T30U

STANDARD FEATURES
n n n n n n n n n n Mechanical governor Mechanically welded chassis with antivibration suspension Power circuit breaker Radiator for wiring Tof 50C [122F] max with mechanical fan Protective grille for fan and rotating parts 9dB(A) silencer supplied separately Charged DC starting battery with electrolyte 12 V charging alternator and starter Supplied with oil and coolant -30C User manual and commissioning guide

Engine MITSUBISHI , S4S-SD Alternator MECC ALTE , ECO28VL

Voltage 480/277 440/254 240/120 230/115 220/127 208/120

Power ESP kWe/kVA 30 / 38 30 / 38 29 / 36 26 / 33 30 / 38 29 / 36

Power PRP kWe/kVA 27 / 34 27 / 34 26 / 33 24 / 30 27 / 34 26 / 33

Standby Amps 46 50 87 83 100 100

Dimensions Length: 1700mm [67in] Width: 896mm [35in] Heigth: 1144mm [45in]

Weight 660kg [1455 lbs] Net 760kg [1676 lbs] Gross

POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1 ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.

TERM OF USE
Standard reference conditions 25 C Air Intlet Temp, 100 m A.S.L. 60 % relative humidity. All engine performance data based on the above mentioned maximum continuous ratings.

Type

dB(A)@1m

dB(A)@7m

M127

76

66.3

Dimensions Length: 2080mm [82in] Width: 960mm [38in] Heigth: 1415mm [56in] Length: 2160mm [85in] Width: 966mm [38in] Heigth: 1582mm [62in]

Weight 890kg [1962lbs] Net 990kg [2183lbs] Gross 1066kg [2350lbs] Net 1296kg [2857lbs] Gross

Tank

100 L

M127-DW

76

66.3

230 L

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.

SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2 Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

ENGINE SPECIFICATIONS
Manufacturer / Model Cylinder Arrangement Displacement Bore and Stroke Compression ratio Rated RPM Piston Speed Max. stand by Power at rated RPM Frequency regulation, steady state BMEP Governor : type Exhaust temperature Exhaust gas flow Max back pressure 110% (Stand By power ) 100% (of the Prime Power) 75% (of the Prime Power) 50% (of the Prime Power) Max. fuel pump flow Total oil capacity w/filters Oil Pressure low idle Oil Pressure rated RPM Oil consumption 100% load Oil capacity carter Heat rejection to exhaust Radiated heat to ambiant Heat rejection to coolant Max. intake restriction Engine air flow Radiator & engine capacity Max water temperature Outlet water temperature Fan power Fan air flow w/o restriction Available restriction on air flow Type of coolant Thermostat PM CO Nox HC MITSUBISHI S4S-SD , 4-strokes, Athmo , [N/A] 4 X L 3.33L [203.2C.I.] 94mm [3.7in.] X 120mm [4.7in.] 22 : 1 1800 Rpm 7.2m/s [23.6ft./s] 35.4kW [47BHP] < 5% 7.28bar [105psi] MECA 600C [1112F] 122L/s [259cfm] 680mm CE [27in. WG] 11.5L/h [3.0gal/hr] 9.8L/h [2.6gal/hr] 8.2L/h [2.2gal/hr] 6L/h [1.6gal/hr] 36L/h [9.5gal/hr] 10L [2.6gal] 1bar [14.5psi] 5bar [72.5psi] 0.11L/h [0.029gal/hr] 9L [2.4gal] 35kW [1990Btu/mn] 6kW [341Btu/mn] 35kW [1990Btu/mn] 200mm CE [8in. WG] 45L/s [95cfm] 8.9L [2.4gal] 100C [212F] 93C [199F] 1.5 kW 1m3/s [2119cfm] 10mm CE [0.4in. WG] Gencool 76.5-90 C N/A N/A N/A N/A

STANDARD FEATURES

EXHAUST SYSTEM

FUEL SYSTEM

OIL SYSTEM

THERMAL BALANCE AIR INTAKE

COOLANT SYSTEM

EMISSIONS LEVEL

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.

SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2 Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

ALTERNATOR SPECIFICATIONS
Manufacturer Type Number of phase Power factor (Cos Phi) Altitude Overspeed Pole : number Exciter type Insulation : class, temperature rise Voltage regulator Total harmonics (TGH/THC) Wave form : NEMA = TIF TGH/THC Wave form : CEI = FHT TGH/THC Bearing : number Coupling Voltage regulation 0 to 100% load Recovery time (20% Volt dip) ms SkVA with 90% of nominal sustained voltage (at 0.4PF) Continuous nominal rating @ 40C Standby rating @ 27C Efficiencies @ 4/4 load Air flow Short circuit ratio;50 (Kcc) Direct axis synchro reactance unsaturated (Xd) Quadra axis synchro reactance unsaturated (Xq) Open circuit time constant;50 (Tdo) Direct axis transient reactance saturated (Xd) Short circuit transient time constant (Td) Direct axis subtransient reactance saturated (Xd) Subtransient time constant (Td) Quadra axis subtransient reactance saturated (Xq) Zero sequence reactance unsaturated (Xo) Negative sequence reactance saturated (X2) Armature time constant (Ta) No load excitation current (io) Full load excitation current (ic) Full load excitation voltage (uc) Recovery time (Delta U = 20% transitoire) Motor start (Delta = 20% perm. Or 50% trans.) Transient dip (4/4 charge) PF : 1.8 AR No load losses Heat rejection MECC ALTE ECO28VL 3 0.8 1000 [N/A] 4 NO H /H SR7/2 [N/A] [N/A] 2 1 Direct [N/A] [N/A] N/A 36 kVA 36.3 kVA 86.5 % 0.096m3/s [203.41cfm] 0.62 165 % 71 % 0.93 ms 15.4 % 46 ms 8.8 % 12 ms 19 % 2.8 % 13.2 % 11 ms [N/A] [N/A] [N/A] [N/A] [N/A] [N/A] [N/A] [N/A]

GENERAL DATAS

OTHER DATAS

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.

SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2 Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com

CONTROL PANEL

Standard

NEXYS
Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faults Oil pressure, water temperature, Overcrank, Overspeed ( >60 kVA), Min/max alternator, Low fuel level, Emergency stop Engine parameters Hours counter, Engine speed, Battery voltage, Fuel level, AIr preheating

Option

TELYS
Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faults Oil pressure, water temperature, No start-up, Overspeed, Min/max alternator, Min/max battery voltage, Low fuel level, Emergency stop Engine parameters Hours counter, Oil pressure, Water temperature, Engine speed, Battery voltage, Fuel level

OPT2 OPT3

This document is not contractual - The SDMO company reserves the right to modify any of the characteristics stated in this CD Rom without notice, in a constant effort to improve the quality of its products.

SDMO Industries 12bis rue de la Villeneuve CS 92848 29 228 BREST CEDEX 2 Tel +33 (0)2 98 41 41 41 Fax : +33 (0)2 98 41 63 07 www.sdmo.com