Está en la página 1de 124

Instruction Manual R30, R40 Series Line Recorders

Instruction Manual R30, R40 Series Line Recorders

HANDLING OF ELECTRONIC EQUIPMENT


A person's normal movements can easily generate electrostatic potentials of several thousand volts. Discharge of these voltages into semiconductor devices when handling electronic circuits can cause serious damage, which often may not be immediately apparent but the reliability of the circuit will have been reduced. The electronic circuits of ALSTOM T&D Protection & Control Ltd products are completely safe from electrostatic discharge when housed in the case. Do not expose them to the risk of damage by withdrawing modules unnecessarily. Each module incorporates the highest practicable protection for its semiconductor devices. However, if it becomes necessary to withdraw a module, the following precautions should be taken to preserve the high reliability and long life for which the equipment has been designed and manufactured. 1. Before removing a module, ensure that you are at the same electrostatic potential as the equipment by touching the case. 2. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the electronic components, printed circuit track or connectors. 3. Do not pass the module to any person without first ensuring that you are both at the same electrostatic potential. Shaking hands achieves equipotential. 4. Place the module on an antistatic surface, or on a conducting surface which is at the same potential as yourself. 5. Store or transport the module in a conductive bag. More information on safe working procedures for all electronic equipment can be found in BS5783 and IEC 60147-0F. If you are making measurements on the internal electronic circuitry of an equipment in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap is not available, you should maintain regular contact with the case to prevent the build up of static. Instrumentation which may be used for making measurements should be earthed to the case whenever possible. ALSTOM T&D Protection & Control Ltd strongly recommends that detailed investigations on the electronic circuitry, or modification work, should be carried out in a Special Handling Area such as described in BS5783 or IEC 60147-0F.

CONTENTS
SAFETY SECTION 1. 1.1 1.2 1.3 1.4 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 3 3.1 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.4.1 3.2.4.2 3.2.4.3 3.2.5 3.2.5.1 3.2.5.2 3.2.5.3 3.2.5.4 3.2.5.5 3.2.5.6 3.3 3.4 3.5 3.6 3.6.1 3.6.2 4 4.1 4.1.1 4.1.2 4.1.3 4.1.4 INTRODUCTION General information Qualified person Warning information Approved use APPLICATION Purpose Standard Designs Options Delivery Conversion Environmental protection DESIGN AND MODE OF OPERATION Summary Recorder components Housing Measuring module Central processing unit Power supply AC 230V or AC 115V DC 24V AC 24V Chassis Chassis support Control PCB Clock backup Recording system Chart carriage User interface Mode of operation Scope of delivery Accessories, consumable materials Options Digital input/output DC 24V output PREPARATION FOR OPERATION Recorder identification Rating plate Object version Module release version Firmware version 12 12 12 12 13 14 14 14 14 15 15 15 15 16 16 17 17 17 18 18 18 18 18 19 19 19 19 19 19 19 21 21 21 21 21 22 22 22 22 22 23 23

Page 4

4.2 4.3 4.4 4.4.1 4.4.2 4.4.3 4.5 4.5.1 4.5.2 4.5.3 4.5.5 4.5.6 4.5.7 4.5.8 4.5.9 4.5.10 4.5.11 4.6 4.7 4.8 5 5.1 5.2 5.3 5.3.1 5.3.1.1 5.3.1.2 5.3.2 5.3.2.1 5.3.2.2 5.3.2.3 5.3.2.4 5.3.2.5 5.3.3 5.3.3.1 5.3.3.2 5.3.3.3 5.3.3.4 5.3.4 5.3.4.1 5.3.4.2 5.3.4.3 5.3.4.4 5.3.4.5 5.3.5 5.3.5.1

Installation guidelines Mechanical preparation of recorder for operation Connection of power supply Connection to ac 230V or ac 115V Connection to ac 24V or dc 24V Selection of 50/60Hz Connection of analog channels Labels DC U DC I Direct thermocouple connection Indirect thermocouple connection, constant cold junction temperature Indirect thermocouple connection, variable cold junction temperature RTD, R Two-wire measurement of thermoelectric resistance and standard resistance Three-wire measurement of thermoelectric resistance and standard resistance Three-wire measurement of potentiometers Digital input/output DC 24V output Starting up the recorder OPERATION Display and control elements Display elements Levers Functions of service lever and lever 2 Releasing the chassis Service lever Releasing the chart carriage Lever 2 Functions of Levers 1, 3 and 4 in recording mode Zero adjustment Lever 1 PAUSE ON Lever 1 PROG menu ON Lever 3 Lever 3 Lever 4 TEST menu ON Functions of Levers 1, 3 and 4 in the PAUSE status Lever 1 PAUSE OFF PROG menu ON Lever 3 Chart feed Lever 3 Lever 4 TEST menu ON Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu DEC Lever 1 INC Lever 1 PROG menu OFF Lever 3 ENTER Lever 3 Lever 4 Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu DEC Lever 1
Page 5

25 26 26 27 27 28 28 31 31 31 31 32 32 33 33 33 34 34 37 38 38 39 40 40 41 41 41 41 41 42 42 42 42 43 43 43 43 43 44 44 44 44 44 44 45 45

5.3.5.4 Lever 3 ENTER 5.3.5.5 Lever 4 TEST menu OFF 5.4 Settings via PROG menu 5.4.1.1 P[0], P[10] Chart speeds A, B 5.4.1.2 P[5], P[15] Condition 5.4.1.3 Event-dependent chart speed 5.4.1.5 Example 5.4.2 Measured-value table (only R40 version) 5.4.2.1 P[20] Measured-value table 5.4.2.2 Printing the measured-value table 5.4.3 Parameterizing the Analog Channels 5.4.3.1 P[25] Analog channel 5.4.3.2 P[30] Mode 5.4.3.3 P[35] Measuring range 5.4.3.4 P[40] Sensor 5.4.3.6 TC 5.4.3.7 RTD, R, Pot. 5.4.3.9 P[60] Open-circuit 5.4.3.10 P[65] Damping 5.4.4 Parameterizing the digital channel (only R40 version) 5.4.4.1 P[70] Channel (digital) 5.4.5 Alarm 5.4.5.1 P[80] Alarm 5.4.5.2 P[85] Mode 5.4.5.3 P[90] Channel 5.4.5.4 P[95] Value 5.4.6 Print (only R40 version) 5.5 Settings using TEST menu 5.5.1 Measuring mode 5.5.1.1 T[0] Measuring mode 5.5.2 Diagram 5.5.2.1 T[5] Diagram (only R40 version) 5.5.2.2 Start line (only R40 version) 5.5.2.3 T[10] Cycle 5.5.2.4 Time marker 5.5.2.5 T[15] Grid (only R40 version) 5.5.3 Text (only R40 version) 5.5.3.1 T[20] Text, T[25] Editing, T[30] Condition 5.5.3.2 Programming text 5.5.3.3 Instrument text 5.5.3.4 Event text 5.5.4 Clock (only R40 version) 5.5.4.1 T[35] Clock: Mode, T[40] Hours: hh, T[45] Minutes: mm, T[50] Day: DD, T[55] Month: MM, T[60] Year: YY 5.5.5 Control input DI4 5.5.5.1 T[65] Control input DI4

45 45 46 47 47 48 49 49 49 49 50 50 51 52 52 53 53 57 57 58 58 59 59 59 60 60 61 61 62 62 63 63 63 64 64 64 65 65 65 66 66 66 66 67 67

Page 6

5.5.5.2 5.5.5.3 5.5.5.4 5.5.5.5 5.5.5.6 5.5.6 5.5.6.1 5.5.7 5.5.7.1 5.6 5.6.1 5.6.2 5.6.3 5.6.4 5.6.5 5.6.6 5.6.7 5.6.8 5.6.9 5.6.10 5.6.11 5.6.12 6 6.1 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 6.1.6 6.1.7 6.1.8 6.1.9 6.1.10 6.1.11 6.1.12 6.2 7 7.1 7.2 7.3 7.4 7.5 7.6 7.7

Chart feed Time marker Clock sync. 3:00 (only R40 version) Summer time (MESZ) (only R40 version) TEST locking Language (only R40 version) T[70] Language PROG Locking T[75] PROG locking Parameterization examples Setting the chart speed Setting the output of the measured-value table Parameterizing the analog channel Parameterizing the digital channel Parameterizing the alarms Parameterizing the measuring mode Parameterizing the diagram (only R40 version) Parameterizing texts (only R40 version) Parameterizing the time Parameterizing the control input DI4 Parameterizing the language (only R40 version) Parameterizing the PROG locking MEASURING AND RECORDING MODE Chart formatting (only R40 version) Main time line (only R40 version) Instrument text (only R40 version) Switch-on text (only R40 version) Event text (only R40 version) Start line (only R40 version) Time markers (only R40 version) Limit line and alarm markers (only R40 version) Measured-value table (R40 version) Grid (only R40 version) Priorities of text outputs Configuration data (only R40 version) Error messages and Status messages (only R40 version) Example recording with explanations SERVICING AND MAINTENANCE Removing the chart carriage Inserting the chart carriage Setting the main time line Removing a fanfold pack Inserting a fanfold pack Removing a chart roll Inserting a chart roll

67 68 68 68 68 69 69 69 69 70 70 71 71 74 74 75 76 76 78 80 80 81 81 81 82 82 82 82 83 83 83 84 84 85 85 87 87 89 89 90 90 91 91 92 93

Page 7

7.8 Moving chassis into maintenance position 7.9 Returning chassis from maintenance position 7.10 Removing chassis from housing 7.11 Inserting chassis into housing 7.12 Removing the guide tongue 7.13 Inserting the guide tongue 7.14 Labelling and inserting the measuring-point label 7.15 Replacing the pens for the analog channels 7.16 Replacing the pen for alphanumeric text (only R40 version) 7.17 Replacing the scale 7.18 Replacing the battery (only R40 version) 7.19 Adjustment, test prints, carriage/text positions 7.19.1 Adjustment 7.19.1.1 T[80] Adjustment: Range, T[85] Channel 7.19.2 Carrying out the adjustment 7.19.3 Test print 7.19.3.1 T[90] Test print 7.19.4 Maintenance 7.19.4.1 T[95] Maintenance 7.19.4.2 Setting example for text channel 7.19.5 Service 7.19.5.1 T[100] Service 8 TECHNICAL DATA Measuring functions general data R30 version R40 version Operation, displays Recording Digital input/output (option) DC 24V output (option) Power supply Ambient conditions Mounting position Degree of protection Electric safety Electromagnetic compatibility Dimensions, mounting Weight Explanation of error data SCOPE OF DELIVERY, OPTIONS, ACCESSORIES Scope of delivery Available accessories and consumable material Available options REPAIR FORM

95 96 96 97 97 98 98 98 99 99 99 100 100 100 102 102 102 104 104 105 105 105 106 106 107 108 110 110 111 112 112 112 112 112 112 113 114 114 114 116 116 117 118 119

8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 9 9.1 9.2 9.3

Page 8

SAFETY SECTION
This Safety Section should be read before commencing any work on the equipment. Health and safety The information in the Safety Section of the product documentation is intended to ensure that products are properly installed and handled in order to maintain them in a safe condition. It is assumed that everyone who will be associated with the equipment will be familiar with the contents of the Safety Section. Explanation of symbols and labels The meaning of symbols and labels which may be used on the equipment or in the product documentation, is given below.

Caution: refer to product documentation

Caution: risk of electric shock

Protective/safety *earth terminal

Functional *earth terminal. Note: this symbol may also be used for a protective/ safety earth terminal if that terminal is part of a terminal block or sub-assembly eg. power supply. *Note: The term earth used throughout the product documentation is the direct equivalent of the North American term ground.

Installing, Commissioning and Servicing


Equipment connections Personnel undertaking installation, commissioning or servicing work on this equipment should be aware of the correct working procedures to ensure safety. The product documentation should be consulted before installing, commissioning or servicing the equipment. Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated. If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards. Voltage and current connections should be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. To ensure that wires are correctly terminated, the correct crimp terminal and tool for the wire size should be used.
Page 9

Before energising the equipment it must be earthed using the protective earth terminal, or the appropriate termination of the supply plug in the case of plug connected equipment. Omitting or disconnecting the equipment earth may cause a safety hazard. The recommended minimum earth wire size is 2.5 mm2, unless otherwise stated in the technical data section of the product documentation. Before energising the equipment, the following should be checked: Voltage rating and polarity; CT circuit rating and integrity of connections; Protective fuse rating; Integrity of earth connection (where applicable) Equipment operating conditions The equipment should be operated within the specified electrical and environmental limits. Current transformer circuits Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to personnel and could damage insulation. External resistors Where external resistors are fitted, these may present a risk of electric shock or burns, if touched. Battery replacement Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity, to avoid possible damage to the equipment. Insulation and dielectric strength testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected. Insertion of modules and pcb cards These must not be inserted into or withdrawn from equipment whilst it is energised, since this may result in damage. Fibre optic communication Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

Page 10

Decommissioning and Disposal


Decommissioning: The auxiliary supply circuit in the relay may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the relay (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to decommissioning. Disposal: It is recommended that incineration and disposal to water courses is avoided. The product should be disposed of in a safe manner. Any products containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of lithium batteries.

Page 11

Section 1. INTRODUCTION
1.1 General information This Manual contains the information required for approved use of the products described in it. It is directed at technically qualified personnel who are specially trained or have appropriate knowledge in the field of instrumentation and control, referred to below as automation technology Knowledge of the safety information and warnings present in this Manual and their technically correct application are requirements for safe installation and commissioning as well as safe operation and repair of the described products. Only qualified personnel in the sense of Section 1.2 have the required specialist knowledge in order to correctly interpret the general safety information and warnings present in this document for a specific case, and to apply them appropriately. For organizational reasons, this Manual must be ordered separately. For clarity reasons, the manual does not cover all details on all types of the described products, and cannot describe every possible case in connection with installation, operation or maintenance. Should you require further information, or should particular problems occur which are not handled in sufficient depth in this Manual, help can be requested through your local ALSTOM T&D Protection & Control office or representative. Your attention is additionally drawn to the fact that the contents of this Instruction Manual are not part of a previous or existing agreement, commitment or statutory right and do not change these. All commitments on the part of ALSTOM T&D Protection & Control are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions. These warranty conditions in the contract are neither extended nor limited by the contents of this Manual. 1.2 Qualified person Unqualified interventions in the devices or the non-observance of the warnings present in this Manual or on the devices may lead to severe personal injury or damage to property. Therefore only suitably qualified personnel may work on these devices: q Configuring personnel familiar with the safety concepts of automation technology q Operating personnel instructed in the handling of equipment for automation technology and acquainted with the contents of this Manual which are important for operation q Commissioning and servicing personnel who are trained to repair such automation technology equipment or who are authorized to energize, earth and tag circuits and devices in accordance with established safety practices. 1.3 Warning information Warning information with the following meanings is used in this Instruction Manual and in the warning information on the products: Danger means that death, severe personal injury or substantial damage to property will occur if the appropriate safety precautions are not observed.

Page 12

Warning means that death, severe personal injury or substantial damage to property can occur if the appropriate safety precautions are not observed. Caution means that slight personal injury or damage to property can occur if the appropriate safety precautions are not observed. Note: 1.4 is important information on the product, its handling or the respective part of the documentation to which particular attention should be paid.

Approved use q The devices must only be used for applications described in the Catalog and the Instruction Manual, and only in conjunction with other devices and components recommended by or approved of by ALSTOM T&D Protection & Control. q The products have been developed, manufactured, tested and documented in accordance with the appropriate safety standards. If the handling guidelines and safety information are observed during configuring, assembly, approved use and maintenance, the products do not therefore present a danger in the normal case with respect to property or the health of persons. Warning q Following removal of the housing or the guard, certain parts of these devices are accessible which may carry dangerous voltages. q Only suitably qualified personnel should work on these devices. q These should be thoroughly familiar with all sources of danger and maintenance measures according to the information in this Manual. q Correct and safe operation of the products is dependent on proper transport, storage, installation and assembly as well as careful operation and maintenance. Documentation In addition to this Instruction Manual - which can be used by all target groups - the following relevant technical documentation is also available for the devices: q Leaflet "Parameterization a concise overview". Explains in visual form the basic operation and parameterization as well as the PROG and TEST menus. Target group: configuring and maintenance personnel.

Page 13

Section 2.
2.1

APPLICATION

Purpose The devices q line recorder, referred to below as R30 version, and q line recorder with alphanumeric output, referred to below as R40 version, can be used to measure, record and monitor analog and digital values.

2.2

Standard The recorders can be used to cyclically measure the following variables : q DC voltage (DC U) q direct current (DC I) and also with the R40 version q thermocouple connection (TC) q thermoelectric resistance, resistance and potentiometer connection (RTD, R) to process these and to document them on chart paper. As a result of the short cycle time, the recorders are also suitable for recording fast, dynamic process parameters. Even when delivered according to customer-specific requirements, the recorders can still be subsequently and easily adapted to requirements within the input, measuring and recording ranges. The recorders can be equipped with up to three coloured pens for the analog recording of measured values connected via channels #1 to #3. The R40 version has an additional pen for a text channel for the output of alphanumeric characters and the recording of up to two digital channels d#1 and d#2. The recorder functions can be set manually using levers.

2.3

Designs The recorders vary with respect to their recording systems, measuring ranges and power supplies: q R30 version: no alphanumeric text q R40 version: with alphanumeric text q Standard measuring ranges q Universal measuring ranges q Power supply ac 230V q Power supply ac 115V q Power supply ac 24V q Power supply dc 24V

Page 14

2.4

Options The recorders can be equipped with the following options: q Digital input/output q DC 24V output The Digital input/output provides four inputs (DI1 to DI4) for control functions and six outputs (DO1 to DO6) for alarms, status signals or control signals. The inputs and outputs are electrically isolated from the recorder circuits. Two different outputs can be selected: q Digital input/output, electronic version with semiconductors or q Digital input/output, relay version with changeover contacts. The option DC 24V output provides a power output for external devices or options to a limited extent such as eg. a transmitter or digital input/output. Design Recording Alphanumeric Measuring ranges Standard Universal Power supply AC 230V or AC 115V or AC 24V or DC 24V Options Digital input/output, electronic Digital input/output, relay DC 24V output q Included in standard delivery v v v v Possible options v v v q q q q q q q q q q q R30 version R40 version

Table 1
2.5 Delivery

Summary of recorder versions and options

The recorders are delivered as standard designs, or manufactured, parameterized and prepared for operation in the factory according to the customers order. 2.6 Conversion Conversions to the recorders such as eg. changing the power supply or subsequently installing options must only be carried out by the certified servicing department. 2.7 Environmental protection Only environmentally-friendly materials have been used for the packaging system of the recorders.
Page 15

Section 3.

DESIGN AND MODE OF OPERATION

The following chapter describes the mechanical and electrical design as well as the recorder components. 3.1 Summary The recorders are designed as panel mounted instruments with a format 144 mm x 144 mm. Installation without interspacing is possible in panels and mosaic systems with sufficient ventilation. The modern recorders have digital data processing. Measured values are recorded serially in channels and with solid state technology. As a result of the exclusive use of step motors, the drive system for recording operates completely without contacts. This technology permits a wide range of applications and high functional reliability. Fig. 1 and Fig. 2 show views of the recorder. The mode of operation of the recorders is explained down to the block diagram level using Fig. 3.

1. Door 2. Chart carriage 3. Levers

4. (Not used) 5. LEDs 6. Visual operating aids

Fig. 1

Front view of R30, R40 versions

Page 16

1. Earth connection 2. Terminals for dc 24V output 3. Connection of digital input/output 4. (Not used)

Connection of power supply

6. Fuse F2 7. Window of measuring point allocations 8. Input terminals

Fig. 2
3.2 3.2.1 Housing

Rear view of R40 version (ac 115/230V design)

Recorder components The housing is made of sheet-steel. The chassis and the chart carriage are present at the front; the measuring module, the central processing unit, parts of the power supply and the options are located at the rear. The housing is mounted in the panel, mosaic system or desk upright panel using the supplied, standardized mounting elements.

3.2.2

Measuring module The measuring module has up to three channels, a multiplexer with semiconductor relays and an analog-to-digital converter. The input ranges are set specifically for each channel using jumpers. The channels are electrically isolated from one another by staggered control of the semiconductor relays. Control is handled by the central processing unit. All channels to be measured during a cycle are connected to the input amplifier in succession via the individual
Page 17

semiconductor relays. The amplified signal is applied to an analog-to-digital converter which operates according to the dual-slope procedure. In order to permit equally accurate measurements in sensitive ranges, reference measurements are carried out cyclically in the recorder version with universal measuring ranges. A cyclic check is also carried out for open-circuits. The terminal block also contains a sensor for measuring the terminal temperature when carrying out temperature measurements using thermocouples. 3.2.3 Central processing unit The central processing unit is the heart of the electronics. It contains a microprocessor as well as the program memory (EPROM), main memory (RAM) and non-volatile memory (EEPROM) for configuration data. Central component of the processing section is a microprocessor system with firmware. This is used, inter alia, for: q Sequence control q Calculation of measured values q Positioning of pen assemblies q Evaluation of input commands q Use of PC interface. The central processing unit permits control of the module Digital input/output. A crystal-controlled calendar/clock with external synchronization facility provides the date and time as a reference for sets of measured values and the chart. The central processing unit is located at the rear of the housing and is accessible from the front following removal of the chassis. It contains the plugs for connection of the other modules. 3.2.4 Power supply The recorders have different designs on the input side as a result of the four different power supplies which can be ordered. 3.2.4.1 AC 230V or AC 115V The mains power supply is connected to the recorder via an appliance plug with subsequent fuses, filter and transformer. The stepped down ac voltage is rectified, filtered and applied to dc/dc converters which generate the required internal dc voltages. Note: 3.2.4.2 DC 24V The dc 24V supply connected via the terminals is applied via a fuse to a power inverter whose output is connected to a transformer. The secondary side of the transformer is connected as in the recorder version with a mains power supply. 3.2.4.3 AC 24V The ac 24V supply connected via the terminals is applied via a fuse to the primary side of the transformer. The secondary side is connected as in the recorder version with a mains power supply.
Page 18

The recorder must only be connected to the envisaged power supply. Observe the corresponding note on the rear of the recorder.

3.2.5

Chassis The chassis contains the chassis support, control PCB, recording system, user interface, PC interface and chart carriage. The chassis is connected to the central processing unit via a multi-conductor ribbon cable with plug. The cable length is such that the chassis can be completely removed from the housing without loosening the connection.

3.2.5.1 Chassis support This is the support for the motors of the recording system, the control PCB, user interface and PC interface. The chart carriage latches into the chassis support and can be removed at any time using lever 2, eg. to replace the chart. 3.2.5.2 Control PCB The control PCB contains the power electronics for the step motors of the drives as well as the light barrier for detection of the carriage zero points. It also contains a microswitch for recognizing the end of the chart paper, and several microswitches which are activated using the levers. 3.2.5.3 Clock backup Only R40 version: the clock backup consists of a backup battery and capacitor. If a battery is not present, or if the chassis is separated from the central processing unit, the capacitor buffers the internal clock for approx. 5 minutes. The status of the clock buffer is checked when the power supply is switched on. The support for the backup battery is present on the control PCB and accessible following removal of the chassis. 3.2.5.4 Recording system The recording system consists of up to seven step motors depending on the recorder version. These are used for: q Chart drive q Positioning of the three coloured pens in the xdirection q Pen lift q R40 version: positioning of pen for text channel in x and ydirections 3.2.5.5 Chart carriage The chart carriage permits fanfold packs or rolls to be used as the chart paper. A take-up spool is required when using rolls. In addition, the chart carriage must be adapted when changing from fanfold paper to rolls. The required operations are described in Section 7 Servicing and Maintenance. 3.2.5.6 User interface The user interface consists of four levers and two LEDs underneath the chart carriage. A further lever is present on the side of the chassis and is only visible when the chassis is in maintenance position. Mechanical operations are directly activated by two of the four levers underneath the chart carriage. The other two levers can be used for two different actions each by moving the respective lever to the left or right. The TEST menu can be activated and switched off again using the switch which is accessible on the side of the chassis. Green and red LEDs indicate different recorder statuses depending on how they are activated (on, off, flashing).
Page 19

Measuring module

Recording system for 33 analog channels and 2 digital channels

2x

5x

Only R40 version

Fig. 3

Block diagram of R30, R40 versions

Page 20

3.3

Mode of operation As a result of the many different possible uses, the recorders are delivered preset to the basic setting of 4 to 20mA. Customer-specific presetting is also possible as required. The recorder can then be used immediately following installation and commissioning. The values measured cyclically by the recorder are amplified, digitized and processed further by a microprocessor system. In addition to processing of the measured values, the microprocessor system is responsible for sequence control, self-test, event processing, control of the step motors of the recording system, feedbacks from the recording system and the user interface. The microprocessor system converts the measured value into positioning commands for the recording system. The pens draw a continuous line on the chart paper according to the measured signal. You can adjust the measuring and recording ranges such that the signal is recorded with an optimum resolution and display. It is also possible to define limits which are constantly recorded in the R40 version as vertical lines. The recorders can output an alarm text if the limit is violated. The number of limits and the alarm function can be parameterized within wide ranges. If the recorder is equipped with the digital input/output option, the alarms can be output for further processing. The R40 version can output a measured-value table, event text and recorder text cyclically or event-controlled. The texts must be entered previously via the user when setting up the recorder. The outputs are made depending on the recorder parameters.

3.4 3.5 3.6

Scope of delivery The scope of delivery is listed in Section 9.1. Accessories, consumable materials The accessories and consumable materials are listed in Section 9.2. Options The following options are available: q Digital input/output with 4 inputs and 6 outputs q DC 24V output

3.6.1

Digital input/output The input signals (DI1 to DI4) of the four digital inputs are applied to the basic electronics via opto isolators and processed further on the central processing unit. The output signals (DO1 to DO6) of the digital outputs are externally available at the interface electrically isolated either via opto isolators or relays depending on the version. q Electronic version: the output signals are generated by short-circuit-resistant semiconductor switches. The switches are controlled via opto isolators. The semiconductor switches must be powered via an external voltage source since they are electrically isolated from the basic device. q Relay version: the electrical isolation is provided by relays whose changeover contacts are externally available.

Page 21

3.6.2

DC 24V output The dc 24V output option can be used for the following purposes: q Power supply to external transmitters q Power supply to digital input/output, electronic version The dc 24V output module is powered by the rectified and filtered internal dc voltage. The floating output is available as a bipolar terminal on the rear of the recorder. Refer to Section 9.2 for the ordering data.

Section 4.

PREPARATION FOR OPERATION

The following chapter describes all preparations necessary for operation of the recorders. 4.1 Recorder identification The recorders and modules can be identified with respect to their application and release version by means of various labels: q Rating plate with object version for recorder q Part No. with release version for modules 4.1.1 Rating plate The rating plate (Fig. 4) provides information on: q Recorder type q Serial number q Object version q Channel assignments (only rating plate on rear). There are three rating plates on the recorder: q On the rear (eg. Fig. 8), q On the left inside the housing (visible after removing the chassis), q On the left side of the chassis (eg Fig. 63) If the input ranges are changed, a blank label can be inscribed using a waterresistant felt pen and adhered to the part of the rating plate which is no longer valid. 4.1.2 Object version The object version (Fig. 4) of the recorder can be read from the rating plate. The digit marked with a cross identifies the hardware release of the recorder. The Instruction Manual references the object version. This Manual is valid for the object version 1 shown in Fig. 4.

Page 22

Line Recorder DC U/I


Serial No H6-966 X 2 3 4 5 6 7 5 9 10 11

CHANNEL 1: 4....20mA 2: 4....20mA 3: 4....20mA


Made in France

Fig. 4
4.1.3

Example of rating plate for R40 version

Module release version The release version (Fig. 5) documents the hardware release of modules. The release version is indicated on the following relevant modules: q Central processing unit with power supply (bottom right, visible following removal of chassis) q Chassis (bottom right, visible following removal of chassis) Record the release version of the modules in your instrument passport so that you can pass this information on to the servicing department if necessary.

1 2 3 4 5 6 7 8 9 10 11

Fig. 5
4.1.4

Release version (example)

Firmware version The release version of the firmware can be read on a label adhered to the EPROM. The release version can be read on the EPROM label following removal of the chassis. The Instruction Manual references the firmware release. This Manual is valid for the release version shown in Fig. 6. Record the release version of the firmware in your instrument passport so that you can pass this information on to the servicing department if necessary.

Page 23

Fig. 6

Positions of EPROM and jumper for 50/60Hz on module Central processing unit

DC 24V 81+ 82

1 2 3 4 5 6 7

Cut-out prepared for digital input/output Fuse F1 Power supply connection Grip for cable detensioning Window with channel inscriptions for setting of input ranges (design for standard measuring ranges) Input terminals Cut-out prepared for dc 24V output

Fig. 7

Rear view of R30 version (dc 24V design)

Page 24

2 3 6

2 7 8 9

1 2 3 4 5 6 7 8 9

Earth connection DC 24V output (option) Digital input/output (option) Transformer with rating plate Fuse F1 Power supply connection with mains supply Fuse F2 Window with channel inscriptions for setting of input ranges (design for universal measuring ranges) Input terminals for channel #1 bis #3

Fig. 8
4.2

Rear view of R40 version (ac 115/230V design)

Installation guidelines Insert the recorder into the prepared panel cut-out (see Fig. 9 for dimensions), insert two clamps into the corresponding positions on the housing, and tighten the screws. Special clamps must be used when fitting in a 72mm mosaic system. The permissible ambient temperature according to the technical data must be observed at the mounting position. This must be particularly observed when installing without interspacing. Note When installing, observe the safety guidelines in Section 1.

The following information is generally applicable to installation: q No special requirements are placed on power supply, measuring and control cables which do not carry a dangerous contact potential. q Voltages which are not dangerous to contact are up to dc 50V or ac 25V if they are generated by safety transformers, batteries etc. and are not connected to other circuits (low-voltage networks with safe isolation).
Page 25

q The isolation of power cables with a dangerous contact potential must be selected according to the max. voltage. q The cross-section of the protective earth conductor must be selected at least as large as the largest cross-section of the power cable. q The connection between the protective earth connection and the protective earth conductor must be made before any other connections.

Fig. 9
4.3

Dimensions for installation of R30, R40 versions

Mechanical preparation of recorder for operation Note Only use recorders with the scales and pens fitted.

The following points refer to the mechanical preparation of the recorders, and must be carried out in the defined sequence prior to starting up: 1. Remove chart carriage (Section 7.1) 2. Insert recording system (Section 7.15) 3. Insert roll or fanfold pack (Section 7.7, Section 7.5) 4. Insert chart carriage (Section 7.2) 4.4 Connection of power supply Depending on the recorder design, the connection is for q AC 230V or q AC 115V or q AC 24V or q DC 24V.
Page 26

Before connecting, check that the technical data (Fig. 10) for the power supply as specified by the manufacturer on the recorder agrees with the data of the power supply to be connected. Note The data for the power supply must lie within the values specified for this design in the technical data.

F1 = F2 = T0, 125/250C

Fig. 10 Power supply information on recorder


4.4.1 Connection to ac 230V or ac 115V The connection to an ac 230V mains supply is made using the supplied appliance plug. The correct connection for ac 230V and ac 115V is identical and shown in Fig. 11.

Fig. 11 Connection of mains supply


4.4.2 Connection to ac 24V or dc 24V The connection inscriptions depend on the recorder design. The connection must be made to the provided screw terminals according to the defined inscriptions. The cable must be secured using a grip to reduce the strain (Fig. 12).

Page 27

Earth

Earth

Fig. 12 Connection of ac 24V or dc 24V


4.4.3 Selection of 50/60Hz The measured values are recorded according to an integrated measuring procedure. In order to suppress interferences (hum), the measuring period (integration time) must be matched to the mains frequency. The basic setting is 50Hz. The setting can be changed using a jumper on the module "Central processing unit" (Fig. 6). If the recorder is powered via a dc supply, the frequency of the surrounding ac supply must be set. The chassis must be removed from the housing in order to check or change the jumper setting (Section 7.10). 4.5 Connection of analog channels The following types of measurement are possible for each channel: q DC U or q DC I or q TC (only recorder design with universal measuring ranges) or q RTD, R (only recorder design with universal measuring ranges) The type of measurement is set using jumpers. In order to set the jumpers, you must first remove the window for setting the input ranges (Fig. 13). The transparent plastic part can be easily removed by inserting a small screwdriver at the side.

Fig. 13 Connection of analog channels #1 to #3 to recorder design with universal measuring range

Page 28

Jumper positions

Input ranges Direct connection

Measuring ranges TC/RTD/R/Pot./U (only recorder with universal range) DC U 0/1V 0.2/1V 1V DC U 0/10V 2/10V 10V DC I 0/20mA 4/20mA 20mA

1V

10V

20mA

Fig. 14 Jumper settings

Fig. 15 Basic connections for channel inputs with R30 version


Page 29

Fig. 16 Basic connections for channel inputs with R40 version

Page 30

4.5.1

Labels A label with information (Fig. 17 or Fig. 18) on the possible connections of the analog channels is adhered on the transformer (Fig. 8 or Fig. 7) above the window for setting the input ranges.

Fig. 17 Possible connections for analog channels in design with standard measuring ranges
4.5.2 DC U The connection is made according to Fig. 17 and the jumper settings according to Fig. 14. The parameters are set according to Section 5.5.3. 4.5.3 DC I The connection is made according to Fig. 17 and the jumper settings according to Fig. 14. The parameters are set according to Section 5.5.3.

Fig. 18 Label with information on the possible connections for the analog channels in design with universal measuring range
4.5.4 TC Thermocouples can be connected as follows: q Directly with an internal cold junction q Indirectly with an external cold junction at constant temperature q Indirectly with an external cold junction at any temperature The basic connections are shown in the following Figs. The jumpers of the input channels are set according to Fig.14 and the parameters according to Section 5.5.3. 4.5.5 Direct thermocouple connection (Internal cold junction) The connections of the thermocouples or the associated equalizing conductors must be connected directly to the recorder terminals. The temperature of the terminal block (reference temperature) is measured by the recorder and compensated. The connection is made as in Fig. 19.

Page 31

Fig. 19 Thermocouple connection


4.5.6 Indirect thermocouple connection, constant cold junction temperature (External cold junction at constant temperature) The connections of the thermocouple are connected via a cold junction, eg. thermostat. The temperature of the cold junction must be entered. The cables between the external cold junction and the recorder terminals can be made using any conductors with the same material (usually Cu). The connection is made according to Fig. 18.

Fig. 20 Thermocouple connection to external cold junction at constant temperature


4.5.7 Indirect thermocouple connection, variable cold junction temperature (External cold junction at variable temperature) The connections of the thermocouple are connected via a cold junction at any temperature. The temperature of the cold junction must be measured using another channel and is calculated internally. Thermocouples as well as resistance thermometers are possible for recording the cold junction temperature. The connection is made according to Fig. 21.

Fig. 21 Thermocouple connection to external cold junction at any temperature

Page 32

4.5.8

RTD, R Thermoelectric resistors as well as standard resistors can be connected as follows: q Two-wire measurement q Three-wire measurement

4.5.9

Two-wire measurement of thermoelectric resistance and standard resistance This type of connection is preferably selected for a short distance between the sensor and the recorder. It is necessary to either select the cables with such a low resistance that an error in measurement does not occur (Fig. 22), or they must be adjusted to 10 (Fig. 23).

Fig. 22 Two-wire system without additional line compensation

Fig. 23 Two-wire connection with line compensation (RA) to 10


4.5.10 Three-wire measurement of thermoelectric resistance and standard resistance This type of connection presupposes that the resistances of the cables between the sensor and terminals 12 and 13 on the recorder are of equal magnitude. The connection is made according to Fig. 24.

Fig. 24 Three-wire system

Page 33

4.5.11

Three-wire measurement of potentiometers The resistances of the three cables between the sensor and the recorder must also be of equal magnitude with this measurement. The setting is made according to the Section Selecting the type of connection. Two methods are basically possible. 1. The cables have such a low resistance that no errors in measurement occur.

Fig. 25 Connection for potentiometer measurement


2. The total of the full-range resistance of the potentiometer and the cable resistance is adjusted to 10 using additional external line compensation.

Fig. 26 Connection for potentiometer measurement with additional line compensation (RA2, RA3) to 10
4.6 Digital input/output A 25-pin subminiature plug (Fig. 8) is present on the rear of the recorder for the option Digital input/output. See Section 3.6 for technical details. In the electronic version, the semiconductor switches which are isolated from the basic electronics by opto isolators must be powered by an external 24V supply. If the recorder is equipped with a dc 24V output (option), it is alternatively possible to use this source, taking into account the technical data (Fig. 27). A 25-pin subminiature plug for connection of the digital input/output is included in the delivery. The pin assignments are shown in Table 2 and Table 3. Parameterization of the digital input/output is described in Section 5.7.4.

Page 34

Plug pin 24

Input Input DI1

Parameterizable functions Measuring mode normal on/off Measuring mode fast - on/off Measuredvalue table 1) Event text 1) Digital channel 1)

Remarks Low off, High on Low off, High on Edge following High output Edge following High output Recording of time characteristic Edge following High on Edge following High on, only if condition for A is not fulfilled Edge following High output Edge following High output Recording of time characteristic 2) Edge following High output Edge following High output Recording of time characteristic 3)

12

Input DI2

Chart feed A on Chart feed B on Measuredvalue table 1) Event text 1) Digital channel 1)

25

Input DI3

Measured-value table 1) Event text 1) Digital channel 1)

13

Input DI4

Control input for Chart feed 10mm to 100mm Time marker Clock synchronization 3:00 Summer time (MESZ) TEST locking Measured-value table Event text 1) Digital channel 1)
1)

Edge following High acc. to feed Edge following High zero adj. Edge following High synchronization Low MEZ, High MESZ 3) Low on, High off Edge following High output Edge following High output Recording of time characteristic 2)

11

Reference potential 0V (DI) Only R40 version Max. two channels MEZ Central European time MESZ Central European summer time

1) 2) 3)

Table 2

Pin assignments Digital input/output (DI1 to DI4)

Page 35

Plug pin

Assignments for electronic version Output DO1 Output DO2 Output DO3 Output DO4 Output DO5 Output DO6 Ext. power supply 24V (DO) Ext. power supply 0V (DO)

Assignments for relay version Output DO1: NO contact Common point NC contact Output DO2: NO contact Common point NC contact Output DO3: NO contact Common point NC contact Output DO4: NO contact Common point NC contact Output DO5: NO contact Common point NC contact Output DO6: NO contact Common point NC contact

14 2 15 3 16 4 17 5 18 6 19 7 20 8 21 9 22 10 23 1

Table 3 Pin assignments "Digital input/output" (DO1 to DO6)

Page 36

Digital input/output electronic version

0V (DO) DO1 24V (D0) OV (DI) D14

1 14 23 11 13 DIG IN/OUT

To pin 23 To pin 14 To pin 1

24V {D0}

81+ 82+

DIG IN/OUT OV (DI) D14 11 13

81+ 82+ To pin 11 To pin 13

OV {DI} 24V Synchronization 3:00 hours

Time synchronization 3:00 hours Lamp triggering via DO1 Supply of digital input/output via DC 24 V output

Fig. 27 Example of connection for digital input/output


4.7 DC 24V output Following installation of the option dc 24V output, a bipolar terminal (Fig. 28) is available at the rear of the recorder with a floating output for the supply of external components. The following connections are permissible since the current output is limited to max. 75mA: Up to three two-wire transmitters with a current consumption of 25mA each Digital input/output Note If several two-wire transmitters are powered, these must be connected together on one side and are thus not electrically isolated from one another. For noise reasons (differences in potential), this arrangement is only meaningful for transmitters which are close together.

Page 37

Fig. 28 Example of connection for two-wire transmitter to the dc 24V output option (R30 version, dc 24V design)
4.8 Starting up the recorder All recorder settings have already being made in the factory if the recorder has been delivered according to customer specifications. The standard settings have been made for recorders delivered without customer specifications. The standard settings are listed in Section 5 Operation in the respective subsections. If you are not acquainted with the recorder, it is recommended to start with simple measurements after working through Sections 2 to 5. Measurements with the standard settings are most appropriate initially.

Section 5.

OPERATION

The following chapter describes how to operate the recorders. Note Replacing the chart and the battery for backing up the clock are described in Section 7.

You are guided by menus when operating the recorders. The menus provide information in the form of a table on the respective functions or values for an input (leaflet Parameterization a concise overview). The input menus consist of several elements which are comprised in turn of menu code numbers and designations.

Page 38

In the first input step (selection of row) you decide which function or parameter is to be called. The red LED lights up. In the second step (selection of column) you can define or modify the corresponding setting of the recorder. The red LED flashes. The input of a menu code number is terminated by ENTER. You can scroll through the menu using the INC/DEC functions. 5.1 Display and control elements Operation is carried out using four horizontal levers located below the chart carriage (Fig. 29). A further lever is present on the side of the chassis. Two coloured LEDs which are also located below the chart carriage serve to support you when setting up the recorders and for the output of status messages. In the R40 version status messages are additionally printed on the chart paper by means of the text channel (Section 6).

1. 2 3 4

Scale channel 3 Pen channel 1 Pen channel 2 Pen channel 3

5 6 7 8

Lever 3 LED, green Lever 2 LED, red

9 10 11 12

Lever 1 (Not used) Service lever Parameterization scale

Fig. 29 Display and control elements at front

Page 39

Fig. 30 Chassis in maintenance position, activation of lever 4


5.2 Display elements The recorders are equipped with two colored LEDs whose combined statuses (on, off, flashing, fast flashing) indicate status messages. Table 4 lists a summary of the status messages assigned to the LED statuses.

Table 4
5.3 Levers

Summary of LED status messages

The levers have different effects. The black service lever and lever 2 act directly on the mechanics. The other levers act on microswitches whose signals are processed by the central processing unit. The levers are used for recording, START, STOP or PAUSE OFF, PAUSE ON, high chart speed and recorder settings via the PROG and TEST menus.

Page 40

Feedbacks for the user when setting up the recorders are via the LEDs and the positions of the pens. The rows and columns of the PROG and TEST menus designed in tabular form directly correspond to the value of the parameterization scale, ie. a scale value of 15% corresponds to row 15 or column 15 depending on the status of the red LED. The levers are assigned different functions during operation, PAUSE and when setting up the recorder. Fig. 31 shows a summary of the lever functions. These functions are described in detail in the following sections.

Fig. 31 Summary of lever functions


5.3.1 Functions of service lever and lever 2 Releasing the chassis The service lever is used to release the chassis. The chassis must be moved to the maintenance position in order to change the pens or scales. To do this, briefly move the service lever to the left, and simultaneously pull out the chassis until this latches in the maintenance position. The chassis must be returned to its original position following the required operations. To do this, move the service lever to the left again, and simultaneously push in the chassis until it latches in place. The chassis can be completely removed from the housing in order to replace the battery for backing up the clock (only R40 version). To do this, release the chassis in the maintenance position using the service lever, and pull out the chassis to the front. When inserting the chassis again, you must again release it at the maintenance position using the service lever. Section 7 describes the above operations in detail. 5.3.1.2 Lever 2 Releasing the chart carriage Lever 2 is used to release the chart carriage from the chassis. This is necessary in order eg. to replace the chart. Section 7 describes the above operations in detail. 5.3.2 Functions of Levers 1, 3 and 4 in recording mode Zero adjustment Briefly moving lever 1 (labelled 1) to the left starts a zero adjustment without marking. The pens are moved to the right edge and carry out an adjustment. Recording mode is subsequently continued.
Page 41

5.3.1.1 Service lever

5.3.2.1 Lever 1

5.3.2.2 Lever 1

PAUSE ON

Briefly moving lever 1 to the right stops recording (PAUSE ON). The recording system is lifted up, and the pens move to the maintenance position (text channel: approx. 15%, bottom pen: approx. 40%, middle pen: approx. 60%, top pen: approx. 85%). All instrument functions apart from recording remain active. 5.3.2.3 Lever 3 PROG menu ON Briefly moving lever 3 to the left activates the PROG menu. The following actions identify the transition to the parameterization state: 1. Recording system lifts up. 2. All pens are driven to the 100% mark and carry out an adjustment there. 3. Channel 1 moves to the code number position for the PROG/TEST menu and writes a mark which must correspond to the version number of the PROG/TEST menu (cf. data in leaflet Parameterization a concise overview, version: code number n). 4. The pen for channel 1 moves to the 0% position and thus indicates Row 0, PROG menu. The red LED lights up, the green LED is off. The recorder is now in the parameterization status. All parameters can be set which are available in the PROG menu. Note The function PAUSE ON (lever 1 ) is not required in order to enter the parameterization status.

The PROG menu is switched off by moving the lever again. The red LED goes out, the green LED lights up. The recorder is switched back to its original status. Individual actions: 1. The recording system is lifted up. 2. An adjustment of the pens is carried out at the 100% mark. 3. The pens move to the measured values. 4. The recording system is lowered, and recording is continued. 5.3.2.4 Lever 3 The lever 3 5.3.2.5 Lever 4 has no function in recording mode. TEST menu ON

The chassis must first be moved to the maintenance position before lever 4 can be activated. Lever 4 is used to activate the TEST menu. Lever 4 is accessible on the side of the chassis and can be moved down eg. using a ball-point pen (Fig. 30). The mechanical sequences of the recording system correspond to those when activating Lever 3 .

Page 42

Table 5
5.3.3

Lever functions in recording mode

Functions of Levers 1, 3 and 4 in the PAUSE status Recording is not carried out in the PAUSE status. The pens are lifted up and are located in the maintenance position. The measurements are continued, and the measured values stored in a buffer to a limited extent. The measured values and text outputs (only R40 version) are written when returning to recording mode.

5.3.3.1 Lever 1

PAUSE OFF

Termination of PAUSE. Brief activation of lever 1 leads to adjustment of the recording system and continuation of recording. 5.3.3.2 Lever 3 PROG menu ON The procedure is described in Section 5.3.2. Reactivation of lever 3 returns to the PAUSE status. 5.3.3.3 Lever 3 Chart feed The chart is moved forward at maximum speed as long as lever 3 is held pressed to the right. 5.3.3.4 Lever 4 TEST menu ON The procedure is described in Section 5.3.2. Reactivation of lever 4 returns to the PAUSE status.

Page 43

Table 6
5.3.4 5.3.4.1 Lever 1

Lever functions in the PAUSE status


DEC

Functions of Levers 1, 3 and 4 with Recorder Settings using PROG Menu The PROG menu is organized as a matrix with rows and columns. In the parameterization status, the row or column number can be decremented, ie. switched by one digit in the zero direction with each activation. If the lever is activated when the pen is positioned at zero, this moves to the maximum row or column value (menu code number).

5.3.4.2 Lever 1

INC

As DEC, except that adjustment of the next higher menu code number is possible (incrementing (INC)). 5.3.4.3 Lever 3 PROG menu OFF The red LED must light up (selection of row): the PROG menu is switched off, and the recorder returns to the original operating status. 5.3.4.4 Lever 3 ENTER The number of the row or column selection currently marked by the pen is confirmed and entered. A switch is simultaneously made to the next selection level. Two cases are possible: 1. Parameterization commences with selection of the row. ENTER is used to switch to selection of the column, and the currently set value is displayed. Activating ENTER again switches over to selection of the row again. Whether you are positioned in selection of a row or column is indicated by lighting-up or flashing of the red LED. 2. A subsequent input, eg. text input (only R40 version), is provided in the same row for the function to be parameterized, this status is indicated by fast flashing of the red LED. 5.3.4.5 Lever 4 Lever 4 has no functions with the PROG menu activated.

Page 44

Recorder parameterization using PROG menu

Service lever

Releasing of chassis Red LED lit: decrement menu row (DEC) Red LED flashes: decrement menu column (DEC) Red LED lit: increment menu row (INC) Red LED flashes: increment menu column (INC) Chart carriage released Red LED lit: switch off PROG menu Red LED flashes: none 1. Red LED lit: confirm row selection (every activation leads to change between 1. and 2.) 2. Red LED flashes: confirm column selection None

DEC

Lever 1

INC

Lever 1

Lever 2

PROG

Lever 3 Lever 3

ENTER

TEST

Lever 3

Table 7
5.3.5 5.3.5.1 Lever 1

Lever functions with PROG menu activated


DEC

Functions of Levers 1, 3 and 4 with Recorder Settings using TEST Menu The TEST menu is organized as a matrix with rows and columns. In the parameterization status, the row or column number can be decremented, ie. switched by one digit in the zero direction with each activation. If the lever is activated when the pen is positioned at zero, this moves to the maximum row or column value (menu code number).

5.3.5.2 Lever 1

INC

As DEC, except that adjustment of the next higher menu code number is possible (incrementing (INC)). 5.3.5.3 Lever 3 Lever 3 5.3.5.4 Lever 3 has no functions with the TEST menu activated. ENTER

The number of the row or column selection currently marked by the recording system is confirmed and entered. A switch is simultaneously made to the next selection level. Two cases are possible: 1. Parameterization commences with selection of the row. ENTER is used to switch to selection of the column, and the currently set value is displayed. Activating ENTER again switches over to selection of the row again. Whether you are positioned in selection of a row or column is indicated by lighting-up or flashing of the red LED. 2. A subsequent input, eg. text input (only R40 version), is provided in the same row for the function to be parameterized, this status is indicated by fast flashing of the red LED. 5.3.5.5 Lever 4 TEST menu OFF The red LED must light up (selection of row): the TEST menu is switched off, and the recorder is reset to the original operating status.

Page 45

Recorder parameterization using TEST menu

Service lever

Releasing of chassis Red LED lit: decrement menu row (DEC) Red LED flashes: decrement menu column (DEC) Red LED lit: confirm row section (INC) Red LED flashes: increment menu column (INC) Chart carriage released None 1. Red LED lit: confirm row section (every activation leads to change between 1. and 2.) 2. Red LED flashes: confirm column selection None

DEC

Lever 1

INC

Lever 1

Lever 2

Lever 3 Lever 3

ENTER

TEST

Lever 4

Table 8
5.4

Lever functions with TEST menu activated

Settings via PROG menu The following sections explain the settings which can be achieved using the PROG menu by means of text, figures and examples. You can call and modify all recording, measurement and alarm settings in the PROG menu. Access to the PROG menu can be protected by two interlocking steps. With interlocking step 1, only the chart feed A can change, with stage 2, the PROG menu is completely disabled. Note You can orientate yourself using the cross-references, eg. P[0] (means PROG menu, row 0), and the associated PROG menu table (leaflet Parameterization a concise overview).

Page 46

Section 5.5.1
Chart speed A

Section 5.5.1
Chart speed B

Section 5.5.2 Section 5.5.3

Section 5.5.4

Section 5.5.5

Section 5.5 6

Fig. 32 Summary of PROG menu, rows


5.4.1 Chart speed The parameters for chart speed A or B can be used to define two combinable speeds for the chart paper. The selectable values are listed in Fig. 33. 5.4.1.2 P[5], P[15] Condition Chart speed A and/or B can be linked to a condition if required so that the chart speed changes dependent on an event. The possible conditions are shown in Fig. 33. 5.4.1.1 P[0], P[10] Chart speeds A, B

Page 47

5.4.1.3 Event-dependent chart speed The recorder selects chart speed A when switched on. The event sources are also processed even if recording is switched off. The currently active status is retained if no conditions are fulfilled for chart feeds A and B or if both conditions are fulfilled simultaneously. A change is made to chart speed B if the condition set for it is fulfilled. The same applies to a change from B to A. If the alarm of a channel is used as the condition, if Mode OFF is selected for the associated channel. See Section 5.6.1 for setting example.

Fig. 33 Programmable parameter Chart speed


5.4.1.4 Details on selection of chart speed Switching over commences with a marker in the form of small horizontal lines on the curves and a fast feed of at least 7mm such that a setting on the main time lines - if set - is retained. Small horizontal lines are then again drawn on the curves, and the recording commences with the new chart speed. At the same time, the text channel of the R40 version starts to write a chart switching line. Note If the chart speed is switched over too frequently in succession, the recording system would be overloaded and the measured values lost. Therefore the recorder switches over again at the earliest after approx. 30s.

The following example clarifies the mode of operation of chart speeds A and B with condition.

Page 48

5.4.1.5 Example Chart speed A is set to 20mm/h [P0.30]. The condition is present at Input DI2 [P5.70]. Chart speed B is set to 120mm/h [P10.40]. The condition is at /Input DI2 [P15.75]. Result: The chart speed is 20mm/h in measuring mode if the signal at input DI2 is High. The chart speed is switched over to 120mm/h if the signal changes to Low. This status is retained until DI2 changes to High again. The chart speed then returns to 20mm/h. 5.4.2 Measured-value table (only R40 version) The R40 version prints a measured-value table (Fig. 56 Example recording for R40 version as required with the following information, if relevant: q Date and time q Channel number q Measured value q Dimension q Symbol for open-circuit q Status of alarms assigned to the channel. Printing can be triggered cyclically or event-controlled. Parameterization is carried out according to Fig. 34. 5.4.2.2 Printing the measured-value table The graphic recording is not interrupted when printing the measured-value table, ie. the 2nd and 3rd lines are only printed if the chart feed has reached a full line height since the last line. If a further trigger function for a measured-value table or an event text arrives whilst a table is being printed, this is only commenced when the table has been completely printed and the chart feed has reached a full line height since the last line. The printout of the measured-value table always coincides with a time mark if it is carried out cyclically. The first line of the measured-value table is omitted in this case. The minimum distance between two cyclic printouts is 10 mm. The measured values at the printed time are stored in intermediate memory before being output. Only those channels are printed out for which Measuring or Recording has been selected. See Section 5.6.2. for setting example. 5.4.2.1 P[20] Measured-value table

Page 49

Fig. 34 Summary of parameters Measured-value table


5.4.3 Parameterizing the Analog Channels The channel-specific variables are set using the parameters for channel (analog), mode, measuring range, sensor, connection, left value, right value, open-circuit and damping. 5.4.3.1 P[25] Analog channel This is used to select the number of the analog channel you wish to parameterize. The channel number is preceded by the symbol # in the printouts, eg. #1. The recorders have one to three analog channels: #1, #2, #3. The associated pen is activated following selection of the channel. The following table lists the channel assignments: Channel #1 Position in recording system Bottom Channel #2 Centre Channel #3 Top

Table 9

Characteristics of analog channels #1 to #3

The possible setting parameters are shown in Fig. 35.

Page 50

Fig. 35 Summary of parameter Channel (analog)


See Section 5.6.3 for setting example. 5.4.3.2 P[30] Mode You can use this parameter to select the Measure or Recording mode for the selected channel (Section 5.5.3). Select Off if the measuring and recording modes are to be switched off. In Measure and Recording modes, the associated channel is scanned cyclically. The alarm is generated by comparing the measured value with the set alarm value. In Recording mode, the measured values are additionally recorded by the recording system.

Fig. 36 Summary of parameter Channel (analog), Mode


See Section 5.6.3 for setting example.
Page 51

5.4.3.3 P[35] Measuring range The measuring ranges are selected according to the set input range (Section 4.5). The recording range (left value, right value) is fixed to the measuring range limits for certain standard ranges (Fig. 37) and cannot be changed. With the other measuring ranges, you can enter the start-of-scale and full-scale values yourself within the range limits. Table 10 shows the possible values for the set ranges.

Fig. 37 Summary of parameter Channel (analog), Measuring range


See Section 5.6.3 for setting example. 5.4.3.4 P[40] Sensor The parameter Sensor is used to define the type of sensor when using thermocouples or resistor thermometers. The associated linearization values are automatically taken into account during measured-value processing. The appropriate operating range of the sensor must be selected when using resistors, potentiometers or sensors with a voltage output. The possible settings are shown in Fig. 38.

Page 52

Fig. 38 Summary of parameter Channel (analog), Sensor


See Section 5.6.3 for setting example. 5.4.3.5 P[45] Connection This parameter is used to select the input for the reference temperature when measuring with thermocouples. Select the desired reference point from Fig. 39. 5.4.3.6 TC With the setting Ref.: internal, the temperature of the input terminals is used as the reference. Select the setting Ref.: 0C to Ref.: 70C if the external reference point is held stable at one of the corresponding temperatures. The reference point can be measured via a further input if the temperature varies. In this case, select the settings Ref.: #1 to Ref.: #6. 5.4.3.7 RTD, R, Pot. You can select either a three-wire or two-wire connection (Section 5) for measurements via resistance thermometers, resistors and potentiometers. Select RL: 10 in the case of a two-wire system with adjustment of the line resistance to 10 . Select RL: 0 if the line resistance is negligibly small.

Page 53

Fig. 39 Summary of parameter Channel (analog), Connection


See Section 5.6.3 for setting example. 5.4.3.8 P[50] Left value P[55] Right value The recording range can be set within limits using the parameters Left value and Right value, apart from certain standard measuring ranges (Fig. 40). The factory-set recording ranges are listed in Table 10 (default settings for left value/ right value). The recording range is set numerically for the inputs Left value and Right value. The input refers to the set measuring range and is set in a uniform manner. The sign is entered first, followed by 4 digits separated by a decimal point. If modifications are necessary, only the associated digits or the sign are overwritten. If illegal inputs are made, adaptation is automatically made according to the measuring range.

Page 54

Fig. 40 Summary of parameter Channel (analog), Left value and Right value
See Section 5.6.3 for setting example.

Page 55

Measuring range

Dimension Start

Setting range End Left value +00.00 +04.00 +0.000 +0.200 +00.00 +02.00 22.00 1.100 21.00 44.00 110.0 440.0 1100. 030.0 0100. 010.0 010.0 0273. 0273. 0273. 0273. 0273. 0273. 0273. 0273. 0273. 0273. 0273. 0273. +22.00 +1.100 +21.00 +44.00 +110.0 +440.0 +1100. +330.0 +1100. +110.0 +110.0 +2000. +2000. +2000. +2000. +2000. +2000. +2000. +2000. +2000. +2000. +2000. +2000. 20.00 1.000 10.00 44.00 100.0 400.0 1000. +000.0 +0000. +000.0 +000.0 +0000. +0000. +0000. +0000. +0000. +0000. +0000. +0000. +0000. +0800. +0800. +0800.

Preset Right value +20.00 +20.00 +1.000 +1.000 +10.00 +10.00 +20.00 +1.000 +10.00 +44.00 +100.0 +400.0 +1000. +300.0 +1000. +100.0 +100.0 +0500. +0500. +0500. +0500. +0400. +0500. +0500. +0500. +0500. +1500. +1500. +1500.

0/20mA 4/20mA 0/1V 0.2/1V 0/10V 2/10V 20mA 1V 10V U: U: U: U: 40mV 100mV 400mV 1000mV

mA mA V V V V mA V V mV mV mV mV % % C C C C C C C C C C C C

R: 300 R: 1000 Pot: 300 Pot: 1000 RTD: Pt 100 RTD: Ni 100 TC: TC: TC: TC: TC: TC: TC: TC: TC: TC: J L T U K N E S R B

Table 10

Setting of recording range

Page 56

5.4.3.9 P[60] Open-circuit Only R40 version. Monitoring is carried out for an open-circuit in the mV measuring ranges and the TC, RTD, R and Pot. ranges based on them. As soon as the internal resistance of the sensor exceeds a certain value, the recording is continued on the left of the 0% line in the case of the setting < 0% (Fig. 41), and on the right of the 100% line in the case of >100%. The R40 version additionally outputs the event Open-circuit in the measured-value table (Section 5.4.2) printed on the chart paper. An open-circuit is not detected in the setting OFF.

Fig. 41 Summary of parameter Channel (analog), Open-circuit


See Section 5.6.3 for setting example.

Fig. 42 Example of display with open-circuit


5.4.3.10 P[65] Damping The damping is determined by the time constant of a 1st order low-pass via which the signal connected to the input terminals of the recorder is filtered. The output signal of the low-pass is an exponential function following a jump in the signal at the input. The time constant defines how long it takes until the output signal has attained 63.2% of the stationary final value. Set 0s for output of unfiltered measured values. The damping must be set individually for each channel. With the setting auto, the damping is automatically adapted to the chart speed. The basic setting is 0s.
Page 57

The following Figure shows the parameterizable time constants.

Fig. 43 Summary of parameter Channel (analog), Damping


See Section 5.6.3 for setting example. 5.4.4 Parameterizing the digital channel (only R40 version) The recorder has two digital channels in addition to the three analog channels. An alarm (Section 5.4.5) or a digital input (Section 5.6) can be selected as the source. The binary signals of the digital inputs are displayed as a square-wave signal at defined chart positions (Table 11): Channel #1d Logical 0 (Low) Logical 1 (High) 81% 89% Channel #2d 91% 99% 5.4.4.1 P[70] Channel (digital)

Table 11

Chart positions of channels (digital)

The digital channels are recorded by the mechanical system of the text channel. Edges from logical 0 to 1 and logical 1 to 0 as well as peaks are recorded as continuous lines. Constant signal sequences are recorded as dashed lines. The lines are spaced at 10 mm with low chart speeds, and at 20mm with high chart speeds (see Fig. 56 Example recording for R40 version). Fig. 44 shows the possible parameters. See Section 5.6.4 for setting example.

Page 58

1) Only R30 version

Fig. 44 Summary of parameter Channel (digital)


5.4.5 Alarm The recorder permits the programming of up to six alarms, each of which is assigned to a fixed output of the digital input/output (option) (Table 3). A set alarm becomes active in Measure or Recording mode if the set limit is violated. The assignments of the alarms to the individual channels, mode and alarm value are freely selectable. The settings always commence with selection of an alarm. See Section 5.6.5 for setting example. 5.4.5.1 P[80] Alarm The parameter Alarm is used to select one of the available alarms A1 to A6 to which the mode, channel and value apply in a subsequent setting. 5.4.5.2 P[85] Mode The parameter Mode can be used to define whether the alarm is to be triggered when MIN is fallen below or MAX exceeded. With the R40 version, limit lines can be drawn parallel to the time axis. These lines are vertical and approx. 1mm long. The spacing between the individual lines is reduced by half if the limit is violated. The lines are drawn by the mechanical system of the text channel. The alarm symbol, the associated alarm number, the channel number or the character (with the setting All channels) are written cyclically next to the limit lines. The limit line can be set for each alarm using the parameter MIN with line or MAX with line. In the setting Status (only available in recorders with option Digital input/output), recorder readiness is signalled if all of the following conditions are fulfilled: q Power supply present q PROG menu not switched on q TEST menu not switched on

Page 59

q Recording started q Chart paper present q Last adjustment of recording system fault-free. Use of the status message is particularly meaningful if the recorder cannot be directly viewed. A control signal is output in the position Time marker (only available in recorders with option Digital input/output) at the start of the zero adjustment. This signal can be used to synchronise the cyclic zero adjustment of several recorders using this one as the master. An alarm is not output in the position OFF. All alarms are switched off in the basic setting. 5.4.5.3 P[90] Channel The 6 alarms can be freely assigned to the individual analog channels. The basic setting is as follows: q Alarms A1 and A2 to channel 1 q Alarms A3 and A4 to channel 2 q Alarms A5 and A6 to channel 3 A further possibility is the assignment of a common alarm to the channels in the setting All channels and applies to the channels for which Measure or Recording mode has been selected. The alarm is triggered if the value is exceeded (max) or fallen below (min) for at least one of the channels. 5.4.5.4 P[95] Value The setting Alarm, Value is used to define the percentage with respect to the recording range at which the alarm to be triggered. The selectable range of values is identical to the recording range and can be set in steps approx. 0.1%.

Page 60

85: Condition

Fig. 45 Summary of parameter Alarm


5.4.6 Print (only R40 version) Printing of the configuration data is triggered by the parameter Print. The color of the text channel is black. A different color setting is not possible. Note: 5.5 All printing operations triggered via the input menu can be aborted using ENTER

Settings using TEST menu The following sections explain the settings which can be achieved using the TEST menu by means of text, figures and examples. Note You can orientate yourself using the cross-references, eg. T[0], in the associated TEST menu table (leaflet Parameterization - a concise overview).

Page 61

Section 5.5.1 Section 5.5.2

Section 5.5.3

Section 5.5.4

Section 5.5.5 Section 5.5.6 Section 5.5 7 Section 7.19

Section 7.19.3 Section 7.19.4 Section 7.19.5

Fig. 46 Summary of TEST menu, rows


5.5.1 Measuring mode Five settings are possible for the parameter Measuring mode. No acquisition of measured values is carried out in the position OFF, ie. all other associated functions such as chart speed and alarm monitoring are also switched off. The setting Normal or Fast determines the cycle time. The resolution of measured values is higher with the setting Normal. The cycle times can also be switched on or off via the option Digital input/output with DI1. Measuring mode is carried out with the set cycle time as long as input DI1 remains at High. Measuring mode is terminated if the signal changes to Low. 5.5.1.1 T[0] Measuring mode

Page 62

0.0: 0.5:

OFF ON normal

0.10: ON fast 0.15: DI1 normal 0.20: DI1 fast

Fig. 47 Summary of parameter Measuring mode


See Section 5.6.6 for setting example. 5.5.2 Diagram The parameter Diagram is used to select the chart formatting. All texts are output if recording is switched on with the setting Alphanumeric ON. These texts include: q Start line when starting recording q Chart switching line when changing the chart speed q Text with PAUSE ON q Date/time marker and instrument text q Event texts q Inscription of limit lines. These texts are suppressed in the setting Alphanumeric OFF. Output of the time at the left edge of the chart is suppressed in the setting Time OFF. The underline character is still output. The date is still printed out every 12h. The following texts are suppressed with the setting Status line OFF: q Start line when starting recording q Chart switching line when changing the chart speed q Text with PAUSE ON (see Fig. 56 Example recording for R40 version ). See Section 5.6.7 for setting example. 5.5.2.2 Start line (only R40 version) The printout of the start line and the graphic recording commence simultaneously, ie. the arrangement of the pens means the start line appears in the chart (see Fig. 56 Example recording for R40 version). The start line consists of the word START, the date, time, active chart speed and measuring cycle. The graphic recording commences together with printing of the start line. An abbreviated start line is printed when the chart speeds A and B are changed. This line consists of the time and the active chart speed. 5.5.2.1 T[5] Diagram (only R40 version)

Page 63

5.5.2.3 T[10] Cycle This menu item can be used with the line recorders to set the time between two time markers. The possible settings are shown in the following Figure. A time marker is not output in the position OFF. Only a zero adjustment is carried out every 24h with this setting.

1) Only R40 version

Fig. 48 Summary of parameter Diagram


5.5.2.4 Time marker A time marker is written cyclically for all channels at the right edge of the chart. The time between two markers can be selected between 1h and 24h. If the time marker is to be output for several recorders synchronously, this is possible via the control input DI1 Time marker (T[65.85], see Section 5.5.5). The used chart feed can be determined for the R30 version from the distance between the time markers. 5.5.2.5 T[15] Grid (only R40 version) This parameter can be used to print a grid on the chart. The vertical distance between the markers (crosses) is independent of the chart speed. The number of grids over the chart width is selectable. At chart speeds from 300mm/h to 1200mm/h however, markers are only output at 0% and 100% independent of this setting. The markers are synchronised with the time marker and independent of the starting time of the recording (see Fig. 56 Example recording for R40 version). Note A grid printout is only meaningful with slow chart speeds since the grid is written oblique at fast speeds.

Fig. 48 shows the possible settings for the parameter Grid.

Page 64

5.5.3

Text (only R40 version) Various texts can be programmed in order to make evaluation and documentation of the results easier. The recorder can store one Instrument text and five Event texts and write these depending on conditions. Conditions are cyclic, alarms A1 to A6 or digital inputs DI1 to DI4. The editing function is used for entering texts. Fig. 49 shows the function set for text, editing and condition.

5.5.3.1 T[20] Text, T[25] Editing, T[30] Condition

1) Only R40 version

Fig. 49 Summary of parameters Text Editing Condition


5.5.3.2 Programming text The editing function provides three characters per column in each of the columns 0 to 70. Selection of one of three characters is possible using the lower ranges of the fields 25.0 to 25.10 (1 to 3) for lower-case letters and 25.15 to 25.25 (SHIFT 1 to SHIFT 3) for upper-case letters.

Page 65

After setting line 25 Editing, select the character group which contains the desired letter. The LED flashes rapidly following ENTER. Then select one of three letters using the fields 25.0 to 25.25 and define upper-case or lower-case letters at the same time. The LED flashes more slowly following confirmation with ENTER, the selected character is printed, and the chart transported forwards until the character is visible. The next character can then be entered. Input of the alphanumeric characters is terminated using End. See Section 5.6.8 for setting example. Note An extended character set is accessible via the PC interface.

5.5.3.3 Instrument text The instrument text is used for user-specific identification of recorders, eg. in order to permit differentiation between several recorders in a larger plant. The instrument text consists of the actual text (max. 20 characters), the date and time. The output is made when the recorder is started, at 12 a.m., 12 p.m., and when the recording is stopped (lever 1 , PAUSE). 5.5.3.4 Event text The event text provides information which supports the application, eg. as a note to the operating personnel. Up to five different event texts can be programmed. An event text consists of the actual text (max. 20 characters) and the time. With the condition Cyclic, the texts are output every 20mm in ascending order up to a chart speed of 120mm/h. The texts are output at intervals of 40mm in the case of higher chart speeds. The event text can only be output depending on events (cyclic, alarm, DI1 to DI4). Event texts are stored in intermediate memory to prevent overwriting of one another. The format of an event text is shown in Fig. 56 Example recording for R40 version. 5.5.4 Clock (only R40 version) 5.5.4.1 T[35] Clock: Mode, T[40] Hours: hh, T[45] Minutes: mm, T[50] Day: DD, T[55] Month: MM, T[60] Year: YY The R40 version has an adjustable clock. You can select either a 24 or 12 hour format. It is possible to synchronise and switch over the clock if required via the digital input/output option, control input DI4, using an external signal q Clock synchronization 3:00 q Summer time (MESZ). Further information can be found in Section 5.6.10. In the event of a power failure, the clock component is buffered by a capacitor for approx. 5 minutes. A battery is required for longer backup times and can be ordered as an accessory (Section 8). It is not included in the basic instrument. When setting the clock, the seconds are set to zero with ENTER following each input, and the clock started. To permit inputs exact to the minute even if the parameterization procedure takes >1 minute, the minutes input should be entered last. The adjustable values are shown in Fig. 50. Section 5.6.9 shows an example for setting the clock.

Page 66

1) Only R40 version

Fig. 50 Summary of parameter Clock


5.5.5 Control input DI4 The following functions of the recorder can be remote-controlled via the interface Digital input/output (option) using control input DI4: q Chart feed q Time marker q Clock synchronization q Summer/winter time switchover q TEST locking. None of the above functions is activated in the position OFF. 5.5.5.2 Chart feed With the setting Chart feed 10 ... 100mm, a corresponding chart feed is carried out when the signal at control input DI4 changes from Low to High. With the alphanumeric text function switched on (Section 5.6), the device text is additionally inserted with the R40 version. The chart feed initiated via control input DI4 has the highest priority and is always carried out independent of the current recorder status. 5.5.5.1 T[65] Control input DI4

Page 67

5.5.5.3 Time marker The setting Time marker is used to synchronise several recorders operating as slaves. A time marker can be written at the same time on several instruments when the signal changes from Low to High at DI4. A zero adjustment is carried out in addition. The following Figure shows an example.
P[85.30]: Alarm, mode Time marker T[10.35] Diagram, Cycle, 1 h T[65.85]: Control input DI4, Time marker T[10.40] Diagram, Cycle, 2 h

Master Alarm, Time marker Control input DI4, Time marker

Slave

Slave

Control input DI4, Time marker

Digital input/output interface

Fig. 51 Example of time marker and synchronization for several recorders


A higher value should be set for the time marker on the slave than on the master. If OFF is selected for the time marker, only a zero adjustment is carried out. A marker is additionally drawn at the right edge of the chart in the case of all other settings. Synchronization can also be carried out using any other suitable clock generator (eg. master clock with hours signal). See Section 5.6.10 for setting example. 5.5.5.4 Clock sync. 3:00 (only R40 version) The setting Clock sync. 3:00 is used to synchronise the internal clock by means of a master clock signal and permits accurately timed operation of several recorders. The synchronization is carried out by a change in signal from Low to High at DI4. The internal clock is set to 3:00 hours independent of summer or winter time. 5.5.5.5 Summer time (MESZ) (only R40 version) The time is increased by one hour with the setting Summer time if the signal level is High at control input DI4. 5.5.5.6 TEST locking With the setting TEST locking, q the complete TEST menu is locked if the signal level is Low at control input DI4. q the complete TEST menu is unlocked if the signal level is High at control input DI4. The possible settings for control input DI4 are shown in Fig. 52.

Page 68

Fig. 52 Summary of parameter Control input DI4


5.5.6 Language (only R40 version) The setting Language permits selection of the language for printout of the recorder settings and error messages. Three languages can be selected. Fig. 52 shows a summary of the parameter Language. 5.5.6.1 T[70] Language

Fig. 53 Summary of parameter Language


See Section 4.7.11 for setting example. 5.5.7 PROG Locking You can use the PROG locking to protect the recorder programming from unauthorized or unintentional interventions. In the setting Stage 1, only changing the chart speed A (P[0]) is enabled. The PROG menu is completely disabled in Stage 2. For unlimited access to the PROG menu, select the setting OFF. Fig. 54 shows the possible settings.
Page 69

5.5.7.1 T[75] PROG locking

Fig. 54 Summary of parameter PROG locking


See Section 5.6.12 for setting example. 5.6 Parameterization examples The following examples will help you to parameterize the recorders. Similar cases can be easily implemented using the examples by slightly changing the parameters. In addition, further examples are present in the leaflet Operation - a concise overview. 5.6.1 Setting the chart speed Example: chart speed A = 300mm/h, condition is alarm A5
No. 1 2 3 4 5 6 7 8 9 10 INC DEC ENTER PROG INC DEC ENTER INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 PROG Lever 4 Description/feedback Switch on PROG menu. Red LED lights up (row input). Set row 0 (chart feed A). Confirm input. Red LED flashes (column input). Set column 40 (300 mm/h). Confirm input. Red LED lights up (row input). Set line 5 (condition). Confirm input. Red LED flashes (column input). Set column 50 (alarm A5). Confirm input. Switch off PROG menu.

Page 70

5.6.2

Setting the output of the measured-value table Example: print measured-value table cyclically every 4h
No. 1 2 3 4 5 6 INC DEC ENTER PROG INC DEC ENTER Lever 1 Lever 3 PROG Lever 4 Description/feedback Switch on PROG menu. Red LED lights up (row input). Set row 20 (measured-value table). Confirm input. Red LED flashes (column input). Set column 20 (cyclic 4h). Confirm input. Switch off PROG menu.

5.6.3

Parameterizing the analog channel Parameterization of a channel always commences with the channel number (row 25) and ends with the setting for the damping (row 65). The following example is shown accordingly. Example: q Channel number: 2 q Mode: recording q Measuring range: RTD q Sensor: Pt 100 q Connection: three-wire q Left value: from presetting +0C to 100C q Right value: presetting +500C (no input necessary) q Open-circuit: at >100% q Damping: 1s Channel number
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 PROG Lever 4 Description/feedback Switch on PROG menu. Red LED lights up (row input). Set row 25 (analog channel). Confirm input. Red LED flashes (column input). Set column 5 (#2). Confirm input.

Page 71

Mode
6 7 8 9 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 30 (mode). Confirm input. Red LED flashes (column input). Set column 10 (recording). Confirm input.

Measuring range
10 11 12 13 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 35 (measuring range). Confirm input. Red LED flashes (column input). Set column 50 (RTD). Confirm input.

Sensor
14 15 16 17 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 40 (sensor). Confirm input. Red LED flashes (column input). Set column 50 (Pt100). Confirm input.

Connection
18 19 20 21 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 45 (connection). Confirm input. Red LED flashes (column input). Set column 55 (three-wire). Confirm input.

Page 72

Set left value of +0000.C (default setting) to 0100.C (user)


22 23 24 25 26 27 28 29 30 31 32 33 34 35 INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 50 (left value). Confirm input. Red LED flashes (column input). Set column 60 (): (0000.). Confirm input. Red LED flashes rapidly (Subsequent input for columns). Set column 45 (0): (0000.). Confirm input. Red LED flashes rapidly (Subsequent input for columns). Set column 0 (1): (0100.). Confirm input. Red LED flashes rapidly (Subsequent input for columns). Set column 45 (0): (0100.). Confirm input. Red LED flashes rapidly (Subsequent input for columns). Set column 45 (0): (0100.). Confirm input. Red LED flashes rapidly (Subsequent input for columns). Set column 50 (.): (0100.). Confirm input.

Signal open-circuit at >100%


36 37 38 39 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 60 (open-circuit). Confirm input. Red LED flashes (column input). Set column 10 (>100%). Confirm input.

Damping 1s
40 41 42 43 44 INC DEC ENTER PROG INC DEC ENTER Red LED lights up (row input). Set row 65 (damping). Confirm input. Red LED flashes (column input). Set column 10 (1s). Confirm input. Switch off PROG menu.

Page 73

5.6.4

Parameterizing the digital channel Parameterization consists of definition of the channel number (row 70) and selection of a data source to be recorded (alarm A1 to A6, DI1 to DI4). Example: q Channel number: #2d q Recording: DI1 Channel number
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 PROG Lever 4 Description/feedback Switch on PROG menu. Red LED lights up (row input). Set row 70 (digital channel). Confirm input. Red LED flashes (column input). Set column 5 (#2d). Confirm input.

Recording DI1
6 7 8 9 10 INC DEC ENTER PROG INC DEC ENTER Red LED lights up (row input). Set row 75 (recording). Confirm input. Red LED flashes (column input). Set column 35 (input DI1). Confirm input. Switch off PROG menu.

5.6.5

Parameterizing the alarms Parameterization consists of the alarm number (A1 to A6), mode, channel number and value, ie. % position on chart paper. Example: q Alarm: A4 q Mode: MAX q Channel: #2 q Value: 85% of recorded value Alarm
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 PROG Lever 4 Description/feedback Switch on PROG menu. Red LED lights up (row input). Set row 80 (alarm). Confirm input. Red LED flashes (column input). Set column 15 (alarm A4) Confirm input.

Page 74

Mode
6 7 8 9 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set column 85 (mode). Confirm input. Red LED flashes (column input). Set column 15 (MAX). Confirm input.

Channel
10 11 12 13 INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 90 (channel). Confirm input. Red LED flashes (column input). Set column 5 (#2). Confirm input.

Value
14 15 16 17 18 INC DEC ENTER PROG INC DEC ENTER Red LED lights up (row input). Set row 95 (value). Confirm input. Red LED flashes (column input). Set position 85%. Confirm input. Switch off PROG menu.

5.6.6

Parameterizing the measuring mode Parameterization consists of setting the cycle time, where control is possible via DI1. Example: q Measuring mode: input DI1, fast Measuring mode
No. 1 2 3 4 5 6 INC DEC ENTER TEST INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 0 (measuring mode). Confirm input. Red LED flashes (column input). Set column 20 (input DI1, fast). Confirm input. Switch off TEST menu.

Page 75

5.6.7

Parameterizing the diagram (only R40 version) Parameterization consists of setting the alphanumeric function on/off, suppressing the time marker at the left edge, switching the START/STOP text off, setting the cycle time for alphanumeric outputs and the grid on/off. Example: q Diagram: time marker: date q Cycle: 6 h Diagram: time marker: date
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 5 (diagram). Confirm input. Red LED flashes (column input). Set column 10 (time marker: date). Confirm input.

Cycle: 6 h
6 7 8 9 10 INC DEC ENTER TEST INC DEC ENTER Red LED lights up (row input). Set row 10 (cycle). Confirm input. Red LED flashes (column input). Set column 55 (6h). Confirm input. Switch off TEST menu.

5.6.8

Parameterizing texts (only R40 version) Parameterization applies to the instrument text and five event texts. Output can be cyclic or linked to a condition. Example: q Text: event text 2 q Editing: temp. 80 q Condition: alarm A3 Event text
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 20 (text). Confirm input. Red LED flashes (column input). Set column 10 (event text 2). Confirm input.

Page 76

Editing
6 7 8 9 10 INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER IINC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 25 (editing). Confirm input. Red LED flashes (column input). Set column 35 (T U V). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 15 (SHIFT 1 (1st character, upper-case letter T)): (T). Confirm input. Red LED flashes (column input). Set column 10 (D E F). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 5 (2 (2nd character, lower-case letter e)): (Te). Confirm input. Red LED flashes (column input). Set column 25 (M N O). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 0 (1 (3rd character, lower-case letter m)): (Tem). Confirm input. Red LED flashes (column input). Set column 30 (P R S). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 0 (1 (4th character, lower-case letter p)): (Temp). Confirm input. Red LED flashes (column input). Set column 65 (. : *). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 0 (1 (5th character, decimal point)): (Temp.). Confirm input. Red LED flashes (column input). Set column 0 (space Q Z). Confirm input. Red LED flashes rapidly (subsequent input for columns ). Set column 0 (1 (6th character, space)): (Temp. ). Confirm input.

11 12 13 14

15 16 17 18

19 20 21 22

23 24 25 26

27 28 29 30

31

Page 77

32 33 34

INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER INC DEC ENTER

Red LED flashes (column input). Set column 55 (7 8 9). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 5 (2 (7th character 8)): (Temp. 8). Confirm input. Red LED flashes (column input). Set column 60 (0 # %). Confirm input. Red LED flashes rapidly (subsequent input for columns). Set column 0 (1 (8th character 0)): (Temp. 80). Confirm input. Red LED flashes (column input). Set column 75 (end). Confirm input.

35 36 37 38

39 40 41

Condition
14 15 16 17 18 INC DEC ENTER TEST INC DEC ENTER Red LED lights up (row input). Set row 30 (condition). Confirm input. Red LED flashes (column input). Set column 20 (alarm A3). Confirm input. Switch off TEST menu.

5.6.9

Parameterizing the time Parameterization permits setting of the time and date for 24h or 12h (am/pm) mode. Example: q Mode: 24-hour (already preset and need not be changed) q Hours: 13 q Day: 26. q Month: 04 q Year: 1995 q Minutes: 45

Page 78

Hours: 13
No. 1 2 3 4 5 6 7 INC DEC ENTER INC DEC ENTER Lever 1 INC DEC ENTER Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 40 (hours: hh). Confirm input. Red LED flashes (column input). Set column 0 (1): (1). Confirm input. Red LED flashes (column input). Set column 10 (3): (13). Confirm input.

Day: 26.
8 9 10 11 12 13 INC DEC ENTER INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 50 (day: TT). Confirm input. Red LED flashes (column input). Set column 5 (2): (2). Confirm input. Red LED flashes (column input). Set column 25 (6): (26). Confirm input

Month: 04.
14 15 16 17 18 19 INC DEC ENTER INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 55 (month: MM). Confirm input. Red LED flashes (column input). Set column 45 (0): (0). Confirm input. Red LED flashes (column input). Set column 15 (4): (04). Confirm input

Year: 95
20 21 22 23 24 25 INC DEC ENTER INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 60 (year: YY). Confirm input. Red LED flashes (column input). Set column 40 (9): (9). Confirm input. Red LED flashes (column input). Set column 20 (5): (95). Confirm input.

Page 79

Minutes: 45
26 27 28 29 30 31 32 INC DEC ENTER TEST INC DEC ENTER INC DEC ENTER Red LED lights up (row input). Set row 45 (minutes: mm). Confirm input. Red LED flashes (column input). Set column 15 (4): (13:4). Confirm input. Red LED flashes (column input). Set column 20 (5): (13:45). Confirm input Switch off TEST menu.

5.6.10

Parameterizing the control input DI4 Parameterization permits control of one of the following functions via DI4: chart feed, time marker, clock synchronization 3:00 hours, setting of summer time and locking. of TEST menu via digital input/output, DI4. Example: q Control input DI4: chart feed 50 mm Chart feed 50 mm
No. 1 2 3 4 5 6 INC DEC ENTER TEST INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 65 (control input DI4). Confirm input. Red LED flashes (column input). Set column 25 (chart feed 50 mm). Confirm input. Switch off TEST menu.

5.6.11

Parameterizing the language (only R40 version) Parameterization permits German, English or French as the language. Example: q Language: English
No. 1 2 3 4 5 6 INC DEC ENTER TEST INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 70 (language). Confirm input. Red LED flashes (column input). Set column 5 (English). Confirm input. Switch off TEST menu.

Page 80

5.6.12

Parameterizing the PROG locking Parameterization permits the setting of two locking stages. Example: q PROG locking: stage 2
No. 1 2 3 4 5 6 INC DEC ENTER TEST INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set row 75 (PROG locking). Confirm input. Red LED flashes (column input). Set column 10 (stage 2). Confirm input. Switch off TEST menu.

Section 6.

MEASURING AND RECORDING MODE

In measuring and recording mode, the measured values are displayed on the scales and recorded on the chart as an amplitude/time diagram. The parameters such as the chart speed are set in the PROG and TEST menus (Section 5). Measuring mode can be switched on and off in the TEST menu. Measuring mode is interrupted if you call the PROG or TEST menu. In measuring and recording mode, all channels for which measured-value acquisition is switched on are scanned cyclically, processed and documented on the chart paper by means of the recording system. Measured values are linearized if applicable and corrected using auxiliary values such as the terminal temperature and line resistance. Alarms are generated by comparing the measured values with the programmed limits. Buffer time The measured values pass through a buffer before they are recorded. This prevents values from being lost if there is an interruption in the recording procedure such as when changing the chart or pen. The measured values are increasingly compressed as the buffer becomes fuller in that min./max. values are generated. The capacity of the buffer corresponds to approx. 6mm of chart. A chart feed is carried out if the buffer capacity is exceeded, and the symbol for a buffer overflow =><= is printed out together with a chart switching line. 6.1 Chart formatting (only R40 version) You should preferably select the recording range (left value and right value) such that round values result on the measured-value lines. This facilitates evaluation of the chart and the determination of the absolute values of a curve. Programming of the left and right values is described in Section 5.5.3.

Page 81

6.1.1

Main time line (only R40 version) With a correctly set recorder, the time markers are written on the main time lines. The chart position can be adjusted in the PAUSE status such that the time markers coincide with the main time lines with a subsequent recording. After writing the start line (Section 6.1.5), the chart is shifted forwards such that the time markers are written on the time lines in the future. The chart now remains adjusted until the recording is interrupted by one of the following events: q PROG menu on q TEST menu on q Removal of chart carriage q Power supply on/off. The exact operations for setting the main time line are explained in Section 7.

6.1.2

Instrument text (only R40 version) An instrument text is output: q As part of the switch-on text q With time markers at 12.00 and 00.00 hours q When recording is stopped (lever 1 , PAUSE ON) The instrument text consists of up to 20 characters and can be freely programmed by the user (Section 5). An instrument text may be eg. the plant-specific name of the recorder.

6.1.3

Switch-on text (only R40 version) The switch-on text line consists of the date, time and instrument text. The line is printed when the power supply is switched on if measuring mode is not switched on. The instrument text consists of up to 20 characters and can be freely programmed by the user (Section 5).

6.1.4

Event text (only R40 version) An event text Fig. 56 Example recording for R40 version) can be printed out cyclically or dependent on events. Up to five event texts can be programmed with up to 20 characters each (Section 5) and assigned to the alarms. Possible trigger conditions are: q Cyclic q Alarms A1 ... A6 (with every change in edge) q Input DI1 ... DI4 (only with change in level from Low to High) The graphic recording is not interrupted when printing the event text. A further event text or a measured-value table is only printed if the chart feed has reached a full line height since the last text. This prevents overwriting. Event texts which are printed out cyclically consist only of the event text. Event texts which are controlled by a digital input are only printed out with a change in level from Low to High. They consist of the time exact down to seconds, and the instrument text. Event texts which are controlled by an UP or DOWN alarm consist of the time, alarm symbol, channel number assigned to the alarm, and event text. If the alarm is deactivated, the Alarm line is written as with an activated alarm, but without an event text. If the alarm is assigned to all channels, the total character appears instead of the channel number.

Page 82

The cyclic output of the event texts depends on the set chart speed. Chart speed 1 120 mm/h 300 1200 mm/h Output cycle Every 100 mm Every 200 mm Offset from text to text 20 mm 40 mm Offset from main time line 15mm 15mm

Table 12 Output cycle for event text


6.1.5 Start line (only R40 version) The start line (Fig. 56 Example recording for R40 version) appears each time the graphic recording has been interrupted and restarted. The line consists of the word START, date, time, chart speed and set measuring cycle. 6.1.6 Time markers (only R40 version) A time printout (Fig. 56 Example recording for R40 version) is made cyclically at the left edge of the chart depending on the chart speed. A horizontal marking line is printed as the first character followed by the date and time in hours and minutes. The date is printed with the first time printout after 12:00 and 00:00 hours. Either the 24-hour clock or the 12-hour clock can be used for the time printout. The intervals between the time markers depend on the set chart speed and are listed in the following table: Chart speed [mm/h] OFF 1 1.25 2.5 5 10 20 60 120 300 600 1200 6.1.7 Interval [mm] -12 10 10 10 10 20 20 20 50 100 200 h] -12 8 4 2 1 1 20 10 10 10 10 Time interval [min] --

Table 13 Interval between time markers


Limit line and alarm markers (only R40 version) Limit lines (Fig. 56 Example recording for R40 version) can be drawn parallel to the time axis. The lines are vertical and approx. 2mm long. The spaces of the dashed line are halved when an alarm occurs. The limit lines are written by the text channel. Section 5 describes the parameterization of these functions (MIN. or MAX. with line). The associated alarm status changes when the measured curve cuts the limit line. The symbol, alarm number, channel number or are written cyclically next to the limit line.
Page 83

Note that there is a time offset between the measured curves and the inscription of the limit line. 6.1.8 Measured-value table (R40 version) A measured-value table (Fig. 56 Example recording for R40 version) can be printed out cyclically or event-controlled. Only measured values are printed for channels for which the mode Measure or Record has been selected. Possible trigger conditions: q Cyclically every 1, 2, 3, 4, 12 hours q Alarms A1 to A6 q Inputs DI1 to DI4 The graphic recording is not interrupted when printing the measured-value table, ie. the 2nd and 3rd lines are only printed if the chart feed has reached a full line height since the last line. If a further trigger function for a measured-value table or an event text arrives whilst a table is being printed, this is only commenced when the table has been completely printed and the chart feed has reached a full line height since the last line. The printout of the measured-value table always coincides with a time marker if it is carried out cyclically. The first line of the measured-value table is omitted in this case (reading direction: from bottom to top). The information of an analog channel comprises (from left to right): q Channel number, eg. #3 q Measured value with sign q Dimension of parameterized measuring range q Symbol for open-circuit if applicable q Symbols of alarms assigned to the channel The information of a digital channel comprises (from left to right): q Channel number with code letter d for digital q Measured value 0 for Low or 1 for High 6.1.9 Grid (only R40 version) Function in preparation! The text channel (R40 version) can be used to print a grid on (preferably) unprinted paper. The interval between the grids depends on the chart speed. The grids are synchronised with the time markers and independent of the starting time for recording. The grid crosses at 20, 40, 60 and 80% are omitted if q a recorder text is written at 12 a.m. and 12 p.m., and q a measured-value table is printed and q an event text is printed. At a high chart speed, the markers are no longer on a time line, they are written oblique. With a chart speed from 300 to 1200mm/h, only the 0% and 100% markers are written.

Page 84

6.1.10

Priorities of text outputs The printing of texts is triggered cyclically or event-controlled. The texts are printed in chronological order. If several texts are waiting to be printed, the print messages are buffered and the printout of the next text line delayed so that the texts can be printed without overwriting. A congestion of printer messages may occur if a large number of texts occurs within a short time or large time intervals exist between the text lines because of a slow chart speed. The recorder carries out the following measures in order to avoid a buffer overflow in the event of congestion: q If the buffer for print messages is close to overflowing, the printing of texts is not delayed until they do not overwrite one another. q Texts which are triggered cyclically and which only contain redundant information are delayed, or omitted if texts with a higher priority are present during a complete cycle. q Texts are printed out in abbreviated form. The texts are always abbreviated if the printing of a further text with a higher priority is also present. The following priority list applies: High priority
v

Switch-on line START line Chart switching line Edge of digital channel Grid Time mark Event-controlled measured-value table Event-controlled event text Event-controlled time mark and carriage adjustment Cyclic measured-value table Cyclic event text Cyclic carriage adjustment Cyclic limit lines

Low priority

Cyclic digital channel lines

Time markers and edges of digital channels are exceptions for two reasons: Time markers and edges of digital channels are printed without being delayed, ie. they can be printed over other texts. If a time marker or a digital channel edge occurs whilst printing a text, the text is only interrupted and not aborted. 6.1.11 Configuration data (only R40 version) The set configuration data can be printed if required. Printing is triggered using the PROG menu [100,10] . Fig. 55 shows an example of a printout.

Page 85

PROG locking Language Control input Time Condition Text5 Condition Text4 Condition Text3 Condition Text2 Condition Text4 Condition Text1 Instrument text Grid Cycle Diagram Measuring mode Value Channel Operating mode Alarm Value Channel Operating mode Alarm Value Channel Operating mode Alarm Recording Channel Damping Open-circuit Right value Left value Connection Sensor Measuring range Mode Channel Measured-value table Condition Chart feed PROG

OFF English OFF 10. 01. 85 04 : 40 53 OFF ...................................... OFF ...................................... OFF T3.................................. OFF T2.................................. OFF T4.................................. OFF T1.................................. Hello Word! OFF 1h Alphanumeric ON Normal OFF A5 OFF A5 OFF A3 OFF #1d 0s 4/20mA Recording #1 Input DI1 /Input DI2 A: 120mm/h 10.01.85 04:1617 OFF A6 OFF A6 OFF A4 Alarm A1 #2d 0s 4/20mA Recording #2 Input DI2 B: 1200mm/h 0s 4/20mA Recording #3

Fig. 55 Example of configuration data (R40 version)

Page 86

6.1.12

Error messages and Status messages (only R40 version) The following error messages and status messages are printed on the chart: No. 1 2 3 4 5
1)

Error/status message EPROM (program memory) defective EEPROM missing or defective EEPROM initialized or corrected EEPROM copied Check backup battery

Remarks Inform servicing department Inform servicing department


1) 2) 3)

No configuration data have yet been stored, or the stored data did not correspond to the recorder configuration and have therefore been corrected. Status message for servicing department. Following return of the power supply, the clock has been reset to 01.01.85 00:0000 with the MEZ setting or 01:0000 with the MESZ setting. This must be changed when using a battery. The clock must be newly set.

2) 3)

Further error messages and status messages are output on the LEDs (Table 4). 6.2 Example recording with explanations Fig. 56 shows an example recording for the R40 version. The same example basically applies to the R30 version, but without text outputs and recording of the digital channels.

Page 87

Fig. 56 Example recording for R40 version

Page 88

Section 7.

SERVICING AND MAINTENANCE

This chapter describes servicing and maintenance. The work described must only be carried out by trained specialists. Note 7.1 An arrow, eg. Lever 1 is used to simplify the description. In this context the arrow means: Move lever 1 to right.

Removing the chart carriage The chart carriage (Fig. 59 and Fig. 61) must be removed from the recorder in order to replace the chart. PAUSE ON must be selected if the measured values are to be stored in intermediate memory whilst the chart is being replaced. Proceed as follows: Step 1 2 3 4 Measure Open door. Lever 1 PAUSE ON (stop recording). The pens are moved to the PAUSE status (Fig. 63). Lever 2 release chart carriage. Pull chart carriage out to front using grip (Fig. 61).

1 2 3 4

Take-up spool 1) Chart guide Pin wheel with transport roller Transport roller
1)

5 6 7 8 Used only with rolls

Curved flap Chart supply through Guide tongue 1) Front flap

Fig. 57 Front and rear views of chart carriage (without chart paper)

Page 89

7.2

Inserting the chart carriage Proceed as follows to replace the chart carriage into the recorder following replacement of the chart: Step 1 2 3 4 Measure Insert chart carriage into chassis. Press on the grip to push the chart carriage completely into the recorder until it latches in place. Set the main time line (Section 7.3). Lever 1 PAUSE OFF (start recording).

7.3

Setting the main time line The position of the chart can be adjusted when in the PAUSE status so that the time markers coincide with the main time lines during the subsequent graphic recording. This setting is always necessary: q Following parameterization q If the chart carriage has been removed from the chassis, eg. in order to replace the chart q When the recorder has been switched on/off Step 1 2 3 Measure Open door Lever 1 PAUSE ON (stop recording). The carriage moves to the maintenance position (Fig. 63). Lever 3 activate chart high-speed until a time line is positioned underneath the knobs which are present on the rear of the adjustment scale (Fig. 58). Lever 1 PAUSE OFF (start recording).

Fig. 58 Adjustment scale with knobs

Page 90

7.4

Removing a fanfold pack The steps required to remove the fanfold pack from the chart carriage are described below. Step 1 2 3 4 5 6 7 Measure Open door Lever 1 PAUSE ON (stop recording). Use lever 3 (chart high-speed) to transport the chart forwards until the desired position has been reached. Lift up the front flap of the chart carriage and swing out. Hold fanfold pack in the middle and remove. Tear off along the perforation in the case of a daily chart record. Swing back front flap and latch in place. Use lever 3 chart high-speed) to transport the chart paper forwards until at least one sheet with the preferred fold direction lies flat on the floor of the chart carriage. 1) Set the main time line (see Section 7.3). 1) Lever 1 PAUSE OFF (start recording). 1)

8 9
1)

When removing the daily chart record

7.5

Inserting a fanfold pack When inserting fanfold paper, observe the symbols on the intermediate plate of the chart supply trough. Step 1 2 3 4 5 6 7 Measure Remove chart carriage as described in Section 7.1. If necessary, remove the guide tongue (Fig. 57, Item 8) according to Section 7.12 and take out the take-up spool (Fig. 57, Item 1). Swing up the curved flap (Fig. 57, Item 5). Insert fanfold pack horizontally into the chart supply trough such that the longitudinal perforation is on the right when viewed from the front. Pull up three or four sheets of chart, swing back the flap and latch in place. Swing the chart guide (Fig. 57, Item 2) to the front. Pull the chart paper underneath the chart guide and place onto the pins of the transport roller (Fig. 57, Item 4). The time lines of the chart paper must be parallel to the chart guide. Press down chart guide. Transport the chart paper forwards by rotating on the wheel of the transport roller until at least one sheet with the preferred fold direction lies flat on the floor of the chart carriage. Insert chart carriage according to Section 7.2.

8 9

10

Page 91

Fig. 59 Chart carriage (equipped with fanfold paper)


7.6 Removing a chart roll Step 1 2 3 4 5 6 7 8 9 10
1)

Measure Open door Lever 1 PAUSE ON (stop recording). Use lever 3 chart high-speed) to transport the chart forwards until the desired position has been reached. Lift up the front flap of the chart carriage and swing out. Remove the take-up spool (Fig. 57, Item 1). When removing a daily chart record, cut off the chart using scissors. Remove the black flange of the take-up spool, then remove the roll from the mandrel. Replace flange and insert take-up spool. Swing back front flap and latch in place. Use lever 3 (chart high-speed) to transport the chart forwards until the beginning is grasped by the take-up spool. 1) Set the main time line (see Section 7.3). 1) Lever 1 PAUSE OFF (start recording). 1)

When removing the daily chart record

Page 92

7.7

Inserting a chart roll When inserting a roll, observe the symbols on the intermediate plate of the chart supply trough. Step 1 2 3 4 5 6 7 8 Measure Remove chart carriage as described in Section 7.1. If necessary, insert the guide tongue according to Section 7.13. Observe the note at the end of this table. Swing up the curved flap (Fig. 57, Item 5). Insert roll into the chart supply trough such that the longitudinal perforation is on the right when viewed from the front (Fig. 61). Pull out beginning of chart paper, and swing back the curved flap again. Swing the chart guide (Fig. 57, Item 2) to the front. Pull the chart paper underneath the chart guide and place onto the pins of the transport roller (Fig. 57, Item 5). The time lines of the chart paper must be parallel to the chart guide. Press down chart guide. Lift up the front flap (Fig. 57, Item 8) of the chart carriage and swing out. Insert the take-up spool (Fig. 57, Item 1) into the chart carriage such that the black flange of the take-up spool is on the right side when viewed from the front. Press the take-up spool into the chart carriage until the pins slide into the bearings. Swing back the front flap and latch in place. The teeth then fit into the take-up spool again. Transport the chart paper forwards by rotating the wheel of the transport roller until the beginning of the paper is grasped by the take-up spool. Insert chart carriage according to Section 7.2.

9 10 11

12 13 14

15

Note

The side edges of the roll must be flat. If necessary, place the roll on a flat surface with the concave edge downwards and press the convex end flat (Fig. 60).

Page 93

Fig. 60 Preparation of chart roll

Fig. 61 Chart carriage (equipped with roll)

Page 94

7.8

Moving chassis into maintenance position The chassis must be moved to the maintenance position to permit replacement of the pens and scales. Step 1 Measure Press the service lever to the left using your left index finger, simultaneously grab the front flap of the chart carriage (Fig. 57, Item 8) at the bottom right using your right index finger and thumb, and pull out of the latched position. When released, pull on the left and right of the front flap until the chassis latches into the maintenance position.

Fig. 62 Releasing the chassis

Page 95

Fig. 63 Chassis in maintenance position, pens in PAUSE status


7.9 Returning chassis from maintenance position Step 1 Measure Push service lever to left using your left thumb, and push back the chassis on the left and right using your index fingers in the vicinity of the knurled wheels (at top of chart carriage) until the chassis latches in place.

7.10

Removing chassis from housing The chassis must be completely removed from the housing eg. to replace the battery for backing up the clock. Step 1 2 Measure Move chassis into maintenance position according to Section 7.8. Loosen the chassis from the maintenance position by again pressing and simultaneously pulling to the front out of the the service lever housing. If necessary, disconnect the plug of the ribbon cable between the chassis and the basic electronics.

Note

The chassis contains modules on which electrostatic sensitive devices are present. Observe the ESD guidelines!

Page 96

Fig. 64 Chassis removed, view onto rear


7.11 Inserting chassis into housing Step 1 Measure If the chassis has been disconnected from the basic electronics, reconnect the plug of the ribbon cable to the chassis. Observe the note at the end of this table. Insert chassis into housing up to maintenance position. The chassis latches into this position. Move service lever and push chassis completely into the rear mounting position. It latches in at this position.

2 3

Note

You must always compare the serial Nos. on the chassis and on the rating plate in the housing before inserting the chassis. Chassis from different recorders must not be interchanged.

7.12

Removing the guide tongue The guide tongue (Fig. 57, Item 7) must be removed when using fanfold paper. Step 1 2 3 Measure Remove chart carriage as described in Section 7.1. Lift up the front flap of the chart carriage and swing out. Remove the take-up spool. Place the chart carriage onto its rear. Hold the guide tongue using your index finger and thumb. Press onto the latch of the guide tongue using eg. a ball-point pen and carefully pull out the tongue. Insert chart carriage according to Section 7.2.

Page 97

7.13

Inserting the guide tongue The guide tongue (Fig. 57, Item 7) must be fitted for use with rolls. The tongue is inserted into the base of the chart carriage. Step 1 2 3 4 Measure Remove chart carriage as described in Section 7.1. Lift up the front flap of the chart carriage and swing out. Remove the chart paper. Insert the wide end of the tongue into the opening in the base of the chart carriage until the latch of the tongue fits in place. Insert chart carriage according to Section 7.2.

7.14

Labelling and inserting the measuring-point label Step 1 2 3 Measure Bend the measuring-point label and pull out of the lateral guides of the door. Label the corresponding lines with the channel inscriptions. Bend the label and latch into the lateral guides.

7.15

Replacing the pens for the analog channels Step 1 2 3 Measure Use lever 1 PAUSE ON (stop recording). The pens move to the PAUSE status (Fig. 63). Move chassis to maintenance position according to Section 7.8. Lift up the scale above the pen, hold the pen on the pointer and pull out of the carriage fork. The pens of the upper channels can be removed to permit easier handling. Plug on new pen. Note: Never bend the pointer of the pen! Lower scale. Insert chassis according to Section 7.11. Lever 1 PAUSE OFF (start recording)

4 5 6 7 Note

Channels which are not used for recording must be equipped with a special dummy pen.

Page 98

7.16

Replacing the pen for alphanumeric text (only R40 version) Step 1 2 3 Measure Use lever 1 PAUSE ON (stop recording). The pens move to the PAUSE status (Fig. 63). Move chassis to maintenance position according to Section 7.8. Lift up the bottom scale, hold the pointer of the alphanumeric text pen and pull out of its latch. The pens of the analog channels can be removed to permit easier handling. Plug on new pen. Lower scale. Insert chassis according to Section 7.11. Lever 1 PAUSE OFF (start recording)

4 5 6 7 7.17

Replacing the scale Step 1 2 3 4 5 6 7 8 Measure Use lever 1 PAUSE ON (stop recording). The pens move to the PAUSE status (Fig. 63). Move chassis to maintenance position according to Section 7.8. Remove all pens above the scale to be replaced as described in Section 7.15. Remove the scale at the left and right from its support. Plug new scale onto support and latch in on both sides. Insert pens according to Section 7.15. Insert chassis according to Section 7.11. Lever 1 PAUSE OFF (start recording)

7.18

Replacing the battery (only R40 version) The battery can be replaced during operation. Disconnection from the power supply is possible for up to approx. 5 min without the time being lost. Step 1 2 3 4 5 6 Measure Use lever 1 PAUSE ON (stop recording). The pens move to the PAUSE status (Fig. 63). Move chassis to maintenance position according to Section 7.8. Remove battery from holder (Fig. 64) and dispose of in correct manner. Connect the battery with the correct polarity! Insert chassis according to Section 7.11. Lever 1 PAUSE OFF (start recording)

Page 99

7.19 7.19.1

Adjustment, test prints, carriage/text positions Adjustment When adjusting the measuring ranges, a reference value is determined for the individual ranges of the input amplifier using external signals and stored in a nonvolatile data memory. Note The measuring ranges have been adjusted by the manufacturer prior to delivery. A new adjustment, should this be necessary, must only be carried out using suitable calibrators.

7.19.1.1 T[80] Adjustment: Range, T[85] Channel

You require a signal generator or resistance transmitter in order to carry out an adjustment. Connect the source to the signal input terminals. The error of the signal generator or resistance transmitter is included as an additional error in the result of the recorder. Except for 20mA and 10V, the measuring ranges can be adjusted using any channel. Therefore connect the signal generator or resistance transmitter to the input terminals of the associated channel or to all input terminals. Connect the jumpers as in Fig. 14. If the recorder is only used in the range setting you have selected, adjustment of the unused ranges is unnecessary. The setting Adjustment and its subsequent settings support adjustment of the measuring ranges. The adjustment is carried out by setting the measuring range and the channel assignment. If an adjustment is required for each channel, this can be carried out for the individual channels or for all channels together. The field Adjust is subsequently set, and the set measuring range is automatically adjusted (Fig. 65).

Only R40 version

Fig. 65 Summary of parameter Adjustment and subsequent settings

Page 100

Input ranges 1V

Measuring ranges 0/1V 0.2/1V 1V 0/10V 2/10V 10V 0/20mA 4/20mA 20mA

Required adjustment 0V 1V 0V 10V 1) 0V (0mA) 20mA 1)

10V

20mA

1)

Adjustment required for each channel

Table 14 Adjustment required for dc U/I version


Input ranges 1V Measuring ranges 0/1V 0.2/1V 1V 0/10V 2/10V 10V 0/20mA 4/20mA 20mA U, TC U, TC U, RTD, R, Pot. U, RTD, R, Pot. TC, RTD, R, Pot. RTD, R, Pot. RTD, R, Pot. Required adjustment 1V

10V

10V 1)

20mA

20mA 1)

Direct connection

40mV 100mV 400mV 1V 0V 400 1000

1)

Adjustment required for each channel

Table 15 Adjustment required for dc U/I/TC/RTD/R version

Page 101

7.19.2

Carrying out the adjustment The measuring range, channel number and start of automatic adjustment are set by parameterizing. Example: q Range: 20mA q Channel: 3 Range: 20mA
No. 1 2 3 4 5 INC DEC ENTER INC DEC ENTER Lever 1 Lever 3 Lever 4 TEST Description/feedback Switch on TEST menu. Red LED lights up (row input). Set line 80 (Adjustment: Range). Confirm input. Red LED flashes (column input). Set column 5 (20mA). Confirm input.

Adjust channel 3
6 7 8 9 10 11 12 13 INC DEC ENTER TEST INC DEC ENTER ENTER INC DEC ENTER Red LED lights up (row input). Set line 85 (Channel). Confirm input. Red LED flashes (row input) Set line 10 (#3). Confirm input. Confirm input. Red LED flashes (column input). Set column 30 (Adjust) Confirm input. Switch off TEST menu.

7.19.3

Test print Following maintenance and adjustment, you can check the settings and status of the recording systems using test prints. In addition, the test prints are an important aid during troubleshooting. Test print 1: q A step recording is carried out for each analog channel in steps of 10%. No automatic abort. Purpose: checking of linearity and hysteresis. Correct setting under Maintenance, carriage position 1...3 (Section 7.19.4) is a requirement. Test print 2: q A simultaneous and alternating 0% and 100% recording is carried out for all channels. No automatic abort. Purpose: checking of pen offset between individual channels and checking of setting Maintenance, carriage position 1...3.
Page 102

7.19.3.1 T[90] Test print

Test print 3: q Output of a complete character set (text channel). Purpose: checking of text output. Test print 4: q Output of rectangular recordings. Purpose: checking of linearity and hysteresis with different triggering modes. No automatic abort (text channel). Test print 5 to 10: q Not used. Fig. 66 shows the possible settings for the parameter Test print.

Fig. 66 Summary of parameter Test print

Page 103

7.19.4

Maintenance Six settings are available for maintenance purposes. The recording systems can be set to the 0% and 100% lines using Carriage position 1 to Carriage position 4. The setting can be used eg. to adapt the recording system to the chart which has changed as a result of climatic influences. The setting is limited. You should inform the servicing department if the 0% or 100% line cannot be reached using the maintenance facilities. The setting Text position is used to change the space between the pens of the analog channels and the pen of the text channel (only R40 version) (see example on next page). The setting procedure for the recording systems is terminated by End. The possible settings are shown in Fig. 67.

7.19.4.1 T[95] Maintenance

Fig. 67 Summary of parameter Maintenance

Page 104

7.19.4.2 Setting example for text channel The vertical spacing between the pens of channel 1 and the pen of the text channel is typically 7 mm. The exact spacing must be determined in an adjustment procedure and stored in the EEPROM. To do this, select the menu item Maintenance - Text position in the TEST menu.

Fig. 68 Example of text position for text channel: spacing from measuring channel pens
7.19.5 Service The setting Service provides extended setting possibilities but requires additional knowledge. The setting is therefore reserved for the servicing department. 7.19.5.1 T[100] Service

Page 105

Section 8.
Note

TECHNICAL DATA
Only values with tolerances or limits are guaranteed data. Values without tolerances are informative data without guarantee obligation. The defined error limits apply following a warming-up time of 30 minutes.

Measuring functions general data Error in measurement Number of channels Channel isolation Voltage endurance Permissible potential Class 0.5 to DIN 43782 or IEC 484 1, 2 or 3 Electrically isolated via semiconductors See Table 3, protected with varistors from protective earth conductor Max. dc 24V compared to PE conductor; only measuring circuits with safe isolation from power supply are permissible Max. 10% of respective full-scale value Max. 24V continuously in dc U range Max. 50mA continuously in dc I range A/D conversion Resolution Common-mode rejection Series-mode rejection Reference conditions Ambient temperature Relative humidity Source resistance Potential difference Adjustment interval Damping Signal connection (23 2)C (55 10)% 1k 1V 12 months; an additional error of 0.01%/year must be expected with a longer interval 1st order low-pass, 0, 1, 3, 10, 30, 100s or automatic adaptation to chart speed 2 (standard design) or 3 (universal design) screw terminals per channel 0.13 to 2.5mm2 solid conductor 0.13 to 1.5mm2 stranded conductor with sleeves Terminal designations to DIN 45140 One common dual-slope converter 14 1/2 bits/13 1/2 bits with normal/fast 90dB at 47 to 64Hz 60dB at 50.0Hz/60.Hz

Input overload Overload

Page 106

R30 version Measuring ranges Input resistance Measuring mode Measuring cycle Measuring duration Tolerance
Measuring range Resolution Meas. mode normal 1) Graphic

According to Table 11 100k in the dc U range 50 in the dc I range Normal Fast 240ms 150ms

40ms (50Hz), 331/3ms (60Hz) with normal 20ms (40Hz), 16 2/3ms (60Hz) with fast See Table 16
Maximum (typ. 1/3) electric measuring error2) Fel = Foffset + Frel + Ftemp Foffset % Frel MV 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 Ftemp Reference value (23+2)C (% MV + const) /C

1 to +1V 0 to +1V 0.2 to +1V 10 to +10V 0 to +10V +2 to +10 20 to +20mA 0 to +20mA +4 to +20mA
1)

0.1mV 0.1mV 0.1mV 1mV 1mV 1mV 2A 2A 2A

0.6mV 0.6mV 0.6mV 6mV 6mV 6mV 12A 12A 12A

0.03 + 0.02mV 0.03 + 0.02mV 0.03 + 0.02mV 0.03 + 0.2mV 0.03 + 0.2mV 0.03 + 0.2mV 0.03 + 0.5A 0.03 + 0.5A 0.03 + 0.5A

Measuring mode normal

The specified values apply to measuring mode normal, they must be doubled for measuring mode fast; the offset error Foffset becomes approx. 30% larger

2)

Measuring error Foffset Frel Zero error Increasing error Absolute value specified in table Percentage specified in table multiplied by the value of the read measured value (% MV ) Percentage specified in table multiplied by the value of the read measured value (% MV ) plus a constant (const) specified as an absolute value, total multiplied by the value of the temperature difference between the reference value (23 2)C and the ambient temperature

Ftemp

Temperature error at increased ambient temperature

Table 16

Measuring ranges for standard design

Page 107

R40 version Measuring ranges Input resistance According to Table 12 10M in the TC/dc U range at 1000mV 100k in the dc U range at 1V and 10V 50 in the dc I range Tolerance Measuring mode Measuring cycle Measuring duration Normal Fast 300ms 180ms See Table 17

40 ms (50Hz), 33 1/3ms (60Hz) with normal 20 ms (40Hz), 16 2/3ms (60Hz) with fast

Type of connection for resistance measurements


Measuring range (linearization range)4) Resolution Meas. mode normal 1) Graphic

Two-wire or three-wire system

Maximum (typ. 1/3) electric measuring error2) Fel = Foffset + Frel + Ftemp + Fterminal Foffset Frel % MV Ftemp Reference value (23 2)C (% MV + const) /C 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mV 0.02 + 0mA 0.02 + 0mA 0.02 + 0mA 0.02 + 0C Fterm C 0.6

40 to +40mV 100 to +100mV 400 to +400mV 1000 to +1000mV 1 to +1V 0 to +1V 0.2 to +1V 10 to +10V 0 to +10V +2 to +10 20 to +20mA 0 to +20mA +4 to +20mA J (Fe-CuNi) 100 to +1200C (210 to +1200C) K (NiCr-Ni) 100 to +1370C (270 to +1370C)

4V 10V 40V 100V 0.1mV 0mV 0.1mV 1mV 1mV 1mV 2A 2A 2A 0.2C

16V 30V 120V 300V 0.3mV 0.3mV 0.3mV 3mV 3mV 3mV 6A 6A 6A 0.6C

0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.06

0.3C

0.8C

0.06

0.02 + 0C

continued overleaf

Page 108

Measuring range (linearization range)4)

Resolution Meas. mode normal 1) Graphic Foffset

Maximum (typ. 1/3) electric measuring error2) Fel = Foffset + Frel + Ftemp + Fterminal Frel % MV Ftemp Reference value (23 2)C (% MV + const) /C Fterm C 0.4

R (Pt13Rh-Pt) +100 to +1760C (50 to +1760C) T (Cu-CuNi) 100 to +400C (270 to +400C) S (Pt10Rh-Pt) +100 to +1760C (50 to +1760C) N (NiCrSi-NiSi) 100 to +1300C (200 to +1300C) E (NiCr-CuNi) 100 to +1000C (270 to +1000C) B (Pt30Rh-Pt6Rh) +600 to +1820C (+100 to +1820C) L (FeCu-Ni) 100 to +900C (200 to +900C) U (Cu-CuNi) 100 to +560C (200 to +560C) R 300 0 to 300 R 1000 to 1000 Pot. 300 0 to 100% Pot. 1000 0 to 100% Pt 100 200 to +800C (200 to +800C) Ni 100 60 to +180C (60 to +180C)
1), 2) 2)

0.5C

1.8C

0.01 + 0.2C

0.2C

0.6C

0.07

0.02 + 0C

0.6

0.5C

1.8C

0.01 + 0.2C

0.4

0.4C

1C

0.05

0.02 + 0C

0.6

0.15C

0.5C

0.06

0.02 + 0C

0.6

0.6C

2C

0.01 + 0.2C

0.2

0.2C

0.6C

0.06

0.02 + 0C

0.6

0.2C

0.6C

0.07

0.02 + 0C

0.6

0.03 0.1 0.01% 0.01% 0.08C

0.2 0.5 0.05% 0.05% 0.5C

0.07 0.07 0.07 0.07 0.05

0.02 + 0.02 0.02 + 0.04 0.02 + 0.004% 0.02 + 0.004% 0.02 + 0.05C

0.05C

0.25C

0.07

0.02 + 0.025C

See Table 16 Fterm Error of terminal temperature measurement Absolute value specified in table for additional error with direct connection of thermocouples Measuring range with thermocouples with slightly increased error at start-of-scale including overload range

3)

Linearization range

Table 17 Measuring ranges for universal design


Page 109

8.1

Operation, displays Display Scale and pointer for measured values Green LED for display of recorder readiness Red LED for display of programming and test status Operation 2 levers for function settings on front 1 lever for function settings on side 2 levers for service (mechanical release on front) PC interface Connection Real-time clock Format Year, month, day, hour, minute, second; 12/24-hour representation, summer time/ winter time switchover Deviation Backup Service period Max. 5 min/year Via capacitor/battery(accessory) in event of power failure Approx. 5 minutes/36 months Step motor 1 120 Analog recording system Pens Pen spacing in chart direction Colors Recording length Service period Storage life Replaceable fibre pens 1.5mm Red, green, blue Approx. 2000m Approx. 6 months Approx. 24 months in closed packing Approx. 1 month in recorder with standard climate Program-controlled step motor 0.108mm Max. 40mm/s Approx. 101mm 1.25 10 300 2.5 20 600 5 60 1200 mm/h mm/h mm/h For all settings and measured-value scanning 2-pin plug at front, connection to PC via special cable (accessory)

8.2

Recording Chart drive Chart speeds A, B

Pen drive Resolution Pen speed Recording width

Page 110

Recording system error Alphanumeric recording system Pen Character height Characters per line Character set

Fmech 0.35% Replaceable fibre pen Approx. 2.4mm or 2.8mm with descenders 51 ASCII standard with upper-case and lower-case letters, Greek alphabet, special characters, binary signals, limit lines etc. Black Approx. 100 000 characters Approx. 6 months Approx. 24 months in closed packing Approx. 1 month in recorder with standard climate Program-controlled step motors Approx. 0.4 characters/s

Color Recording length Service period Storage live

Pen drive Printing rate 8.3 Digital input/output (option) Digital inputs Switching level Input resistance Digital outputs Electronic version

Low: 3 to +3V, High: +8V to +30V 5k 6 Electrically isolated via opto isolators, semiconductor switches, short-circuit-proof, open collector, P-switching Max. 150mA High: ext. voltage 2V 18 to 30V dc Electrically isolated via relays, floating switchover contacts 50V, 1A 30W or 60VA 1 x 108 mechanical 3 x 106 at max. load 50V, only for connection to low-voltage networks with safe isolation Subminiature plug, 25-pin, lockable

Output current Switching level Ext. power supply Relay version Switching voltage/current Switching capacity Contact life Permissible potential Connections

Page 111

8.4

DC 24V output (option) Output DC 24V 15%, 75mA, short-circuit-proof, capacitive load 33F Power pack with safe isolation AC 115/230V +15% 20% AC 24V +15% 20% 47 to 64Hz Power pack DC 24V +20% 15% 20VA with options at rated voltage To IEC 60654-1 location class B2 (but extended temperature range) 0 to 50C, 0 to 45C with IP53 (max. 75% rel. humidity, no condensation), change in temperature max. 10K/h 25 to + 70C to 45C (max. 75% rel. humidity, no condensation), change in temperature max. 20K/h 3K3 to IEC 60721-3-3 To DIN IEC 60654-3 installation category V.L.4 (low-frequency vibrations), V.H.4 (high-frequency vibrations), V.S.4 (but extended range up to 500Hz)

8.5

Power supply AC power supply Mains voltage Frequency range DC power supply Rated voltage Power consumption

8.6

Ambient conditions Climate Temperature of use

Storage temperature range

Climatic class Mechanical Vibrations during oscillation

8.7

Mounting position To DIN 16257 Operation with roll Operation with fanfold Vertical 30 to +15 Vertical 15 to +15

8.8

Degree of protection To IEC 529 or EN 60529 Front with door Terminals, interfaces, IP 54 IP 20 (IP 53, option with cover) plug connectors

8.9

Electric safety According to low-voltage guideline 73/23/EEC to EN 61010-1, overvoltage category II, degree of contamination 2 (IEC 61010-1, VDE 0411 Part 1) Protection class I

Page 112

8.10

Electromagnetic compatibility The targets of the EMC guideline 89/336/EEC with respect to radio interference suppression to EN 50081-1 and interference rejection to EN 50082-2, as well as NAMUR recommendation NE 21 are observed. Radio interference Power supply
Device under test Influencing variable

Limit class B, measured according to VDE 0875 Part 11 (CISPR 11)


Basic standard Instrument Test condition Response 2) A A A A A A A A B A A B A A

Instrument

RF field AM RF field PM Magnetic field Discharge RF cond. interference Burst Surge RF cond. interference Burst Surge Interruption In-rush current RF cond.interference Burst Surge Interruption In-rush current Overshoots RF cond. interference

IEC IEC IEC IEC

61000-4-3 61000-4-3 61000-4-8 61000-4-2

10V/m1) 10V/m
3)

6kV/8k 10V 1kV/2kV 1kV/2kV4) 10V 2 kV 1 kV/2kV 4) 20ms/100% 15 Irated 10V 2kV 1kV/2kV 4) 20ms/100% 15 Irated Class D 10V

Process, measuring and control lines DC power inputs

IEC 61000-4-6 IEC 61000-4-4 IEC 61000-4-5I IEC 61000-4-6 IEC 61000-4-4 IEC 61000-4-5 IEC SC77BWG3 IEC 61000-4-6 IEC 61000-4-4 IEC 61000-4-5 IEC SC77BWG3 IEC 61000-3-3 IEC 61000-3-2 IEC 61000-4-6

AC power input

Earth connection
1) 2)

3V/m in the ranges 87...108, 174...230 and 470...790MHz A B = class accuracy retained during effect = interference possible during effect = not relevant

3) 4)

Not relevant because of measuring and recording procedure used 1kV symmetric, 2kV asymmetric

Table 18 Interference rejection: test conditions and response

Page 113

8.11

Dimensions, mounting Dimensions Recorder (h x w x d) Mounting Panel mounting Desk and cabinet mounting Distance between centres of two adjacent instruments or one above the other Front door To DIN 43834-A-340 To DIN 43834-A-330 144mm x 144mm x 260mm

144 mm Plastic with spring-loaded latch, lock as option Approx. 4 kg

8.12 8.13

Weight Recorder Explanation of error data The total error to be expected results from several types of error which in turn depend on different influencing variables, the measuring mode, the recorder programming and the recorder design. The recorders correspond to class 0.5 to DIN 43782 or IEC 60484. The class accuracy of 0.5 does not mean that the error is always within 0.5% of the full-scale value or the span under all operating conditions. It means that the error does not exceed 0.5% of the reference value under reference conditions. The maximum range expansion permissible only results from the accuracy required for a specific task. There are no recorder limitations for the range expansion. The maximum total error to be expected results from the total of the individual errors. The actual error will generally be much smaller and typically approx. 1/3 of the maximum total error since it can be assumed that not all influencing variables will have their most unfavourable values, and that some of the influences will mutually cancel one another. The error data refer to the diagram. A requirement is correct adjustment of the carriage position in the TEST menu. Maximum absolute total error: F = Fel + Fmech Fel Fmech = See table of measured values 0.35% q Left value Right value

(See Example 1 on next page)

Page 114

Example 1
Recorder design: Measuring range: Left value: Right value: Actual measured value: Ambient temperature: Measuring ranges of standard design +4mA to +20mA +4mA +20mA 15mA +28C (increase by 3 degrees compared to reference value) Fel = 12A + 0.05% q 15mA + (0.03% x 15mA + 0.5A) x3 = 34.5A Fmech = Maximum absolute total error: F = 0.35% q 16mA = 56A 34.5A + 56A = 90.5A

Example 2
Recorder design: Measuring range: Sensor: Connection: Left value: Right value: Actual measured value: Ambient temperature: Measuring ranges of universal design TC Thermocouple type J Internal +700C +1050C +750C +18C (reduction by 3 degrees compared to reference value) Fel = = Fmech = Maximum absolute total error: F = 0.6C + 0.06% q 750C + 0.02% q 750C q 3 + 0.6C 2.1C 0.35% q 350C = 1.2C 2.1C + 1.2C = 3.3C

Page 115

Section 9.

SCOPE OF DELIVERY, OPTIONS, ACCESSORIES

This chapter lists the scope of delivery, available options, accessories and consumable material. 9.1 Scope of delivery The scope of delivery depends on the order. Designation Documentation Leaflet Parameterization a concise overview Fuse F1/F2 for power pack ac 115/230V Fuse F1 for power pack ac 24V Fuse F1 for power pack dc 24V Cable grip for ac or dc 24V design Short-circuit jumpers per channel for design with universal measuring ranges Mains plug for ac 115/230V supply Pens (one of each), color corresponding to channel assignment Channel 1, red (standard) Channel 1, blue Channel 2, red Channel 2, blue (standard) Channel 3, green (standard) Alphanumeric, black Chart paper (1 off) according to order Roll (with standard grid) 40 div. 50 div. 60 div. Fanfold pack (with standard grid) 2 clamps Blank labels for customer-specific extensions/ranges Measuring-point label Ruler per scale YS5100010 YS5100011 YS5100012 YS1056005 7ND9001-8AB 7ND9001-8AE YS1056004 YS1056006 YS1056007 C79000-M7376-C191 W79054-L1010-T125 Order No.

Page 116

9.2

Available accessories and consumable material Designation Documentation Instruction Manual for recorders Leaflet Parameterization a concise overview Chart paper Roll (with standard grid) 40 div. 50 div. 60 div. Fanfold pack Scale units Without scale With one scale for single-channel recorder With one scale for dual-channel or three-channel recorder Pens Position Bottom Center Top Dummy pen Alphanumeric, black Ruler Without scale With one scale Battery for clock backup Take-up spool Recording unit For fanfold paper For rolls and fanfold paper Jumper for input range
Page 117

Order No. I9-089 C79000-M7376-C19

YS5100010 YS5100011 YS5100012

7ND9300-8RA 7ND9300-8RB-Z 7ND9300-8RC-Z

Color Red Blue Blue Red Green

Channel No. 1 1 2 2 3 YS1056005 7ND9001-8AB YS1056004 7ND9001-8AE YS1056006 C79453-A3049-B522 YS1056007

7ND9262 7ND9272-Z W79084L1002-B1 C72301-A20-B110

C72301-A20-A16 C72301-A20-A17 W79070-G2604-N2

9.3

Available options The following options can be ordered separately and are fitted in the factory. The options can also be ordered following delivery of the recorder. Retrofitting must only be carried out by authorized servicing centers. Designation Digital input/output, electronic, including matching plug (mounting part) Digital input/output, relay, including matching plug (mounting part) DC 24V output Order No. 7ND9400-8BF 7ND9400-8BE 7ND9400-8BG

Page 118

REPAIR FORM
Please complete this form and return it to ALSTOM T&D Protection & Control Litd with the equipment to be repaired. This form may also be used in the case of application queries.

ALSTOM T&D Protection & Control Ltd St. Leonards Works Stafford ST17 4LX, England For: After Sales Service Department ____________________ Model No: ___________________ Serial No: ___________________

Customer Ref:

ALSTOM Contract Ref: ____________________ Date: 1. ____________________

What parameters were in use at the time the fault occurred? DC volts DC current Other: _____________ Battery/Power supply/Transducer _____________ Battery/Power supply/Transducer _____________ Please specify

2. 3. 4.

Which type of test was being used? ____________________________________________ Were all the external components fitted where required? (Delete as appropriate.) List the settings being used ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ Yes/No

5.

What did you expect to happen? ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________

continued overleaf

Page 119

6.

What did happen? ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________

7.

When did the fault occur? Instant Time delayed By how long? Yes/No Yes/No ___________ Intermittent Yes/No

(Delete as appropriate).

8.

What indications if any did the relay show? ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________

9.

Was there any visual damage? ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________

10. Any other remarks which may be useful: ____________________________________________________________________________ ____________________________________________________________________________ ____________________________________________________________________________

______________________________________ Signature ______________________________________ Name (in capitals)

_______________________________________ Title _______________________________________ Company name

Page 120

Page 121

Page 122

Page 123

A L S T O M T & D P r o t e c t i o n & C o n t r o l L t d St Leonards Works, Stafford, ST17 4LX England Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com
1999 ALSTOM T&D Protection & Control Ltd Our policy is one of continuous product development and the right is reserved to supply equipment which may vary from that described.

Publication I9-089B

Printed in England.

También podría gustarte