Está en la página 1de 10

F

Dissolved Gas Analysis of Alternative Fluids for Power Transformers


Key Words: oil/paper insulation, DGA, esters, overheating, low and cold corona-type discharges

Introduction
onventionally, the insulation system of power transformers consists of mineral oil, cellulose paper, and pressboard. In recent years, there has been an increase in the use of environmentally-friendly fluids such as synthetic esters and natural esters in place of mineral oil. This has been particularly prevalent at distribution voltage levels [1], but it now also is taking place at transmission voltage levels [2]. The main driver for the use of alternative fluids from the electrical supply utility perspective is the environmental benefits that result from their use with no compromise on safety or reliability [3]. Mineral oil is a mixture of hydrocarbons and is refined from crude oil. Mineral oil has a low biodegradability (20% of mineral oil will biodegrade within 28 days) resulting in the need to construct bund walls around large transformers preventing escape into the environment should a leak occur. In the case of an oil leak, significant financial penalties would be imposed by environmental enforcement agencies. In contrast, esters are very biodegradable (95% or more of esters will be biodegraded within 28 days [4],[5]), and they conform to the readily biodegradable definition according to the OECD 301 series of tests [6],[7]. In addition to their better environmental performance, esters have higher flash and fire points than mineral oil. This is desirable from a fire safety perspective, particularly for a transformer operating underground or offshore. Esters have been used in distribution transformers for several decades without fires being reported [2]. Esters also are far more hygroscopic than mineral oil as the ester group (COOR) in the molecular chain structure has a higher ability to participate in hydrogen bonding. The high moisture saturation level means that, for the same moisture content expressed in absolute parts per million, esters will have a lower relative humidity in comparison with mineral oil. This means that moisture has less of an impact on the dielectric strength of esters than mineral oil. When esters are used in conjunction with cellulose paper and pressboard, cellulose is kept in a drier

Imad-U-Khan, Zhongdong Wang, and Ian Cotton


Electrical Energy and Power System, University of Manchester, Manchester M60 1QD UK

Susan Northcote
TJ/H2b Analytical Services Ltd., Chester CH1 6ES UK

Ester-based transformer fluids have the same DGA fingerprints as mineral oil. However, with lower volumes of gas produced, they will demand more precise dissolved gas measurements and modified or new ratio criteria to allow fault detection and diagnosis.

condition and the rate of cellulose degradation consequently is slower than in mineral oil [8]. This article examines the impact of alternative fluids on dissolved gas analysis (DGA). DGA has been used for many years as an effective and reliable tool to detect incipient faults in mineral oil-filled transformers. The information provided by DGA analysis is extremely important to the asset managers with electricity supply companies. Therefore, it is essential to ensure that traditional DGA analysis techniques still can be used if alter-

September/October 2007 Vol. 23, No. 5 0883-7554/07/$25/2007IEEE

native oils are used in transformers. In order to clarify that DGA diagnostic techniques still yield the correct result when applied to ester filled transformers, it is necessary to determine if the same types of fault gases are generated, to identify the generation rate, and their concentration in the alternative fluids against a mineral oil benchmark. This article gives the results of experiments that have simulated a number of faults that can be found in power transformers and looks at the DGA analysis results in each case for a number of oil types. Table 1 gives the types of dissolved gases evolved during transformer faults and their indicative relationships with types of faults in mineral oil. A number of diagnostic methods are available to identify the types of faults and their intensities. These include the IEC, IEEE standard and Duval triangle diagnosis methods [9][11]. Two broad categories of faults in a transformer can be detected by DGA: thermal faults and electrical faults. The various DGA standards then subdivide these basic types of fault in different ways. In IEC 60599 [9], thermal faults are represented as being in three temperature bands, <300C (T1), >300C (T2) and >700C (T3). Electrical faults can be further classified as partial discharges of the cold plasma (corona) type (PD), low energy discharges (D1), and high energy discharges (D2). The triangular graphical representation of Duval, which is used to visualize a DGA fault diagnosis, uses the same subdivisions as the IEC standard. However, instead of using the concentration of five gases and three ratios to define the type of fault, the relative percentage of three gases is used for the analysis in the Duval diagnosis technique [12]. The IEEE analysis method uses the concept of key gases [10]. The key gas for each type of fault is identified, and the dominating percentage of this gas to the others is used to diagnose the fault. For example, low intensity PD or corona produces mainly H2. Similarly, the key gas C2H2 is for arcing, C2H4 for overheating oil, and CO is for overheating of cellulose.

The generation of various forms of fault within three dielectric fluids and the analysis of dissolved gas produced are under investigation in this article. The fluids used are a mineral oil Nynas Nytro 10GBN; a synthetic ester, Midel 7131; and a natural ester FR3. The synthetic ester, Midel 7131, consists of four ester groups with saturated chains as shown in Figure 1(a), i.e., there are no double bonds between the carbon atoms in the chain. FR3, the natural ester, is a natural triglyceride ester with a mixture of saturated and unsaturated fatty acids. The triglyceride ester molecule may be represented as in Figure 1(b), the glycerol backbone in blue and the fatty acid parts in red [13].

Fault Gases Evolved by Simulated Thermal Faults


Thermal tests of both oil and oil/paper mixes have been carried out. For the oil/paper mix, the oil/paper ratio was 20:1 by weight. For the tests involving only oil, all the fluids were preprocessed by drying at 85C under a vacuum for 72 hours. For the thermal tests involving both oil and paper, the Kraft papers were preprocessed by drying at 105C in an air circulating oven for 24 hours followed by further drying at 85C under vacuum for 24 hours. The fluids were preprocessed by drying at 85C under a vacuum for 48 hours. Following the drying of both the oil and the paper, the paper was impregnated in the preprocessed fluid and dried under vacuum for an additional 24 hours. At the end of preprocessing, moisture contents in the samples were measured by Karl Fischer titration method using Metrohm KF 786 coulometer and KF Thermoprep 832 (Metrohm, http://www.metrohm.com). The average moisture contents of mineral oil, Midel 7131 and FR3 were 6 ppm, 24 ppm, and 16 ppm, respectively. The paper samples had moisture contents of less than 0.6% by weight. All of the fluid and fluid/paper samples then were sealed in glass bottles and heated uniformly in an air circulating oven at temperatures of 90C, 150C or 200C for periods up to 14

Table 1. Fault indicator gases. Fault gases H2 (hydrogen) CH4 (methane) C2H6 (ethane) C2H4 (ethylene) C2H2 (acetylene) CO (carbon monoxide) CO2 (carbon dioxide) O2 (oxygen) N2 (nitrogen) Overheated oil Arcing Overheated cellulose Key indicator Corona Secondary indicator Arcing, overheated oil Corona, arcing, and overheated oil Corona, overheated oil Corona, arcing Severely overheated oil Arcing if the fault involves cellulose Overheated cellulose, arcing if the fault involves cellulose Indicator of system leaks, over-pressurization, or changes in pressure or temperature. Indicator of system leaks, over-pressurization, or changes in pressure or temperature.

TDGC: The total concentration of the six combustible gases (H2, CH4, C2H2, C2H4, C2H6, CO) in ppm. CO2/CO:Trending Ratio used to determine severity of cellulose degradation. O2/ N2 : Trending Ratio used to determine system leaks, over-pressurization, or changes in pressure or temperature.

IEEE Electrical Insulation Magazine

Figure 1. Chemical structure of synthetic and natural esters. days. This testing was intended to simulate the maximum top oil temperature found in a transformer during operating conditions (90C) and two cases of low intensity thermal faults (150C and 200C). As with all of the other tests described in this article, a number of control samples of fluid and fluid/paper were kept for DGA tests to provide a benchmark. All the DGA results presented are the average of three samples to improve accuracy.

B. DGA Results from Thermal Tests of Oil/Paper at 90C, 150C, and 200C
Table 3 compares the concentration of fault gases of mineral oil, Midel 7131, and FR3 in the presence of Kraft paper (these tests were carried out for 14 days at 90C/150C and 1 hour for 200C). The inclusion of paper has caused an increase in the concentration of carbon monoxide and carbon dioxide for the 90C temperature. These gases are key indicators for cellulose degradation, in both mineral oil and esters. The concentrations of CO and CO2 are the highest in mineral oil, lower in Midel 7131, and the least in FR3 at this temperature. At 150C, the inclusion of paper also increases the level of carbon monoxide and carbon dioxide significantly. This is expected as Kraft paper generally starts to be thermally degraded at temperatures above 105C. The generation of CO is less in esters than in mineral oil suggesting that they may be protecting the paper in some way. Figure 4 shows the relative percentage of fault gases in the TDCG for the oil/paper mix at 90C and at 150C. In the case of mineral oil and Midel 7131, the dominant gas is carbon monoxide; however, for FR3, the concentration of carbon monoxide is similar to that without paper, indicating paper integrity may be preserved [14]. Figure 5 shows the same results with H2 and CO excluded to allow viewing of the other fault gases more prominently.

A. DGA Results from Thermal Tests of Oil at 90C, 150C, and 200C
At the 90C maximum top oil temperature found under operating conditions, both mineral oil and esters should be stable for a long period of time; therefore, no significant dissolved gas should be evolved. This should not be the case for the temperatures of 150C and 200C at which chemical decomposition will take place. Table 2 compares the concentration of fault gases found in the three oils under the different test conditions. In terms of gas volume, Midel 7131 generated the smallest amount of fault gases. In contrast, FR3 generated a significant amount of ethane and hydrogen, particularly in the case of the 90C test. At 90C, none of the three types of fluid produced ethylene, which usually taken is to be a characteristic of high energy thermal faults (see Table 1). This is a positive result as the oils are expected to be stable at this temperature. For the test carried out at 200C, the gases ethylene, ethane, and methane were generated with approximately the same ratios seen at 150C. Figure 2 shows the relative percentages of fault gases in the total dissolved combustible gases (TDCG) at 90C and at 150C. Ethylene, the primary indicator for high energy thermal faults, is negligible in concentration at 90C. It is more dominant in the results relating to the 150C test (see Figure 3 for clarity, which is plotted without H2 and CO). In FR3, Ethane is generated in significant quantities. In Midel 7131 and mineral oil this is not the case. In all cases, methane is not present in significant quantities.

Fault Gases Evolved by Simulated Electrical Faults A. DGA Results from Low-Energy Arc Tests
A 220 V/40 kV, 8 kVA test transformer was used to generate a breakdown across needle to plane electrode configuration with an oil gap distance of 15 mm. When the breakdown occurs, it will degrade the oil locally as the energy being dissipated causes the molecular structure of the oil to be disrupted. This allows the formation of fault gases like acetylene. The fault gases then dif-

September/October 2007 Vol. 23, No. 5

Table 2. Dissolved gas content in parts per million (ppm) for thermal tests of oil only at 90C aAnd 150C for 3 and 14 days and at 200C for 1 hour. The values highlighted in bold italics are considered to be significant shifts in dissolved gas values (only combustible gases examined). Oil type Test temp Test time H2 CH4 C2H6 C2H4 C2H2 CO CO2 TDCG C 5 1 0 1 1 18 73 26 3d 16 2 1 1 0 25 165 45 90C 14d 38 4 2 1 1 98 502 144 Mineral oil 150C 3d 14 48 28 7 0 262 1976 359 14d 16 194 125 14 0 592 3354 941 200C 1h 21 95 48 9 5 148 1006 326 C 7 0 0 1 0 9 111 17 90C 3d 9 1 1 0 0 17 89 28 14d 7 1 0 1 0 60 283 69 Synthetic ester (Midel) 150C 3d 14 7 2 3 0 152 1073 177 14d 14 40 49 34 0 533 3514 670 200C 1h 8 16 4 3 0 74 521 102 C 8 1 2 1 6 6 82 24 3d 64 1 18 0 0 16 129 98 90C 14d 253 4 103 1 0 53 430 414 Natural ester (FR3) 150C 3d 59 7 88 5 0 171 1586 330 14d 19 23 179 16 0 540 5359 777 200C 1h 17 7 177 4 0 68 914 273

fuse from the local fault location to the bulk volume. To ensure a sufficient concentration of fault gases, a total of 20 breakdowns was produced in oil that had previously been preprocessed in a similar way to that described for the thermal tests. There was at least a 1-minute interval between each breakdown. For each breakdown test, the voltage was steadily ramped up until the oil gap broke down. The current was interrupted by the operation of an over-current relay. This relay, on the low voltage side of the power supply, was set at a 3-A limit to ensure rapid interruption of the current following formation of the arc. It normally operated within 20 ms after the formation of the breakdown, but it could reach 100 ms in certain cases.

Oil samples for DGA testing were taken from the bottom valve of a sealed test vessel. The oil was naturally forced into glass syringes according to the BS EN 60567 standard [15]. As the test vessel is sealed, a homogeneous distribution of fault gases can be expected when enough time is left after the tests for the fault gases to diffuse into the bulk of the oil. Table 4 shows the results of these tests. Acetylene should be one of the key gases produced during lowenergy arc discharge faults; and it therefore, is a primary indicator for this type of fault. This is found in the largest concentration in all samples. Hydrogen and ethylene also usually are evident in significant amounts. Although the same level of low energy

Figure 2. Relative percentages of dissolved combustible gases for mineral oil and esters at 90C and 150C (oil only).

IEEE Electrical Insulation Magazine

Figure 3. Relative percentages of dissolved combustible gases (without H2 and CO) for mineral oil and esters at 90C and 150C (oil only).

discharge took place in the three oils, the acetylene concentration in mineral oil is about 5 to 10 times higher than that seen in the esters. Midel 7131 has the lowest amount of dissolved gas as a result of this test; this is the same result as that seen in the thermal tests. Figure 6 shows the relative percentages of fault gases in the total dissolved combustible gases (TDCG).

B. DGA Results from Partial Discharge Tests


The fluids used for the partial discharge test were preprocessed as earlier described. The electrical circuit and test electrodes used were the same as the ones in the arcing test with the addition of a water resistor to limit the current in case of inadvertent break-

down. The partial discharge tests used a standard PD detection circuit. The partial discharge inception voltages were 27.9 kV for mineral oil, 15.5 kV for Midel 7131, and 12 kV for FR3. The PD level measured during the tests was less than 100 pC for all of the types of oil. Table 4 shows the DGA results of three types of fluid for PD activity with a normalized duration of 1 hour (owing to the different generation rates, the test on mineral oil was carried out for half an hour, on Midel 7131 for 4 hours, and on FR3 for 1 hour). As shown in Figure 5, hydrogen is the key indicator for low-energy discharges, and this was found significantly in all of the oils. Mineral oil had the highest generation rate, and Midel had the lowest.

Table 3. Dissolved gas content in parts per million (ppm) for thermal tests of oil and paper at 90C and 150C for 14 days and at 200C for 1 hour. The values highlighted in bold italics are considered to be significant shifts in dissolved gas values (only combustible gases examined). Oil type Test temp H2 CH4 C2H6 C2H4 C2H2 CO CO2 TDCG Control 8 1 0 1 1 6 108 17 Mineral oil 90C 46 10 2 2 1 590 3407 654 150C 34 259 187 25 1 9187 101167 9693 200C 19 90 43 5 0 890 19603 997 Synthetic ester (Midel) Control 7 1 1 1 1 5 45 16 90C 13 3 0 1 1 307 2212 325 150C 24 40 33 16 0 3815 56508 3928 200C 14 15 4 4 1 541 9524 579 Control 8 1 1 1 1 6 82 18 Natural ester (FR3) 90C 244 6 116 2 0 88 1354 456 150C 26 31 179 19 0 5472 60675 5727 200C 23 10 171 7 1 1330 18717 1542

September/October 2007 Vol. 23, No. 5

Figure 4. Relative percentages of dissolved combustible gases for mineral oil and esters at 90C and 150C for 14 days (oil and paper).

DGA Diagnosis
The results obtained were taken as inputs into DGA diagnosis based on the various standards. In doing this, it has to be noted that the laboratory measurement error expected during the DGA measurements is 10% for the 50 ml (minimum) oil samples used in these tests. Figure 7 shows the results of the first analysis technique to be assessed, the Duval triangle DGA fault diagnosis method. Results from the thermal tests and the low-energy, arc discharge test were analyzed. The results of the corona test were not analyzed for reasons that will be detailed later. In terms of the results for mineral oil, use of the Duval triangle method diagnosed all faults correctly as being either in the T1 region (thermal fault of less than 300C) or in region D1 (lowenergy discharges). This result is to be expected if the laboratory tests are assumed appropriate. For Midel 7131, the Duval triangle places the oil used in the 200C thermal test into the T1 region (i.e., overheating < 300C). The oil subjected to the 150C thermal tests was placed incorrectly into the T2 region (i.e. overheating temperature T, 300C< T <700C). The low-energy, arc discharge test results in the allocation of the data points into the D1 region, the correct diagnosis as per test conditions. For FR3, all thermal test results ended up as being identified as being in the T2 region, thermal overheating temperature, therefore, is over-estimated in this case as was the case for Midel being tested at 150C. Again, low-energy, arc discharge is correctly allocated into the D1 region. In the case of cold corona type discharge (PD) the fault gases concentrations are not sufficient to allow a diagnosis. There is some evidence of generation of methane, ethylene, and acetylene in Table 4, but the values are very low. Other authors have suggested that the use of the Duval triangle is indeterminate, unless

the PD activity is intense and/or occurs over a long period of time [11]. To allow the correct diagnosis of this form of discharge using the Duval technique, results need to have dissolved gas that is >98% CH4 and <2% C2H4. The next form of analysis carried out uses the IEC 60599 standard [9]. The results of this analysis are given in Table 5. Some results produced during the tests lead to a no valid result being placed into the table. These are cases in which the gas concentration produced during the tests was not sufficient to fall into the code ranges within the standard. This was the case for all tests at 90C. The temperature was low enough for the oils or oil/paper being stable enough for insufficient fault gases to be generated. At 150C, tests using all of the oil types with and without paper correctly diagnose thermal faults in the low temperature range (<300C). For the tests at 200C, the generation of methane in the natural ester is too low to diagnose the fault correctly. For the synthetic ester, the magnitude of the thermal fault is overstated for the case when it was tested with paper. For the electrical faults, the IEC 60599 diagnosis method [9] recognizes all of the low-energy, arc discharge faults correctly as is shown in Table 6. For partial discharge, the result from the test involving the synthetic ester is correct, the results for mineral oil and the natural ester showing an incorrect diagnosis of a highenergy discharge. The reason for this is that a low concentration of C2H6 was generated in mineral oil, and a large amount of C2H4 was generated in the synthetic ester. To confirm the diagnosis of PD, the CH4/H2 ratio also should be approximately between 0.02 and 0.14. Table 7 shows the results from the final method of analysis that was examined, the IEEE method [10] that is based on the identification of key gases. For faults involving overheating of oil, the key gas is ethylene. This is expected to be 63% of the

10

IEEE Electrical Insulation Magazine

Figure 5. Relative percentages of dissolved combustible gases (without H2 and CO) for mineral oil and esters at 90C and 150C for 14 days (oil and paper).

total dissolved combustible gases with 20% of ethane also being present. None of the samples exhibit this gas concentration. In all cases, no fault would be diagnosed by using the key gas method (KGM). This is the case for both mineral oil and both of the alternative fluids. Table 8 shows the analysis of the KGM for thermal tests involving both oil and paper. Overheating of cellulose is indicated by having a relative proportion of CO above or equal to 92%. Therefore, the results suggest that the paper degradation is occurring in all cases for the test sample that uses the synthetic ester; only the 150C test indicates the correct fault for the mineral oil and natural ester tests. Table 9 shows the results of the KGM on the fault gases generated as a result of electrical faults. For the low-energy, arc discharge, C2H2 is the key indicator of that form of fault and the

relative percentage according to KGM should be greater than or equal to 30%. This was the case for all three oils, suggesting that the KGM is applicable in this case. In case of a cold corona-type discharge, H2 is the primary indicator and the relative percentage should be greater than or equal to 85%. The test results show that hydrogen is the dominant gas that is generated, its percentage of the TDCG is not at that level; however, its percentage of the TDCG is less than the specified level of 85% by the KGM method. These results lead to doubts on the applicability of setting exact percentages of key gases for fault diagnosis (both for mineral oils and for alternative fluids). It is felt that defining a range of percentage would be more appropriate, a view also expressed in [16] In mineral oil, the ratio of the C2H2 and H2 gas concentrations usually reflects the intensity of electrical discharges. When C2H2/H2 is close to or more than 1; the discharges are of the high

Figure 6. Relative percentages of dissolved combustible gases for mineral oil and esters.

September/October 2007 Vol. 23, No. 5

11

Table 4. DGA results for low energy arc discharge and cold corona type discharge in mineral oil and esters. Oil type Sample H2 CH4 C2H6 C2H4 C2H2 CO TDCG C* 5 1 0 1 1 18 26 Mineral oil LEDTa CDTb 901 145 24 270 1540 6 2886 20 2 0 2 2 2 28 C 7 0 0 1 0 9 17 Synthetic ester LEDT 97 9 2 26 126 37 297 CDT 5 2 0 0 0 2 9 C 8 1 2 1 6 6 24 Natural ester LEDT CDT 191 14 10 63 280 51 609 23 2 1 2 2 8 38

*: Control samples.
a b

: Low energy arc-discharge test.

: Corona type discharge test.

Figure 7. Duval triangle diagnostic results for three oils (mineral oil black, Midel 7131 red and FR3 green) under thermal and electrical faults.

energy type. When C2H2/H2 is smaller than one, the discharges are weaker and belong to the low energy discharge category (i.e., PD).

Conclusions
Although the molecular structures of esters are different from those of mineral oil, the thermal test results show that the gases generated by a selection of thermal and electrical faults are not different from those generated by mineral oil. The rate of generation of dissolved gases in esters is less in comparison with mineral oil. Esters are particularly stable under medium tempera-

Table 5. IEC 60599 diagnosis results for thermal tests. Test method Oil type Diagnosis result (oil only) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault t< 300C) No valid result (CH4 too low) Diagnosis result (oil and paper) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault (t< 300C) Thermal fault (300C< t <700C) No valid result (CH4 too low)

ture range thermal faults. However, FR3 is shown to generate a significant amount of ethane for thermal faults, suggesting that this also should be used as a key indicator of thermal faults in combination with ethylene in equipment using this type of fluid. The thermal tests also confirm that carbon monoxide and carbon dioxide are the key indicators of cellulose degradation in both mineral oil and esters. For electrical faults, acetylene is the key fault gas observed for low energy discharges, and hydrogen is the key fault indicating gas for partial discharges. Again, less gas is evolved by esters in comparison to that evolved by mineral oil. For both forms of fault, the reduction in the total gas generation will make it more difficult to identify faults at an early stage in practical applications unless the analysis process sensitivity can be improved. In terms of the diagnosis of the DGA samples using three different methods, thermal faults in all three oils are correctly diagnosed by the Duval triangle method. However, the temperature range of the fault is overestimated for the tests involving the

14 days at 150C Mineral oil Synthetic ester Natural ester 1 hour at 200C Mineral oil Synthetic ester Natural ester

Table 6. IEC 60599 diagnosis results for electrical tests. Test method Low energy discharge Oil type Mineral oil Synthetic ester Natural ester Cold corona-type discharge Mineral oil Synthetic ester Natural ester Diagnosis result Discharge of low energy Discharge of low energy Discharge of low energy Discharge of high energy Partial discharge Discharge of high energy

12

IEEE Electrical Insulation Magazine

Table 7. Key gas method analysis for thermal test (oil only). Oil/gas (%) Mineral oil Time (days) H2 CH4 C2H6 C2H4 C2H2 CO 21 29 6 15 3 3 13 15 7 4 23 65 1.5 3 5 3 2 1.5 0 1.5 0 0 0 0 63 46 80 70 70 25 Diagnostic result N/A N/A N/A N/A N/A N/A

Table 9. Key gas method for electrical tests. Oil/gas (%) Mineral oil Test type LED CDT Synthetic ester LED CDT Natural ester LED CDT H2 31 72 32.5 56 31 61 CH4 C2H6 C2H4 C2H2 CO 5 7 3 22 2.5 5 0.8 0 1 0 2 3 10 7 9 0 53 7 42 0 Diagnostic result

14 days at 150C 2 1 hour at 200C 7

0.2 Arcing in oil 7 N/A

Synthetic ester 14 days at 150C 2 1 hour at 200C 8

12.5 Arcing in oil 22 8 21 N/A Arcing in oil N/A

Natural ester 14 days at 150C 3 1 hour at 200C 6

10.5 46 5 5

esters. Correct identification of thermal faults also takes place for the majority of samples assessed using the IEC technique, the only exceptions being natural esters tested with paper at 200C in which no result could be produced (not enough methane was generated) and synthetic esters tested with paper at 200C in which case the temperature of the fault was overestimated. For electrical discharges, all methods correctly identify the low-energy arcing fault. For corona discharge, significant hydrogen is generated in all cases, but only the test involving the synthetic ester that was then diagnosed using the IEC technique yielded the correct results. When comparing the three diagnostic methods on different types of oil under thermal and electrical tests, it is concluded that Duval triangle and IEC methods are more applicable than the IEEE KGM (see Table 10). Esters have the same DGA fingerprints as mineral oil but to yield the correct fault diagnosis result, the criteria of fault gas ratio or percentage needs to be redefined.

Table 10. Correctly identified faults for different types of analysis. Standard diagnosis methods Mineral Oil Synthetic Ester Natural Ester Duval 6 of 7 5 of 7 4 of 7 IEC 5 of 6 6 of 6 3 of 6 IEEE 2 of 6 3 of 6 2 of 6

Acknowledgements
The authors wish to thank AREVA T & D, EdF Energy, M & I Materials, National Grid, Scottish Power, TJ|H2b analytical services and United Utilities for their financial and technical support to form the research consortium Alternative fluids for large power transformers at The University of Manchester. The authors particularly appreciate the help given from Ian James, Alan Darwin, Paul Dyer, Russell Martin, James ONeil, Paul Jarman, Peter Docherty, Dave Walker, John Noakes, and Tony Byrne for providing invaluable expertise and technical guidance toward the project.

References
Table 8. Key gas method analysis for thermal test (oil and paper). Oil/gas (%) Mineral oil Time (days) H2 Diagnostic CH4 C2H6 C2H4 C2H2 CO result 2 4 1 0.7 0.3 0.5 0.4 0.7 0.3 0.4 0.01 95 0.03 85 0 0.1 0 97 93 96 Overheated cellulose N/A Overheated cellulose Overheated cellulose Overheated cellulose N/A

14 days at 150C 0.4 3 1 hour at 200C 2 9

Synthetic ester 14 days at 150C 0.6 1 1 hour at 200C Natural ester 2.5 3

14 days at 150C 0.5 0.5 3 1 hour at 200C 1.5 0.6 11

0.04 87

[1] K. Rapp, and P. Stenborg, Cooper Power Systems field analysis of Envirotemp FR3 fluid in sealed versus free-breathing transformers, CP0414, Cooper Power Systems, Waukesha, WI, 2004. [2] D. Martin, I. U. Khan, J. Dai, and Z. D. Wang, An overview of the suitability of vegetable oil dielectrics for use in large power transformers, in Proc. 5th Annual Euro TechCon, Chester, United Kingdom, November 2830, 2006. [3] EPRI Report 1000438: Environmentally acceptable transformer fluids; Phase 1 state of the art review; Phase 2 Laboratory testing of fluids, Palo Alto, CA, Nov. 2000. [4] T. V Oommen, C. C. Claiborne, and C. T. Mullen, Biodegradable electrical insulation fluids, in Proc. IEEE Electrical Insulation Conference, Chicago, 1997, pp. 465468. [5] T. V. Oommen, C. C. Claiborne, and E. J. Walsh, A new vegetable oil based transformer fluid: Development and verification, in Proc. Conf. IEEE Elect. Insul. Dielect. Phenomena, 2000, pp. 308312.

September/October 2007 Vol. 23, No. 5

13

[6] OECD 301 test series OECD guideline for testing of chemicals, Adopted by the Organisation for Economic Co-operation and Development Council, Paris, France, on July 17, 1992. [7] C. P. McShane, Vegetable oil based dielectric coolant, IEEE Industry Appl. Mag., vol. 8, pp. 3441, May/June 2002. [8] K. Rapp, C. McShane, and J. Luksich, Interaction mechanisms of natural ester dielectric fluid and Kraft paper, in Proc. IEEE Int. Conf. Dielect. Liquids, 2005, pp. 393396. [9] IEC60599, Mineral oil-impregnated electrical equipment in service: Guide to the interpretation of dissolved and free gases analysis, IEC Publication 60599 (19992003), Mar. 1999. [10] IEEE Guide for the Interpretation of Gases Generated in OilImmersed Transformers, IEEE Standard C57.104-1991, June/July 1991. [11] M. Duval, A review of faults detectable by gas-in-oil analysis in transformers, IEEE Elect. Insul. Mag., vol. 18, pp. 817, May/ June 2002. [12] M. Duval and A. dePablo, Interpretation of gas-in-oil analysis using new IEC Publication 60599 and IECTC 10 Databases, IEEE Elect. Insul. Mag., vol. 17, pp. 3141, Mar./Apr. 2001. [13] T. V. Oommen Vegetable oils for liquid filled transformers, IEEE Elect. Insul. Mag., vol. 18, pp. 611, Jan./Feb. 2002. [14] C. McShane, K. Rapp, J. Corkran, G. Gauger, and J. Luksich, Aging of paper insulation in natural ester dielectric fluid, in Proc. IEEE/PES Transmission Distribution Conf. Exposition, Oct. 28Nov. 2, 2001. [15] BS EN60567 Oil-filled electrical equipment Sampling of gases and of oil for analysis of free and dissolved gases Guidance, pp 1939, Dec. 2005. [16] X. Chen and W. Chen, Research of relationship between partial discharge and dissolved gases concentration in oil, in Proc. XIVth Int. Symp. High Voltage Eng., Tsinghua University, Beijing, China, August 2529, 2005.

Zhongdong Wang received the BEng. and MEng. degrees in high voltage engineering from Tsinghua University of Beijing in 1991 and 1993, and a Ph.D. in electrical engineering from UMIST in 1999. Dr. Wang joined the Electrical Energy and Power Systems Group of the School of Electrical and Electronic Engineering at the University of Manchester in 2000, where she now is a senior lecturer. Her current research interests include condition monitoring, transformer modeling and FRA and transients simulation, insulation aging, and alternative insulation materials for transformers. Ian Cotton (M98, SM07) received a Class I BEng. (Hons.) degree in electrical engineering from the University of Sheffield in 1995 and a Ph.D. degree in electrical engineering from UMIST in 1998. He is currently a Senior Lecturer at the Electrical Energy and Power Systems Group of the School Of Electrical and Electronic Engineering at the University of Manchester. His current research interests include power systems transients, the use of higher voltage systems in aerospace applications, and power-system induced corrosion. He is a member of the Institution of Electrical Engineers and a Chartered Engineer. Susan Northcote is a Chartered Chemist and a Designated European Chemist. She is the Operational Director for TJ|H2b Analytical Services European Centre. Ms. Northcote represents the Royal Society of Chemistry on the British Standards Gel 10 committee and represents the UK on a number of IEC maintenance teams, whose roles are to evaluate and update methods for the analysis of insulating media.

Imad-Ullah-Khan received a BEng. (Hons.) degree in electrical engineering from the National University of Science and Technology, Pakistan, in 2004. He is currently a Ph.D. student at the Electrical Energy and Power Systems Group at the University of Manchester. His research interests include alternative transformer insulation, electric stress analysis using FEM and dissolved gas analysis. He is a student Member of the Institution of Engineering and Technology (IET).

14

IEEE Electrical Insulation Magazine

También podría gustarte