PROYECTO
BELLEZZIAN
FECHA:
CM T1
TABLERO:
SOTANO
CARGA ELECTRICA
DEPTO.
NIVEL
TABLERO
EQUIPO
INSTALADA
(KW)
FD
DEMANDADA
(KW)
CORRIENTE
NOMINAL
(A)
FACTORES DE
CORRECION
FT
FA
CORRIENTE
CORREGIDA
(A)
Octubre 2014
CALCULO : FMR
CONDUCTOR SELECCIONADO
LONGITUD
(m)
por I.
por e%
SECCION
TRANSVERSAL
ALIMENTADOR
CAIDA DE
TENSION REAL e
%
INTERRPTOR DE
PROTECCION
101
PB
9.47
0.54
5.13
20.20
1.00 1.00
20.20
25.00
10
8.37
0.55
2P - 30A
102
PB
11.61
0.51
5.92
23.31
1.00 1.00
23.31
28.00
10
8.37
0.71
2P - 30A
103
PB
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
10.00
10
8.37
0.25
2P - 30A
104
PB
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
18.00
10
8.37
0.46
2P - 30A
201
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
28.00
10
8.37
0.71
2P - 30A
202
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
31.00
10
8.37
0.79
2P - 30A
203
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
13.00
10
8.37
0.33
2P - 30A
204
B'
11.63
0.51
5.93
23.33
1.00 1.00
23.33
21.00
10
8.37
0.53
2P - 30A
301
12.24
0.50
6.16
24.25
1.00 1.00
24.25
31.00
10
13.3
0.51
2P - 30A
302
C'
13.31
0.49
6.53
25.73
1.00 1.00
25.73
34.00
10
13.3
0.60
2P - 40A
303
A'
9.20
0.55
5.04
19.83
1.00 1.00
19.83
16.00
10
8.37
0.34
2P - 30A
304
A'
9.20
0.55
5.04
19.83
1.00 1.00
19.83
24.00
10
8.37
0.52
2P - 30A
401
PH1
14.87
0.48
7.14
28.10
1.00 1.00
28.10
26.00
10
13.3
0.50
2P - 40A
402
PH2
14.53
0.48
7.02
27.63
1.00 1.00
27.63
35.00
10
13.3
0.66
2P - 40A
403
PH3
15.36
0.52
7.94
31.24
1.00 1.00
31.24
21.00
10
13.3
0.45
2P - 40A
404
PH4
15.10
0.55
8.25
32.47
1.00 1.00
32.47
27.00
10
13.3
0.60
2P - 40A
SOT
PH5
10
#DIV/0!
TOTAL
194.65
0.51
99.72
BELLEZZIAN
TORRE 1
TORRE 2
4
4
4
4
4
4
4
4
16
16
ALUMBRADO
CONTACTOS
1,008
1,109
1,527
1,549
1,589
6,400
6,000
8,200
8,200
8,800
NIVEL
NIVEL 4
NIVEL 3
NIVEL 2
PLANTA BAJA
TIPO DE DEPARTAMENTO
1
2
3
4
5
A
A'
B
B'
C
6
7
8
9
10
C'
PH
PH
PH
PH
1
2
3
4
1,778
2,412
2,240
2,094
2,272
9,800
10,800
10,600
10,600
11,200
41,83
T0RRE 3
T0RRE 4
T0RRE 5
T0RRE 6
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
16
16
16
16
RELACIN DE C
VA
CONTACTOS
DEDICADOS
INSTALADOS
F.D
DEMANDADOS
VENTILACION
3,000
3,000
3,000
3,000
3,000
10,408
10,109
12,727
12,749
13,389
0.54
0.54
0.50
0.50
0.50
5,593
5,488
6,404
6,412
6,636
109
109
173
173
208
3,000
3,000
3,000
3,000
3,000
14,578
16,212
15,840
15,694
16,472
0.48
0.47
0.47
0.47
0.47
7,052
7,624
7,494
7,443
7,715
208
305
305
231
305
41,837
TOTAL X NIVEL
4
4
4
4
TORRE 1
PH1
C
B'
A
PH2
C'
B'
B
PH3
A'
B'
B'
V.A.
DEMANDADOS
INSTALADOS
F.D
5,702
5,597
6,577
6,585
6,844
9.37
9.10
11.45
11.47
12.05
0.54
0.54
0.50
0.50
0.50
16
1,143
1,143
7,260
7,929
7,799
8,817
9,163
13.12
14.59
14.26
14.12
14.82
0.48
0.47
0.47
0.47
0.47
RE 1
PH4
A'
B'
B'
WATTS
DEMANDADOS VENTILACIN
5.03
4.94
5.76
5.77
5.97
0.10
0.10
0.16
0.16
0.19
TOTAL
5.13
5.04
5.92
5.93
6.16
MONTAPLATOS
INSTALADOS
9.47
9.20
11.61
11.63
12.24
6.35
6.86
6.74
6.70
6.94
0.19
0.27
0.27
0.21
0.27
6.53
7.14
7.02
6.91
7.22
1.03
1.03
13.31
14.87
14.53
15.36
15.10
FASE 2
C1
C1
C1
C3
F.D
DEMANDADOS
0.54
0.55
0.51
0.51
0.50
5.13
5.04
5.92
5.93
6.16
A1 A2
A1 A2
A4
A4
0.49
0.48
0.48
0.52
0.55
6.53
7.14
7.02
7.94
8.25
FASE 2
C4
C4
FASE 3
A1
A1
A4
A4
C1
C1
C1
C3
A3 B3 B2 B1 A2
A3 B3 B2 B1 A2
A5
A5