Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Alcatel BSS
Site Engineering Method SPP- 59
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 1/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Contents
Preface ..................................................................................................3 1. Customer or Operator Services......................................................6 2. Alcatel Services ...............................................................................8 3. General specifications of product ................................................10 4. Site preparation and supply requirements for Customer or Operator..............................................................................................19 5. Installation and supply requirements for Alcatel ........................27 Appendix A: Installation help, rack layout and shelf positions. ....29 Appendix B: Installation help, site cabling cable tray with A9130 BSC/MFS Evolution cabinet, power supply, DDF 120 ohms, EAB, LMT.................................................................................30 Appendix C: Installation help, Site cabling raised floor with A9130 BSC/MFS Evolution, power supply, DDF 75 ohms, EAB, LMT......................................................................................................32 Abbreviations .....................................................................................34
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 2/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Preface
Purpose
The document defines the conditions regarding site preparation, for installing EVOLIUM A9130 BSC/MFS Evolution and activities to be handled by Customers and Alcatel services.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 3/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
History
Date 06/12/04 Edition 01 Comments Released.
Audience
Alcatel Staff (Intermediate level) Installers Customer and Alcatel services
Assumed knowledge
You must have a basic understanding of the following: BSS Alcatel operations Site Engineering methods
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 4/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Document Structure
This section provides a summary of the contents of every chapter. Chapter 1 : Chapter 2 : Chapter 3 : Chapter 4 : Customer or Operator Services Alcatel Services General specifications of product Site preparation and supply requirements for Customer or Operator Installation and supply requirements for Alcatel
Chapter 5 :
Appendix A : Installation help, rack layout and shelf positions. Appendix B : Installation help, site cabling cable tray with A9130 BSC/MFS Evolution cabinet, power supply, DDF 120 ohms, EAB, LMT. Appendix B : Installation help, site cabling raised floor with A9130 BSC/MFS Evolution cabinet, power supply, DDF 75 ohms, EAB, LMT. Abbreviations : Acronyms encountered within the document.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 5/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 6/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
The customer or operator is responsible for choosing the site and for all preparation work. The main services are as follows: Site Preparation of site. Power supply Earth PCM links. Lighting Circuit breaker Lightning protection (if necessary) Power distribution box : 48VDC or 60VDC Ground bar/plate Cable way runs from the infrastructure to each BSC and/or MFS. PCM network termination (NTL) upline (if necessary) PCM and alarm distributor (DDF) Of main supplies,
Main supplies
Installation
All services not provided by Customer or Operator shall be treated as additional Alcatel services.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 7/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
2. Alcatel Services
This chapter describes the services to be supplied by Alcatel. 2.1 - Services to be performed
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 8/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel installs the rack . The main services are listed hereafter:
Basic installation kit. PCM cables from Alcatel equipment to DDF. Ethernet cables (for local OMC-R connection and/or for EAB connection). DC power and ground cables, External Alarm Box (delivered with BSC only). Earthquake kit, optional DDF, optional A9130 BSC/MFS Evolution installation. PCM & Ethernet cables installation. DC power and ground cables installation. External Alarm Box installation, (BSC configuration only) DDF installation, optional. Commissioning of EVOLIUM A9130 BSC/MFS Evolution. Acceptance of EVOLIUM A9130 BSC/MFS Evolution.
Installation
Commissioning
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 9/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 10/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 11/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Environmental conditions for EVOLIUM A9130 BSC/MFS Evolution (EN 300 019) Environmental parameter Low air temperature High air temperature low Low relative humidity High relative humidity Low absolute humidity High absolute humidity Low air pressure High air pressure Sand Dust (suspension) Dust (sedimentation) Stationary vibration, sinusoidal: - Peak-displacement amplitude - Peak-acceleration amplitude - Frequency range Non-stationary vibration including shock: - Shock-response spectrum type L, peak acceleration - Shock-response spectrum type II, peak acceleration Unit
C C % % g/m g/m kPa kPa mg/m mg/m mg/(mh)
mm m/s Hz
2
0.3 1 2 to 9 9 to 200
3.5 10 2 to 9 15
1.5 5 2 to 9 9 to 200
m/s
40
---
40
m/s
---
100
---
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 12/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Electromagnetic environment
EVOLIUM A9130 BSC/MFS Evolution compliant with EN 300 386 (2001) class B requirements.
Acoustic noise
EVOLIUM A9130 BSC/MFS Evolution compliant to ETS 300 753 Class 3.1: Acoustic noise emitted by Telecommunication equipment. Telecom equipment room attended.
Safety
EVOLIUM A9130 BSC/MFS Evolution compliant with: EN 60950-1 (2001): Safety of information technology equipment.
Waterproofness
EVOLIUM A9130 BSC/MFS Evolution compliant with: IEC 529 / EN 60529 / IP20: Degrees of protection provided by enclosures (IP class). DC Power supply: ETSI EN 300 132-2
EVOLIUM A9130 BSC/MFS Evolution compliant with the new European directives for environment: WEEE: Wastes of Electrical and Electronic Equipment. RoHS: Restriction of Hazardous Substances. Ecodesign requirements: TR/70 ECMA technical report (guideline).
Minimum configuration includes 1 ATCA shelf + 1 LIU shelf Maximum configuration includes 2 ATCA shelves + 2 LIU shelves
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 13/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 14/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 15/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
E1 interfaces: LIU shelf E1 boards E1 links 120 Ohms 1 or 2 per BSC/MFS cabinet. Up to 16 x E1 boards per shelf. 16 x E1 per board. Total = 256 E1
PCM lines are: - Multipair cable 34 pairs arranged as two insulated copper conductors, twisted per pair, with one SCSI 68 pins connector at both ends (not adjusted on site). On DDF side, these cables are connected to patch pannel interface. This module performs adaptation: From SCSI connector to insertion terminal blocks (for 120 network). The terminal blocks (8 pairs) accept wire diameter 0.32 to 0.8 mm. From SCSI connector to BALUN transformer (for 75 network).
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 16/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Specification of 2 Mbit/s - 34 pairs PCM cable: Type of cable 34 pairs 28 AWG solid cable Conductor diameter = 0,32 mm (copper) Jacket diameter = 11, 3 mm Minimum bend radius = 66 mm Loss max. @ 1 MHz = 3.5 dB / 100 m Customer connection DDF side Inserting (120 ). BNC or 1.6/5.6 female (75 ).
1 or 2 per cabinet (depends on configuration) 2 boards per shelf Physical interface: 10/100/1000Base TX Connector type: RJ45. Ethernet cable 30m UTP category 5 / 2 twisted pairs Connectors: RJ45 male
Cable type
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 17/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
Buscoupler connection: RJ45. The alarm level is defined as follows: - Voltage via power jumper contacts = DC 24V (-15% +20%) - Signal voltage (0) = DC 3V +5V - Signal voltage (1) = DC 15V 30 V - Input filter = 3ms - Current supply (typ) = 4.5 mA - Isolation = 500V system / supply. External Alarm Box dimensions (overall): - Height : 280 mm - Width: 380 mm - Depth: 180 mm Fixing points between axis are: 254mm x 354mm.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 18/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for the Customer or the Operator
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 19/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 20/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
The site shall be handed over with the leased lines in operation.
The client shall provide the site (in which the equipment is to be installed) with hoisting and handling devices to ease delivery of the equipment . If not, the costs incurred by the installer will be added to the installation costs and charged to the client. The entrances to the buildings must be large enough to transport the rack in an upright position. Access to the sites must be facilitated: - either by the presence of a local correspondent during delivery, assembly/wiring, and initial start-up of the equipment. - or by obtaining a set of duplicate keys to the sites prior to those operations. A set of furniture is provided, in sufficient quantity, as part of preparation of the room: at least 1 table and 2 chairs, (work space for the operating terminals). One or two phone lines are needed for the periods of installation and initial start-up of the equipments. The ceiling height must be greater than or equal to 2.5 m. The floor must be able to bear a load of 300 kg per cabinet.
Service facilities
Ceiling Floor
Each cabinet must be fixed to the floor or on raised floor with four anchor bolts. If earthquake option kit is required, it can be installed only with a raised floor exactly 34 cm high from the concrete ground. Distance constraints Various clearance spaces must be provided for maintenance and inspection operations and to allow equipment ventilation. The external ports of the equipment (power supply, lines, etc.) should be protected.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 21/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
Cables are fed in through the top or the botom of the rack. The power cables from DC distribution box to the BSC/MFS cabinet should not exceed 40 meters. The PCM cables from DDF to BSC/MFS cabinet must not exceed 40m.
Lighting and wall The lighting in the room must have an intensity of 300 Lux at 1 m above the floor. No more than 500 Lux. sockets The external lamps on site should be of the electronic ballast type. 230V wall sockets must be provided in the room [one socket every 3 m; 2 poles (L, N) and ground; 16 A]. Sockets providing a 230 V emergency backup source must be provided for the operating equipment (LMT, )
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 22/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
Labtop LMT provided in option, but necessary during the installation and commissioning. The length of connecting cables between labtop equipment and racks on the sites shall not exceed 15 meters Clearance Length of cables from BSC/MFS to LMT terminal Side clearance (Only one side is necessary) Front clearance Rear clearance Dimension and weight Width (mm) Depth (mm) Height (mm) Maximum weight (kg) 100-240V, 50-60 Hz consumption Maximum power consumption (W) Fuse gauges, earth leakage protection 30 mA Gauge (A) 6 200 300 265 45 3 15 m 0,7 m 1m 0,2 m
The customer shall install all cables at the position of first rack.
The power plant should include standard backup batteries for emergency power.
The EVOLIUMTM A9130 BSC/MFS Evolution cabinet requires a nominal input voltage of 48VDC or 60VDC. The static input range should not exceed 38.4VDC to 72VDC. The EVOLIUMTM A9130 BSC/MFS Evolution cabinet must operate with two 48V(BAT A / BAT B) wires and two 0V (BATRET A / BATRET B) wires with redundancy between them. A power distributing box must be provided as part of the room preparations. It must include marked fuses for each output, and a grounding bus bar for the power cables. The box or power station must be marked.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 23/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
Power cable Lugs are necessary at cable end on equipment side. The power input terminals are M6 (thread stud) type connector. recommended Double sheathing. Multi-strand flexible copper core. Strand composition 0,41 mm max. class 5 (IEC 60 228). Cable type to be compliant with local legislation and standard for electrical installation in technical site. 5 cables (4x-48V/0V + Ground) are necessary: Signal -48 V DC, (BAT A / BAT B) 0V DC, (BATRET A / BATRET B) Frame Ground Distribution box Section 16 mm 25 mm 16 mm 25 mm 35 mm Length Up to 20m >20m to 40m Up to 20m >20m to 40m Up to 40 m Yellow/Green Black Color Blue
The distribution should be defined for using lugs of system 8 mm for BAT RET (0V), 8 mm for BAT A / BAT B (-48VDC), 8 mm for electrical earth. The customer provides breakers with the following gauges (with lightning protection if necessary): - The gauges should be calculated to operate with ETS300132-2 standard (-40,5VDC). - The breakers are only on BAT A and BAT B wires. - On first approach, the gauge is calculated like: I max. + 1/3 I max. (Imax at -40.5VDC)
Breakers recommendations
It is wished to put the gauge in agreement with the final configuration to avoid an interruption of service during an extension. Number of fuses per BSC/MFS cabinet Standard gauge for each cabinet fully equipped 2 (BAT A and BAT B) 80 A
Grounding distribution
A ground plate directly connected to the ground box of the building must be available in the room. The grounding system is composed of a metallic grounding network, formed of iron flooring .The grounds are respectively connected to grounding plate, and to the metallic ground of the power distributing box. The ground wire circuit resistance must be less than 3 Ohms.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 24/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
The following shall also be handed over: a diagram of the distribution frame, identifying the lines, a wiring diagram, the technical and commercial references of each line, the lines connected to the line terminal blocks, the looped Tx/Rx lines on the cable side in the room, the quality tested lines of the local distribution frame to the remote distribution frame.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 25/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 4: Site preparation and supply requirements for Customer or Operator
The customer shall produce an overall drawing for each unit site.
General site The drawing shall be submitted to Alcatel, after the initial site inspection, or in preliminary project documentation concerning the site supplied by the customer. information requirements The drawing shall indicate the position of the unit with its connections, relative to a reference point. The site data sheet must be completed based on data provided by the client or during site inspection. The site information procedure document should be completed by the customer or during a site inspection visit with Alcatel. The operator shall hand over to the constructor, with the preliminary study document or on the occasion of the site inspection: A drawing of the distribution frame locating the links with technical and commercial numbers of each link. The links with transmit/receive loops set up on the cable side at the unit.. Links qualified as far as the unit. The client shall draw up a layout map for each site. The map will indicate the location of: racks, power supplies, air-conditioning system, cable ways, collector rod system, grounding plate, digital distribution frame (positioning of the terminal blocks), furniture for the operating and maintenance tools.
Layout
That plan is submitted to the manufacturer, either after an initial inspection of the site or in a preliminary project file for the site provided by the client.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 26/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 5: Installation and supply requirements for Alcatel
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 27/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Chapter 5: Installation and supply requirements for Alcatel
- Preliminary preparation. - Rack installation. - Additionnal shelf (ATCA or LIU) installation. - Power supply cables installation. - PCM cables installation. - Ethernet cables installation - External Alarm box installation - Finishing installation. and are detailed in EVOLIUM A9130 BSC/MFS Evolution installation manual. BSC/MFS Evolution powering up and running in accordance with EVOLIUM A9130 BSC/MFS Evolution commissioning manual. Customer agrees that BSC/MFS Evolution has been installed, commissioned and are running in accordance with EVOLIUM A9130 BSC/MFS Evolution acceptance test document.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 28/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Appendix A: Installation help, rack layout and shelf positions.
PDU
Stand-alone configurations
ATCA shelf 4
1 3
1 1
1 0
1 2
1 4
XP E M
XL IU
XL IU
X L IU
XL I U
XL I U
XL I U
X L IU
XL IU
XM UX
X MU X X L IU
X LI U X L I U
X L IU
XL I U
XL I U
XL IU X L I U XP E M
XP E M
XL IU
XL I U X L IU
XL I U
XL I U
XL IU
X L IU
XL I U XM UX
X MU X X L IU
X L IU X L IU
X L IU
XL I U
XL IU
XL I U X L IU
XP E M
X P EM
X P EM
-4 8/ 60 V DC
- 48 /60 V DC
-4 8/ 60 V DC
-48 /60 V DC
4A
4A
4A
4A
MFS (21GP)
ATCA shelf 3
1 3
1 1
1 0
1 2
1 4
Rack-shared configuration
X P E M X LIU X P EM
X LIU
X LI U
X LI U
X LI U
X LI U
X LIU
X LIU X M U X
X M U X X LIU
X L IU X LI U
X LI U
X LI U
X LIU
X LIU X LIU X P E M
-48 /6 0 VD C
-48 /6 0 VD C
4A
4A
XP E M
XL IU
XL I U X L I U
XL I U
XL I U
XL IU
X L I U X L IU X MU X
XM UX XL IU
X L IU
X L IU
XL I U
XL IU
X L I U X L I U X L IU
XP E M
X P EM
- 48 /60 V DC
- 48 /60 V DC
4A
4A
X P E M X LIU X P EM
X LIU
X LIU
X LIU
X LIU
X LIU
X LI U
X LIU X M U X
X M U X X L IU
X LIU X LIU
X LIU
X LIU
X LI U
X LI U X LIU X PE M
XP E M XL IU XL I U X L IU XL I U XL I U XL IU X L IU XL I U XM UX X MU X X L IU X L IU X L IU X L IU XL I U XL IU XL I U X L IU XP E M
X P EM
-4 8/ 60 V DC
-48 /60 V DC
4A
4A
-4 8/60 V DC
-48 /60 VD C
4A
4A
BSC/MFS or 2 x BSC
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 29/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Appendix B: Installation help, site cabling cable tray with A9130 BSC/MFS Evolution cabinet, power supply, DDF 120 ohms, EAB, LMT, ground plate.
Appendix B: Installation help, site cabling cable tray with A9130 BSC/MFS Evolution cabinet, power supply, DDF 120 ohms, EAB, LMT.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 30/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Appendix B: Installation help, site cabling cable tray with A9130 BSC/MFS Evolution cabinet, power supply, DDF 120 ohms, EAB, LMT, ground plate.
Clearance
AC Box
Ground Plate
600 mm
600 mm
Alcatel
Edition 01
Status Released
LMT
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
1 meter
Date 06/12/04
Page 31/34
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Appendix C: Installation help: Site cabling raised floor with A9130 BSC/MFS Evolution, power supply, DDF 75 ohms, EAB, LMT, ground plate.
Appendix C: Installation help, Site cabling raised floor with A9130 BSC/MFS Evolution, power supply, DDF 75 ohms, EAB, LMT.
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 32/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
SPP-59, EVOLIUMTM A9130 BSC/MFS Evolution Appendix C: Installation help: Site cabling raised floor with A9130 BSC/MFS Evolution, power supply, DDF 75 ohms, EAB, LMT, ground plate.
Clearance
AC Box
Ground Plate
600 mm
600 mm
Alcatel
Edition 01
600 mm
Status Released
LMT
546 mm
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel
1 meter
Date 06/12/04
Page 33/34
Abbreviations
Sigle ATCA BSC CBC DC DDF E1 EAB GP GSM IP LIU LMT MFS O&M OMC-R PCM PDU SGSN SG SSW Base Station Controller Cell Broadcast Center. Direct Current Digital Distribution Frame 2.048 Mbit/s External Alarm Box GPU board for MX project (ATCA) Global System for Mobile communication Internet Protocol Line Interface Unit. Local Maintenance Tool. Multi-BSS Fast packet Server. Operation & Maintenance Operation and Maintenance Center - Radio Pulse Code Modulation Power Distribution Unit Serving GPRS Support Node Signal Ground Subrack SWitch END OF DOCUMENT Description Advanced Telecom Computing Architecture
Alcatel
Edition 01
Status Released
Date 06/12/04
Page 34/34
All rights reserved. Passing on and copying of this document, use and communication of its contents not permitted without written authorization from Alcatel