Está en la página 1de 17

ASHIDA Numerical Single Pole EF /Sensitive EF Protection Relay

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

Features: EF Relay with wide setting (Model AM-120-01-02-07-03-00-00) EF Relay with Sensitive Setting (Model-AM-220-01-02-07-03-00-00) Dual Stage relay (separate settings for ALARM and TRIP). Suitable for REF or current operated Neutral Displacement Protection. Back - lit LCD display for settings. Display of Load current in terms of primary. Cold Load pickup for prolong inrush current. Selection of Curve: Seven selectable curves Normal Inverse 1 (C1), Normal Inverse 2 (C2), Very Inverse (C3), Extremely Inverse (C4), Extremely Inverse (C4A) EE equivalent, Long Time Inverse (C5) & Definite Time (C6). Design using DSP technology. Latching of fault current up-to last 5 Faults with time stamping. Password protection for setting. Site selectable CT secondary. Relay can be made either IDMT or Define time. In build Breaker Fail & Trip Circuit Supervision Function. Programmable operating time in instantaneous element. SCADA Compatibility (RS232 and RS485 Communication For model ADR211E). General: The ADR111E is member of Ashida Numerical Relay family (Aditya Series) design to meet demand of low and medium switchgear control. The ADR111E is two stage single pole EF relay with instantaneous high set and programmable output to simplify feeder protection wiring. The relay also can be used as REF (with Stabilizing Resistor) or Neutral Displacement application, where the two stage protection is require. The ADR111E continuously monitors earth current, through CT connections. The high-speed microcontroller samples this current through a 12-bit A/D converter. The micro-controller performs the powerful Digital Algorithms to find out Amplitude of current signal, and then this value is use for Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 1/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

protection and metering function. All measurement is tuned to fundamental frequency. Input current is displayed on 16 x 2 LCD display for metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3) Measurement 1. Protection Functions:

The ADR111E give maximum benefit/cost ratio. The ADR111E give all the advantage of numerical relay at affordable cost. Following is summery of different protection functions provided by relay.

ANSI 50N 51N 1.1.

IEC IE>> IE>t, IEP

Protection Functions Instantaneous Earth Fault Protection. Time Over current Protection.

Protection Function:

The ADR111E has single element (EF). The tripping current can be set in dual stage from 5% to 100% in steps of 1% by Keys provided on front panel. The unit has selection of IDMT characteristic of International IEC standard, Very inverse / Extremely Inverse / Long Inverse and Standard Inverse (3.0 sec, 1.3sec, 1.5 Sec, 0.8 sec & 13.3 sec at 10 times). The unit also has Time Multiplier Setting (TMS) from x0.01 to x1.5 for IDMT delay multiplication. The instantaneous tripping function is having range of 50% - 3000% in steps of 50%. The high speed CPU continuously monitors the current input and compares with IDMT as well as instantaneous setting. If current is above instantaneous setting the relay provides immediate trip command bypassing IDMT delay. If is input current is less than instantaneous setting but more than IDMT setting, CPU calculate IDMT delay as per selected IDMT characteristic multiply it with TMS setting and provide trip command if fault is persist even after this time delay. All the settings are password protected to prevent unauthorised change. 2.0 2.1 Supervision Function: Self-supervision: -

The continuously keeping track on its internal hardware and the movement it detect any failure of any component, it give message on LCD display, This feature is very useful to give pre information to avoid any mall - operation. In such situation it uses some default setting and remains in protection mode. 3.0 Measurement Function:

In normal condition this display shows all settings. Via keyboard the display can be program to show the actual current flowing through the relay. If current excesses set value the relay gives trip command. The type of fault is displayed on LCD display. Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 2/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

During the fault condition the relay measure the fault current and store in non-volatile memory. The fault current can be read via keyboard on LCD display Last 5 fault values along with tripping counter can be view via key-board. All settings are save in electrically erasable read only memory and remain. 4.0 Breaker Fail Function (BF or LBB) Normally after tripping current should be come Zero within 100 200ms time depend upon type of fault and breaker mechanism. After Fault Relay start one internal timer (settable from 0.05s to 0.8s) if fault is not cleared during this time then relay declare as Breaker fail (LBB function) and operates the BF relay. 5.0 Cold Load Pickup Relay also equipped with cold load pick feature. During switching of load relay sense closing of CB by auxiliary contact of CB (through dedicated Status input marked as CB NO). Once CB closing is detected relay automatically switch settings to cold load setting (which independently adjustable) for pre define time (adjustable). After this cold load time relay switch back to original setting automatically and avoid wrong operation of relay. 6.0 Trip circuit Supervision & Status:-

The ADR111E is having 2 separate digital opto-coupler status input which can be used to continuously monitor continuity of trip-circuit. The general scheme is as shown in fig.
B+ TCCOM
1 6 2

To Relay CPU

CB NO B-

S4

S3 TC CB NC

6 2

To Relay CPU

Fig. Trip Circuit Logic

Relay monitor Trip coil continuity through CB NO during close condition and through CB NC during Trip condition. If any discontinuity observed it generate Alarm signal. One changeover contact is provided for ALRAM and will operates when S3 and S4 both active and both inactive. i.e CB NO as well as CB NC are both close or open. Along with this two general purpose Status inputs S1 and S2 are given for SCADA application

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 3/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

7.0

Ordering Information: The relay is available with nos. of different option. The option is specified by model no. It is user responsibility to specify correct model no. while ordering. W h i le Or der in g S pec i fy t h e fo ll ow ing I n for m a t ion f or ADR111E Relay

Definition of Model No for ADR111E Relay AM XXX XX XX XX XX XX - XX

XX = CT. 03 1/5 Amp.

XX = PT. 00 Not Applicable

XX = Communication Protocol 00 Not Applicable 02 IEC - 103


Note: Communication Protocol is applicable only for ADR211E.

XX = Cabinet Size 01 CSA (138 x138mm )

XX = Cabinet Type 01 Non Draw out 02 Draw out

XX = Auxiliary Supply. 06 18 52 VDC 07 77 250 VDC 08 18 250 VDC 28 18 250 VAC/DC

XXX = Sub Type 110 Single pole (EF/REF/NDR ) EF : 5 - 100 % in steps of 1%, HF: 50 3000 % In steps of 50% , TMS: X0.01 X1.5 In steps of X0.01 Contacts: 2NO For trip (stage 2), 4 NO for Ann. Of stage 1&2, 1NO for BF, 1C/O for TCS. Status: 2 nos. Dedicated for TCS and 2 Nos. for Spare. With Cold Load function. Single pole (OC/EF/REF/NDR ) EF : 5 - 100 % in steps of 1%, HF: 50 3000 % In steps of 50% , TMS: X0.01 X1.5 In steps of X0.01 Contacts: 2NO For Trip (Stage 2) and 2 NO for Ann. (Stage 1). Single Pole Sensitive EF EF 2% to 50% in steps of 1% HF 50 1000% in steps of 1%, TMS: X0.01 X1.5 In steps of X0.01 Contacts: 2NO For Trip (Stage 2) and 2 NO for Ann. (Stage 1).

120

220

Note: Universal Supply (18 -250 VDC) & Cold Load function are currently not available in Draw out model.

O rd er ing in fo rmat ion : ADR111E AM XXX XX XX XX XX XX XX

A va i l ab l e M od e ls: F or N or ma l ADR111E AM-110-01-01-28-03-00-00. (Non draw out cabinet) ADR111E AM-120-01-02-06-03-00-00. (draw out cabinet) ADR111E AM-120-01-02-07-03-00-00. (draw out cabinet) ADR211E AM-110-01-01-28-03-00-02. (Non draw out cabinet)

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 4/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

ADR211E AM-120-01-02-06-03-00-02. (draw out cabinet) ADR211E AM-120-01-02-07-03-00-02. (draw out cabinet)

For Sensitive EF 8.0 ADR111E AM-220-01-01-28-03-00-00. (Non draw out cabinet) ADR111E AM-220-01-02-06-03-00-00. (draw out cabinet) Technical Specifications: Particulars
: : Setting : TMS : Operating Time Site selatctable CT 1 or 5 Amp. For EF 5% - 100% for both stages(For AM 110 & 120) For EF 2% - 50% for both stages (For AM 220) X0.01 to x1.5 in steps of x0.01. Normal Inverse 1 (C1) Normal Inverse 2 (C2) Very Inverse (C3) Extremely Inverse (C4) Extremely Inverse (C4A) EE Equivalent. Long Time Inverse (C5) Definite Tme (C6) 00(Inst) 99.9Sec : Inst. Setting For HF 50% - 3000%. or bypass In steps of 50% (for AM 110 &120) For HF 50% - 1200%. or bypass In steps of 50% (for AM 220 Inst = < 40ms and additional adjustable software delay of 00 2.0Sec in steps of 10ms. 0.1 to 10.0s in steps of 0.1s For IDMT 5% - 100 % In steps of 1% X0.01 to x1.5 in steps of x0.01. HF 50% - 3000%. or bypass In steps of 50%. Inst = < 40ms and additional adjustable software delay of 00 2.0Sec in steps of 10ms. 1) 2) 3) 4) 2 NO Trip duty for Stage 2. 4 NO Ann. duty for Stage 1 & 2. 1 NO for Breaker Failure 1 C/O for Trip Circuit Supervision

Sr.No. Specification
I. Inputs Protection Relay Setting Range

: Inst Operating Time Cold Load Settings : Cold Load Delay : Setting : TMS : Inst. Setting : Inst Operating Time Output contacts : Model AM-110-0101-xx-xx-xx-xx.

: Model AM-120-0102-xx-xx-xx-xx.

2 NO Trip duty and 2 NO Ann. Duty contact.

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 5/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

II. Pickup Current III. Resetting Current IV. Time Accuracy V. Burden on CT VI. Aux. Supply VII. Burden on Aux. Supply VIII. Contact Rating Trip Duty

: Within 1.1 times of set current value. : Within 90% of set value. : Within class 2.5 As per IS: 3231. : Less than 0.2VA. : 18 52 VDC or 77 250 VDC or 18 250 VDC. To be specified while ordering. (18 250 VDC is currently not available in draw out model). : Less than 10VA on any supply. : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make & carry for 3 sec : 15A

IX. Operational Indicators (Flags) ON / Error PKP / HF Stage1 / Stage 2 TRIP / BF : Green LED indicates Relay OK : Red LED indicates Problem in relay Hardware. : Green LED indicates the relay Pickup. : Red LED indicates the relay is tripped with HF. : Green LED indicates the relay tripped by stage 1, Hand Reset (HR) Type. : Red LED indicates the relay tripped by stage 2, Hand Reset (HR) Type. : Green LED Indicates that Trip pulse is being executed. When BYPASS P.B. is pressed, actual trip is not executed. : Red LED indicates the Breaker Failure is operated. : 40 times the normal current for 3sec. : 2 times Continuous : IEC 60255-5 : Except DC Voltage 2.0 kV (RMS), 50Hz : Only DC voltage 2.8 kV DC : Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz : Between Open contact of ALARM 1kV (RSM) 50Hz : IEC60255-5 : 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse at interval of 5 sec : IEC 60255-22-1, Class III : 2.5 kV (peak) 1MHz , = 15s 400 surges / s duration 2 s XIV. Electro static Discharge XV. Irradiation with radio frequency field, pulsemodulated, XVI. Fast transient interference/bursts : IEC 60255-22-2 Class III and IEC 61000-4-2 class III : 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri 330 : IEC 60255-22-3 and IEC 61000-4-2 class III : 10V/m; 80 to 1000MHz; 80%; 1kHz AM : IEC 60255-22-3 and IEC 61000-4-3, class III : 4kV; 5/50ns; 5kHz burst duration = 15ms; : Repetition rate 300ms; Both polarities; Ri = 50; duration 1 min.

X. Thermal Withstand Capacity XI. High Voltage Test

XII. Impulse Voltage Test (all circuit class III) XIII. High Frequency test

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 6/7

Type: ADR111E ADR211E


(ADITYA Series) (Preliminary)

XVII. Shock Test

: IEC 60255-21-2 class 1 : Semi-Sinusoidal : 5g acceleration, duration 11ms, : Each 3 shocks in both direction of the 3 axes : IEC 60255-21-1 class 1 / IEC 60068-2-6 : Sinusoidal 10 to 60Hz 0.035 mm : Amplitude, 60 to 150Hz, 0.5g acceleration : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal

XVIII. Vibration Test

XIX. Drawing References

: For Cabinet Type : For Operating Characteristics

CSA -150 CSA -150D C1 C2 C3 C4 C4A C5

- MAC00101 - MAC00107 - APR02201 - APR01801 - APR05101 - APR05201 - APR02801 - APR05301 - APR07407_A - APR07407_B - ACAGRxxxx

: For Electrical Connection

Model: AM-110-01-01-xxxx-xx-xx. Model: AM-120-01-02-xxxx-xx-xx.

: For Stabilizing Resister Datasheet Change Log for ADR111E Issue No. (Revision) 01 02 03 04 05 Date 15.01.06 07.06.10 01.11.11 10.12.11 30.06.12 Description /Changes Original Revision Settings and back terminal layout changed

Model Definition changed and the cold load settings added. C4A Added Addition of Sensitive EF model

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD. Plot No. A-308, Road No. 21, Wagle Industrial Estate, Thane (W)-400 604. INDIA. E-mail: sales@ashidaelectronics.com Web: www.ashidaelectronics.com

Ref.: ADR111E Issue: 05 30.06.2012 Page 7/7