type: Stainless steel Nuts & Bolts and any other material for total completion of the installation.
INDICATION LAMPS
The alarm shall be DC hooter with audible control, fixed on the AMF panel. Accept and Reset pushbuttons shall be provided to accept the alarm and to reset the system after fault has been cleared. All Indication lamps shall be LED type rated suitably for control and power voltage. Pushbutton for testing all lamps. Status indication: Mains healthy Load on Mains DG set running Load on DG
Alarms with warning lamps only : Low Fuel Level (Lamp indication shall not be reset unless fuel is filled) Low battery voltage. Battery charger failure.
PROTECTION:
All protection systems as per local regulatory norms shall be incorporated (IDMT CDG-11) Start failure lockout after fixed consecutive attempts. Emergency stop pushbutton to stop the DG in case emergency in auto and manual modes.
PNP
RGCA
Shutdown protection (after a delay of 10s) with warning lamp and alarm: Fail to start Low Lubrication Oil Pressure Over load. High water temperature. V belt failure. Engine over speed.
LIST OF APPROVED MAKES: Engine Alternator MCCB Measuring instruments Energy meter (Sealable type) Power contactors Current transformer Overload relays/Timers Indication lamps/Pushbuttons Line Voltage monitor Three attempt starter Low fuel sensor /Control relays Selector switches DC hooter with audible control Control wire Phase reversal protection Battery Charger Battery Earth fault relay Cummins/MTU/CATER PILLAR/ Leroy somer/CATERPILLAR Stamford Merlingerin-Masterpact/ABB/Siemens L&T/AE/Meco Conserve/Enercon / Cadel ABB/Telemechanique Kappa/Altran/AE L&T/alstom LEDstar/Vaishnov Minilec (VMI). PIC PIC PLA Kaycee//L&T. Vaishnov Finolex - FRLS Minilec (VMR) Naren electronics / New Horizon / ACME Electronics Exide Alstom / Easun
Any Electronic control circuitry that is fabricated shall be fabricated with high quality, high precision components of reputed make, neatly and logically arranged and well soldered to give trouble free performance. Any change in the make shall have prior approval from Consultant / CLIENT.
PNP
RGCA
Inspection and testing shall be carried out based on this specification and with approved drawings certified by the consultant / CLIENT. The CLIENT and their consultants shall have the right to carry out stage inspection and shop visit to review the manufacturing progress. All routine and type tests specified shall be carried out during final inspection. 15 days advance notice shall be given for carrying out the final inspection. Any fuel charges for load testing shall be included in the offer, which shall be indicated separately in the Offer. Bidder shall ensure that a competent testing authority calibrates all meters and equipment used testing and the calibration certificates are valid at the time of carrying out test. After completion of inspection and testing Bidder shall furnish all as built document in two sets. Only on receipt of final documents the release order for dispatch of equipment shall be issued.
GUARANTEE
PNP
RGCA
The performance figures indicated in attached questionnaire form shall be guaranteed within the tolerance specified or as permitted by relevant standards. In case of failure of equipment to meet the guaranteed performance, CLIENT reserves the right to reject the equipment. However, CLIENT also reserves the right to use the rejected equipment until the Bidder supplies new equipment meeting the guaranteed performance requirements. If any equipment supplied by the Bidder fails at site during erection, commissioning or service [within guarantee period), the Bidder shall repair and put back into successful operation the failed equipment within the time frame and procedure of repair agreed with the CLIENT depending on nature of failure at no extra cost to the CLIENT . The bidder shall clearly specify the parts covered under replacement warranty and details of service provided during warranty period. The guarantee period shall be not less than 24months from the date of commissioning of DG set. The quotes shall not be evaluated if the questionnaire is not filled in.
REFERENCES & STANDARDS Diesel Engine Power Speed Governor Diesel Fuel ISO 3046-1 ISO 3046-4 IS 1460
Generator /Alternator Degree of Protection of generator (IP Codes) Permissible limits of Noise level of Rotating Machines
IS 12065
IP 41 as per IS 2147
IP 41 as per IS 2147
PNP
RGCA Operating and Maintenance instruction manual .The documentation supplied with the generating sets specifies the operations for use and maintenance of the generating set which includes: General recommendations and safety requirements Guidelines to installation of DG Sets Recommended grade of fuels & consumables Routine maintenance instructions Special instructions for maintenance of optional equipments Trouble shooting Technical specifications
Maintenance Safety measures Running maintenance Fault detection Specification charts Spare Parts Description of parts Exploded view Part list
PNP
RGCA
LOCATION
:RGCA, CHENNAI,
ENGINE DATA
Name plate rating BHP : Engine speed : Method of starting : Electric Aspiration : Water Cooled Turbo charged Lube oil consumption : Cylinder jacket heating (cooling water heating) with Thermostat : Required Lube oil-priming facility : Required Lube oil pump : Engine driven Standby lube oil pump : Not required Engine noise level in dB Bare engine With acoustic enclosure ( At various loads ) At 1mtr : At 3mtrs : At 6mtrs :
PNP
COOLING SYSTEM
Method of Jacket cooling Heat Removal Dimensions in mm (LXWXH] Operating weight Qty of coolant : Air : Radiator with expansion tank : :
: : :
EXHAUST SYSTEM
Exhaust silencer type Exhaust noise level (with Silencer) Heat rejection to exhaust system Max. Permissible back pressure in Exhaust Exhaust gas flow : Residential : max _______ dB at 3.0 mtrs : deg over ambient : : kg/cm sq
PNP
RGCA
GOVERNER DATA
Make : Type : Whether adjustable droop provided : Response time : Recovery time : Speed raise / lower from panel provided
ALTERNATOR
Technical particulars Make : No. of phases : 3 phase and neutral Enclosure : IP 25/23 Terminal voltage & freq : 415V AC & 50Hz Time permitted to build up rated voltage : 5 secs max. Permissible voltage dip : 5% Rating of biggest motor to be started DOL with permissible voltage dip when the generator is Unloaded : 50% loaded : 80% loaded : Power transfer : Rating : ___________at 0.8 P.F Make / Model No : Insulation class-Armature : Class H Field: Class H Inertia time constant : KW-Sec/KVA Bearing type : Short circuit withstand time : Overload withstand capacity (min. 150% for 15sec}. : Neutral earthing : Solidly Earthed
TYPE OF COOLING
Cooling system of alternator Cooling medium temperature Temp. rise of armature winding Temp. rise of field winding Heating time constant Cooling time constant : : : : : :
EFFICIENCY OF ALTERNATOR
At 100% MCR & rated p.f. At 75% MCR & rated p.f. At 50% MCR & rated p.f. : :
PNP
RGCA
AVR
Type of AVR Mounting of AVR Voltage regulation Dead band Response time Voltage of operation Line drop compensator provided to Maintain bus voltage constant Range of voltage adjustment Fine turning adjustment : self regulated : : : % : : : : :
: : : : :Accuracy : Accuracy : Microprocessor based, specify: : required : min. 3 starts :in secs.
PNP
RGCA
BATTERY
Type AH capacity Back up duration Battery voltage End cell voltage Nos. of starts without recharging Location Make : : AH : Hrs :V :V :3 : OUTDOOR :
BATTERY CHARGER
Type : SMPS BASED Manufacturer : Charger rating : Standby Float charger to be provided : required Boost charger : required Metering : Voltmeter and Ammeter Indications for : Battery fully charged, Charger fail, Charger mode
enclosure
: :
kg kg
DIMENSIONAL DETAILS
Dimensions (L X B X H) detail requirements of the following DG set without acoustic : L (mm) x B (mm) x H Foundation size required : L (mm) x B (mm) x H (mm) (mm)
PNP
RGCA
Bidder shall submit dimensional drawing showing location of all equipments inside the acoustic room enclosure housing the DG sets. The hard and soft copy of proposed DG set is to be enclosed with foundation details.
TESTING
The following tests shall be carried out at the Bidders works for the assembled DG Set in presence of Consultants / CLIENT s.
TESTS OF ENGINE
25% load for 30 minutes 50% load for 30 minutes 75% load for 30 minutes 100% load for one hour followed by 10 minutes running at 110% of load
Load bank should be arranged by the vendor at factory and also transformer / DG capacity shall be available at factory.
PNP
RGCA
TESTS ON ALTERNATOR
Insulation measurement : High voltage test on rotor and stator winding: Temperature rise test : Mechanical balance : Stator voltage balance : Over speed : Stator phase sequence check : Vibration & noise level : Stator & rotor winding resistance : measurement Overload capability test :
STATUTORY CLEARANCES
The Bidder will be responsible for the statutory clearances from the electrical inspector, factory inspector, pollution control board, regulatory authority, and any other statutory agency appointed for the purpose by the state / central / municipal bodies. The documents / drawings required for obtaining the approval shall be prepared by the bidder.
SPECIAL NOTES
Major civil works like RCC foundation etc is included in the scope. All other works and materials, tools, tackles, hardware, consumables, fuel, oil etc. including grouting of the foundation bolts, metal support structure, scaffolding as required and necessary
PNP
RGCA
hardware to complete and commission the installation is deemed as included in the offer unless specifically stated and agreed to by the CLIENT before the placement of order. The Bidder shall be responsible for providing foundation drawings and load calculation to the Consultant / CLIENT for making necessary foundations.
PNP
RGCA Ministry of Enviornment & forests New Delhi 17th May , 2002 SPECIFIC REQUIREMENTS SHOULD MEET LIMITS OF NOISE LIMIT FOR GENERATOR SETS RUN WITH DIESEL
APPLICABILITY
These rules shall apply to all new diesel engines for genset applications (herein after referred to as 'engine') manufactured in India and all diesel engines for genset applications and diesel gensets (herein after referred to as 'product'), imported into India, after the effective date: Provided that these rules shall not apply to:
a. any engine manufactured or engine or product imported for the purpose of export outside India, or; b. any engine or product intended for the purpose of sample only and not for sale in India.
1. REQUIREMENT OF CERTIFICATION
Every manufacturer of engine or every importer of engine or product must have valid certificates of Type. Approval and certificates of Conformity of Production for each year, for all engine models being manufactured or for all engine or product models being imported, after the effective date with the emission limit as specified in paragraph 1.
2. SALE, IMPORT OR "USE OF ENGINE OR PRODUCT NOT COMPLYING WITH THESE RULES
No person shall sell, import or use of an engine or a product which is not having a valid Type Approval certificate and Conformity of Production certificate as per paragraph 3.
PNP
RGCA
a. name and address of the engine manufacturer or the engine or product importer (if the address is given in the owner's manual, it may not be included in the label); b. statement that 'this engine or product conforms to the Environment (protection) Rules, 1986'; c. type approval certificate number; d. date of manufacture of engine or in case of import, the date of import of the engine or the product.
5. NODAL AGENCY
1. The Central Pollution Control Board shall be the, nodal agency for implementation of these rules. 2. In case of any dispute or difficulty in implementation of these rules the matter shall be referred to the nodal agency. 3. The nodal agency shall constitute a Committee to advise it on all matters, including the disputed matters, related to the implementation of these rules.
8. FUEL SPECIFICATION
The specification of commercial fuel applicable for -diesel gensets shall be the same as applicable for commercial HSD(High Speed Diesel) applicable for diesel vehicles in the area, from time to time."