Course Outline
Presenter Biographies
ASHRAE Standards
62.1 and 90.1
and VAV Systems
an
Engineers Newsletter
Live telecast
2008 Trane
2008 Trane
Agenda
Demand-controlled ventilation
Dehumidification
Simultaneous heating and cooling
Questions
Summary
2008 Trane
Todays Presenters
Dennis Stanke
staff applications
engineer
ASHRAE Standards
62.1 and 90.1
and VAV Systems
DemandDemand-controlled
ventilation
2008 Trane
90.1 requirements
Dynamic Reset
dynamic reset
Zone Calculations
1. Calculate breathing-zone outdoor airflow, using
(Table 6-2)
2008 Trane
dynamic reset
dynamic reset
Multiple-Zone Systems
Cant deliver OA with 100% efficiency
because some excess OA exhausts
VAV
air handler
Some excess
(unused) OA
leaves building
OA
EA
RA
VAV
VAV
PA
RA
zone 1
OVERVENTILATED
PA
VAV
RA
zone 2
PROPERLY
VENTILATED
PA
RA
zone 3
OVERVENTILATED
2008 Trane
System Calculations
6.2.5 Multiple-Zone Recirculating Systems
Ev = 1 + Xs Zd
2
Xs = Vou/Vps
Zd = Voz/Vdz
4
2008 Trane
system calculations
=
=
=
=
=
=
=
=
=
=
(entry)
(entry)
Vbz/Ez
(measured)
Voz/Vdz
=
=
=
=
=
Vbz
Vou/Vdz
1 + Xs Zd
smallest (Evz)
Vou/Ev
=
=
=
=
=
uncorrected OA flow
average OA fraction
zone vent. efficiency
system vent. efficiency
outdoor air intake flow
2008 Trane
300 1,300
85
760
0.283 0.585
8, 810
8,810
w/VRC
w/o VRC
8,810
8,410
dynamic reset
10
part load
ventilation optimization
At part load:
2008 Trane
Pz
140
140
260
260
Vot
Vot
w/vent w/vent
reset
& DCV
40
500 1,300
8,810
85 TOD
760
0.170
0.585
scheduled
8,810
TOD
even more
2008 Trane
11
ASHRAE Standards
62.1 and 90.1 and
VAV Systems
90.1 Requirements
Demand-Controlled
ventilation
2008 Trane
ventilation optimization
lounge
rest
room
office
AHU
CO2
OCC
corridor
TOD
elevators
vestibule
reception area
storage
mech
room
OCC
office
CO2
conference rm
TOD
computer room
2008 Trane
12
c.
2008 Trane
13
Economizers
Climate zone
Economizer unnecessary
135,000 Btu/h
65,000 Btu/h
2008 Trane
14
Dry
Moist
Required for
Systems > 11T
Required for
Systems > 5T
Economizer
Not Required
2008 Trane
2008 Trane
15
2008 Trane
2008 Trane
16
Equation to
VIot3 COA
Vpz , Cs
I
correlate CO2
setpoints to OA
rate derived from
basic principals
C R COA
N, v, CR
VIot3 CR
8400E z m
R A
Rp a z
Pz
VIot3 CR
2008 Trane
17
2008 Trane
=
=
=
=
=
=
=
=
18
2008 Trane
(CO2max)
19
1000
Room
CO2
Voz
Vat
0
800
600
OA rate
w/DCV
400
62.1 min
OA rate
0
10
1200
20
30
40
zone population, Pz
50
60
200
0
2008 Trane
infrared
incandescent
infrared
source
interactive
sensor
element
reduction
oxidation
(voltage output)
light
resistance
emission
change
quenching
(color change)
custom designed
infrared filters
reference
diffusion
target gas
membranes
patented
waveguide
microprocessor
dual beam
micro-machined
thermopile
detector
2008 Trane
20
2008 Trane
sensor in
breathing
zone
zone
CO2
sensor
2008 Trane
21
2008 Trane
1) Increase zone
airflow and reheat?
CO2
2008 Trane
22
OA
Minimum
Setpoint
0%
CO2 Signal
2008 Trane
ASHRAE
Standards 62.1
and 90.1 and VAV
Systems
Dehumidification
2008 Trane
23
90.1 requirements
Dehumidification
Std 62.1-2007 limits space relative
2008 Trane
24
single-zone system
T
space
EA
constantspeed fan
OA
MA
SA
full load
basic CV system
OA 96F DB,
76F WB
85
80
,
re
MA 80.6F DB
(1,500 cfm)
u
-b
et
w
55
t
lb
60
30
35
40
SA
160
140
drier
full load
OA
65
120
100
80
MA
50
30
warmer
F 75
4.8atu
r to70
ns
pe
em
SA 55.7F DB
45
colder
60
RA
40
20
40
50
60
70
80
dry-bulb temperature, F
90
100
RA 74F DB,
52% RH
180
wetter
0
110
2008 Trane
25
part load
basic CV system
OA 76F DP,
84F DB
85
MA 77F DB
e,
ur
(1,500 cfm)
l
bu
et
w
55
50
35
40
F 75
part load
OA
m
te 65
RA'
60
160
140
full load
OA
t
ra 70
pe
SA 63F DB
30
80
65% RH
120
100
MA
80
SA
60
RA
45
40
20
30
40
50
60
70
80
dry-bulb temperature, F
90
100
RA 74F DB,
52% RH
180
0
110
2008 Trane
part load
basic CV system
OA 76F DP,
84F DB
85
compared
to 52% at
full load , F
MA 77F DB
re
SA 63F DB
(1,500 cfm)
m
te
u
-b
et
w
55
50
30
30
35
40
45
40
80
part load
OA
75
SA
65
120
100
MA
80
RA
3.7 tons
50
140
full load
OA
tu
ra 70
pe
lb
60
160
60
70
80
dry-bulb temperature, F
compared
to 4.8 tons
at full load
90
100
60
40
20
RA 74F DB,
67% RH
180
0
110
2008 Trane
26
OA
CA
CA
CA
SA
SA
RA
direct to
spaces
RA
2008 Trane
100% OA system
part load
OA 76F DP,
84F DB
CA 52F DB,
52F DP
(cold air)
85
m
te
u
-b
et
w
55
50
30
30
35
40
45
CA
lb
60
part load
OA
F 75
tu
ra 70
pe
120
100
65
80
RA'
SA
140
RA
60
40
20
40
50
60
70
80
dry-bulb temperature, F
90
100
,
re
RA 74F DB,
50% RH
(1,050 cfm)
160
80
(450 cfm)
SA 68F DB
180
0
110
2008 Trane
27
Single-Path VAV
EA
RA
space
T
OA
MA
SA
variablespeed fan
space
T
2008 Trane
part load
OA
RA
DP,
DB
DB,
RH
MA
79F DB
SA
55F DB
compared to
67% with
80
basic CV system
85
180
160
part load
OA
75
70
(900 cfm)
65
50
30
30
35
40
SA
45
120
100
MA
80
60
55
140
60
RA
40
20
40
50
60
70
80
dry-bulb temperature, F
90
100
76F
84F
74F
57%
0
110
2008 Trane
28
67%
73%
watch out
65%
70%
not so good
+ mixed-air bypass
52%
65%
68%
not so good
+ 2-speed fan
52%
60%
68%
works OK
+ return-air bypass
52%
55%
60%
works well
+ reheat (direct)
52%
55%
55%
works well*
50%
53%
55%
works well*
52%
57%
60%
works well
2008 Trane
29
section 6: HVAC
Mandatory Provisions
prescriptive
requirements
mandatory
provisions
(6.4)
proposed
HVAC design
(6.5)
Energy Cost
Budget Method
(ECB, 11)
Simplified
Approach
Option
(6.3)
90.1-compliant
HVAC system
2008 Trane
Reheating
2008 Trane
30
simultaneous heatingcooling
Dehumidification Exceptions
a) Reducing supply airflow to 50%, or minimum
ventilation rate specified by 62.1
b) Systems < 6.67 tons that can unload at least 50%
c) Systems smaller than 3.3 tons
d) Systems with specific humidity requirements for
process needs (e.g. museums, surgical suites,
supermarkets)
e) 75% of reheat/recool energy is site-recovered or
site-solar
f)
2008 Trane
31
possible
2008 Trane
Compliance Techniques
VAV Systems
32
Compliance Techniques
Single zone systems
2008 Trane
maximum speed
supply air
temperature
setpoint
minimum speed
minimum setpoint
heating loop signal
33
ASHRAE
Standards 62.1
and 90.1 and VAV
Systems
Simultaneous Heating
and Cooling
2008 Trane
No reheating
No recooling
No mixing or simultaneously
supplying mechanically (or
economizer) cooled and
mechanically heated air
2008 Trane
34
simultaneous heatingcooling
Zone-Control Exceptions
a) Reduce zone airflow to
prescribed limit
pressurization requirements
or code-required minimum
circulation rates
c) Site-recovered or site-solar
2008 Trane
simultaneous heatingcooling
Zone-Control Exceptions
Zone airflow does not exceed whichever
is largest:
a) ASHRAE Standard 62s zone
requirements for outdoor air
b) 0.4 cfm/ft
2008 Trane
35
Reheat Minimum
0.5
1.5
2.5
2008 Trane
simultaneous heatingcooling
Zone-Control Exceptions
Zone airflow does not exceed whichever is
largest:
a) ASHRAE Standard 62s zone
requirements for outdoor air
b) 0.4 cfm/ft
c) 30% of supply air
d) 300 cfm
e) ASHRAE Standard 62s
multiple-space requirements,
if approved by AHJ
2008 Trane
36
90.1 requirements
2008 Trane
RA
space
T
OA
MA
SA
variablespeed fan
space
T
2008 Trane
37
2008 Trane
Zone Calculations
1. Calculate breathing-zone outdoor airflow, using
(6-1)
(Table 6-2)
(6-2)
2008 Trane
38
Multiple-Zone Systems
4.
5.
(6-6)
6.
7.
(6-8)
2008 Trane
Multiple-Zone Systems
Step 4 (find Zd = Voz/Vdz), use minimum
2008 Trane
39
If Vdz-exp = Voz
Questionableairflow
design:
100% OA
discharge
airflow
Vdz-exp
Vdz-rht
Vdz-clg
Voz
local reheat
design heating
deadband
zone load
If Vdz-exp = Vdz-rm
Conservativeairflow
design:
< 100% OA
discharge
airflow
Vdz-exp
Vdz-rht
Vdz-clg
Voz
local reheat
design heating
deadband
zone load
design cooling
40
Less
airflow
conservative
design:
<< 100% OA
discharge
airflow
Vdz-exp
Vdz-rht
Vdz-clg
Voz
local reheat
design heating
deadband
zone load
discharge
airflow
Vdz-exp
Vdz-rht
Vdz-clg
Voz
local reheat
design heating
deadband
zone load
design cooling
41
possible
62MZCalc
compared to DOAS
42
62MZCalc Spreadsheet
2008 Trane
62MZCalc Spreadsheet
2008 Trane
43
62MZCalc Spreadsheet
2008 Trane
62MZCalc Spreadsheet
2008 Trane
44
62MZCalc Spreadsheet
2008 Trane
2008 Trane
45
2008 Trane
2008 Trane
46
2008 Trane
2008 Trane
47
2008 Trane
2008 Trane
48
2008 Trane
Answers to
Your Questions
2008 Trane
49
62.1 allows
No conflict
CO2 sensing is often used
2008 Trane
No conflict
Use VAV or two-speed fans
Consider recovering energy, even if not
required
2008 Trane
50
No conflict, but
Challenges must be met through proper system
2008 Trane
www.trane.com/engineersnewsletter
2008 Trane
51
ENL Archives
www.trane.com/bookstore
Air distribution
Refrigerant-to-air systems
Control strategies
Acoustics
Ventilation
Dehumidification
2008 Trane
May 13
Ice Storage System Design: Round-theClock Operation for Office Buildings and
K-12 Schools
November 4
2008 Trane
52
Bibliography
Industry Standards and Handbooks
ASHRAE Standard
62.1 and 90.1 and
VAV Systems
Trane Publications
Murphy, J., Better Part-Load Dehumidification,
Engineers Newsletter 33-2 (2004).
Murphy, J., Advances in Desiccant-Based Dehumidification,
Engineers Newsletter 34-4 (2005).
Stanke, D., Dehumidify with Constant-Volume Systems,
Engineers Newsletter 29-4 (2000).
Page 1 of 2
Bibliography
Stanke, D., Dedicated Ventilation Systems,
Engineers Newsletter 30-3 (2001).
Trane, Air-to-Air Energy Recovery in HVAC Systems Trane application
manual SYS-APM003-EN (2002)
Trane, Dehumidification in HVAC Systems Trane application manual
SYS-APM004-EN (2002)
Murphy, J., CO2-based demand-controlled ventilation with ASHRAE
Standard 62.1-2004, Engineers Newsletter 34-5 (2005).
Stanke, D. Addendum 62n,
Engineers Newsletter 33-1 (2004).
Analysis Software
Trane Air-Conditioning and Economics (TRACE 700). Available at
<www.trane.com/Commercial/DNA/View.aspx?i=1136>
TRACE 700 Users Manual, CDS-PRM001-EN, 2005.
Page 2 of 2