Motor Protection
Protection
n Stator thermal overload protection n 2 Protection principles for the rotor overload protection n Motor starting time supervision n Restart inhibit n Earth-fault protection (I0>;U0>; (U0, I0)) n Overcurrent time protection n Current differential protection n Negative sequence protection (I2/IN) n Temperature sensors (RTDs) n Undercurrent protection, Active power protection (P<) n Undervoltage protection
ANSI - No.
49
48 66 50G 50 87 46 38 37 32U 27 40
n Undervoltage
(Starting torque not reached M ~ U2 or start too long) (of a synchronous motor)
n Asynchronous operation
n Underexcitation protection
Protection functions
ANSI
7SJ60
7SJ61
7SJ62
7SJ63/64
7UM61
7UM62
Stator overload protection Starting time supervision Locked rotor protection Restart inhibit Earth-fault protection non-directional directional Overcurrent time protection Current differential protection Negative sequence protection Temperature supervision (via RTD - module) Undercurrent protection Active power protection (P<) Undervoltage protection Underexcitation protection Frequency protection Breaker failure protection Freely programmable logic (PLC) Control functions Measuring transducers Flexible serial interfaces nn
X X X X
X X X X
X X X X
X X X X
X X X X
X X X X
X 1) X X 1) X X X 1) X 1) X X X X
X X X X X X X
X X X X X X X
X X X X X X X X
X X X X X X X X X X X X X X X X
X X X1) X X X X X X X
X X X X X X
X X X X X X
2/3
1)
in preparation (7SJ602)
Asynchronous Motor
100 kW - 500 kW
7SJ60 Basic device 7SJ61 + more I/Os + control functions + flexible serial interfaces + better local HMI (4line display; digital keyboard)
Synchronous Motor
< 2MW
7UM61 (Option: Generator Basic)
500 kW - (1-2) MW
7SJ62 Basic device + control functions 7UM61 + more I/Os (7UM612) + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz)
< 10 MW
7UM62 (Option: Generator Basic)
or with control functions via bay mimic diagram in graphic display 7SJ63 Basic device 7SJ64 + synchro check function + high sensitivity + extensive control function + 1 serial interface more
> 2 MW
7UM62 + differential protection + control functions + high accuracy + high sensitivity + operating range in a wide frequency band (11Hz - 68Hz)
> 10 MW
+
7UM62 (Option: Generator Basic)
7UM61 (Option: Generator Basic) or with control functions via bay mimic diagram in graphic display
A (L 1) B (L 2) C (L 3) ANSI 52 A (L 1) B (L 2) C (L 3) N
7SJ600/602
n Stator thermal overload protection n Starting time supervision n Earth-fault protection n Overcurrent time protection n Negative sequence protection 49 48 50G 50, 51 46
Motor
A (L 1) B (L 2) C (L 3) ANSI 52 A (L 1) B (L 2) C (L 3) N
7SJ62/63
n Stator thermal overload protection 49 66, 49R 48 50G 64G 67G
IEE
n Restart inhibit (rotor protection) n Starting time supervision n Earth-fault protection (non-directional, directional)
VE
C (L 3) A (L 1)
protection n Undervoltage protection n Undercurrent protection n Breaker failure protection n external RTD - module
46 27 37 50BF 38
A (L 1) B (L 2) C (L 3) ANSI 52
e
7UM62
R 13 R 14 R 15 R 17 R 18 R 16 J1 J2 J3 J4 J5 J6
VE
7UM62
n Stator thermal overload protection n Restart inhibit (rotor protection) n Earth-fault protection
(non-directional, directional)
Q8 Q7 K 13 +
IEE2
RTD module
Measuring transducer for injection of any analog signal e.g. speed, vibration, pressure
TD1
K 14 K 15 + K 16 K 17 +
TD2
TD3
To serial interface
K 18 J7 J8 Q1 Q2 Q3 Q4 Q5 Q6 IEE1
n Differential protection n Overcurrent time protection n Negative sequence protection n Undervoltage protection n Undercurrent protection n Active power protection n Frequency protection
Port C or D
Siemens AG Power Transmission and Distribution Power Automation Division P.O. Box 48 06 90026 Nuremberg Germany www.siprotec.com