Oilon ChillHeat
A worthwhile investment
A heat pump is an investment with short payback period. Annual savings in energy can reach up to eighty per cent and the same goes for CO2 emissions as well!
ChillHeat heat pumps use recovered waste heat at refrigeration plants to generate hot water, thereby substituting valuable primary energy. The COP in these applications is typically between 4 and 6.
Refrigeration applications
ChillHeat products can provide energy-efficient refrigeration for industrial applications, ice rinks, or supermarkets
Highest temperature
The highest temperature of the generated heat, throughout the entire capacity range. An optional superheater can use part of the generated heat energy in order to raise the temperature further
Limited
In demanding conditions
Highest temperature 63 C
Large residential buildings 10000-20000 m Combined cooling and heating Heat extraction from outdoor air Water chiller applications Ground source heating
Oilon ChillHeat RE heat pumps are best suited for heating and cooling large residential buildings and industrial plants. In our RE line, we use scroll compressors only from the most well-known and reliable compressor manufacturers.
TECHNICAL SPECIFICATIONS
ChillHeat product No. of compressors, compressor type No. of refrigerant circuits Dimensions RE210 2 scroll 1 2060 1560 890 R410A 211 4.4 252 3.6 193 3.5 3x200A 1700 RE330 4 scroll 2 2060 2720 890 R410A 334 3.9 426 3.6 291 2.9 3x400A 2400 RE420 4 scroll 2 2060 2720 890 R410A 423 4.4 544 4.1 385 3.5 3x400A 2600
Height mm Width mm Depth mm EN 14511 0/35 C EN 14511 0/35 C 18/8 C, 40/55 C 18/8 C, 40/55 C 12/7 C, 36/42 C 12/7 C, 36/42 C A, 3/N/PE 400 V 50 Hz kg
Refrigerant Heat output, ground source heating (kW) COP Heat output, heating network (kW) 1 COP Cooling output, air conditioning (kW) 2 COPc 2 Fuses Weight 1) Performance with subcooler
Using this table to estimate heating or cooling output under other operating conditions is not permitted. Contact manufacturer for final specifications for your application.
Highest temperature 80 C
Large residential buildings 5000-15000m Combined cooling and heating Heat recovery at refrigeration plant (ammonia, HFC, CO2) Heat recovery from industrial processes (evaporators, cooling towers, and driers) Heat recovery from waste waters
Oilon Chill Heat P heat pumps generate hot water up to 80 C very efficiently even when running at partial capacity. A culmination of years of research and development work, energyefficient and reliable piston compressors keep the operating and maintenance costs down.
P series heat pumps can be fitted with an additional sound proofing cover.
All P series heat pumps use R134A refrigerant as standard. For customized solutions, alternative refrigerants can also be specified.
TECHNICAL SPECIFICATIONS
ChillHeat product No. of compressors, compressor type No. of refrigerant circuits Dimensions, without cover and extra legs P150 2, piston 1 2060 1560 890 R134A 150 4.2 189 3.7 152 2.7 146 3.3 3x200A 1600 P220 3, piston 1 2060 2720 890 R134A 226 4.2 283 3.7 229 2.7 220 3.3 3x250A 1800 P300 4, piston 2 2060 2720 890 R134A 301 4.15 415 4.0 341 2.9 293 3.3 3x315A 2600 P380 5, piston 1 2060 3880 890 R134A 380 4.1 472 3.7 381 2.7 365 3.3 3x400A 3100
Refrigerant Heat output, ground source heating (kW) EN 14511 0/35 C COP EN 14511 0/35 C Heat output, heating network (kW) 1 18/8 C, 40/55 C COP 18/8 C, 40/55 C Heating output, heating network with high temperature (kW) 1 18/8 C, 55/75 C COP 18/8 C, 55/75 C Cooling output, air conditioning (kW) 2 12/7 C, 36/42 C COPc 2 12/7 C, 36/42 C Fuses A, 3/N/PE 400 V 50 Hz Weight kg 1) Performance with subcooler 2) Performance without subcooler, refrigerant circuits in parallel. Temperatures are evaporator and condenser line in and line out temperatures.
Using this table to estimate heating or cooling output under other operating conditions is not permitted. Contact manufacturer for final specifications for your application. Oilon Scancool Oy may change specifications without prior notice.
Large residential buildings 5000-25000m2 Heat recovery at refrigeration plants (ammonia, HFC, CO2) Heat recovery from combustion gases Refrigeration applications Heat recovery from industrial processes (evaporators, cooling towers, driers)
Oilon ChillHeat S heat pumps generate hot water up to 67 C very efficiently. When equipped with the HT option, then are capable of generating hot water up to 80 C. The S series heat pumps come equipped with energyefficient rotary compressors, proven to be reliable.
S series heat pumps can be fitted with an additional sound proofing cover.
All S series heat pumps use R134A refrigerant as standard. For customized solutions, alternative refrigerants can also be specified.
S180 1 screw 1 2060 2720 890 R134A 180 4.3 228 3.6 213 2.8 173 3.5 3x200A 2300 S280 1 screw 1 2060 2720 890 R134A 280 4.3 358 3.7 342 2.8 270 4.6 3x250A 2900 S380 1 screw 1 2060 2720 890 R134A 380 4.4 480 3.8 447 2.9 367 4.6 3x315A 3600 S490 1 screw 1 2060 3880 890 R134A 493 4.5 630 3.9 590 3.0 481 4.8 3x500A 4000 S540 1 screw 1 2060 3880 890 134A 542 4.2 689 3.7 645 2.8 518 4.5 3x500A 4100
TECHNICAL SPECIFICATIONS
ChillHeat product No. of compressors, compressor type No. of refrigerant circuits Dimensions, without cover and extra legs
Height mm Width mm Depth mm EN 14511 0/35 C EN 14511 0/35 C 18/8 C, 40/55 C 18/8 C, 40/55 C 18/8 C, 50/65 C 18/8 C, 50/65 C 12/7 C, 36/42 C 12/7 C, 36/42 C A, 3/N/PE 400 V 50 Hz kg
Refrigerant Heat output, ground source heating (kW) COP Heat output, heating network (kW) 1 COP Heating output, heating network with high temperature (kW) 1 COP Cooling output, air conditioning (kW) 2 COPc 2 Fuses Weight 1) Performance with subcooler
Specificied temperatures are evaporator and condenser line in and line out temperatures.
Using this table to estimate heating or cooling output under other operating conditions is not permitted. Contact manufacturer for final specifications for your application. Oilon Scancool Oy may change specifications without prior notice.
Free cooling can be used for refrigeration using cool outdoor air. A frequency converter can be used for faster, more precise adjustments. Extra gauges can be used for measuring and displaying the heating output and COP of the unit. Sound insulation A superheater can be used for producing domestic hot water. Waste water option. The heat pump comes with an evaporator that can be opened for cleaning. The NH3-HR option allows for heat recovery from the condensate of ammonia refrigeration units. An extra refrigeration circuit can be used, for example, to convert a single circuit unit to run two independent refrigeration circuits
In addition, we may use various other technical solutions, such as an Economizer or high temperature options in order for the unit to correspond to the customers specifications as closely as possible.
MEDIUM
- Clear, easy to use graphical user interface and a reliable, programmable industrial controller enable controlling multiple ChillHeat units. - Modbus, Profibus, and Profinet protocols available - Remote monitoring and programming
ADVANCE
- For controlling industrial processes - An industrial PC and reliable programmable industrial controller enable clear process views and versatile process control options. - Modbus, Profibus, and Profinet protocols supported - Remote monitoring and programming - Process event logging enables comprehensive reporting and trend monitoring. Advance user interface.
Oilon Scancool Oy Oy Oilon Scancool Yrittjntie 6, 67100 Kokkola, Finland Yrittjntie 6, 67100 KOKKOLA Tel. +358 (0)207 281 868 Puh. +358 (0)207 281 868 info@oilon.com, www.oilon.com info@oilon.com, www.oilon.com