Documentos de Cultura
3.
Alpha Electronic Static Meter High Precision 0.2s Class ABT Compliant, TOD, microprocessor/ microcontroller based Meters with remote communication facility having 2 Nos simultaneously accessible independent ports & Optical front communication port.
A1800 meter
ANSI/MODBUS protocol with High speed data processing 1200 bps to 28000bps Default Memory 128kB, Optional Expandable Memory upto 1MB
5. 6. 7.
IEC 62053-22 / IS14697 0.2 S 1A to 10A (Same meter can be used for Ib ranging from 1A to 5 A) 2 Times Ib For IN 110V(Phase to phase) or 63.5V (Phase to Neutral) 50 Hz 5% 0.7 TO 1.2 Vref 46V to 526V Self Powered from VT supply Optional Auxiliary Supply AC/DC
Rated maximum current as percentage of basic. Rated voltage (Volts) Rated frequency (Hz) Specified operating voltage range Enhanced Voltage Range Auxiliary Supply
13. a b c d e
SERVICE CONDITIONS Maximum Ambient Air Temperature Minimum Ambient Air Temperature Average Daily Ambient Air Temperature Maximum Relative Humidity Max. Altitude above mean sea level (m)
GTP A1800 f Average Annual Rainfall (mm) g 14. a) (i) (ii) b) Seismic level POWER CONSUMPTION Power consumption in voltage circuit at rated current Active in watts Apparent in VA Power consumption in current circuit (in VA) at rated current Current that meter is capable of carrying continuously without injury to the meter (Amp.). Short time over current capability of the meter (for duration of 0.5 second) Percentage minimum current which will start the meter and continue to run thereafter at rated percentage and unity power factor (% of basic current) Type of material along with its thickness or dimensions (in mm) and details of the important components parts of the meter. Case Terminal covers Terminals TOD requirement
As per IS Less than 1.0W Less than 10VA Less Than 1.0VA
15.
----------200% Ib-----
16. 17.
18.
a) b) c) 19
High grade engineering plastic High grade engineering plastic High grade engineering plastic Programmable 132 TOD Switch times, 12 seasons, 4 Rates
20 a) b)
Load Profile Load profile interval Load Survey Parameters Energy parameters Demand
1-60 minutes Programmable as per the requirement 8 Energy Values kWh, KVAh, KVARH for Import & Export 6 Demands: kW, kVA, kVAR for Import & export.
Instrumentation Parameters
Elster Metering (P) Ltd More than 65 days Depends on No of Channels for Load Survey & instrumentation For 15 minutes interval.
d).
32 nos. of Instrumentation Parameters Programmable as per customer requirements from the following: Phase A, B or C Current Voltage KW KVar KVA Voltage angle Current angle Harmonic % THD
21
Midnight values for last 35 days 1. net kWh (del.-rec.) 2. net KVARh high 3. net KVARh low 4. net KVARh between 5. net KVARh stayput
5 Energy Values ( Parameters are selectable from the list given by the Customer before programming)
22
23 25
Previous 12 Months Billing History 1 no Optical Port 1 no.- RS485 Port with MODBUS 1 no RS485/RS232 port (Optional)
Elster Metering (P) Ltd 4 Relay Outputs programmable as per customer requirements LED Pulse output for kWh & kVARh
24
Display Parameters-64 Parameters Programmable as per list given kVARh (Q2 - Q3) kVARh (Q2 + Q3) kVARh (Q3 - Q2) kVARh delivered (Q1 + Q2) kVARh net kVARh Q1 kVARh Q2 kVARh Q3 kVARh Q4 kVARh received (Q3 + Q4) kVARh sum kWh delivered kWh net kWh received kVA delivered kVA received kVAr delivered kVAr received Current Billing Energy values TOD Rate wise with Four Rates
(Selectable from the following Parameters before programming) kVAh delivered (Q1 + Q4) kVAh Q1 kVAh Q2 kVAh Q3 kVAh Q4 kVAh received (Q2 + Q3) kVAh sum kVARh (Q1 - Q4) kVARh (Q1 + Q4) Frequency Average PF delivered Average PF received THD for Voltages THD for Currents kW delivered KW received ABT odometric energy values Date & Time Demand reset counts