Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Rising energy and general building services running costs have led end users to expect far more than just cooling and heating from their air conditioning. A truly complete and acceptable system therefore, must be energy efcient, economic to run, easy to install, exible, reliable and user friendly. Fresh air must also be supplied without increasing energy consumption and central management and control facilities have gained in importance, particularly for medium to large sized buildings. The Daikin Hi-VRV system meets all these requirements:
Air Conditioning
HRV Ventilation
VRV air conditioning can be found in ofces, restaurants, theatres, hospitals, universities, museums, shops - in short, in any location where the provision of a balanced, pleasant working environment can improve the lifestyle and comfort of the individual.
VRVIII RXYSQ4-6P7V3B new RXYSQ4-6P7Y1B RXQ5-18P7W1B(A) RXYQ5-18P7W1B(A) RXYQ20-36P7W1B(A) RXYQ38-54P7W1B(A) RXYQ16-36P7W1B new REYQ18-48P7Y1B VRVII REYQ8-48M8W1B(A) RWEYQ-MY1 INDOOR UNITS 1. Cassette units new FXFQ-P7VEB FXZQ-M8V1B FXCQ-M8V3B FXKQ-MAVE 2. Concealed ceiling units FXDQ-M8V3B FXDQ-P/NA FXSQ-M8V3B FXMQ-MAVE 3. Wall mounted units FXAQ-MAVE 4. Ceiling suspended units FXHQ-MAVE FXUQ-MAV1 5. Floor standing units FXNQ-MAVE FXLQ-MAVE 6. Outdoor air processing unit FXMQ-MFV1 SELECTION PROGRAMMES HRV VAM-FA VKM-GA(M)
132 133 134 135 136 137 138 139 140 141
143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159
131
RXYSQ4-6P7V3B
VRVIII-S Inverter heat pump
z z z z z z z
High COP values Maximum 9 indoor units per outdoor unit Silent operation Small capacities - 4, 5 & 6HP Super wide range of indoor units Slim & exible design Space saving outdoor unit
RXYSQ-P7V3B
HEAT PUMP
Outdoor Unit Capacity range Capacity Dimensions Weight Sound Level Cooling Heating (Height x Width x Depth) Sound Power Cooling Sound Pressure Cooling Heating Cooling Heating Cooling Min~Max Heating Min~Max HP kw kw mm kg dBA dBA dBA m/min m/min CDB CWB RXYSQ4P7V3B 4 11.2 12.5 RXYSQ5P7V3B 5 14.0 16.0 1,345x900x320 125 67 51 53 106 105 -5.0~46 -20~15.5 R-410A 1~/230V/50Hz 8 9.52 / 15.9 / 26 x 3 300 RXYSQ6P7V3B 6 15.5 18.0
66 50 52 102
69 53 55
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas/Drain Max total length
6 mm m
9 9.52 / 19.1 / 26 x 3
132
RXYSQ4-6P7Y1B
VRVIII-S Inverter heat pump
z z z z z z z
High COP values Maximum 9 indoor units per outdoor unit Silent operation Small capacities - 4, 5 & 6HP Super wide range of indoor units Slim & exible design Space saving outdoor unit
RXYSQ-P7Y1B
HEAT PUMP
Outdoor Unit Capacity range Capacity Dimensions Weight Sound Level Cooling Heating (Height x Width x Depth) Sound Power Cooling Sound Pressure Cooling Heating Cooling Heating Cooling Min~Max Heating Min~Max HP kw kw mm kg dBA dBA dBA m/min m/min CDB CWB RXYSQ4P7Y1B 4 11.2 12.5 RXYSQ5P7Y1B 5 14.0 16.0 1,345x900x320 120 67 51 53 106 105 -5.0~46 -20~15.5 R-410A 3~/280-415V/50Hz 8 9.52 / 15.9 / 26 x 3 300 RXYSQ6P7Y1B 6 15.5 18.0
66 50 52 102
69 53 55
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas/Drain Max total length
6 mm m
9 9.52 / 19.1 / 26 x 3
133
RXQ5-18P7W1B(A)
VRVIII inverter cooling only
z z z z z z z
z z z
Wide range of indoor units: 13 different models in a total of 75 variations Compact size of outdoor units Increased COP 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Easy installation thanks to automatic refrigerant charging operation, automatic test operation Quiet operation Leak detection function
RXQ5P
RXQ8-12P
RXQ14-18P
COOLING ONLY
RXQ-P(A) Capacity range Capacity Power input (Nominal) Dimensions Weight Sound Level Cooling Cooling (Height x Width x Depth) HP kw kw mm kg dBA dBA m/min CDB 5 5 14.0 3.52 1,680x635x765 157 72 54 95 8 8 22.4 5.56 185 78 57 171 58 185 196 -5.0~43.0 R-410A 3N~/400V/50Hz 19 12.7 / 28.6 10 10 28.0 7.42 1,680x930x765 238 80 60 233 12 12 33.5 9.62 14 14 40.0 12.4 314 16 16 45.0 14.2 1,680x1,240x765 18 18 49.0 16.2 322 83 63 239
Sound Power Cooling Sound Pressure Cooling Air Flow Rate (nominal at 230V) Cooling Operation Range Cooling Min~Max Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas
mm
8 9.5 / 15.9
13 9.5 / 19.1
16 9.5 / 22.2
23 12.7 / 28.6
26
29 15.9 / 28.6
134
RXYQ5-18P7W1B(A)
VRVIII Inverter heat pump Small footprint combination
z z z
z z z z z z z
z z z
Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a total of 75 variations Flexible combination of outdoor units: small footprint combination, high COP combination or any other combination of your choice Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Easy installation thanks to automatic refrigerant charging operation, automatic test operation Quiet operation Leak detection function
RXYQ5P
RXYQ8-12P
RXYQ14-18P
HEAT PUMP
RXYQ-P(A) Capacity range Capacity Power input (Nominal) Dimensions Weight Sound Level Air Flow Rate (nominal at 230V) Operation Range Cooling Heating Cooling Heating (Height x Width x Depth) Sound Power Sound Pressure Cooling Heating Cooling Heating Cooling Cooling HP kw kw kw kw mm kg dBA dBA m/min m/min CDB CWB 5 5 14.0 16.0 3.52 4.00 1,680x635x765 159 72 54 95 95 8 8 22.4 25.0 5.56 5.86 187 78 57 171 171 58 185 185 196 196 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 19 1000 10 10 28.0 31.5 7.42 7.70 1,680x930x765 240 80 60 233 233 12 12 33.5 37.5 9.62 9.44 14 14 40.0 45.0 12.4 11.30 316 16 16 45.0 50.0 14.2 12.90 1,680x1,240x765 18 18 49.0 56.5 16.2 15.30 324 83 63 239 239
Min~Max Min~Max
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
mm m
8 9.5 / 15.9
13 9.5 / 19.1
16 9.5 / 22.2
23 12.7 / 28.6
26
29 15.9 / 28.6
135
RXYQ20-36P7W1B(A)
VRVIII Inverter heat pump Small footprint combination
z z z
z z z z z z z
z z z
Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a total of 75 variations Flexible combination of outdoor units: small footprint combination, high COP combination or any other combination of your choice Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Easy installation thanks to automatic refrigerant charging operation, automatic test operation Quiet operation Leak detection function
RXYQ20-24P
RXYQ26-30P
RXYQ32-36P
HEAT PUMP
RXYQ-P(A) Modules RXYQ8P RXYQ10P RXYQ12P RXYQ14PA RXYQ16PA RXYQ18PA Cooling Heating Cooling Heating (Height x Width x Depth) Sound Power Sound Pressure Cooling Heating Cooling Heating Cooling Cooling HP kw kw kw kw mm kg dBA dBA m/min m/min CDB CWB 20 1 1 22 1 1 24 26 1 28 1 2 1 1 1 26 71.4 81.5 21.8 21.2 1 28 77.0 88.0 23.6 23.0 185 + 239 185 + 239 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 45 1000 1 30 82.5 94.0 25.8 24.7 1 32 89.0 102.0 28.6 26.6 1 1 34 94.0 107.0 30.4 28.2 2 36 98.0 113.0 32.4 30.6 30 32 34 36
Capacity range Capacity Power input (Nominal) Dimensions Weight Sound Level Air Flow Rate (nominal at 230V) Operation Range
Min~Max Min~Max
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
32 mm m 15.9 / 28.6
35
39 15.9 / 34.9
42
49 19.1 / 34.9
52
55
58 19.1 / 41.3
136
RXYQ38-54P7W1B(A)
VRVIII Inverter heat pump Small footprint combination
RXYQ38-42P
z z z
RXYQ44-48P
RXYQ50-54P
z z z z z z z
z z z
Increased outdoor unit capacity up to 54 HP Wide range of indoor units: 13 different models in a total of 75 variations Flexible combination of outdoor units: small footprint combination, high COP combination or any other combination of your choice Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Easy installation thanks to automatic refrigerant charging operation, automatic test operation Quiet operation Leak detection function
HEAT PUMP
RXYQ-P(A) Modules RXYQ8P RXYQ10P RXYQ12P RXYQ14PA RXYQ16PA RXYQ18PA Cooling Heating Cooling Heating (Height x Width x Depth) Sound Power Sound Pressure Cooling Heating Cooling Heating Cooling Cooling HP kw kw kw kw mm kg dBA dBA m/min m/min CDB CWB 38 1 1 40 1 1 42 44 1 46 1 2 1 1 2 2 46 48 126.0 132.0 145.0 151.0 39.8 42.0 38.3 40.0 171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 61 64 19.1 / 41.3 1000 1 38 105.0 119.0 31.4 30.6 1 40 111.0 126.0 33.2 32.4 1 42 116.0 132.0 35.4 34.2 2 44 120.0 138.0 38.0 36.5 2 50 138.0 158.0 44.8 41.9 1 2 52 143.0 163.0 46.6 43.5 3 54 147.0 170.0 48.6 45.9 48 50 52 54
Capacity range Capacity Power input (Nominal) Dimensions Weight Sound Level Air Flow Rate (nominal at 230V) Operation Range
Min~Max Min~Max
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
mm m
137
RXYQ16-36P7W1B
VRVIII Inverter heat pump High COP combination
z z z z z z z z
z z z
Wide range of indoor units: 13 different models in a total of 75 variations Compact size of outdoor units Increased COP Increased external static pressure: up to 78.4Pa 2 steps in night quiet mode: eg. 10HP: 58 dBA, 1st step: 54dBA, 2nd step: 45dBA In line with RoHS Easy combination with HRV Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Easy installation thanks to automatic refrigerant charging operation, automatic test operation Quiet operation Leak detection function
RXYQ8-12P
HEAT PUMP
RXYQ-P Modules RXYQ8P RXYQ10P RXYQ12P Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Min~Max Heating Min~Max HP kw kw kw kw mm m/min m/min CDB CWB 16 2 18 1 1 18 50.4 56.5 13.0 13.6 171 + 171 171 + 171 171 + 185 171 + 185 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 26 12.7 / 28.6 29 1000 32 15.9 / 28.6 35 185 + 185 185 + 185 20 2 20 56.0 63.0 14.8 15.4 22 1 1 22 61.5 69.0 17.0 17.1
Capacity range Capacity Power input (Nominal) Dimensions Air Flow Rate (nominal at 230V) Operation Range
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
mm m
HEAT PUMP
RXYQ-P Modules RXYQ8P RXYQ10P RXYQ12P Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Min~Max Heating Min~Max HP kw kw kw kw mm m/min m/min CDB CWB 24 3 26 2 1 26 72.8 81.5 18.5 19.4 171 + 171 + 185 171 + 171 + 185 28 1 2 28 78.4 88.0 20.4 21.3 171 + 185 + 185 171 + 185 + 185 30 3 30 84.0 94.5 22.3 23.1 185 + 185 + 185 185 + 185 + 185 -5.0~43.0 -20.0~15.0 R-410A 3N~/400V/50Hz 48 19.1 / 34.9 1000 2 32 89.4 100.0 24.8 24.7 171 + 196 + 196 171 + 196 + 196 32 1 34 1 2 34 95.0 107.0 26.7 26.6 185 + 196 + 196 185 + 196 + 196 36 3 36 101.0 113.0 28.9 28.3 196 + 196 + 196 196 + 196 + 196
Capacity range Capacity Power input (Nominal) Dimensions Air Flow Rate (nominal at 230V) Operation Range
24 67.2 75.0 16.7 18.9 171 + 171 + 171 171 + 171 + 171
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
mm m
39 15.9 / 34.9
42
45
52
55
58 19.1 / 41.3
138
REYQ18-48P7Y1B
VRVIII Heat recovery
REYQ18-24P
z
REYQ42-44P
Its operation range for example 8hp to 48hp in 2hp increment steps (21 system combinations), is wider than any of its contemporaries. Its ability to run no less than 64 indoor units in heat recovery format cannot at present be matched by other comparable systems. The ability to control each conditioned zone keeps VRVIII system running costs to an absolute minimum. Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms. Modular design enables Daikin VRVIII outdoor units to be joined together in rows with an outstanding degree of uniformity.
z z z z z
The design of the outdoor units is sufciently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problems. Increased EER/COP Extra low noise during night time operation (step 1: 50 dBA; step 2: 45 dBA). Continuous heating (resulting in a higher integrated heating capacity). Quick cool/heat change over. Typical VRVIII specs (longer piping length, higher distance between outdoor & indoor unit, autocharging).
HEAT RECOVERY
Outdoor unit Capacity range Modules HP REMQ8P REMQ10P REMQ12P REMQ14P REMQ16P Cooling Heating (Height x Width x Depth) 18 18 1 1 20 20 1 1 22 22 1 1 24 24 26 26 1 2 1 1 1 73.0 78.5 81.5 87.5 1,680x930 + 1,240x765 254 + 334 185 + 230 200 + 230 1 1 2 85.0 90.0 95.0 100.0 1,680x1,240 + 1,240x765 334 + 334 230 + 230 28 28 30 30 32 32
Capacity
Dimensions Weight Air Flow Rate (nominal at 230V) Cooling Refrigerant Power Supply Piping connections Liquid (OD) Gas Discharge Gas Oil Equalising
kw kw mm kg m/min
50.4 56.5
55.9 61.5 62.5 69.0 1,680x930 + 930x765 204 + 254 180 + 200
67.0 75.0
180 + 185
HEAT RECOVERY
Outdoor Unit Capacity range Modules HP REMQ8P REMQ10P REMQ12P REMQ14P REMQ16P Cooling Heating (Height x Width x Depth) 34 34 1 1 36 36 1 1 1 95.4 107.0 38 38 1 1 40 40 42 42 1 2 1 44 44 46 46 48 48
Capacity
Dimensions Weight Air Flow Rate (nominal at 230V) Cooling Refrigerant Power Supply Piping connections Liquid (OD) Gas Discharge Gas Oil Equalising
kw kw mm kg m/min
mm mm mm mm
1 1 1 1 2 2 2 3 101.0 107.0 112.0 118.0 124.0 130.0 135.0 113.0 119.0 125.0 132.0 138.0 145.0 150.0 1,680x930 + 930 + 1,240x765 1,680x930 + 1,240 + 1,240x765 1,680x1,240 + 1,240 + 1,240x765 204 + 254 + 334 254 + 254 + 334 254 + 334 + 334 334 + 334 + 334 180 + 185 + 230 180 + 200 + 230 185 + 200 + 230 200 + 200 + 230 185 + 230 + 230 200 + 230 + 230 230 + 230 + 230 R-410A 3~/380-415V/50Hz 19.1 34.9 41.3 28.6 34.9 19.1
139
REYQ8-48M8W1B(A)
VRVII Heat recovery
z z
Its operation range for example 8hp to 48hp in 2hp increment steps (21 system combinations), is wider than any of its contemporaries. Its ability to run no less than 40 indoor units in heat recovery format cannot at present be matched by other comparable systems. The ability to control each conditioned zone keeps VRVII system running costs to an absolute minimum. Only those areas calling for air conditioning need to be cooled or heated and the system can be shut down completely in unoccupied rooms. Modular design enables Daikin VRVII outdoor units to be joined together in rows with an outstanding degree of uniformity. The design of the outdoor units is sufciently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problems.
REYQ8-10M
REYQ12-16M
REYQ
Outdoor Unit Modules REYQ8M REYQ10M REYQ12MA REYQ14MA REYQ16MA Cooling Heating Cooling Heating (Height x Width x Depth) Sound Power Sound Pressure Cooling Heating Cooling Heating Cooling Cooling HP kw kw kw kw mm kg dBA dBA m/min m/min CDB CWB 8 1 10 1 1 1 8 10 22.40 28.00 25.00 31.50 6.97 9.00 6.89 9.31 1,600x930x765 245 78.0 57.0 58.0 175.00 180.00 175.00 180.00 1 12 14 16 33.50 40.00 44.50 37.50 45.00 50.00 10.60 14.24 15.60 10.80 12.90 14.00 1,600x1,240x765 291 337 80.0 60.0 210.00 210.00 18 50.40 56.50 16.00 16.50 20 56.00 63.00 18.00 19.00 22 61.50 69.00 19.60 20.50 12 14 16 18 1 1 20 2 22 1 1 24 1 1 24 68.00 76.50 23.24 22.60 1 26 72.50 81.50 24.60 23.80 1 28 78.00 87.50 26.20 25.30 26 1 1 1 1 30 84.50 95.00 29.90 27.50 1 2 32 89.00 100.00 31.20 28.60 81.0 61.0 355.00 360.00 355.00 360.00 82.0 62.0 390.00 390.00 83.0 63.0 420.00 420.00 -5.0~43.0 -20.0~15.5 R-410A 3N~/400V/50Hz 32 19.1 / 34.9 300 84.0 64.0 570.00 570.00 600.00 600.00 85.0 65.0 630.00 630.00 34 96.00 108.00 32.20 32.10 1 36 101.00 113.00 33.60 33.30 1 38 106.00 119.00 35.20 34.80 28 30 32 34 2 36 2 38 1 1 40 1 1 1 40 113.00 127.00 38.90 37.00 42 1 1 2 42 117.00 132.00 40.20 38.10 2 44 123.00 138.00 41.80 39.60 1 2 46 129.00 145.00 45.50 41.80 3 48 134.00 150.00 46.90 42.90 44 46 48
Capacity range Capacity Power input (Nominal) Dimensions Weight Sound Level Air Flow Rate (nominal at 230V) Operation Range
Min~Max Min~Max
Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Gas Max total length
mm m
19 12.7 / 28.6
20 15.9 / 28.6
22 15.9 / 34.9
34
36
38 19.1 / 41.3
40
140
RWEYQ-MY1
Water-cooled VRV
RWEYQ10M
z z z z z z z
Wide condensing unit range: 10, 20 & 30HP via 1 single refrigerant circuit High COP values: 5.21 nominal value Up to 32 indoor units connectable to a 30HP condensing unit Wide range of indoor units: 13 different models in a total of 75 variations Compact design Operation range (inlet water temperature): 10-45C Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Flexible piping length
HEAT PUMP
Outdoor Unit Capacity range Capacity Power input (Nominal) Cooling Heating Cooling Heating (Height x Width x Depth) HP kw kw kw kw mm kg dBA RWEYQ10MY1 10 26.70 31.50 6.03 6.05 1000x780x550 150 51.0 RWEYQ20MY1 20 53.40 63.00 12.10 12.10 300 54.0 R-410A 3~/380-415V/50Hz 20 15.9/28.6 450 56.0 RWEYQ30MY1 30 80.10 94.50 18.10 18.20
Dimensions Weight Sound Level Sound Pressure Cooling Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Discharge Gas
mm
16 9.5/22.2
32 19.1/34.9
141
RWEYQ-MY1
Water-cooled VRV
RWEYQ10M
z z z z z z z
Wide condensing unit range: 10, 20 & 30HP via 1 single refrigerant circuit High COP values: 5.21 nominal value Up to 32 indoor units connectable to a 30HP condensing unit Wide range of indoor units: 13 different models in a total of 75 variations Compact design Operation range (inlet water temperature): 10-45C Connectable to current Daikin control systems: DSnet, Intelligent Touch Controller, Intelligent Manager, BACnet Gateway, DMS-IF Flexible piping length
HEAT RECOVERY
Outdoor Unit Capacity range Capacity Power input (Nominal) Cooling Heating Cooling Heating (Height x Width x Depth) HP kw kw kw kw mm kg dBA RWEYQ10MY1 10 26.70 31.50 6.03 6.05 1000x780x550 150 51.0 RWEYQ20MY1 20 53.40 63.00 12.10 12.10 300 54.0 R-410A 3~/380-415V/50Hz 20 15.9 / 28.6 / 22.2 450 56.0 RWEYQ30MY1 30 80.10 94.50 18.10 18.20
Dimensions Weight Sound Level Sound Pressure Cooling Refrigerant Power Supply Max n of indoor units to be connected Piping connections Liquid (OD)/Discharge Gas
mm
142
FXFQ-P7VEB
Round Flow Cassette
z z z z z z z z z
Modern style decoration panel in white (RAL9010) 360 air discharge ensures uniform air ow and temperature distribution Air discharge from the corners avoids dead zones that may be subject to temperature differences Comfortable horizontal air discharge ensures draughtfree operation and prevents ceiling soiling 23 different air ow patterns possible Fresh air intake: up to 20 % Reduced installation height: 214mm for class 20-63 Easy visible drain check thanks to clear drain socket Drain-up pump with 850 mm lift tted as standard.
optional
standard
optional
optional
FXFQ-P7VEB
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections Decoration Panel Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating High/Low High/Low High/Low High/Low kw kw kw kw mm kg m/min m/min dBA dBA dBA 20 2.20 2.50 25 2.80 3.20 0.053 0.045 20 12.5 / 9.0 12.5 / 9.0 49.0 31.0 / 28.0 31.0 / 28.0 13.5 / 9.0 13.5 / 9.0 50.0 32.0 / 28.0 32.0 / 28.0 32 3.60 4.00 40 4.50 5.00 0.063 0.055 204x840x840 50 5.60 6.30 0.083 0.067 21 15.5 / 10.0 15.0 / 9.5 51.0 33.0 / 28.0 33.0 / 28.0 R-410A 1~/220-240V/50Hz BYCQ140CW1 RAL9010 50x950x950 5.5 63 7.10 8.00 0.095 0.114 80 100 9.00 11.20 10.00 12.50 0.120 0.173 0.108 0.176 246x840x840 24 23.5 / 14.5 26.5 / 17.0 23.5 / 14.5 28.0 / 17.5 55.0 58.0 38.0 / 32.0 41.0 / 33.0 38.0 / 32.0 42.0 / 34.0 125 14.00 16.00 0.258 0.246 288x840x840 26 33.0 / 20.0 33.0 / 20.0 61.0 44.0 / 34.0 44.0 / 34.0
mm
6.35 / 12.7 / 32
6.40 / 12.7 / 32
9.5 / 15.9 / 32
mm kg
143
FXZQ-M8V1B
600x600 4-Way Blow Ceiling Mounted Cassette
FXZQ-M8
z
BRC1D52
BRC7E531/E530
z z z z
z z z
z z
New and extremely compact casing (575mm in width and depth) enables unit to t ush into ceilings and match standard architectural modules, without cutting ceiling tiles Modern style decoration panel in white (RAL9010) Whisper quiet operation: down to 25 dBA sound pressure level Excellent low draught characteristics Vertical auto-swing function moves the discharge aps up and down for efcient air distribution throughout the room Since the aps can move to a 0 degree position, virtually no draught can be experienced 5 different air ow patterns: Any one of 5 air ow patterns can be freely selected between zero and 40 degrees and will then be maintained during the operational cycle of the air conditioner. Air can be discharged in any of 4 directions Possibility to shut 1 or 2 aps for easy installation in corners
optional
optional
optional
FXZQ-M8V1B
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections Decoration Panel Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA dBA FXZQ20M8V1B 2.20 2.50 0.073 0.064 FXZQ25M8V1B 2.80 3.20 FXZQ32M8V1B 3.60 4.00 0.076 0.068 286x575x575 18 9.50 / 7.50 49.0 32.0 / 26.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / 26 BYFQ60B7W1 White (Ral 9010) 55x700x700 2.7 FXZQ40M8V1B 4.50 5.00 0.089 0.080 FXZQ50M8V1B 5.60 6.30 0.115 0.107
mm
mm kg
144
FXCQ-M8V3B
2-Way Blow Ceiling Mounted Cassette
FXCQ20,25,32M8
z z z
BRC1D52
BRC7C67/C62
z z z
Compact dimensions, can easily be mounted in a ceiling void of only 355mm Easy to install: depth of all units is 600mm Auto-swing function ensures efcient air and temperature distribution and prevents ceiling soiling. Quiet operation Leaves maximum oor and wall space for furniture, decorations and ttings Easy to clean at suction grille
optional
optional
optional
FXCQ-M8V3B
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections Decoration Panel Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating High/Low High/Low High/Low High/Low kw kw kw kw mm kg m/min m/min dBA dBA dBA 20 2.20 2.50 0.077 0.044 25 2.80 3.20 0.092 0.059 305x780x600 26 9.0 / 6.5 9.0 / 6.5 50.0 35.0 / 29.0 35.0 / 29.0 35.5 / 30.5 35.5 / 30.5 R-410A 1~/230V/50Hz BYBC50GJW1 White (10Y9/0,5) 53x1245x680 8.5 32 3.60 4.00 40 4.50 5.00 0.130 0.097 305x995x600 31 12.0 / 9.0 12.0 / 9.0 32 50 5.60 6.30 63 7.10 8.00 0.161 0.126 305x1180x600 35 16.5 / 13.0 16.5 / 13.0 52.0 38.0 / 33.0 38.0 / 33.0 80 125 9.00 14.00 10.00 16.00 0.209 0.256 0.176 0.223 305x1670x600 47 48 26.0 / 21.0 33.0 / 25.0 26.0 / 21.0 33.0 / 25.0 54.0 60.0 40.0 / 35.0 45.0 / 39.0 40.0 / 35.0 45.0 / 39.0
145
FXKQ-MAVE
Ceiling Mounted Corner Cassette
FXKQ63MA
z z z
BRC1D52
BRC4C63/C61
Slim design for exible installation Auto-swing function ensures efcient air and temperature distribution. Choice between 3 auto-swing positions for maximum comfort: standard, draught prevention, ceiling soiling prevention Optimum air ow conditions are created by either downward air discharge or frontal air discharge (via optional grille) or a combination of both Leaves maximum oor and wall space for furniture, decorations and ttings
optional
optional
optional
FXKQ-MAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Decoration Panel Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXKQ25MAVE 2.80 3.20 0.066 0.046 215x1110x710 31 11.00 / 9.00 38.0 / 33.0 R-410A 1~/220-240V/50Hz Liquid (OD)/Gas/Drain Model Colour HeightxWidthxDepth Weight mm 6.4 / 12.7 / 32 BYK45FJW1 White mm kg 70x1240x800 8.5 70x1440x800 9.5 9.5 / 15.9 / 32 BYK71FJW1 13.00 / 10.00 40.0 / 34.0 FXKQ32MAVE 3.60 4.00 FXKQ40MAVE 4.50 5.00 0.076 0.056 FXKQ63MAVE 7.10 8.00 0.105 0.085 215x1310x710 34 18.00 / 15.00 42.0 / 37.0
146
FXDQ-M8V3B
Concealed Ceiling Unit (Small)
BRC1D52
z z z z z z z
BRC4C64/C62
FXDQ20,25M8
Designed for hotel bedrooms Compact dimensions (230mm high & 652mm deep), can easily be mounted in a ceiling void Blends unobtrusively with any interior dcor: only the suction and discharge grilles are visible Extremely quiet in operation both indoors and outdoors The air suction direction can be altered from rear to bottom suction Air suction lter tted as standard For easy mounting, the drain pan can be located to the left or the right of the unit.
optional
optional
optional
FXDQ-M8V3B
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating High/Low High/Low High/Low High/Low kw kw kw kw mm kg m/min m/min dBA dBA dBA FXDQ20M8V3B 2.20 2.50 0.050 0.050 230x502x652 17 6.70 / 5.20 6.70 / 5.20 50.0 37.0 / 32.0 37.0 / 32.0 R-410A 1~/230V/50Hz 6.4 / 12.7 / 27.2 7.40 / 5.80 7.40 / 5.80 FXDQ25M8V3B 2.80 3.20
Liquid (OD)/Gas/Drain
mm
147
FXDQ-P/NA
Slim Concealed Ceiling Unit
BRC1D52
z z z z z z z
BRC4C64/C62
FXDQ20-32P
Slim design for exible installation Compact dimensions, can easily be mounted in a ceiling void of only 240mm Quiet operation: down to 29 dBA sound pressure level Blends unobtrusively with any interior dcor Can be installed in both new and existing buildings. Leaves maximum oor and wall space for furniture, decorations and ttings Medium external static pressure facilitates unit use with exible ducts of varying lengths
optional
optional
optional
FXDQ-PVE/FXDQ-NAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXDQ20PVE 2.20 2.50 0.086 0.067 FXDQ25PVE 2.80 3.20 FXDQ40NAVE FXDQ50NAVE 4.50 5.60 5.00 6.30 0.160 0.165 0.147 0.152 200x700x620 200x900x620 23.0 27.0 28.0 8.0 / 6.4 10.50 / 8.50 12.50 / 10.00 33.0 / 29.0 34.0 / 30.0 35.0 / 31.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / VP20 (I.D. 20/O.D. 26) FXDQ32PVE 3.60 4.00 0.089 0.070 FXDQ63NAVE 7.10 8.00 0.181 0.168 200x1100x620 31.0 16.50 / 13.00 36.0 / 32.0
Liquid (OD)/Gas/Drain
mm
148
FXSQ-M8V3B
Concealed Ceiling Unit
FXSQ20,25,32M8
z z z z z z
BRC1D52
BRC4C64/C62
Blends unobtrusively with any interior dcor Leaves maximum oor and wall space for furniture, decorations and ttings Drain pump tted as standard Long life lter tted as standard The air suction direction can be altered from rear to bottom suction Ideal for shops, restaurants or ofces requiring maximum oor space for furniture, decorations and ttings High external static pressure facilitates unit use with exible ducts of varying lengths
optional
optional
optional
FXSQ-M8V3B
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Refrigerant Power Supply Piping connections Decoration Panel Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating High/Low High/Low High/Low High/Low kw kw kw kw mm kg m/min m/min dBA dBA dBA 20 2.20 2.50 25 2.80 3.20 0.110 0.090 300x550x800 30 9.00 / 6.50 9.00 / 6.50 50.0 32.0 / 28.0 32.0 / 28.0 9.50 / 7.00 9.50 / 7.00 51.0 33.0 / 28.0 33.0 / 28.0 32 3.60 4.00 0.114 0.094 40 50 63 4.50 5.60 7.10 5.00 6.30 8.00 0.127 0.143 0.189 0.107 0.123 0.169 300x700x800 300x1000x800 31 41 11.50 / 9.00 15.00 / 11.00 21.00 / 15.50 11.50 / 9.00 15.00 / 11.00 21.00 / 15.50 56.0 58.0 56.0 33.0 / 29.0 35.0 / 31.0 35.0 / 30.0 33.0 / 29.0 35.0 / 31.0 35.0 / 30.0 R-410A 1~/230V/50Hz BYBS45DJW1 BYBS71DJW1 White (10Y9/0,5) 55x800x500 55x1100x500 3.5 4.5 100 11.20 12.50 0.242 0.222 300x1400x800 51 27.00 / 20.00 28.00 / 20.50 27.00 / 20.00 28.00 / 20.50 55.0 56.0 37.0 / 31.0 38.0 / 33.0 37.0 / 31.0 38.0 / 33.0 80 9.00 10.00 0.234 0.214 125 14.00 16.00 0.321 0.301 52 38.00 / 28.00 38.00 / 28.00 65.0 40.0 / 35.0 40.0 / 35.0
mm BYBS32DJW1 mm kg 55x650x500 3
6.35 / 12.7 / 32
149
FXMQ-MAVE
Concealed Ceiling Unit (Large)
FXMQ80,100,125MA
z z z
BRC1D52
BRC4C64/C62
Leaves maximum oor and wall space for furniture, decorations and ttings Complete range of models (5 -> 31,5 kW) More than 150 Pa external static pressure allows extensive ductwork runs and exible application: ideal for use in large areas Built-in drain pump (accessory): housing the drain pump inside the unit has reduced the required installation space
optional
optional
optional
optional
FXMQ-MAVE
Indoor Units Capacity Power input (Nominal) Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA 40 4.50 5.00 50 63 5.60 7.10 6.30 8.00 0.211 0.211 390x720x690 44 14.00 / 11.50 39.0 / 35.0 100 125 11.20 14.00 12.50 16.00 0.411 0.619 0.411 0.619 390x1110x690 45 63 65 19.50 / 16.00 29.00 / 23.00 36.00 / 29.00 42.0 / 38.0 43.0 / 39.0 45.0 / 42.0 R-410A 1~/220-240V/50Hz 9.5 / 15.9 / 32 80 9.00 10.00 0.284 0.284 200 250 22.40 28.00 25.00 31.50 1.294 1.465 1.294 1.465 470x1380x1100 137 58.00 / 50.00 72.00 / 62.00 48.0 / 45.0
Liquid (OD)/Gas/Drain
mm
6.4 / 12.7 / 32
150
FXAQ-MAVE
Wall Mounted Unit
BRC1D52 BRC7E619/E618
z z z
FXAQ40,50,63MA
z z z
Compact design Fits neatly on a wall Auto-swing function ensures efcient air distribution via louvers that close automatically when the unit is switched off 5 different discharge angles can be programmed via the remote control Both horizontal aps and front panel can easily be removed and washed Discharge angle automatically returns to its previous position on restart (initial setting 10 degrees for cooling and 70 degrees for heating) All maintenance operations can be carried out from the front of the unit
optional
optional
optional
FXAQ-MAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXAQ20MAVE 2.20 2.50 0.016 0.024 FXAQ25MAVE 2.80 3.20 0.022 0.027 290x795x230 11 8.00 / 5.00 36.0 / 29.0 FXAQ32MAVE 3.60 4.00 0.027 0.032 FXAQ40MAVE 4.50 5.00 0.020 0.020 FXAQ50MAVE 5.60 6.30 0.027 0.032 290x1050x230 14 15.00 / 12.00 42.0 / 36.0 FXAQ63MAVE 7.10 8.00 0.050 0.060
R-410A 1~/220-240V/50Hz Liquid (OD)/Gas/Drain mm 6.4 / 12.7 / 18 6.35 / 12.7 / 18 9.5 / 15.9 / 18
151
FXHQ-MAVE
Ceiling Suspended Unit
BRC1D52
z z z z z z z z
BRC7E66/E63
FXHQ32MA
Reduced sound pressure level Leaves maximum oor and wall space for furniture, decorations and ttings Can be installed in both new and existing buildings. Use of W-shaped Coanda ap enhances horizontal and vertical air circulation characteristics Wider air discharge thanks to Coanda effect: up to 100 degrees Easy installation and maintenance Long life lter tted as standard Drain pump kit available as accessory
optional
optional
optional
optional
FXHQ-MAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXHQ32MAVE 3.60 4.00 0.111 0.111 195x960x680 24 12.00 / 10.00 36.0 / 31.0 FXHQ63MAVE 7.10 8.00 0.115 0.115 195x1160x680 28 17.50 / 14.00 39.0 / 34.0 R-410A 1~/220-240V/50Hz 9.5 / 15.9 / 26 FXHQ100MAVE 11.20 12.50 0.135 0.135 195x1400x680 33 25.00 / 19.50 45.0 / 37.0
Liquid (OD)/Gas/Drain
mm
6.4 / 12.7 / 26
152
FXUQ-MAV1
4-Way Blow Ceiling Suspended Cassette
BRC1D52 BRC7C529/C528
z z z z z z z z z z z
FXUQ71MAV1
Can be installed in both new and existing buildings. Group control with other VRV indoor units possible Cool heat selection Prevention of cold draught at hot start, defrost and oil return in heating 5m maximum distance between FXUQ unit and junction box Air can be discharged in any of 4 directions Possibility to shut 1 or 2 aps for easy installation in corners Auto-swing function ensures efcient air and temperature distribution. Air ow distribution for ceiling heights up to 3.5m without loss of capacity. Air can be discharged at 5 different angles between 0 and 60 degrees Air lter, drain pan and heat exchanger n are mildew proof and anti-bacterial treated.
optional
2 steps
optional
optional
FXUQ-MAV1
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound power (nominal) Sound Pressure Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Cooling Cooling Heating High/Low High/Low High/Low High/Low kw kw kw kw mm kg m/min m/min dBA dBA dBA FXUQ71MAV1 8.0 9.0 0.180 0.160 165x895x895 25 19.00 / 14.00 19.00 / 14.00 56.0 40.0 / 35.0 40.0 / 35.0 FXUQ100MAV1 11.2 12.5 0.289 0.269 230x895x895 31 29.00 / 21.00 29.00 / 21.00 59.0 43.0 / 38.0 43.0 / 38.0 R-410A 1~/220-240V/50Hz 9.5 / 15.9 / I.D. 20/O.D. 26 BEVQ100M 32.00 / 23.00 32.00 / 23.00 60.0 44.0 / 39.0 44.0 / 39.0 FXUQ125MAV1 14.0 14.0
Refrigerant Power Supply Piping connections Liquid (OD)/Gas/Drain Combination with junction box
mm BEVQ71M
BEVQ125M
153
FXNQ-MAVE
Concealed Floor Standing Unit
FXNQ20,25MA
z z z z z
BRC1D52
BRC4C64/C62
Ideal for installation beneath a window All models are available with remote control Long life lter tted as standard Requires very little installation space The connecting port faces downward, eliminating the need to attach auxiliary piping
optional
optional
optional
FXNQ-MAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXNQ20MAVE 2.20 2.50 FXNQ25MAVE 2.80 3.20 FXNQ32MAVE 3.60 4.00 FXNQ40MAVE 4.50 5.00 FXNQ50MAVE 5.60 6.30 FXNQ63MAVE 7.10 8.00 0.049 0.049 610x930x220 19 7.00 / 6.00 35.0 / 32.0 0.090 0.090 610x1070x220 23 8.00 / 6.00 11.00 / 8.50 38.0 / 33.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / O.D. 21 0.110 0.110 610x1350x220 27 14.00 / 11.00 16.00 / 12.00 39.0 / 34.0 40.0 / 35.0
Liquid (OD)/Gas/Drain
mm
154
FXLQ-MAVE
Floor Standing Unit
FXLQ20,25MA
z z z z
BRC1D52
BRC4C64/62
Ideal for installation beneath a window All models are available with remote control Requires very little installation space Running the pipes from connections at the back, enables the unit to be wall mounted which in turn allows cleaning beneath the unit where dust tends to accumulate Long life lter tted as standard
optional
optional
optional
FXLQ-MAVE
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Sound Pressure Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Cooling High/Low High/Low kw kw kw kw mm kg m/min dBA FXLQ20MAVE 2.20 2.50 FXLQ25MAVE 2.80 3.20 FXLQ32MAVE 3.60 4.00 FXLQ40MAVE 4.50 5.00 FXLQ50MAVE 5.60 6.30 FXLQ63MAVE 7.10 8.00 0.049 0.049 600x1000x222 25 7.00 / 6.00 35.0 / 32.0 0.090 0.090 600x1140x222 30 8.00 / 6.00 11.00 / 8.50 38.0 / 33.0 R-410A 1~/220-240V/50Hz 6.4 / 12.7 / O.D. 21 0.110 0.110 600x1420x222 36 14.00 / 11.00 16.00 / 12.00 39.0 / 34.0 40.0 / 35.0
Liquid (OD)/Gas/Drain
mm
155
FXMQ-MFV1
Outdoor Air Processing Unit
FXMQ250MF
z z z z
100% fresh air intake possible Leaves maximum oor and wall space for furniture, decorations and ttings Operation range: -5C to 43C 225 Pa external static pressure allows extensive ductwork runs and exible application: ideal for use in large areas Drain pump kit available as accessory
FXMQ-MFV1
Indoor Units Capacity Power input Dimensions Weight Air Flow Rate Refrigerant Power Supply Piping connections Cooling Heating Cooling Heating (Height x Width x Depth) Cooling Heating Medium Medium kw kw kw kw mm kg m/min m/min FXMQ125MFV1 14.0 8.9 0.359 0.359 470x744x1100 86 18.0 18.0 FXMQ200MFV1 22.4 13.9 0.548 0.548 470x1380x1100 123 28.0 28.0 220-240V/50Hz 9.5 / 19.1 / PS1B 35.0 35.0 FXMQ250MFV1 28.00 17.40 0.638 0.638
Liquid (OD)/Gas/Drain
mm
156
VRV Xpress
Daikin has developed a new user friendly, software tool that allows rapid VRV selection and provides a professional result in the 7 following steps: 1. Select indoor units 2. Connect outdoor units to indoor units 3. Automatic receipt of piping diagram with joints 4. Automatic receipt of wiring diagram 5. Connect appropriate centralised control systems 6. Visualise result in Word or Excel format 7. Save project Using VRV Xpress enables VRV selection to be achieved in a simple, complete and professional manner.
157
HRV
Heat Recovery Ventilation
Clean outdoor air Total heat exchanged foul air
The Daikin heat recovery ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced signicantly. HRV units can be controlled individually or integral with the air conditioning system (Daikin VRV or Sky Air series).
9 models to choose from Compact, energy saving ventilation Specially developed heat exchange element with HEP (High Efciency Paper) Easy integration into the VRV system Connectable to current Daikin control systems:
VAM-FA7 Ventilation Air ow rate Sound pressure level (max.) (1) External static pressure (max.) Temperature exchange efciency Enthalpy exchange efciency Dimensions m3/h dBA Pa % % % mm mm mm kg mm VE VAM150FA7 VAM250FA7 VAM350FA7 VAM500FA7 VAM650FA7 VAM800FA7 VAM1000FA7 VAM1500FA7 VAM2000FA7 150 250 350 500 650 800 1,000 1,500 2,000 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5 69 64 98 98 93 137 157 137 137 74 72 75 74 74 74 75 75 75 58 58 61 58 58 60 61 61 61 64 64 65 62 63 65 66 66 66 269 269 285 285 348 348 348 710 710 760 760 812 812 988 988 988 1,498 1,498 509 509 800 800 852 852 1,140 852 1,140 24 24 33 33 48 48 61 132 158 100 150 150 200 200 250 250 350 350 1 ~, 50Hz, 220-240V
heating cooling H W D
158
HRV
Heat Recovery Ventilation
Heat purge (economiser): heat accumulated indoors is discharged at night Integration of humidication and air conditioning into HRV unit Increased static pressure thanks to improved fan performance Individual control via HRV remote control Connectable to current Daikin control systems:
VKM-GAM Ventilation, DX coil & humidier Fresh air conditioning load Air ow rate Sound pressure level - 220V Sound pressure level - 240V Static pressure Temperature exchange efciency Enthalpy exchange efciency - cooling Enthalpy exchange efciency - heating Humidier type Humidication capacity Dimensions Cooling Heating UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L kW kW m3/h dBA dBA Pa % % % kg/h mm mm mm kg V1 VKM50GAM 4.71 5.58 500 - 500 - 440 37 - 35.5 - 32 38 - 36 - 34 160 - 120 - 100 76 - 76 - 77.5 64 - 64 - 67 67 - 67 - 69 2.70 387 1,764 832 102 VKM80GAM 7.46 8.79 750 - 750 - 640 38.5 - 36 -33 40 - 37.5 - 35.5 140 - 90 - 70 78 - 78 - 79 66 - 66 - 68 71 - 71 - 73 natural evaporating humdier 4.00 387 1,764 1,214 120 1 ~, 220-240V, 50Hz VKM100GAM 9.12 10.69 950 - 950 - 820 39 -37 - 34 40 - 38 - 35.5 110 - 70 - 60 74 - 74 - 76.5 62 - 62 - 66 65 - 65 - 69 5.40 387 1,764 1,214 125
VKM-GA Ventilation & DX coil Fresh air conditioning load Air ow rate Sound pressure level - 220V Sound pressure level - 240V Static pressure Temperature exchange efciency Enthalpy exchange efciency - cooling Enthalpy exchange efciency - heating Dimensions Cooling Heating UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L UH - H - L Height Width Depth kW kW m3/h dBA dBA Pa % % % mm mm mm kg V1 VKM50GA 4.71 5.58 500 - 500 - 440 38 - 36 - 33.5 39 -37 - 33.5 180 - 150 - 110 76 - 76 - 77.5 64 - 64 - 67 67 - 67 - 69 387 1,764 832 96 VKM80GA 7.46 8.79 750 - 750 - 640 40 - 37.5 - 34.5 41.5 - 39 - 37 170 - 120 - 80 78 - 78 - 79 66 - 66 - 68 71 - 71 - 73 387 1,764 1,214 109 1 ~, 220-240V, 50Hz VKM100GA 9.12 10.69 950 - 950 - 820 40 - 38 - 35 41 - 39 - 36.5 150 - 100 - 70 74 - 74 - 76.5 62 - 62 - 66 65 - 65 - 69 387 1,764 1,214 114
159
160
In order to realise maximum efciency, commercial air conditioning systems must be subject to precise, 24 hour control. Daikin manufactures and markets a complete suite of advanced computerised central control and monitoring systems designed to simplify air conditioning management and reduce energy usage running costs. Daikin computerised control systems not only provide the highly sophisticated regulation and day to day monitoring necessary for modern, hi tech air conditioning installations they also provide owners, landlords and tenants of commercial buildings with valuable performance data on consumption as well as a wide range of operating parameters. Dedicated Daikin central control can be applied to both VRV and mixed VRV/Sky Air and Split installations with up to 1,024 indoor units and can also be integrated with building management systems.
Control Systems
CENTRALISED CONTROL SYSTEMS Centralised remote control Unied on/off control Schedule timer NETWORK SOLUTIONS 163 164 166 167 167 162 162 162
161
Centralised control of the VRV system can be achieved via 3 user friendly compact controls: centralised remote control, unied on/off control and schedule timer. These controls may be used independently or in combination where 1 group = several (up to 16) indoor units in combination and 1 zone = several groups in combination. A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation, enabling indoor units to be classied in groups per tenant (zoning). The schedule timer programmes the schedule and operation conditions for each tenant and the control can easily be reset according to varying requirements.
DCS302C51
DCS301B51
DST301B51
DCS302C51
Centralised remote control Providing individual control of 64 groups (zones) of indoor units. a maximum of 64 groups (128 indoor units, max. 10 outdoor units) can be controlled a maximum of 128 groups (128 indoor units, max. 10 outdoor units) can be controlled via 2 centralised remote controls in separate locations zone control group control malfunction code display maximum wiring length of 1,000m (total: 2,000m) air ow direction and air ow rate of HRV can be controlled expanded timer function
DCS301B51
Unied ON/OFF control Providing simultaneous and individual control of 16 groups of indoor units. a maximum of 16 groups (128 indoor units) can be controlled 2 remote controls in separate locations can be used operating status indication (normal operation, alarm) centralised control indication maximum wiring length of 1,000m (total: 2,000m)
DST301B51
Schedule timer Enabling 64 programmed. groups to be
a maximum of 128 indoor units can be controlled 8 types of weekly schedule a maximum of 48 hours back up power supply a maximum wiring length of 1,000m (total: 2,000m)
162
Network Solutions
The ideal solution for control and management up to 2,000 Sky Air and/or VRV indoor units
Modem Public phone line RS458 Malfunction Modem RS232C Max. of 10 DS-NET adapters
APPLICATION AREA A small commercial area of less than 40 indoor units. Critical applications for centralized monitoring. SYSTEM LAYOUT Allows monitoring and control of up to up to 50 stores or sites and 2,000 indoor units with just one modem and phone line.
Automates daily air conditioning operation in order to free users from the hassle of air conditioning operation/management. The daily schedule setting allows automatic operation afterward. Automates alarm (report messages) for any malfunctions / errors. Immediate report of any indoor unit breakdown to the servicing company. Automatic report of breakdown/ malfunction information. Minimizes the inconvenience of not having air conditioning via rapid messages
FUNCTIONS Schedule setup (Daily schedule) - Start/Stop Air conditioning malfunction report - Send message to monitoring system Manual operation - Start/Stop, Set temperature, Operation mode, Fan speed Status monitoring (Start/Stop, Set temperature, Operation mode, Room temperature, Operation time, Error code)
163
Network Solutions
Allows detailed & easy monitoring and operation of VRV systems (max. 2 X 64 groups/indoor units).
third party controller (domotics, BMS, etc.) Public line AIRNET Onboard modem
new
Ethernet Forced OFF contact input Fire alarm
PCMCIA ash memory CSV output of PPD (option) result Pi-port Onboard Ethernet port Links to the wattmeter when using the PPD (option) function
DIII-NET
Indoor units
HRV
Malfunction
new
Remote monitoring/control via internet, e-mail PPD data is available on the internet RS-232C
164
LANGUAGES
English French German Italian Spanish
CONTROL
Individual control (set point, start/stop, fan speed) (max. 2 x 64 groups/indoor units) Enhanced scheduling function (8 schedules, 17 patterns) Flexible grouping in zones Yearly schedule Fire emergency stop control Interlocking control Increased HRV monitoring and control function Automatic cooling / heating change-over Heating optimization Temperature limit Password security: 3 levels (general, administration & service) Quick selection and full control Simple navigation
COST PERFORMANCE
Labour saving Easy installation Compact design: limited installation space Overall energy saving
SYSTEM LAYOUT
Up to 2 x 64 indoor units can be controlled Onboard Ethernet port (web browser + e-mail) Digital i/o contacts (option) Touch panel (full colour LCD via icon display)
OPEN INTERFACE
Communication to any third party controller (domotics, BMS, etc.) is possible via open interface
CONNECTABLE TO:
VRV HRV Sky Air (via interface adapter) Split (via interface adapter)
MANAGEMENT
Web application & internet compatibility - Monitoring & control according to user - Remote monitoring & control of more than one building - Remote monitoring & control of more than one building via internet Power Proportional Distribution: PPD (option) PPD data is available on the internet Easy management of electricity consumption Enhanced history function
MONITORING
Visualisation via Graphical User Interface (GUI) Icon colour display change function Indoor units operation mode Error messages via e-mail & mobile phone (option) Indication lter replacement Multi PC
ne
165
Network Solutions
The ideal solution for control and management of maximum 1,024 VRV indoor units.
4 units max.
Operation Status Monitoring Schedule Management Tenant Management ...etc Fire alarm Security Centralised control systems
HRV
Indoor units
LANGUAGES
English French German Italian Spanish
MANAGEMENT
Web access (option) Power Proportional Distribution (option) Operational history management (start/stop, malfunction, operation hours) Generation of reports (graphics & tables) (daily, weekly, monthly) Peak load shedding Advanced tenant management Sliding temperature Eco mode (option)
MONITORING
Visualisation via a Graphical User Interface (GUI) featuring free layout Operation mode of indoor units Fault indication Indication lter replacement Setpoint indication Operation time monitoring Multi PC On-line help
SYSTEM LAYOUT
Up to 1,024 indoor units can be controlled (by 4 iPUs) Ethernet TCPIP / 10 base / T communication Integrated digital contacts on the Intelligent Processing Unit (iPU) 19 general input ports 2 digital outputs Stand alone operation of the iPU for minimum 48 hours Compatible with UPS shutdown software
ne
CONTROL
Individual control (setpoint, start/ stop, fan speed) (max. 1,024 indoor units) Group control (100 groups) Schedule control (128 programs) Fire emergency stop control (32 programs) Interlocking control Setpoint limitation Automatic cooling/heating change-over Power failure/release control Temperature limit (automatic start) Timer extension
COST PERFORMANCE
Labour saving Easy installation Compact design: limited installation space Overall energy saving
CONNECTABLE TO:
VRV HRV Sky Air (via interface adapter) Split (via interface adapter)
166
Lon (FTT-10A)
Lon BMS
Fire alarm
Security Elevator Pump Lighting ...etc Power supply facility Centralised control systems
HRV
Indoor units
ne
BMS
Fire alarm
Security Elevator Pump Lighting ...etc Power supply facility Centralised control systems
HRV
Indoor units
167