TABLERO:

UBICACIN:

TRX-2UN2
(X1)
NIVEL 0 URGENCIAS

FASES: 3
HILOS: 4
CAPACIDAD INTERRUPTIVA: 14
VOLTIOAMPERIOS

PROTECCIN
AMPS

POL

40

A
CIRCUITO FUERZA RAYOS X

1500
1500

40

1500

CIRCUITO FUERZA RAYOS X


1500

40

1500

CIRCUITO FUERZA RAYOS X

1500

TOTAL

AMPS = VOLTAMPS / (VOLTS*1.732)


=

10,83 AMPS

3000

3000

240
VOLTS, N/S, B/T,MB.
MONTAJE: EMBUTIDO

K AMPS.
FASES

N
CIRC

N
CIRC

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

3000

12 SALIDAS

VOLTIOAMPERIOS
A

VOLT AMPS FASE A

VOLT AMPS FASE B

VOLT AMPS FASE C

3000

3000

3000

F.D. 50 %
1500

F.D. 50 %
1500

F.D. 50 %
1500

PROTECCIN
C

ALIMENTADOR: Cu THHN
(DE TRAFO A
TABLERO)

TOTAL VOLTIOAMPERIOS
4500

UNIPOLAR
4 1/C # 12 AWG Cu THHN
1 1/C # 10 AWG Cu THHN

CANALIZACIN: TUBO
1 TUBO DE DIMETRO 3/8 " (12 mm)

MAIN BREAKER: 30 A/3P

ALIMENTADOR:
(DE TABLERO
SUPERIOR AL
TRAFO)

Cu THHN
UNIPOLAR
3 1/C # 10 AWG Cu THHN
1 1/C # 10 AWG Cu THHN

TRANSFORMADOR: 15kVA-480/240V-Dd

CANALIZACIN: BANDEJA
DIMENSIN: VER CLCULO BANDEJAS

OUTPUT BREAKER EN TABLERO SUPERIOR: 30 A/3P

AMPS

POL

40

40

40

TOTAL