SECTION 16715 VOICE AND DATA COMMUNICATION CABLING 00000000PART 1 - GENERAL 1.1 A. B.

DESCRIPTION: The Work shall consist of furnishing and installation of voice and data communication cabling as shown on the drawings and specified herein. Basic Criteria: A complete structured cabling system shall be designed based on ISO/IEC 11801 2002, EIA/TIA 568A, B. and EIA/TIA 569. The system shall be unified and supports telephone, data, video and others. The system shall support Ethernet as defined by IEEE 802.3 standard and shall be open to any new applications that require an ISO/IEC 11801. Structured cabling system shall be installed, tested certified and guaranteed by an authorized supplier/contractor. The warranty shall provide performance guarantee for 20 years. The system shall support IEEE 802.3 10GBASE-T 10 Giga speed (CAT 6A) component, and shall be configured in star configuration with full redundancy using fiber optic as back bone and UTP category 6A horizontal cable to each communication outlets The system shall include, but not limited to: Backbone Cabling (dual 12 core Fiber optic cables) Horizontal cabling (UTP) Telecommunication face plates and outlets Patch Panels Patch Cords and connection cords Equipment Racks Modular rack-mounted UPS Pathways

All the component of the structured cabling system shall be as required by IHGIT specs and as per the requirement of CAT 6a (Class Ea) as per EIA/TIA 568A, B and ISO/IEC 11801 and. and shall meet the following minimum requirement: C. Backbone Cabling: The intra building cabling system shall be designed to support 10 Gbps Ethernet based converged networking to ANSI, TIA and EIA standards with all network endpoints designed to support 10/100/1000 Mbps. Dual 12 core Tight-buffered multimode fiber optic 50/125 cables will provide connectivity between the main telecom room and each comm. room. This topology will allow for redundant connectivity to both Guest and Admin network active equipment, the implementation of future technologies and ensures capability to implement a 10 Gbps Ethernet backbone throughout the hotel.
ITCC in Riyadh Residential Complex J10-13300 16715-1 Voice & Data Communication Cabling

The backbone fiber cables will be terminated with either SC or LC connectors and housed in rack mounted optical fiber patch panels. All cables will be Low Smoke Zero Halogen (LSZH) sheathing material that does not give off toxic fumes in case of fire. Single mode fiber optic cables shall be used to cover long distances. D. Horizontal Cabling: The horizontal cabling shall be 4 pairs Unshielded Twisted Pairs (UTP) category 6a. The cable shall have solid conductor of 0.55mm diameter. Cable shall be PVC insulated and twisted and shall be LSZH (low smoke Zero Halogen). Performance and twisting shall be guaranteed to meet or exceed the ISO/IEC 11801 standard Each Telecommunication outlet shall have two cables in general Fiber optic cables can be used for the horizontal cabling if the distances between telecommunication outlet and patch panel communication cabinet exceeds 90m. Telecommunication Outlets (Faceplates): As recommended by the ISO/IEC 11801 standard at least 2 RJ45 outlets per Telecommunication outlet. Connection shall be provided for data services to a PC, network printer, or network computing equipment including antennas for wireless IP LAN applications, Voice over IP telephone outlets, P.O.S. outlets, IPTV / HiTV outlets, High Speed Internet Access outlets and Digital Signage outlets. Data cables (horizontal data, copper data patch cables and interface cables) shall be terminated using standard RJ-45 plugs or sockets as appropriate. For back of house offices Telecommunication Outlets shall follow the furniture layout i.e. one telecommunication outlet for each workstation or minimum one outlet for each 10 m2 of usable workspace where there is no recommendation or furniture layout. Every back of house office shall have a minimum of one Telecommunication outlet (one faceplate with 2 RJ45 outlets) A minimum of four RJ45 outlets shall be provided in meeting rooms for telephone, TV and other services. RJ45 outlets shall be provided in front of house areas where telephone, TV, workstations and network printers are planed to be located. A minimum of five RJ45 outlets shall be provided for guest room. These will be used for: 3x Telephone handsets 1x In room Entertainment (IPTV and Hi TV system) 1x RJ45 for future use

The wall-mounted faceplate shall match the wiring devices finishes and shape and it shall accept modular type RJ45 outlets (2 or 4 as required)
ITCC in Riyadh Residential Complex J10-13300 16715-2 Voice & Data Communication Cabling

E.

Patch Panels: Copper patch panels must have 19 to fit in the standard 19 cabinet, rack or bay. Patch panels must be modular, and have RJ45 connectors. A typical 1HU high patch panel shall have 24 port modular snap-in RJ45 connectors Performance and specification shall meet or exceed CAT 6a ISO/IEC 11801 The optical fiber patch panel must have 19 to fit in the standard 19 cabinet, rack or bay. The patch panel shall support the ST or SC connector type. All patch panels, patch cord and accessories shall be CAT 6a rated.

F.

Pathways: The Containment Pathways comprise conduit, riser openings, cable tray systems and containment for the vertical and horizontal cabling. The volume of the pathways required to support each area will be calculated using standards based criteria of the project. Current and future requirements will be considered in the design of the pathways for this project with sufficient additional capacity provided in order to accommodate future moves, add, and changes to the systems. All pathways and support systems will be sized for an installed capacity of 50% i.e. no trunking or cable tray shall be more than 50% occupied on installation. The pathways linking the main telecom room, comm. rooms and Outlets will consist of dedicated vertical and horizontal cable trays and conduits. Cable Trays shall be of hot dip galvanized steel, to provide physical protection from a service-level environment, and electrical protection from EMI/RFI and other signaling interferences. All pathway routes shall be coordinated with other building services (electrical, mechanical, plumbing, etc.) to assure proper clearance and access, as well as to avoid impact from heat, electro-magnetic interference or leakage from other building services. A separation of 300mm between parallel runs of telecommunications and electrical cabling shall be maintained. Backbone copper and optical fiber cabling will follow the vertically and horizontally aligned routes to carry the backbone cables to their respective termination equipment. For horizontal cabling, 25mm conduit shall be provided from the tray infrastructure to each telecommunications outlet location.

1.2 A.

REFERENCES: SASO - Saudi Arabian Standards Organization .


Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

16715-3

SASO 1357

Electrical installation of buildings Part 7: Requirements for special installation or locations Section 707: Earthing Requirements for the installation of data processing equipment.

B.

ISO International Standards Organization ISO/IEC 11801 ISO/IEC TR 14763-1 ISO/IEC TR 24750 Information Technology Generic Cabling for Customer Premises Information technology Implementation and operation of customer premises cabling Part 1: Administration Information Technology Assessment of installed balanced cabling channels in order to support 10 GBASE - T

C.

IEC - International Electrotechnical Commission IEC 60603-7 IEC 60793 IEC 60794 IEC 61156-1 to 6 IEC 61935-1 & 2 Connectors for Electronic Equipment Part 7-1 & 7-7 All parts relevant to these Specifications All parts relevant to these Specifications Multicore and symmetrical pair/quad cables for digital communications Part 1 to 6 Generic cabling systems Specification for the testing of balanced communication cabling in accordance with ISO/IEC 11801 Part 1 & 2 Test on electric cables under fire conditions Test on Gases Evolved During Combustion of Material from Cables

IEC 60332 IEC 60754 D.

EIA - Electronic Industries Association RS-453 EIA 310 EIA/TIA 492AAAA Dimensional, Mechanical and Electrical Characteristics Deferring Phone Plugs and Jacks Racks, Panels and Associated Equipment Detail Specification for 62.5-UM Core Diameter/125-UM Cladding Diameter Class 1A Graded-Index Multimode Optical Fibers Optical Power Loss Measurements of Installed Multimode Fiber Cableplant - OFSTP-14a Commercial Building Telecommunications Wiring Standard Commercial
16715-4

EIA/TIA 526-14-A EIA/TIA 568 A EIA/TIA 568-B.1


ITCC in Riyadh Residential Complex J10-13300

Building

Telecommunications

Cabling

Voice & Data Communication Cabling

Standard, Part 1: General Requirements (ANSI) EIA/TIA 568-B.2 Commercial Building Telecommunications Standard, Part 2: Balanced Twisted-Pair Components (ANSI) Optical Fiber Cabling Components (ANSI) Commercial Building Standard for Telecommunications Pathways and Spaces Telecommunications Buildings EIA/TIA 607 EIA/TIA TSB 67 EIA/TIA TSB 155 E. Administration Standard for the Infrastructure of Commercial Building Cabling Cabling

EIA/TIA 568-B.3 EIA/TIA 569 EIA/TIA 606-A

Commercial Grounding/Bonding/Requirement Standard

Transmission Performance Specifications for Field Testing of UTP Cabling Systems Additional Guidance for 4 Pair 100 ohms Category 6 Cabling for 10 GBASE-T Application

IEEE - Institute of Electrical and Electronic Engineers IEEE 802.3 AN 10 GBASE T Standards 2006

F.

ICEA - Insulated Cable Engineers Association ICEA S-80-576 Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems Standard for Fiber Optic Premises Distribution Cable

ICEA S-83-596 G.

CFR - Code Of Federal Regulations 47 CFR 68 Connection of Terminal Equipment to the Telephone Network

H.

NFPA - National Fire Protection Association NFPA 70 NFPA 78 National Electric Code Lightning Protection Code

I.

NEMA - National Electric Manufacturer Association NEMA 250 NEMA WD 6 Enclosures for Electrical Equipment Wiring Device - Dimensional Requirements

J.

UL - Underwriters Laboratories Inc.


16715-5 Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

UL 50 UL 1863 1.3 A. B.

Enclosures for Electrical Equipment Standard for Accessories SUBMITTALS: Safety, Communications Circuit

Product Data: Include data on features, ratings, and performance for each component specified. Shop Drawings: Include dimensioned plan and elevation views of each individual component. Show equipment assemblies, method of field assembly, workspace requirements, and access for cable connections. Wiring Diagrams: Show typical wiring schematics including workstation outlets, jack and jack assemblies, patch cords, patch panels, fiber-optic boxes and other equipments. Samples: For workstation outlets (TO), jacks, jack assemblies, and faceplates for color selection and evaluation of technical features. Switches specification and data sheet (if applicable). TRANSPORTATION, HANDLING AND STORAGE:

C.

D. E. 1.4 A. B.

Deliver equipment and components in factory-fabricated containers or wrappings, which properly protect equipment from damage. Store equipment and components in original packaging. Store inside in a wellventilated space protected from weather, moisture, soiling, humidity, and extreme temperatures. Handle equipment and components carefully to prevent damage, breaking, and scoring of finishes. Do not install damaged units or components; replace with new. WARRANTY:

C. 1.5 A.

The manufacturer must guarantee to the End User that the products referenced within the specific Warranty Modules (Class E System) when correctly installed in accordance with installation guidelines: Will be free from product defects in materials and workmanship Are guaranteed to exceed the Class E Channel and Permanent Link requirements as specified in ISO/IEC 11801:2002 Supports the following application (not limited): 10BASE T Ethernet 100BASET Fast Ethernet 1000BASE TX Gigabit Ethernet 10GBASE-T 155Mbit ATM 1000Mbit ATM (CB1G) 10 GBASE-T For a duration of 20 years
16715-6 Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

B.

All components including the patch cords have to be produced by the same cabling system manufacturer to ensure warranted performances and applications against the standards. QUALITY ASSURANCE:

1.6 A.

Manufacturer's Qualifications: The items provided under this contract will be from manufacturers that have a minimum of 5 years experience in producing the types of systems and equipment specified. Installer Qualifications: Specialist subcontractor with at least 5 years of successful installation experience with projects utilizing data system similar to that required for this project. Subcontractor shall be subject to approval of Engineer. Materials and installation shall comply with the specified Codes and Standards. Single Source Responsibility: All components and accessories shall be product of single manufacturer except for cables. ENVIRONMENTAL REQUIREMENTS:

B.

C. D. 1.7 A.

Connecting hardware shall be rated for operation under ambient conditions of 0 to 60 degrees C and in the range of 0 to 95 percent relative humidity, noncondensing.

PART 2 - PRODUCTS 2.1 A. SYSTEM DESCRIPTION: The voice and data communication cabling shall consist of horizontal and backbone cables and connecting hardware to transport data (including LAN/WAN) and voice (telephone) system signals between related as shown on drawings. Numbers of outlets shall be as shown on drawings and documents. The Data Local Area Network (LAN) Sub-Contractor shall coordinate his work with telephone equipment Sub-Contractor. The system shall support CATEGORY 6A 10GBASE -T 2.2 A. GENERAL: Materials and equipment shall be the standard products of a manufacturer regularly engaged in the manufacture of the products and shall be of latest technology/version available at the time of installation, and has been in satisfactory use for at least 1 year prior to installation. Materials and equipment shall conform to the respective publications and standards specified herein and to the applicable requirements of ISO/IEC 11801,2002 EIA/TIA 568 and to all additional requirements of IEEE 802.3 AN and TIA TSB 155 and ISO/IEC TR 24750 to support the 10 GBASE-T application over 100 meters channel. HORIZONTAL CABLING: A. Horizontal Distribution Cable: Horizontal distribution cable shall be 10 G (UTP) Category 6A. The cable shall be a four, thermoplastic-insulated, individually
16715-7 Voice & Data Communication Cabling

2.3

ITCC in Riyadh Residential Complex J10-13300

twisted pairs of copper conductors; No.24 AWG, color-coded; enclosed in PVC jacket or a material that does not give off toxic fumes (Low Smoke Zero Halogen - LSZH) in case of fire and offer flame propagation retardant properties. Cable shall be designed to support the IEEE 802.3 1000Base.T (Gigabit Ethernet), potentially 1.2 Gbps ATM and 2.4 Gpbs ATM as well as analogue broadband video up to 550 MHz. Cable shall meet or exceed attenuation and NEXT requirements in ISO/IEC 11801, CENELEC EN50173 and EIA/TIA 568A. All pairs must have impedance of 100 Ohms, with a tolerance of +/- 15 Ohms. In the construction of the cable cross-talk performance shall be maintained using a C3 (Central dielectric Cross-talk Cancellation) member set between the 4 pairs. Insulators in standard Blue/White, Orange/White, Green/White, Brown/White colors must cover the conductors. Cable shall be of latest technology/speed manufactured and available at the installation time. This cable shall be used for horizontal run between data, voice (telephone), clock and security system outlets and floor communicable cabinet. B. Telecom Outlets (TO): Telecom outlets shall be CAT 6A (UTP) RJ45. Each connector shall provide both T568A and T568B color code identification for the pins at the rear of the connector. The punch down is to be in accordance with the T568B color code. Reassignment of pairs is forbidden. All conductors from the CAT6A 4 pair cable shall be terminated on the respective contacts. To avoid installation errors, the wire organizer of the snap-in connector must be identified by the same standard color coding as the wires. All CAT 6A (UTP) RJ45 connectors shall be fully compliant with the ISO/IEC 11801:2002 standard. The presentation of the outlet shall provide for labeling and identification. A transparent window shall protect the labeling tag. All outlets shall be equipped with shutters. Snap-in Format (Where required): The dimensions of the Snap-in format connectors shall be H x W x D: 19.5 mm x 16.8 mm x 35.7 mm. The same format connectors (unscreened) shall be used on each link. The connector fits in specific structural hardware for Snap-in format of third parties. If not available, the Snapin connector can be used in combination with a keystone clip and specific structural hardware for keystone connectors. . C. Copper Patch Panels (RJ45): Patch panels must have 19 equipment practice dimensions to permit mounting in standard cabinets, racks or bays. Provide 24 port Snap-in format (Modular) patch panels equipped with a cable management mechanism that provides strain relief, earthing and grounding features. The presentation of the Patch Panel shall provide for labeling using a printed numbering system. The connector shall provide both T568A and T568B colour code identification for the pins at the rear of the connector. Patch panel outlets must have each Category 6A (UTP) RJ45 connector, connected separately. The punch down is to be in accordance with the T568B color code. Reassignment of pairs is forbidden. The screened connectors from modular patch panel shall provide termination facilities for the drain wire of each category 6A F/UTP cable. All conductors from the 4 pair cable are to be terminated on the respective contacts. To avoid installation errors, IDC blocks must be identified by the same standard color coding as the wires. Each patch panel shall provide a means to locate and clamp the incoming cables without causing damage to the cables or affecting the performance of link. The
ITCC in Riyadh Residential Complex J10-13300 16715-8 Voice & Data Communication Cabling

installer must avoid any risk of cable pinching or compression during the installation of cable. Therefore use of Velcro cables is preferred, In the rack, the Patch Panels shall be separated by metallic patch-guides that have a closed front to protect the patch cords. The height of these guides will be 1U or 2U depending on the layout of the rack. The metal frame of patch panel must not be earthed to the cabinet with a separate earth strap if the patch panels automatically make contact with the metal frame of the cabinets. If the cabinet is not designed to provide the panels with automatic earth, then the patch panels must be connected with separate earth strap to the earth key. D. Patch Cords: To achieve a Class E 10 G Channel performance all Patch Cords will be Category 6A rated. All patch cord cable will be made from PVC or Low Smoke Zero Halogen (LSZH) material (when used in plenum areas). 1. Data Patch Cords: The standard color offered shall be orange for LSZH jacket and grey for PVC jacket. The Category 6A cords must be fitted with Category 6A RJ45 plugs, booted at each connector. The characteristic impedance of the pairs must be identical to that of the horizontal cables. The Patch Cords shall have a guaranteed performance level of greater than 750 insertions without degradation to the performance level of the solution. The cable used for the Patch Cords shall be Category 6A PVC or LSZH patch cable. The cable shall be a 4 twisted pair cable with stranded conductors. Trace ability numbers should accompany the cables supplied from the manufacturers packaging to assist in quality validation of the installed cable. All pairs must have an impedance of 100 Ohms. E. Class E link or channel: Manufacturer should demonstrate guaranteed minimum worst-case performance to compliant with class E channel performance according to the ISO/IEC 11801: 2002 standard. Components used must be compliant with the category 6A standard mentioned above and the manufacturer should be able to demonstrate independent Delta verification. The performance of both the components and the link and channel should show stable performance up to 500 MHz in order to allow for possible future applications requiring crosstalk cancellation up to 500 MHz. The system supplier must be able to demonstrate in house design and manufacturing expertise for all components used (e.g. cables, outlets, panels and cords) in order to ensure compatibility of system elements

2.4 A.

BACKBONE CABLING: Data Backbone: This backbone will link the Switches located in the Floor Distributors (FD) to the Data network server through the Building Distributor (BD). 1 Optical Fiber Cable: The cable shall be suitable for connector manufacturer termination processes (LC, SC or ST connectors). Fiber splicing method should be used for termination of Fiber Cables using fiber pigtails
16715-9 Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

manufactured by the same vendor. Construction: Tight buffered with water blocking Aramid/Glass yarn reinforcements or tape and shall be suitable for indoor or outdoor use making it ideal for short campus links without the use of transition joints. The cable strength member shall be glass yarn laid longitudinally between the fibers and the inside wall of the outer jacket. The cable shall be dielectric construction, i.e. with no metallic content. The cable shall be a dry construction i.e. with no gel content. The jacket material shall be waterproof LSZH with a minimum fire performance of IEC 332 part 3C. 2 Multimode Fiber Optic Cable: The Cabling system must be designed and installed according to ISO 11801 OM2 & OM3 compliant and should also meet EN50173 2nd editions and TIA/EIA 568B3. The Cable shall have 6 or 12 or 24 cores, 50/125 m universal distribution cable with improved performance. Gigabit Ethernet should be supported up to a minimum distance of 550 m. If required, extended distance option with laser optimization should be available to increase this distance up to 800 m in case of 850 nm fiber and 2,000 m in case of 1300 nm. In case 10G Ethernet application has to be used, the fiber shall be OM3 compliant and should support transmission of 10G signal up to a distance of 300 m for 850 nm fiber and 550 m for 1300 nm fiber. 3 Single Mode Fiber Optic Cable: The Cabling system must be designed and installed according to ISO 11801 OS1 compliant and should also meet EN50173 2nd editions and TIA/EIA 568B3. The Cable shall have 6 or 12 or 24 cores, 9.2/125 m universal distribution cable with improved performance. Gigabit Ethernet should be supported up to a distance of 10,000 m using 1300 nm fiber. In case 10G Ethernet application has to be used, the fiber should support transmission of 10G signal up to a distance of 10,000m for 1300nm fiber. 4 Optical Fiber Patch Panel: Optical fiber Patch Panels shall be mounted in 19" frames of the cabinets. The patch panels shall be equipped with a mechanism that ensures the retention and support of incoming cables. An Earth Key shall be provided within the patch panel to earth any metallic part of the cable. The patch panel shall be designed with a sliding mechanism enabling front side installation and maintenance work to be carried out without having to remove the entire panel. The patch panel shall provide facilities to recess the front connector plate deeper than the front of the 19" rails of the cabinet. This will provide sufficient bend radius for the patch cords once connected to the panel. This shall also prevent damage to the patch cords when the cabinet doors are closed. Direct Termination of the connectors on to the fibers as well as splicing of pigtails shall be possible. The Patch Panel shall provide management for 1m of fiber per link after breaking the fibers out from the cable. The Patch Panel shall support the connector type specified for this installation. For multimode fiber links, these can be LC, SC and ST. The panel-mounted
ITCC in Riyadh Residential Complex J10-13300 16715-10 Voice & Data Communication Cabling

couplers shall be protected on the front presentation side of the patch Panel for safety purposes. 5 Optical Fiber Patch Cords: The Fiber adapters will be connected to the active equipment by means of duplex patch cords 2LC-2LC, 2 SC-2 SC or 2 ST2ST as per client site standard. The patch cords consist of 50/125 microns fibers and a LSHF-FR jacket. The SC or ST connectors shall comply with the International standard IEC 74-13. The patch cords should be available in lengths of 2 and 5 meters. To avoid mix of patch cords built around different types of fiber, cords produced with LASER-optimized fiber will be used for both OM1 and OM2 optical fiber cables. When using OM3 optical fiber cables, patch cords produced with the same OM3 fiber have to be installed. 6 2.5 A. Fiber cables shall interface and connect to fiber interface unit at both ends as part of the fiber contractor work.

CABINETS: The metal cabinets shall have a footprint of 800x800 mm. In the frames 19 components can be mounted by means of the standard cage nuts. The front door consists of a metal framework with hinges and a central security glass. The side panels and the panel in the back have to be equipped with a hinge on the left or the right in order to facilitate the access to the equipment. A 42 HU cabinet is preferred providing enough space for active equipment. For an orderly cord storage and easy to manage installation, the following accessories shall be used: Closed 1 or 2 HU patch guides between the patch panels; Lateral cable rings installed at both sides of the frames. The patch rings can be removed very easily by rotation and have to be located on the front rails of the 19" frames in the cabinets. The cabinets should be supplied with: C. A power bar with 6 * 240VAC electrical sockets and a mains isolator switch Up to 4 fans (240VAC) for expelling air, approximately 220W each

B.

Earthing has to be achieved by means of the 19" frame attachments, thus ensuring continuity. The cabinet and frame assembly when installed will also serve as equi-potential plane so that damaging external EMI currents can be drained off. To this end, the inter-cabinet connections shall also be made off by extending the earth connection from cabinet to cabinet in a suite of cabinets. The suite of cabinets shall be connected to the grounding network of the building. The Earth key of the cabinet must be connected to the protective earth. The dimension of the earth conductor is 6mm. If no or only a poor protective earth system is present in the building, a separate earthing to the main earth terminal of the building is required. The dimensions of the conductor should then be 16mm. Cabinet Mounted UPS (Uninterruptible Power Supply): To enable Power over Ethernet (PoE) a smart UPS shall be supplied and installed as a part of the cabinet. The UPS shall have the following minimum features:
16715-11 Voice & Data Communication Cabling

D.

E.

ITCC in Riyadh Residential Complex J10-13300

1.

Output a. b. c. d. Output Power Capacity: 2250 Watts/3000 VA Max. Configurable Power: 2250 Watt/3000 VA Nominal Output Voltage: drawings 230 V or as indicated on power

Typical Back Time: At full load 5.7 minutes (2250 Watts)

2.

Communications & Management a. b. c. Interface Port(s): DB-9 RS-232, SmartSlot Control Panel: LED status display with load and battery bar-graphs and on line: on battery: replace Battery: and overload indicators Alarm when on battery: distinctive low battery alarm: configurable delays

3. 4. 5. 6. 7. 8. 9. 10.

Rack height for UPS shall be 5U or as per manufacturer standards Operating environment shall be 0 - 400C The system shall conform to EN 50091-1 and EN 50091-2 Output Voltage Notes: configurable to 230 nominal output voltage or as required on power drawings Output voltage distortion: Less than 5% at full load Output frequency: 57 63 Hz for 60 Hz nominal Waveform type: Sine wave Output connection: a. b. c. (8) IEC 320 C 13 (1) IEC 320 C 19 (3) IEC Jumpers

11.

Input a. b. c. d. e. Nominal Input: Voltage: 230 V or as indicated on power drawings Input frequency: 60 Hz 3 (auto sensing) Input connections: IEC 320 C20 or as required on site Input voltage range for main operation 174 286 V or as required on site Input voltage adjustable range for main operation: 168 302 V or
16715-12 Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

as required on site 12. Batteries: a. b. c. PART 3 - EXECUTION 3.1 INSTALLATION: A. B. C. The entire system shall be installed by specialist subcontractor approved by the Engineer. Installation shall be in accordance with the approved drawings and manufacturer's written instructions. System components and appurtenances shall be installed in accordance with ISO/IEC 11801, manufacturer's written instructions and as shown. Necessary interconnections, services, and adjustments required for a complete and operable signal distribution system shall be provided. Components shall be labeled in accordance with EIA/TIA 606. Penetrations in fire-rated construction shall be firestopped. Conduits, outlets and raceways shall be installed in accordance with Section 16050 - BASIC ELECTRICAL MATERIALS AND METHODS. Wiring shall be installed in accordance with ISO/IEC 11801, EIA/TIA 568A and EIA/TIA 568B. Cables shall not be installed in the same cable tray, utility pole compartment, or floor trench compartment with ac power cables. Horizontal Distribution Cable: The rated cable pulling tension shall not be exceeded. Cable shall not be stressed such that twisting, stretching or kinking occurs. Cable shall not be spliced. Cable shall not be run through structural members or in contact with pipes, ducts, or other potentially damaging items. Placement of cable parallel to power conductors shall be avoided, if possible; a minimum separation of 300 mm shall be maintained when such placement cannot be avoided. Cables shall be terminated; no cable shall contain unterminated elements. Minimum bending radius shall not be exceeded during installation or once installed. Cable ties shall not be excessively tightened such that the transmission characteristics of the cable are altered. Riser and Backbone Cable: Vertical cable support intervals shall be per manufacturers recommendations. Cable bend radius shall not be less than ten times the outside diameter of the cable during installation and once installed. Maximum tensile strength rating of the cable shall not be exceeded. Cable shall not be spliced. Data Outlets: As a minimum each jack shall be labeled as to its function and a unique number to identify cable link. Minimum of 6 inches of slack cable loosely coiled into the data outlet boxes. Minimum manufacturers bend radius for each type of cable shall not be exceeded. Type: Maintenance-free sealed Lead-Acid battery with suspended electrolyte leak proof Typical recharge time: 3 hour(s) Typical recharge time at half load: 19.2 minutes (1125 Watts)

D.

E.

F.

ITCC in Riyadh Residential Complex J10-13300

16715-13

Voice & Data Communication Cabling

G.

Unshielded Twisted Pair Patch Panels: Patch panels shall be mounted in equipment racks with sufficient modular jacks to accommodate the installed cable plant plus 10 percent spares. Cable guides shall be provided above, below and between each panel. Fiber Optic Patch Panels: Patch Panels shall be mounted in equipment racks with sufficient ports to accommodate the installed cable plant plus 10 percent spares. A slack loop of fiber shall be provided within each panel. Loop shall be 900 mm in length. The outer jacket of each cable entering a patch panel shall be secured to the panel to prevent movement of the fibers within the panel, using clamps or brackets specifically manufactured for that purpose. For excavation and backfilling refer to Section 02200 - EARTHWORK.

H.

I. 3.2

ELECTRICAL SAFETY: A. Separation of telecommunication circuits from the building electrical system and electrical equipment shall conform to the latest publications of Articles 800-3 (a) and 820-13 of National Electric Code (NEC). An earth or ground shall be provided and extended to the termination box and connected to each station protector. The earth or ground shall be installed and bonded in accordance with Article 250, 800 and 820 of National Electric Code (NEC).

B.

3.3

TESTING: A. General: After installation of entire system and prior to acceptance of work, manufacturer's standard tests shall be conducted in the presence of the Engineer to show proper operation of each equipment and the system entirely. The manufacturer of the cabling system shall provide copper (Data) and optical fiber testing procedures that clearly describes the tools and settings to be used to ensure correct measurements of the system. The result of testing shall meet or exceed the requirements of ISO/IEC 11801, latest edition and ISO/IEC TR 24750. Testing of Class E: 100 % of the installed horizontal links shall be tested. The testing procedure has to comply with the standard ISO/IEC 11801: 2002 for Class E, according to the procedure for Channel or Permanent Link. The measurements shall be done using Level III testing equipment. Channel testing shall be preferred. Channels shall be tested to support 10 G 500 MHz

B.

The testers have to be calibrated according to the recommendations made by the supplier of the testing equipment. The following parameters have to be tested Pair continuity (wiremap) Pair length DC Loop resistance per pair Insertion loss (Attenuation) per pair NEXT and Powersum NEXT for every pair combination FEXT and Powersum FEXT for every pair combination The ACR (ratio NEXT/ insertion loss) for every pair combination Return Loss (impedance match, retransmitted signal)
16715-14 Voice & Data Communication Cabling

ITCC in Riyadh Residential Complex J10-13300

The complete test results of all the installed links or channels shall be collected in a certification file. It is preferred to have the test result in electronic format to facilitate the certification procedure. Apart from all the test results mentioned above, a few more documents shall be added to the file: a list of material used for the project, a design of the network, a Cable schedule per distributor and finally all the necessary co-ordinates of the persons responsible of the project. C. Vertical Fiber Testing: The procedure shall comply with the ISO/IEC 14763-3 standard. The ISO/IEC 14763 standard specifies the implementation and operation of customer premises cabling. The part 3 of this ISO document (147633) details test procedures for optical fiber cabling designed in accordance with ISO/IEC 11801:2002 and installed according to the recommendations of ISO/IEC 14763-2 (Planning and installation of customer premises cabling). For Multimode fibers, the test procedure is based on the use of the one-jumper method specified by Method 2 of IEC 61280-4-1. This procedure is used for testing links for which the connector loss is a significant portion of the total link attenuation. This is the case for LAN premises links. For Singlemode fibers, the test procedure to be applied is the same and is based on the use of the one-jumper method specified by Method 1a of IEC 61280-4-2. Fiber-optic Tests applied to links and exclude equipment and work area cord. OF Attenuation testing is used to verify the initial performance of the installed link. All 100 % of the installed OF links have to be tested and must pass the acceptance criteria. The attenuation of the link is measured using the insertion loss method. This method uses an optical source and an optical power meter to compare the difference between two optical power levels. When testing multimode optical fiber links with a Light Source and a Power Meter, this measurement kit has to be capable of operating at 850nm and 1300nm for multimode fibers (OM1, OM2 & OM3) 1310nm and 1550nm for singlemode fibers (OS1)

The test scenario with a Light Source and a Power Meter shall be one of the following for each link: Single direction @ 850nm and @ 1300nm for multimode fibers Single direction @ 1310nm and @ 1550nm for singlemode fibers

The use of certification tool is recommended. Those tools are capable of producing a report logging the time of the test the link identification under test, the link length, the attenuation at the window tested and the acceptable link attenuation. The report shall also identify in which direction the testing was implemented. When testing with basic optical source and power meter, the operator will fill up a report logging:
ITCC in Riyadh Residential Complex J10-13300 Voice & Data Communication Cabling

16715-15

The time of the test, The link identification under test, The link length and attenuation at the window tested. The report shall also identify in which direction the testing was implemented. Acceptable link attenuation (To be calculated)

The measured attenuation of the links shall have a lower value than the acceptable link attenuation calculated. END OF SECTION

ITCC in Riyadh Residential Complex J10-13300

16715-16

Voice & Data Communication Cabling