Preface


1
Description of the device

2
Software installation
SIMATIC

3
Hardware installation
PG/PC - PROFIBUS

4
PC Adapter USB A2
Setting

5
Technical specifications

Operating Instructions
A
Approvals


03/2013
C79000-G8900-C293-01

Siemens AG
Industry Sector
Postfach 48 48
90026 NRNBERG
GERMANY
Order number: C79000-G8900-C293
03/2013 Technical data subject to change
Copyright Siemens AG 2013.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Preface
What the consignment contains
The following parts ship with the PC Adapter USB A2:
CD "PC Adapter USB A2 - Driver Disk"
USB cable
MPI cable (0.3 m)
With the MPI cable, you can connect the PC Adapter USB A2 to MPI networks,
homogeneous PPI networks or to PROFIBUS networks.
Please check that the consignment you have received is complete. If the consignment is
incomplete, contact your supplier or your local Siemens office.
Spare parts

Spare parts Order number
USB cable A5E00276884
MPI cable (0.3 m) A5E00164946
You can order spare parts through your local Siemens contact.
Documentation
Validity of this documentation
These operating instructions are valid for the following product:
PC Adapter USB A2
Order number: 6GK 1571-0BA00-0AA0

Note
The PC Adapter USB A2 (order number 6GK 1571-0BA00-0AA0) replaces the PC Adapter
USB (order number 6ES7 972-0CB20-0XA0).

Content of this documentation
These operating instructions contain information on the installation and use of the PC
Adapter USB A2.
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 3
Preface

PC Adapter USB A2
4 Operating Instructions, 03/2013, C79000-G8900-C293-01
Required basic experience
To understand the operating instructions, you require general knowledge of automation
engineering.
You also need to be familiar with using computers or tools similar to PCs (for example
programming devices) with the Microsoft Windows operating system.
Updated operating instructions on the Internet
You will find the current version of these operating instructions on the Product Support pages
under the following entry ID:
62612012 (http://support.automation.siemens.com/WW/view/en/62612012)
Further support
If you have questions on the use of the products described in the manual and you do not find
the answers here, ask your Siemens contact in the Siemens agency or office responsible for
you. You will find your contacts at:
(http://www.siemens.com/automation/partner)
You will find the links to the available technical documentation for the individual SIMATIC
products and systems at:
(http://www.siemens.de/simatic-tech-doku-portal)
The online catalog and online ordering system can be found at:
(http://mall.automation.siemens.com/)
Further documentation
The documents listed below contain more detailed information on setting up and using the
programming device. You will find this documentation on the Product Support pages on the
Internet with the following link:
Support (http://support.automation.siemens.com/WW/view/en)
Enter the entry ID shown below of the relevant manual as the search item.
System manual PROFIBUS network manual
In this document, you will find detailed information on setting up a PROFIBUS network.
Entry ID:
35222591 (http://support.automation.siemens.com/WW/view/en/35222591)
SIMATIC NET documentation
You will find the entire SIMATIC NET documentation on the pages of Product Support:
10805878 (http://support.automation.siemens.com/WW/view/en/10805878)
Go to the required product group and make the following settings:
Entry list Entry type "Manuals / Operating Instructions"
Preface

PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 5
Service & Support
In addition to the product documentation, the comprehensive online information platform of
Siemens Automation Customer Support supports at any time and at any location in the
world. You will find the Service & Support pages on the Internet at the following address:

(http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo2&aktprim=99&lang=
en)
Apart from news, you will also find the following information there:
Product information, Product Support, Applications & Tools
Technical Forum
Technical Support - Ask the Siemens experts
Our service offer:
Technical Consulting, Engineering support
Field Service
Spare parts and repairs
Maintenance, optimization, modernization and more
You will find contact data on the Internet at the following address:
(http://www.automation.siemens.com/partner/guiwelcome.asp?lang=en)
See also

(https://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=en&objid=38
718979&caller=view)
SITRAIN - Siemens training for automation and industrial solutions
With over 300 different courses, SITRAIN covers the entire Siemens product and system
spectrum in the field of automation and drive technology. Apart from the classic range of
courses, we also offer training tailored for individual needs and a combination of different
teaching media and sequences, for example self-learning programs on CD-ROM or on the
Internet.
You will find detailed information on the training curriculum and how to contact our customer
consultants at the following Internet address:
(www.siemens.com/sitrain)
Preface

PC Adapter USB A2
6 Operating Instructions, 03/2013, C79000-G8900-C293-01
SIMATIC NET glossary
Explanations of the specialist terms used in this documentation can be found in the SIMATIC
NET glossary.
You will find the SIMATIC NET glossary here:
SIMATIC NET Manual Collection
The DVD ships with certain SIMATIC NET products.
On the Internet under the following entry ID:
50305045 (http://support.automation.siemens.com/WW/view/en/50305045)

Table of contents

Preface...................................................................................................................................................... 3
1 Description of the device ........................................................................................................................... 9
1.1 Properties of the PC Adapter USB A2...........................................................................................9
1.2 Function .........................................................................................................................................9
1.3 Characteristics .............................................................................................................................10
1.4 Ports.............................................................................................................................................11
1.5 Power supply................................................................................................................................11
1.6 MPI/DP interface..........................................................................................................................12
1.7 USB interface...............................................................................................................................13
1.8 Meaning of the LED display.........................................................................................................14
2 Software installation................................................................................................................................. 15
2.1 Software requirements.................................................................................................................15
2.2 Installing the driver.......................................................................................................................15
3 Hardware installation ............................................................................................................................... 17
3.1 Hardware requirements ...............................................................................................................17
3.2 Connecting the PC Adapter USB A2 ...........................................................................................17
3.3 Use with a stand-alone system....................................................................................................18
3.4 Use in a networked system..........................................................................................................18
4 Setting ..................................................................................................................................................... 19
4.1 Set PG/PC Interface ....................................................................................................................19
5 Technical specifications........................................................................................................................... 21
A Approvals................................................................................................................................................. 23
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 7
Table of contents

PC Adapter USB A2
8 Operating Instructions, 03/2013, C79000-G8900-C293-01

Description of the device 1
1.1 Properties of the PC Adapter USB A2
The PC Adapter USB A2 can be operated on USB V1.1, V2.0 or V3.0 interfaces. The PC
Adapter USB A2 supports the common energy-saving modes (for example hibernate mode).

Note
The PC Adapter USB A2 is compatible with its predecessor product "PC Adapter USB".

1.2 Function
The PC Adapter USB A2 connects a PC via a USB interface with the MPI/DP interface of an
S7/M7/C7 system.
Since no internal slot is required for the connection, the PC Adapter USB A2 is also suitable
for PCs that cannot be expanded (for example notebooks).

Figure 1-1 Configuration with PC Adapter USB A2

Note
Only one PC Adapter USB A2
Only one PC Adapter USB A2 can be operated on a PC.


PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 9
Description of the device
1.3 Characteristics
PC Adapter USB A2
10 Operating Instructions, 03/2013, C79000-G8900-C293-01
1.3 Characteristics
Characteristics
You can operate the PC Adapter USB A2 on MPI and PROFIBUS networks.
The following table shows which transmission speeds are supported by the PC Adapter USB
A2 on which network type.
Table 1- 1 Bus profiles and transmission speeds
PROFIBUS Transmission
speed
MPI PPI
DP Standard Universal User defined
9.6 kbps - ()*
19.2 kbps ()*
45.45 kbps - - -
93.75 kbps - -
187.5 kbps ()*
500 kbps - -
1.5 Mbps -
3 Mbps - -
6 Mbps - -
12 Mbps - -
()* The PPI bus profile can be used via the "Universal" PROFIBUS bus profile
Further features
Automatic bus profile detection
Up to 16 communications connections of which a maximum of 4 can be slaves (DP/T
connections)
Support of routing
The PC Adapter USB A2 supports the following access to DP slaves:
Slave address assignment
Device diagnostics
Read/write data record




Description of the device
1.4 Ports
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 11
1.4 Ports
The PC Adapter USB A2 has the following connectors and displays:
MPl/DP interface
USB interface


1.5 Power supply
The PC Adapter USB A2 is supplied with power via the USB cable.
The PC Adapter USB A2 has electrical isolation between its MPI/DP and USB interface
within a safety extra low voltage (SELV) circuit. It can therefore also be operated directly on
ungrounded S7/M7/C7 systems.
See also
Technical specifications (Page 21)
Description of the device
1.6 MPI/DP interface
PC Adapter USB A2
12 Operating Instructions, 03/2013, C79000-G8900-C293-01
1.6 MPI/DP interface
Pin assignment
The MPI/DP socket has the following pin assignment:
1
6 9
5

Signal description

Pin no. Short description Meaning Input/output
1 NC not connected -
2 NC not connected -
3 LTG_B Data line B Input and output
4 RTS_AS RTSAS, control signal for received data stream.
The signal is '1' active when the directly
connected S7 automation system sends.
Input
5 M5V Reference potential of the MPI/DP interface for
the signals RTS_AS and RTS_PG
Output
6 P5V +5 V (only for bus termination) Output
7 NC not connected -
8 LTG_A Data line A Input and output
RTS_PG RTS output signal of the PC Adapter USB A2.
The signal is '1' when the PC Adapter USB A2
sends.
The signal is not included in the 0.3 m MPI cable!
Output 9
Shield - on connector housing* -
* The shield is connected through to the USB socket via the adapter electronics module.
Description of the device
1.7 USB interface
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 13
1.7 USB interface
Interface assignment
USB socket from above:
1
4 3
2

Figure 1-2 USB interface
Signal description

Pin no. Signal Meaning
1 +5V Supply voltage
2 -Data - differential signal
3 +Data + differential signal
4 Ground Ground


Note
If several USB devices are being operated on your PC, this can impair the performance of
the PC Adapter USB A2. If optimum performance is required by the functions for
communicating with the automation system, USB devices you do not require should be
unplugged.




NOTICE
Disrupted function or communication abort possible
Removing and inserting USB devices can cause functional disruptions on the USB
interface. In extreme situations, this can lead to the communication via the PC Adapter
USB A2 being aborted meaning that the application needs to be restarted.

Description of the device
1.8 Meaning of the LED display
PC Adapter USB A2
14 Operating Instructions, 03/2013, C79000-G8900-C293-01
1.8 Meaning of the LED display
The LEDs on the PC Adapter USB A2 have the following meaning:

Designation Color Meaning
ACTIVITY green
LED off:
no application active
LED on:
application active
LED flickers:
Application active, PC Adapter USB A2 is in the token ring (bus activity)
LED flashing:
Flashing function via the PG/PC panel active (twice a second)
FAULT red
LED off:
No disruptions
LED flashes fast (twice a second):
serious internal problem
LED flashes rhythmically:
Bus disruption
USB 5V green
LED on:
The PC Adapter USB A2 is being detected by the driver and is operational.
LED off:
The 5 V supply voltage is not available.
LED flashes slowly:
The driver software is not installed.
The operating system is not active.
The PC Adapter USB A2 was "thrown out".
The PC Adapter USB A2 is disabled in the Windows hardware manager.
The power supply of the USB interface is inadequate to operate the PC Adapter
USB A2.
All 3 LEDs are lit
permanently
- Hardware defect:
Replace the PC Adapter USB A2 and send the defective device to your Siemens
contact.

Software installation 2
2.1 Software requirements
To work with the PC Adapter USB A2, you require a PC with one of the following operating
systems:
Windows 7
Windows Server 2008 R2
Windows XP Professional SP2 or higher
Windows XP Home SP2 or higher
Windows Server 2003 Standard Edition
Windows Vista
and
a SIMATIC software package that accesses using MPI communication (for example
STEP 7)
To operate the PC Adapter USB A2 on a PPI network, you also require
the software package STEP 7 Micro/Win32.
2.2 Installing the driver
Requirements for installation


Note
Software requirements
A SIMATIC product (for example STEP 7) must already be installed on your PC before you
install the driver.

Procedure
The installation starts automatically after inserting the CD.
If this function is disabled, follow the steps below:
1. Insert the "PC Adapter USB A2 - Driver Disk" in the CD-ROM drive.
2. Open the main directory on this drive.
3. Start the setup program by clicking on the "setup.exe" file.
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 15
Software installation
2.2 Installing the driver
PC Adapter USB A2
16 Operating Instructions, 03/2013, C79000-G8900-C293-01
The setup program guides you through the entire installation. Note the information on the
installation and use of the PC Adapter USB A2 in the readme file that you will find in the
main directory on the CD.

3 Hardware installation
3.1 Hardware requirements
You require a PC with a USB interface (USB 1.1, 2.0 or 3.0) and a CD/DVD-ROM drive.
3.2 Connecting the PC Adapter USB A2
Connecting to the PC
1. Insert the supplied USB cable in a USB interface of your PC.
2. Insert the other end of the USB cable into the USB interface of the PC Adapter USB A2.
Connecting to the automation system
1. Insert the supplied MPI cable into the PC Adapter USB A2 and screw it tight.
2. Connect the other end of the MPI cable to the MPI/PG interface of your CPU and screw it
tight.
Note

The PC Adapter USB A2 and the S7/M7/C7 system each represent a network node.
In networks made up of 2 nodes (PC Adapter USB A2 and S7/M7/C7 system), the PC
Adapter USB A2 is operated directly on the socket of the S7/M7/C7 system.
In networks made up of more than 2 nodes, the PC Adapter USB A2 is connected to
the "PG socket" of a PROFIBUS connector (SINEC L2 bus connector). This does not
require any change to the setting of the terminating resistors.
A maximum of 32 nodes can be connected to a PROFIBUS network segment. Several
network segments can be connected together using PROFIBUS repeaters to create a
complet network with a maximum of 127 nodes. The transmission speed in the PROFIBUS
network is a maximum of 12 Mbps.
The PC Adapter USB A2 supports transmission speeds up to maximum of 12 Mbps.


NOTICE
Do not insert any extension cords
No extension cord may be inserted in the connection between the PC Adapter USB A2 and
S7/M7/C7 system.

PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 17
Hardware installation
3.3 Use with a stand-alone system
PC Adapter USB A2
18 Operating Instructions, 03/2013, C79000-G8900-C293-01
3.3 Use with a stand-alone system
The following figure shows the connection to a single system (1 network node).

After successful installation of the PC Adapter USB A2 and configuration with the PG/PC
interface, your SIMATIC software package can communicate with the automation system.
3.4 Use in a networked system
The following figure shows you the connection to a networked S7 system (PROFIBUS
network with 2 or more network nodes).

After successful installation of the PC Adapter USB A2 and configuration with the PG/PC
interface, your SIMATIC software package can communicate with the automation system.

Setting 4
4.1 Set PG/PC Interface
1. In the "Set PG/PC Interface" dialog box, select the interface parameter assignment via
which you want to communicate:
- PC Adapter USB A2 (Auto)
- PC Adapter USB A2 (MPI)
- PC Adapter USB A2 (PROFIBUS)
2. In the corresponding "Properties" dialog box, check whether or not the parameter settings
match your system configuration and if necessary modify them.
3. Complete your settings with the OK button.
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 19
Setting
4.1 Set PG/PC Interface
PC Adapter USB A2
20 Operating Instructions, 03/2013, C79000-G8900-C293-01

5 Technical specifications


PC Adapter USB A2
Order number 6GK 1571-0BA00-0AA0
Dimensions approx. 105 x 58 x 26 mm
Weight (including cable) approx. 365 g
Interfaces
to the S7/M7/C7
to the PC
RS-485 (up to max. 12 Mbps)
USB 2.0 High Speed
Supply voltage (via USB interface) 5 VDC
Current consumption 200 mA
Safety
Protection class Protection class III to IEC 60950
Safety specifications IEC 60950 corresponds to DIN/EN 60950
Degree of protection IP20
Electromagnetic compatibility (EMC)
EMC directive The PC Adapter USB A2 meets the requirements of the EC
directive 2004/108/EC (EMC
directive).
Emission Residential areas, business and commercial operations, and
small businesses: EN 61000-6-3
Industrial area: EN 61000-6-4
Immunity Residential areas, business and commercial operations, and
small businesses: EN 61000-6-1
Industrial area: EN 61000-6-2
Noise immunity on signal lines PROFIBUS cable: 2 kV (to IEC 61000-4-4, burst)
USB cable: 1 kV (to IEC 61000-4-4, burst)
Immunity to discharges of static electricity (ESD) 6 kV contact discharge (to IEC 61000-4-2)
8 kV air discharge (to IEC 61000-4-2)
Immunity to RF interference 10 V/m 80 MHz 2 GHz, 80% AM (to IEC 61000-4-3)
1 V/m 2 GHz 2.7 GHz, 80% AM (to IEC 61000-4-3)
RF conductance 10 V/m 10 kHz - 80 MHz (to IEC 61000-4-6)
Climatic conditions
Temperature
Operation
tested to IEC 60068-2-1, IEC 60068-2-2
+0 to +60 , temperature change max. 10 K/h
Storage/transportation -40 to +70 , temperature change max. 20 K/h
Relative humidity
Operation
Storage/transportation
Tested to DIN IEC 60068-2-78
5% to 95% at 30 C
tested to IEC 60068-2-30
25 C and 55 C at 95%
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 21
Technical specifications

PC Adapter USB A2
22 Operating Instructions, 03/2013, C79000-G8900-C293-01
PC Adapter USB A2
Mechanical environmental conditions
Vibration
Operation


Storage/transportation
tested to DIN IEC 60068-2-6
5 - 8.4 Hz: Amplitude 3.5 mm,
8.4 - 150 Hz: Acceleration 9.8 m/s
10 cycles per axis
5 - 8.4 Hz: Amplitude 3.5 mm
8.4 - 500 Hz: Acceleration 9.8 m/s
10 cycles per axis
Resistance to shock
Operation
Storage/transportation
tested to DIN IEC 60068-2-27
150 m/s, 11 ms, 6 shocks per axis
250 m/s, 6 ms, 1000 shocks per axis

Approvals A



Note
Validity of the approvals
The specified approvals apply only when the corresponding mark is printed on the PC
Adapter USB A2.

Electromagnetic compatibility - EMC directive
The PC Adapter USB A2 meets the requirements of the EC directive 2004/108/EC (EMC
directive).
The PC Adapter USB A2 is designed for use in the following areas:


Requirements Area of application


Emission Immunity
Residential areas, business and
commercial operations, and
small businesses
EN 61000-6-3 EN 61000-6-1
Industrial area EN 61000-6-4 EN 61000-6-2
You will find further information on electromagnetic compatibility in the section "Technical
specifications (Page 21)".
EC declaration of conformity
You will find the EC declaration of conformity for this communications processor on the
Product Support pages under the following entry ID:
63367995 (http://support.automation.siemens.com/WW/view/en/63367995)
Machinery directive
The PC Adapter USB A2 is not a machine in the sense of the EC directive 2006/42/EC
(Machinery Directive). For this reason, there is no declaration of conformity for the PC
Adapter USB A2 relating to this EC directive.
If the PC Adapter USB A2 is part of the equipment of a machine, it must be included in the
procedure for obtaining the declaration of conformity by the manufacturer of the machine.
PC Adapter USB A2
Operating Instructions, 03/2013, C79000-G8900-C293-01 23
Approvals

PC Adapter USB A2
24 Operating Instructions, 03/2013, C79000-G8900-C293-01

C-TICK approval
The PC Adapter USB A2 meets the requirements of the Australian AS/NZS 3548 standard.
CSA approval
The PC Adapter USB A2 has an approval in accordance with the Canadian CAN/CSA C22.2
No. 60950-1 standard.
UL approval
The PC Adapter USB A2 has an approval in accordance with the US standard UL 60950-1.
FCC approval
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.