VK/HVK Specifications

Identification

Rated Values
Voltage

Insulation Level

Related Required Capabilities

Current

ShortConcircuit
Nominal
Nominal Rated
Rated
tinuous rm*s
ANSI Typerms
3-phase Maximum Voltage
rms
Current
Line Form of Voltage
Class
rms
Range
Current Rating
No. Breaker Class
(MVA)
Voltage Factor, Low
Rating (at
Crest
(kV)
(kV)(2)* K (3)* Frequency Impulse at 60Hz Rated
rms
Max. kV)
Voltage (A)
Voltage
(kA)(4)*
(kV)
(kV)
Rated Withstand
Test Voltage

Current Values
Rated
Rated
PerInterMissable
rupting
Tripping
Time
Delay, Y
(Cycles)
(Seconds)

Rated
Maximum
rms
Voltage
Divided
by K
(kV)

Maximum
Symmetrical
Interrupting
Capability
(5)*

3 Sec
Short-time
Current
Carrying
Capability

K Times Rated Shortcircuit rms Current


(kA)

(kA)

Closing and
Latching
Capability
1.6K Times
Rated
Shortcircuit rms
Current(kA)

VK6M32A

4.16

250

4.76

1.24

19

60

1200

29

3.85

36

36

58

VK6P32A

4.16

250

4.76

1.24

19

60

2000

29

3.85

36

36

58

(1)*

VK6M40A

4.16

350

4.76

1.0

19

60

1200

41

4.76

41

41

66

(1)*

VK6P40A

4.16

350

4.76

1.0

19

60

2000

41

4.76

41

41

66

VK-6M50 4.16

350

4.76

1.19

19

60

1200

41

4.0

49

49

78

VK-6P50 4.16

350

4.76

1.19

19

60

2000

41

4.0

49

49

78

VK-6Q50 4.16

350

4.76

1.19

19

60

3000

41

4.0

49

49

78

VK8M40A

7.2

500

8.25

1.25

36

95

1200

33

6.6

41

41

66

VK8P40A

7.2

500

8.25

1.25

36

95

2000

33

6.6

41

41

66

(1)* VK-8Q40 7.2

500

8.25

1.25

36

95

3000

33

6.6

41

41

66

VK13.8
10M25A2

500

15

1.30

36

95

1200

18

11.5

23

23

37

VK13.8
10P25A2

500

15

1.30

36

95

2000

18

11.5

23

23

37

VK10M40A

13.8

750

15

1.30

36

95

1200

28

11.5

36

36

58

VK10P40A

13.8

750

15

1.30

36

95

2000

28

11.5

36

36

58

(1)*

VK10Q40

13.8

750

15

1.30

36

95

3000

28

11.5

36

36

58

(1)*

VK10M40A

13.8

1000

15

1.0

36

95

1200

37

15

37

37

59

VK(1)* 10P40A

13.8

1000

15

1.0

36

95

2000

37

15

37

37

59

9
10
11
12

(1)*

VK10Q40

13.8

1000

15

1.0

36

95

3000

37

15

37

37

59

13

VK10M50

13.8

1000

15

1.30

36

95

1200

37

11.5

48

48

77

14

VK10P50

13.8

1000

15

1.30

36

95

2000

37

11.5

48

48

77

15

VK10Q50

13.8

1000

15

1.30

36

95

3000

37

11.5

48

48

77

(1)*

VK20J13

23

500

25.8

60

125

600

12

25.8

12

12

19

(1)*

VY20M25A

23

1000

25.8

1.0

60

125

1200

20.8

25.8

20.8

20.8

33.3

(1)*

VY20P25A

23

1000

25.8

1.0

60

125

2000

20.8

25.8

20.8

20.8

33.3

(1)*

VY30M25A

34.5

1500

38

1.35

80

150

1200

21

28

28.4

28.4

45.5

(1)*

VY30P25A

34.5

1500

38

1.35

80

150

2000

21

28

28.4

28.4

45.5

*Numbers in parentheses refer to the notes below.


(1) ANSI C37.06 does not define these ratings.

(2) Maximum voltage for which the breaker is designed and the upper limit for operation.
(3) K is the ratio of rated maximum voltage to the lower limit of the range of operating voltage in which the required symmetrical and
asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage.
(4) To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum
voltage and rated maximum voltage, the following formula shall be used. Required Symmetrical Interrupting Capability= Rated Short-circuit
Current X (Rated Max. Voltage)/(Operating Voltage)
(5) Current values in this column are not to be exceeded even for operating voltages between the rated maximum voltage and 1/K times rated
maximum voltage, follow (4) above.