Automation Component
AK 1703 ACP
SICAM 1703 - flexible for all applications
Answers for energy. SIEMENS
llAutomation, communication
and telecontrol
A high level of functionality and flexibility are the foundation for a successful auto
mation system. Naturally, that also includes comprehensive options for telecontrol,
communication and for connecting peripheral equipment. That's certainly the case,
at least, with the innovative AK 1703 ACP automation component.
One solution fits all
Thanks to its system concept, the AK 1703 ACP opens
up new possibilities for you to automate power supply
networks to match yaur performance and redundancy
requirements. Automation, telecontrol and commu:
nication functions are combined flexibly and in full
‘compliance with IEC 61850. Especially noteworthy is,
the possibilty of offering client and server functionality,
‘on only one Ethernet interface. This interface was
certified by an independent laboratory to verity
interoperability
You can use the AK 1703 ACP as
Wa central unit or telecontrol substation,
data node or front-end,
automation unit
with autonomous function groups
= with local or remote peripheral equipment.
Central or remote input/output?
If the AK 1703 ACP is augmented with TM 1703,
peripheral elements (up to 200 m away from
the central unit) the question “central or remote?”
ro longer applies, since both are possible.
Handover interfaces are systematically reduced by
direct connection of actuators and sensors with wire
cross-sections of up to 2.5 mm?. Meanwhile, binary
input and output modules up to 220 VOC open up
additional savings potential at the interface level.
TOOLBOX Il: Consistently simple engineering
All engineering activities, from system diagnostics
to online testing, can also be carried out extremely
efficiently from remote locations. The close inter:
facing with design tools such as ELCAD ensures con:
sistent documentation of the entire system, while
the user programs for closed- and open-loop control,
functions are created in CAEx plus according to
IEC 61131-3, thereby minimizing the time and effort
needed for training.
Simple replacement: Plug & Play
Configuration and all parameters of the AK 1703 ACP
are stored on the flash card, This means that in the
event of a fault, a replacement device can be put into
‘operation in secands ~ without a PC or resetting of
parameters. This advantage, in combination with the
comprehensive remote diagnostic options, down:
times can be reduced to a minimum.Configurations
Process control system
TOOLBOX!
‘AK 1703 ACP.
poten palin,
Cental unit:
local inputfourput
tien,
=Central processing
La
fh}
i r
‘AK 1703 ACP
=Data node
“Front end
= Gateway
AK 1703 ACP:
“Turbine contrller
Powerplant management
“automation & control
a
‘TC substation:
1703 ACP ‘AK 1703 ACP.
Station contol unit
“Process coupling
(Geral wide)
Node function
“Automatic functions
Local processing
Decentralized
acquisition
Practical applications of AK 1703 ACP
Architecture
1 Mult-processor and firmware principle
with 32-bit processor technology
f@ One master control element with
~ up to 2 communication interfaces
~ automation function
~ connection to the TOOLBOX I!
engineering system
Up t0 16 addtional processing and
communication elements
Up to 66 protocol elements for
~serial communication (point-to-point,
multi-point, dial-up traffic)
~ LANIWAN (Ethernet)
~ Profibus DP
= Up to 272 peripheral elements
Technical Data
1 Protocols: IEC 60870-5-101, 103, 104,
IEC 61850, Profibus DP, SAT SSI, SAT PCMBA,
Modbus, DNP 3.0, IEC 61107,
1 Open-loop and closed-loop control functions:
512 kB for user program in each case, about
50,000 variables and signals, of which
2,000 buffered, 250 buffered setpoint values
EMC: IEC 60870-2, IEC 60255, IEC 60950,
IEC 61000, EN50082, CISPR 22,
mi Temperature range: 0. +55°C
tm Dimensions (W x H x D):
(CM-2832: 280 x 291 x 285 mm;
Space required: 400 x 451 x 290 mm,
CM-2835: 483 x 291 x 285 mm;
Space required: 604 x 451 x 290 mm,
Overview of functions
Node function for building up multi-hierarchical
networks with virtually any topology
1m Automation functions at all levels of
‘a local or distributed network
1m Drawing up a function plan according to
IEC 61131-3 with CAEx plus for open-loop
‘and closed-loop control functions
1 Configurable telecontrol functions with
‘and without time tagging
1m Time synchronization via minute pulse,
time signal receiver, serial communications link
‘or NTP server (LAN/WAN)
1 Data routing via selective or automatic data flow
Uniform functionality as per
IEC 60870-5-101/1031104 for consistent
addressing fram acquisition to output
Scalable redundancy through:
~ duplication of 1 t0 5 processing!
communication elements
~ duplication of the whole automation unit
Independent functional groups
Decentralized archive
im Standby transmission route concept
Parameter setting, diagnostics and testing
by means of TOOLBOX I! both locally and from
remote locations
i Storage of parameters and firmware on flash cardTechnical Data
Subrack w-2832 '6MF11130C1320AA0__| AK 1703 ACP subrack for 9 slots
cw2835 “GMETT130C1350AA0_ | AK 1703 ACP subrack for 17 slots
Power supply 5-5620 ‘6MFI0130FG200AA0 | Power supply 24-60 VOC
5.5622 ‘GMF10130FG220AA0_| Power supply 110-220 VOC, 115-230 VAC
Master control element cr 20v01cec2s ‘6MF10130CATO0AA_| System functions, processing ad communication
ow2837 ‘6MF10130C13700A0 | Communieationlsys:lO connection (CP2070)
Flash card Fash cord ‘6MFIZ131GADSOAAO | Memory card for parameters and Firmware
Peripheral elements
Peripheral elements (max. 16) Dr2To0RBIsi2S ‘@MFIOT1OCBOODAAO | Binary signalinput (8 x8, 24-60 VOC)
beat roaisi26 ‘GMFIO1TOCBIOOAAD | Binary signal input (8x8, 24-60 VOO), 1 ms resolution
eat wmisiae ‘GMFIOTTOCBTTOAAD | Binary signal input (8x8, 110220 VDC), 1 ms resolution
'D0-2201/815025 | GMFTOTIOCCOIOAAD | Binary output (wansistor, 40 x 1, 24~60 VOC)
1DO-2210/PCCO2x | GMFIOTIOCCTOOAAD | Secured command output 24-60 VOC
100-2211/PCCO2x | GMFTOTIOCCTIOAAD | Secured command output 110-125 VDC
‘A-2300)FAS25 ‘GMFI01TOCDOOOAAO | Analog inputloutput (18 x=20mA +4 x opt. exp”)
‘AL2301/TEMP2S | GMFIOTIOCDOTOAAD | Analog input 32x Y100
MX-24001USI02x __ GMFTOTIOCEODOAAO | Signal inputfoutput (24-60 VOC, =20 mA, + 1x opt. exp")
*) optional expansions sM-0570 ‘GMFIOTIOAF7ODAAO | Analog input (2x 220 mA, =10V)
Most ‘GMFIOTTOAFTIOAAD | Analog input (2x P1700)
M0572 ‘GMFIOTTOAFT20AAD | Analog output (2x=20 mA, =1/10V)
sMas7e “GMETOTTOAFTAOAAD_| Counting pul input (2x24~60 VOC)
‘Connection cable (per peripheral el) | CM-2890 ‘GMEI3131CIO00AA1 | Peripheral cable, cmp 5m, 100 pole
Processing and (CP20T7IPCCX2S GMFIOTOCAI70AAD | Processing and communication
communication element (max. 16) cy 2638 ‘6MF10130C1380AA0 | Communication connection (for each CP-2017)
Protocol elements (hardware)
‘CPU (max. 2 per processing M2557 ‘GMFIO130CFSTOAAO | Serial interface processor 2 serial interfaces (5)
and communication element) and | 542556 “GMFIO130CFSGOARO | Network interface Ethemet 10)1007K
M2557 ‘GMF10130CFS7OARO | Dual network interface Ethernet 1O/T00TX
M2545 “EMFIOTIOCF4SOARO | Profs interface
Submadule for SM-2556 SN-0551 ‘GMFIOTSOAFS1OARO | Serial interface processor 1 SI (configurable on SM-2556)
Path plug (1x per SD ‘ca 7860 ‘MFIZTTOCISODAAO | Patch plug standard V28, Ethemet
an7869 “GMFTZIT2CIGOOKAO | Patch plug Profibus
‘Accessories
Modem= ceo700 ‘MFI TO2ORCOODAAD | V.33 Leated ne modem
e070 “EMFTTO20CABIOAAD | VFT channel modem
“Converters awa? {MFITTTORI27OAAO | Converter V2Bloptical
aw-0829
“@METT 11280200880
‘Converter R52321R5422; R485Applications
WAs telecontrol substation or central unit,
1m With local or remote peripherals
As data node, front-end or gateway
Automation unit with independent
functional groups
1 For rear panel or 19" rack installation
Comprehensive communication
Up to 66 serial interfaces for local
and remote communication
1 Communication (serial, LAN/WAN) as per
IEC 60870-5-101/1039104 and IEC 61850
Numerous third-party protocols available
mw Profibus DP
AK 1703 ACP - The advantages at a glance
Scalable redundancy
Component redundancy
Duplication of processinglcommunication
elements,
Simple engineering and maintenance
1 Creation of user programs for open-loop and
closed-loop control functions as per IEC 61131-3,
1 Object-oriented engineering
W Consistent data storage
Engineering also possible from remote locations
im Plug & Play for spare parts by means of flash card
W Storage of parameters and firmware on flash card
Exchanging of modules without engineering tool
TM 1703: The intelligent terminal
Direct connection of actuators and sensors with
wire cross-sections of up to 2.5 mm?
1 Remote installation possible up to 200 m away
Binary inputioutput also for 110/220 VOC
1 Mounting on 35 mm DIN rail