Está en la página 1de 26

0100DB0902 R06/13

08/2013

Data Bulletin

Replaces 0100DB0902R04/11, 04/2011

Guide to Low Voltage Transformer Protection


and Selective Coordination
Retain for future use.

Introduction

Use this guide for selecting transformer primary circuit breaker, secondary
circuit breaker and the largest branch circuit breakers for total selective
coordination. The circuit breaker selections conform to the NEC Article 450
requirements for transformer protection while providing total selectivity for
the circuits.
See How To Use This Guide, on page 3, for additional information.
Use the Guidelines below for tips on working through systems for
selective coordination.
NOTE: It is still necessary to perform an engineering study to determine the
specific requirements of each system.

Guidelines
Know Your State and Municipal Code

Understand your state and local municipalitys adoption and enforcement


regarding the National Electrical Code (NEC). Part of understanding local
code adoption and enforcement is understanding the threshold of selective
coordination required0.1s (TCCs) or total, for the full operating range of
the protective devices (which typically uses look-up tables). This guide
assumes total selective coordination is required.

Lighting Panelboard Recommendations

In general, do not feed lighting panelboards from other lighting


panelboards unless there is a transformer in between them.

Better levels of selective coordination are available with 225 A and


larger panelboards.

Consider using main lugs panelboards.

Bottom-Up Coordination

When selectively coordinating a system, work from the loads towards the
source(s), coordinate the branch panels first, then the power distribution
panels, then the switchboard or switchgear.

Sizing Upstream Circuit Breakers

The upstream circuit breaker should be at least one frame size larger
than the downstream circuit breaker. This may necessitate increasing
the size of panelboards and feeder conductors.

Very high levels of short circuit selective coordination may be achieved


by using high ampere frame electronic trip circuit breakers with low
ampere sensors and/or lower ampere rating adjustments.

When there is no overlap (at any point) of the TCCs below the available
short circuit current at the downstream panel, the circuit breakers are
fully coordinated.

When there is overlap in the short circuit zone, use the short circuit
selective coordination tables in document number 0100DB0501, Short
Circuit Selective Coordination for Low Voltage Circuit Breakers or

Overlapping Time Current Curves (TCCs)

20112013 Schneider Electric All Rights Reserved

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin

0100DB0902 R06/13
08/2013

document number 0100DB0604, Selectivity Guidelines for


Square D Panelboards.
Automatic Transfer Switch (ATS)
Withstand Ratings

Mixing of Overcurrent Protective


Devices (OCPD)

Arc Flash Incident Energy

Make sure automatic transfer switches have adequate withstand ratings.

It may be necessary to relocate the switch, or It may be necessary to


increase the size of the switch.

Time-Current Curves (TCC) may be used so long as the fault current


does not exceed the instantaneous trip point of the upstream breaker

OCPD from different manufacturers or different types cannot be mixed if


the fault current is outside of the parameters describe above.

Consider how selective coordination impacts the arc flash Protective


Personnel Equipment (PPE) levels.

It may be possible to reduce arc flash incident energy with Zone


Selective Interlocking (ZSI).

Nesting Time-Current Curves

The time-current curve of a thermal magnetic circuit breaker can sometimes


be nested underneath the time-current curve of an upstream electronic trip
circuit breaker.

Circuit Breaker Withstand Capacity

Molded case circuit breakers (UL 489) used for coordination:

New H frame (U) with Micrologic trip unit

New J-Frame (W) circuit breakersselectively coordinate up to 18kA


with 240/120V Circuit Breakers

New L-Frame (W) circuit breakersselectively coordinate up tp 30kA


with 240V and 480Y/277V

LA/LH MC (mission critical) circuit breakerselectively coordinate up to


22 kA with 120 V circuit breakers (obsolete)

D-Frame MC (mission critical) circuit breakerselectively coordinate up


to 30 kA with 120 V circuit breakers (obsolete)

PowerPact PG/PK and RG/RK circuit breakersselectively


coordinate up to 65 kA with 277 V Circuit Breakers

Masterpact NW circuit breakersselectively coordinate up to 100 kA


with larger molded case circuit breakers

Refer to 0100DB0501 for complete, total selectivity tables.

Field Adjustment

Do not neglect to properly adjust circuit breakers in the field as all Square D
low voltage circuit breakers are shipped from the factory with all but the
ampere-rating switch in the lowest position.

As a Last Resort . . .

Change the upstream circuit breaker type to an insulated case circuit


breaker or a low voltage power circuit breaker.

Reduce the voltage if the desired level of selective coordination cannot


be achieved using a 480Y/277 Vac panelboard. Consider feeding a
208Y/120 Vac panelboard through a transformer.

Split up some of the loads and use multiple smaller transformersavoid


feeding a 100 A/208 V panel from another 208 V panel.

Insert impedance through longer run of wire or higher impedance


transformers or reactors.

20112013 Schneider Electric All Rights Reserved

0100DB0902 R06/13
08/2013

How To Use This Guide

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin

1. Determine the available fault current on primary side of transformer and


choose the appropriate reference table.
a. 35 kA/18 kA
b. 65 kA
c. 100 kA
2. Locate the transformer size on far left of chart. Options are available up
to 225 kVA.
3. Based on the specification requirement for aluminum or copper
transformer windings, read the available circuit breaker combinations for
primary, secondary (main), and branch circuit breakers for a selectively
coordinated system.
4. Choose the circuit breaker combination that best suits your system
requirements.
a. The primary circuit breaker should be selected as the device feeding
the transformer, whether in a panelboard or circuit breaker
enclosure.
b. The secondary circuit breaker should be selected as the main circuit
breaker in the panelboard downstream of the transformer; or
optionally, could be mounted in a circuit breaker enclosure to feed a
main lugs only panelboard.
c. The branch circuit breakers are listed to show the maximum size that
can be applied to a full selectively coordinated system. Additionally,
notation is made to present which style of QO(B) circuit breaker is
required based on current rating and number of poles.
5. Reference data bulletin 0100DB0501 if additional circuit breaker
selections are required upstream from the primary circuit breaker to
complete the system. This data bulletin is a comprehensive resource for
selectively coordinated circuit breaker combinations within the same
voltage system.

20112013 Schneider Electric All Rights Reserved

Transformer

EE15T3HCU

EE15T3H

Aluminum

Copper

Catalog
Numbers

General
Purpose
Type

Long Time

Short Time

4.6

125
150
60
60
60

EG
HG

HG_U
3.2

HG_U
3.2S

HG_U
5.2/6.2
40

40

35

40

35

40

40

35

10

10

Frame
Min.
Circuit
Ampere
InstantSize /
Imped
Breaker
Rating2 Setting Delay Setting Delay
aneous
Rating
-ance
8
Frame
A
A
(% Z)1
EG
125
35

HG
150
35

HG U
60
25
25
2

8
3.2
5.1
HG_U
60
40
40

10

8
3.2S
HG_U
60
40
40
2
10
0
8
5.2/6.2

Primary Circuit Breaker

150

150/60
600/150
150/60
600/150
150/60
600/150
150/60
600/150
150/60
600/150

HD_U 3.2
D-MC*
HD_U 3.2
D-MC*
HD_U 3.2
D-MC*
HD_U 3.2
D-MC*
HD_U 3.2
D-MC*

60
60
60
60
60
60
60
60
60
60

60

Frame Ampere
Size / Rating2
Rating
(A)

HD

Circuit
Breaker
Type
(Main)

Short Time

60 A
(0.5)(0.8)
60 A
(0.5)(0.8)
60 A
(0.5)(0.8)
60 A
(0.5)(0.8)
60 A
(0.5)(0.8)

2
4
2
4
2
4
2
4
2
4

15

15

15

15

15

30
30
30
30
30
30
30
30
30
30

30

Max.
Min.
Min.
Instant- Branch
Setting Delay
Settings Delay
aneous Size5
(A)

Long Time

Secondary Circuit Breaker

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

1P
1570
A

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

2P
15100
A

QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH

QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

This table is not meant to replace a selective coordination system study. The purpose of this guide is for activities that occur before the final
system study, such as quotation and iterative design changes, to increase the chance of device combinations being selectively coordinated.
The device combinations presented in this guide represent a level of "total" selective coordination, where the devices were chosen based on
the maximum let-through current.
NEC requirements for transformer protection were also followed in the selection of the device combinations.
Transformers are 480 V primary with 208Y/120 V secondary.

Notes about using this Quick Reference Guide:

Selective Coordination Device Combinations (35 kA)

Branch Circuit Breakers

Transformer

Main Circuit Breaker

Input Circuit Breaker

* NOTE: D-MC and L-MC circuit breakers are obsolete.

15

Size
kVA

Table 1:

Quick Reference Guide for Selective Coordination Based on 35 kA Available Fault Current on 480 Vac Primary

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Aluminum

30

EE30T3H

Catalog
Numbers

Long Time

Short Time

5.5
100

100

100

HG_U
3.2S

HG_U
5.2/6.2

150

HG

HG_U
3.2

125

EG

50

50

50

70

80

50

50

50

10

10

Min.
Frame
Ampere
Circuit
Imped
Size /
InstantRating2 Setting Delay Setting Delay
Breaker
-ance
Rating
aneous
8
Frame
A
(% Z)1
A

* NOTE: D-MC and L-MC circuit breakers are obsolete.

General
Purpose
Type

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

Transformer

Size
kVA

Table 1:

Long Time

Short Time

Circuit
Max.
Frame Ampere
Breaker
Min.
Min.
Instant- Branch
Setting Delay
Size / Rating2
Settings Delay
aneous Size5
Type
Rating
(A)
(A)
(Main)
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.95) 4

60
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.95) 4

60
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
600/
D-MC*
125 (0.9)(0.95) 4

60
150
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2

Secondary Circuit Breaker

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Copper

EE45T3HCU

EE45T3H

EE30T3HCU

Catalog
Numbers

Long Time

Short Time

4.4

6.0

4.6

100
100
100

HG_U
5.2/6.2

100

HG_U
3.2S

HG_U
3.2S

100

HG_U
3.2

150

HG

HG_U
3.2

100

150

125

EG

HG_U
5.2/6.2

80

100

HG_U
5.2/6.2

100

100

70

100

100

70

50

50

100

HG_U
3.2S

50

80

100

150

HG

80

HG_U
3.2

125

EG

100

100

70

100

100

70

50

50

50

10

10

10

10

10

10

15

15

15

12

12

12

10

10

10

Frame
Min.
Circuit
Ampere
InstantSize /
Imped
Breaker
Rating2 Setting Delay Setting Delay
aneous
Rating
-ance
8
Frame
A
A
(% Z)1

* NOTE: D-MC and L-MC circuit breakers are obsolete.

45

Copper

30

Aluminum

General
Purpose
Type

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

Transformer

Size
kVA

Table 1:

Long Time

Short Time

Circuit
Max.
Frame Ampere
Min.
Min.
Instant- Branch
Breaker
Setting Delay
Size / Rating2
Type
Settings Delay
aneous Size5
Rating
(A)
(Main)
(A)
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.95) 4

60
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.95) 4

60
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.95) 4

60
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
HD_U 3.2 150/150 125
125 A
2

15
60
HD_U 3.2S 150/150 125
125 A

10

15
60
HD_U
150/150 125
125 A
2
10
0
15
60
5.2/6.2
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80
JD_W 3.2 250
175
175 A
4

80
D-MC* 600/250 175
(0.7)(1)
8

80

Secondary Circuit Breaker

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

20112013 Schneider Electric All Rights Reserved

Aluminum

75

EE75T3H

Catalog
Numbers

Long Time

Short Time

3.7

250

400

LA/LH
MC

250

JG_U
3.2S

JG_U
5.2/6.2

250

JG_U
3.2

200

125

125

125

125

125

125

10

10

12

12

12

Min.
Frame
Ampere
Circuit
Imped
Size /
InstantRating2 Setting Delay Setting Delay
Breaker
-ance
aneous
8 Rating
Frame
A
(% Z)1
A

* NOTE: D-MC and L-MC circuit breakers are obsolete.

General
Purpose
Type

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

Transformer

Size
kVA

Table 1:

Circuit
Frame Ampere
Breaker
Size / Rating2
Type
Rating
(A)
(Main)
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300

Short Time

(0.9)(1)
(0.7)(0.8)

225

(0.9)(1)
(0.7)(0.8)

225
225

225

(0.9)(1)
(0.7)(0.8)

225
225

225

(0.9)(1)
(0.7)(0.8)

225
225

225

10
16

10

10

16

10

10

16

10

10

16

12

12
12

12

12
12

12

12
12

12

100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

Max.
Min.
Min.
Instant- Branch
Setting Delay
Settings Delay
aneous Size5
(A)
225
8

12
100
225

10

12
100

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)3

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)4

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)
QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
110150
A

QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

Copper

75

EE75T3HCU

Catalog
Numbers

Long Time

Short Time

3.5

250

400

LA/LH
MC

250

JG_U
3.2S

JG_U
5.2/6.2

250

JG_U
3.2

200

125

125

125

125

125

125

10

10

12

12

12

Min.
Frame
Ampere
Circuit
Imped
Size /
InstantRating2 Setting Delay Setting Delay
Breaker
-ance
Rating
aneous
8
Frame
A
(% Z)1
A

* NOTE: D-MC and L-MC circuit breakers are obsolete.

General
Purpose
Type

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

Transformer

Size
kVA

Table 1:

Circuit
Frame Ampere
Breaker
Size / Rating2
Type
Rating
(A)
(Main)
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300
JD_W 3.2 250 225250
JD_W 3.2S 250 225250
JD_W
250 225250
5.2/6.2
600/250 225250
D-MC*
600/400 225300
L-MC*
400 225300

Short Time

(0.9)(1)
(0.7)(0.8)

225

(0.9)(1)
(0.7)(0.8)

225
225

225

(0.9)(1)
(0.7)(0.8)

225
225

225

(0.9)(1)
(0.7)(0.8)

225
225

225

10
16

10

10

16

10

10

16

10

10

16

12

12
12

12

12
12

12

12
12

12

100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

Max.
Min.
Min.
Instant- Branch
Setting Delay
Settings Delay
aneous Size5
(A)
225
8

12
100
225

10

12
100

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)3

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)4

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)
QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
110150
A

QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

20112013 Schneider Electric All Rights Reserved

EE112T3HCU

EE112T3H

Aluminum

Copper

Catalog
Numbers

General
Purpose
Type

Transformer
Long Time

Short Time

3.9

5.2

250

400

LA/LH
MC

250

JG_U
3.2S

JG_U
5.2/6.2

250

400

LA/LH
MC

JG_U
3.2

250

250

JG_U
3.2S

JG_U
5.2/6.2

250

JG_U
3.2

200

175

175

175

200

175

175

175

175

175

175

175

175

175

10

10

10

10

10

10

10

12

12

12

Min.
Frame
Circuit
Ampere
InstantImped
Size /
Breaker
Rating2 Setting Delay Setting Delay
aneous
-ance
Rating
8
Frame
A
1
(% Z)
A

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

* NOTE: D-MC and L-MC circuit breakers are obsolete.

112.5

Size
kVA

Table 1:

Circuit
Frame Ampere
Breaker
Size / Rating2
Type
Rating
(A)
(Main)
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400
LD_W 3.3 400
400
LD_W 3.3S 400
400
LD_W
400
400
5.3/6.3
D-MC* 600/400 300400

Short Time

4
16

(0.8)(0.95)

16
4

(0.8)(0.95)
400
400
400

400

4
16
4

400
(0.8)(0.95)
400
400

4
16
4

400
(0.8)(0.95)
400
400

4
16
4

400
(0.8)(0.95)
400
400

4
16
4

400
(0.8)(0.95)
400
400

4
16
4

400
(0.8)(0.95)
400
400

4
16
4

400
(0.8)(0.95)
400
400

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min.
Min.
Instant- Branch
Setting Delay
Settings Delay
aneous Size5
(A)
400
4

12
150
400

10

12
150

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

QO(B)

QO(B)
QO(B)

3P
15100
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

10

EE150T3CU

EE150T3H

Aluminum

Copper

Catalog
Numbers

General
Purpose
Type

Transformer
Long Time

Short Time

4.7

6.0

400

400

LA/LH
MC

400

LG_U
3.3S

LG_U
5.3/6.3

400

400

LA/LH
MC

LG_U
3.3

400

400

LG_U
3.3S

LG_U
5.3/6.3

400

LG_U
3.3

225

250

250

225

225

225

225

225

250

250

225

225

225

225

10

10

10

10

12

12

12

10

10

10

Min.
Frame
Ampere
Circuit
Imped
Size /
InstantRating2 Setting Delay Setting Delay
Breaker
-ance
Rating
aneous
8
Frame
A
(% Z)1
A

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

* NOTE: D-MC and L-MC circuit breakers are obsolete.

150

Size
kVA

Table 1:

Circuit
Frame Ampere
Breaker
Size / Rating2
Type
Rating
(A)
(Main)
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC* 600/600 600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC* 600/600 600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC* 600/600 600
LD_W 3.3 600
600
LD_W 3.3S 600
600
LD_W
600
600
5.3/6.3
D-MC* 600/600 600

Short Time

2
2

600

2
2

(1)(1)

600

2
2

(1)(1)
600
600

600

2
2

(1)(1)
600
600

(1)(1)
600
600

2
2

(1)(1)
600
600
600

600

2
2
2

600
(1)(1)
600
600

2
2
2

600
(1)(1)
600
600

2
2
2

600
(1)(1)
600
600

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min.
Min.
Instant- Branch
Setting Delay
Settings Delay
aneous Size5
(A)
600
2

11
150
600

11
150

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

2P
15100
A

1P
1570
A

QO(B)

QO(B)
QO(B)

3P
15100
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

20112013 Schneider Electric All Rights Reserved

EE225T3HCU

EE225T3H

Aluminum

Copper

Catalog
Numbers

General
Purpose
Type

Transformer
Long Time

Short Time

3.8

6.5

400

400

LA/LH
MC

400

LG_U
3.3S

LG_U
5.3/6.3

400

400

LA/LH
MC

LG_U
3.3

400

400

LG_U
3.3S

LG_U
5.3/6.3

400

LG_U
3.3

350

400

350

350

350

350

10

10

10

10

0.2

12

12

12

12

12

12

D-MC* 600/600
LD_W 3.3 600
LD_W 3.3S 600
LD_W
600
5.3/6.3
D-MC* 600/600

Short Time

Branch Circuit Breakers for


Total Selective Coordination

600
(1)(1)

6007

(1)(1)
600
600

4
8

4
8

600

600

4
8

(1)(1)
600
600

600

4
8

(1)(1)
600
600

600

4
8

(1)(1)
600
600

600

4
8

(1)(1)
600
600

600

4
8

(1)(1)
600
600

600
(1)(1)
600
600

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

to the minimum D-MC trip in column to the left.

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

Max.
1P
2P
2P
3P
3P
Min.
Min.
Instant- Branch
Setting Delay
1570
15100 110150 15100 110150
Settings Delay
aneous Size5
A
A
A
A
A
(A)
600
8

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
600

10

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

Long Time

6007

6007
6007
6007

Circuit
Frame Ampere
Breaker
Size / Rating2
Type
Rating
(A)
(Main)
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3 600
6007
LD_W 3.3S 600
6007
LD_W
600
6007
5.3/6.3

Secondary Circuit Breaker

1 Values representative of impedance values for Square D transformers.


2 Allow primary trip rating to increase to 250% of rated FLC (NEC 450.4); secondary main trip rating cannot exceed 125% of rated FLC.
3 Selective with 2 pole QO(B) through 80 A rating.
4 Selective with 3 pole QO(B) through 60 A rating.
5 Branch circuit breakers with ampere ratings of 50%, or less, of the D-MC main circuit breaker are selective. Values shown in this column correspond
6 Secondary main circuit breakers will not carry rated secondary current of 416 A.
7 Secondary main circuit breakers will not carry rated secondary current of 325 A.
8 Primary circuit breaker selections shown are for 35 kA SCCRs; if the system has <18 kA available, D-frame circuit breakers may be used.
9 Selective with 3 pole QO(B)-VH circuit breakers through 80 A rating.

225

350

400

350

400

350

350

350

Frame
Min.
Circuit
Ampere
Size /
InstantImped
Breaker
Rating2 Setting Delay Setting Delay
Rating
aneous
-ance
Frame
A
1
A
(% Z)

Primary Circuit Breaker

Selective Coordination Device Combinations (35 kA)

* NOTE: D-MC and L-MC circuit breakers are obsolete.

225

Size
kVA

Table 1:

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

11

12

Transformer

Long Time

Short Time

Primary Circuit Breaker

Size
kVA

General
Purpose
Type

Catalog
Numbers

60

60
60
60
60
60
60
60
60
60
60

150

150/60
600/150
150/60
600/150
150/60
600/150
150/60
600/150
150/60
600/150

Frame Ampere
Size / Rating2
Rating
(A)

60
(0.5)(0.8)
60
(0.5)(0.8)
60
(0.5)(0.8)
60
(0.5)(0.8)
60
(0.5)(0.8)

Min.
Pickup

Short Time

2
4
2
4
2
4
2
4
2
4

15

15

15

15

15

30
30
30
30
30
30
30
30
30
30

30

Max.
Min. Min. Min. Instant- Branch
Delay Pickup Delay aneous Size5
(A)

Long Time

Secondary Circuit Breaker

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

1P
1570
A

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

2P
15100
A

QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH

QO(B)

3P
1510
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

This table is not meant to replace a selective coordination system study. The purpose of this guide is for activities that occur before the final
system study, such as quotation and iterative design changes, to increase the chance of device combinations being selectively coordinated.
The device combinations presented in this guide represent a level of "total" selective coordination, where the devices were chosen based on
the maximum let-through current.
NEC requirements for transformer protection were also followed in the selection of the device combinations.
Transformers are 480 V primary with 208Y/120 V secondary.

Notes about using this Quick Reference Guide:

Selective Coordination Device Combinations (65 kA)

Branch Circuit Breakers

Transformer

Main Circuit Breaker

Input Circuit Breaker

Frame
Min.
Circuit
Ampere
Circuit
Size /
InstantImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating
aneous
ance
Frame
A
Type
(Main)
A
(% Z)1
EJ
125
35

HJ
150
35

HJ_U
60
25
25
2

8
3.2
Aluminum
EE15T3H
5.1
HD
HJ_U
60
40
40

10

8
3.2S
HJ_U
60
40
40
2
10
0
8
5.2/6.2
HD_U 3.2
EJ
125
35

15
D-MC*
HD_U 3.2
HJ
150
40

D-MC*
HD_U 3.2
HJ_U
Copper
EE15T3HCU
4.6
60
25
25
2

8
3.2
D-MC*
HD_U 3.2
HJ_U
60
45
45

10

8
3.2S
D-MC*
HD_U 3.2
HJ_U
60
45
45
2
10
0
8
5.2/6.2
D-MC*
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

Quick Reference Guide for Selective Coordination Based on 65 kA Available Fault Current on 480 Vac Primary

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

Frame
Min.
Circuit
Ampere
Circuit
General
Size /
InstantCatalog
Size
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Purpose
Rating
aneous
kVA
Numbers
ance
Frame
A
Type (Main)
Type
A
(% Z)1
HD_U 3.2
HD_U 3.2S
EJ
125
80

HD_U
5.2/6.2
D-MC*
HD_U 3.2
HD_U 3.2S
HJ
150
70

HD_U
5.2/6.2
D-MC*
HD_U 3.2
Aluminum
EE30T3H
5.5
HD_U 3.2S
HJ_U
100
50
50
2

8
HD_U
3.2
5.2/6.2
D-MC*
HD_U 3.2
HJ_U
HD_U 3.2S
100
50
50

10

8
3.2S
HD_U
5.2/6.2
HD_U 3.2
HD_U 3.2S
HJ_U
100
50
50
2
10
0
8
5.2/6.2
HD_U
5.2/6.2
30
HD_U 3.2
HD_U 3.2S
EJ
125
80

HD_U
5.2/6.2
D-MC*
HD_U 3.2
HD_U 3.2S
HJ
150
80

HD_U
5.2/6.2
D-MC*
HD_U 3.2
Copper
EE30T3HCU
4.6
HD_U 3.2S
HJ_U
100
50
80
2

10
HD_U
3.2
5.2/6.2
D-MC*
HD_U 3.2
HJ_U
HD_U 3.2S
100
50
50
10
10
3.2S
HD_U
5.2/6.2
HD_U 3.2
HJ_U
HD_U 3.2S
100
50
50
2
10
0
10
5.2/6.2
HD_U
5.2/6.2
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

20112013 Schneider Electric All Rights Reserved


125
125
125
125

150/150
150/150
150/150
150/150

125
125
125
125

150/150
600/150
150/150
150/150

125
125
125
125

150/150
600/150
150/150
150/150

125
125
125
125

150/150
600/150
150/150
150/150

125
125
125

150/150
150/150
150/150

125
125
125

150/150
150/150
150/150

125
125
125
125

150/150
600/150
150/150
150/150

125
125
125
125

125
125
125

600/150
150/150
150/150
150/150

125

150/150

600/150
150/150
150/150

125
125

150/150
150/150

Frame Ampere
Size / Rating2
Rating
(A)

125

125
125

125

(0.9)(0.93)
125
125

125

(0.9)(0.93)
125
125

125

(0.9)(0.93)
125
125

125

125
125

125

125
125

125

(0.9)(0.93)
125
125

125

(0.9)(0.93)
125
125

125

(0.9)(0.93)
125
125

125

125
125

Min.
Pickup

Short Time

4
2

4
2

4
2

4
2

4
2

4
2

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

15

15
15

15

15
15

15

15
15

15

15
15

15

15
15

15

15
15

15

15
15

15

15
15

15

15
15

15

60

60
60

60

60
60
60

60

60
60
60

60

60
60
60

60

60
60

60

60
60

60

60
60
60

60

60
60
60

60

60
60
60

60

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

Max.
1P
Min. Min. Min. Instant- Branch
1570
Delay Pickup Delay aneous Size5
A
(A)
2

15
60
QO(B)

10
15
60
QO(B)

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

2P
15100
A

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)-VH
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

3P
1510
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

13

14

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

Size
kVA

General
Purpose
Type

Catalog
Numbers

Min.
Frame
Circuit
Ampere
Circuit
ImpedSize /
InstantBreaker
Rating2 Setting Delay Setting Delay
Breaker
ance
Rating
aneous
Frame
A
Type (Main)
(% Z)1
A
JD_U 3.2
EJ
125
80

D-MC*
JD_U 3.2
HJ
150
150

D-MC*
JD_U 3.2
HJ_U
Aluminum
EE45T3H
6.0
100
70
70
4

12
3.2
D-MC*
JD_U 3.2
HJ_U
100
100
100

10

12
3.2S
D-MC*
45
JD_U 3.2
HJ_U
100
100
100
2
10
0
12
5.2/6..2
D-MC*
JD_U 3.2
HJ_U
100
70
70
4

15
3.2
D-MC*
JD_U 3.2
HJ_U
Copper
EE45T3HCU
4.4
100
100
100

10

15
3.2S
D-MC*
JD_U 3.2
HJ_U
100
100
100
2
10
0
15
5.2/6..2
D-MC*
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)
175
(0.7)(1)

250
600/250
250
600/250
250
600/250
250
600/250
250
600/250
250
600/250
250
600/250
250
600/250

175
175
175
175
175
175
175
175
175
175
175
175
175
175
175
175

Min.
Pickup

Frame Ampere
Size / Rating2
Rating
(A)

Short Time

Max.
Min. Min. Min. Instant- Branch
Delay Pickup Delay aneous Size5
(A)
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80
4

12
80
8

80

Long Time

Secondary Circuit Breaker

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

1P
1570
A
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

2P
15100
A

QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH
QO(B)
QO(B)-VH

3P
1510
A

3P
110150
A

Continued on next page

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

20112013 Schneider Electric All Rights Reserved

EE75T3HCU

EE75T3H

Aluminum

Copper

Catalog
Numbers

General
Purpose
Type

Transformer
Long Time

Short Time

3.5

3.7

250

250

250

JJ_U
3.2S

JJ_U
5.2/6.2

250

JJ_U
5.2/6.2

JJ_U
3.2

250

JJ_U
3.2S

125

125

125

125

125

125

125

125

125

125

10

10

10

10

12

12

12

12

12

250

250
250
225

225250

225

225

225

225

225
225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225
225

225250
225250

Min.
Pickup

Short Time

10
16

10

10
16

10

10
16

10

10

16

10

10

16

10

10

16

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

Max.
1P
Min. Min. Min. Instant- Branch
1570
Delay Pickup Delay aneous Size5
A
(A)
8

12
100
QO(B)

10

12
100
QO(B)

Long Time

Secondary Circuit Breaker

Frame Ampere
Size / Rating2
Rating
(A)

600/250
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD_W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD_W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD_W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD_W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD_W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400

Min.
Frame
Circuit
Ampere
Circuit
ImpedSize /
InstantBreaker
Rating2 Setting Delay Setting Delay
Breaker
ance
Rating
aneous
Frame
A
Type
(Main)
(% Z)1
A
JD_W 3.2
JD_W 3.2S
JD_W
JJ_U
250
125
125
4

12
5.2/6.2
3.2
D-MC*

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

* NOTE: D-MC and L-MC circuit breakers are obsolete.

75

Size
kVA

Table 2:

QO(B)4

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)
QO(B)

3P
1510
A

3P
110150
A

Continued on next page

QO(B)
QO(B)3

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)

2P
110150
A

QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

2P
15100
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

15

16

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

Size
kVA

General
Purpose
Type

Catalog
Numbers

Frame
Min.
Circuit
Ampere
Circuit
Size /
InstantImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating
aneous
ance
Frame
A
Type
(Main)
A
(% Z)1
LD_W 3.3
LD_W 3.3S
JJ_U
250
175
175
4

12
LD_W
3.2
5.3/6.3
D-MC*
LD_W 33
LD_W 3.3S
JJ_U
250
175
175

10

12
Aluminum EE112T3H
5.2
LD_W
3.2S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
JJ_U
250
175
175
4
10
0
12
LD_W
5.2/6.2
5.3/6.3
D-MC*
112.5
LD_W 3.3
LD_W 3.3S
LJ_U
400
175
175
4

10
LD_W
3.3
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
Copper EE112T3HCU 3.9
400
225
225

10

10
LD_W
3.3S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
225
225
4
10
0
10
LD_W
5.3/6.3
5.3/6.3
D-MC*
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

400

400

400

400
400

Min.
Pickup

400

400

400

400

400

400

400

400

400

400

600/400 300400 (0.8)(0.95)

400

600/400 300400 (0.8)(0.95)


400
400
400
400
400
400

400

600/400 300400 (0.8)(0.95)


400
400
400
400
400
400

400

600/400 300400 (0.8)(0.95)


400
400
400
400
400
400

400

600/400 300400 (0.8)(0.95)


400
400
400
400
400
400

400

600/400 300400 (0.8)(0.95)


400
400
400
400
400
400

400
400

400
400

Frame Ampere
Size / Rating2
Rating
(A)

Short Time

16

16
4

10

10

10

10

10

4
16
4

10

10

4
16
4

10

10

4
16
4

10

10

16
4

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min. Min. Min. Instant- Branch
Delay Pickup Delay aneous Size5
(A)
4

12
150

10

12
150

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

1P
1570
A

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

2P
15100
A

QO(B)

QO(B)
QO(B)

3P
1510
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

Size
kVA

General
Purpose
Type

Catalog
Numbers

Min.
Frame
Circuit
Ampere
Circuit
ImpedSize /
InstantBreaker
Rating2 Setting Delay Setting Delay
Breaker
ance
Rating
aneous
Frame
A
Type
(Main)
(% Z)1
A
LD_W 3.3
LD_W 3.3S
LJ_U
400
225
225
4

10
LD_W
3.3
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
225
225

10

10
Aluminum EE150T3H
6.0
LD_W
3.3S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
225
225
4
10
0
10
LD_W
5.3/6.3
5.3/6.3
D-MC*
150
LD_W 3.3
LD_W 3.3S
LJ_U
400
225
225
4

12
LD_W
3.3
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
Copper
EE150T3CU
4.7
400
250
250

10

12
LD_W
3.3S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
250
250
4
10
0
12
LD_W
5.3/6.3
5.3/6.3
D-MC*
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

(1)(1)
600
600
600
(1)(1)
600
600
600

600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600

600
600
600
600
600
600
600
600
600
600
600

20112013 Schneider Electric All Rights Reserved


600
600/600
600
600
600
600/600
600
600
600
600/600

(1)(1)

600

(1)(1)
600
600

600

(1)(1)
600
600

600

(1)(1)
600
600

600

600

600

600
600

600
600

Min.
Pickup

600
600

Frame Ampere
Size / Rating2
Rating
(A)

Short Time

2
2

2
2

2
2

2
2

2
2

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min. Min. Min. Instant- Branch
Delay Pickup Delay aneous Size5
(A)
2

11
150

11
150

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

1P
1570
A

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

2P
15100
A

QO(B)

QO(B)
QO(B)

3P
1510
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
110150
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

17

18

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (65 kA)

General
Purpose
Type

Catalog
Numbers

(1)(1)

6007
6007
6007

600/600
600
600

600/600

6007

600

600

6007
6007
6007

600/600
600
600

6007

600
(1)(1)
600
600

6007

600

6007

600
(1)(1)
600
600

6007
6007
6007

600/600
600
600

600

600
(1)(1)
600
600

6007

600

4
8

4
8

4
8

4
8

600
(1)(1)
600
600

6007
6007
6007
6007

600
600/600
600
600

8
4
8

600
(1)(1)
600
600

6007
6007
6007
6007

600
600

Short Time

Branch Circuit Breakers for


Total Selective Coordination

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

to the minimum D-MC trip in column to the left.

10

10

10

10

10

10

Max.
1P
2P
2P
3P
3P
Min. Min. Min. Instant- Branch
1570
15100 110150
1510 110150
Delay Pickup Delay aneous Size5
A
A
A
A
A
(A)
8

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

600

6007
6007

Min.
Pickup

600/600
600
600

600
600

Frame Ampere
Size / Rating2
Rating
(A)

Long Time

Secondary Circuit Breaker

1 Values representative of impedance values for Square D transformers.


2 Allow primary trip rating to increase to 250% of rated FLC (NEC 450.4); secondary main trip rating cannot exceed 125% of rated FLC.
3 Selective with 2 pole QO(B) through 80 A rating.
4 Selective with 3 pole QO(B) through 60 A rating.
5 Branch circuit breakers with ampere ratings of 50%, or less, of the D-MC main circuit breaker are selective. Values shown in this column correspond
6 Secondary main circuit breakers will not carry rated secondary current of 416 A.
7 Secondary main circuit breakers will not carry rated secondary current of 325 A.
8 Primary circuit breaker selections shown are for 35 kA SCCRs; if the system has <18 kA available, D-frame circuit breakers may be used.
9 Selective with 3 pole QO(B)-VH circuit breakers through 80 A rating.

Size
kVA

Frame
Min.
Circuit
Ampere
Circuit
Size /
InstantImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating
aneous
ance
Frame
A
Type
(Main)
A
(% Z)1
LD_W 3.3
LD_W 3.3S
LJ_U
400
350
350
4

12
LD_W
3.3
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
350
350

10

12
Aluminum EE225T3H
6.5
LD_W
3.3S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
400
350
350
4
10
0
12
LD_W
5.3/6.3
5.3/6.3
D-MC*
225
LD_W 3.3
LD_W 3.3S
LJ_U
600
350
350
4

11
LD_W
3.3
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
600
400
400

10

11
Copper EE225T3HCU 3.8
LD_W
3.3S
5.3/6.3
D-MC*
LD_W 3.3
LD_W 3.3S
LJ_U
600
400
400
4
10
0
11
LD_W
5.3/6.3
5.3/6.3
D-MC*
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 2:

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Transformer

Long Time

Short Time

Primary Circuit Breaker

Long Time

Secondary Circuit Breaker


Short Time

20112013 Schneider Electric All Rights Reserved


QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
2P
15100 110150
A
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

This table is not meant to replace a selective coordination system study. The purpose of this guide is for activities that occur before the final
system study, such as quotation and iterative design changes, to increase the chance of device combinations being selectively coordinated.
The device combinations presented in this guide represent a level of "total" selective coordination, where the devices were chosen based on
the maximum let-through current.
NEC requirements for transformer protection were also followed in the selection of the device combinations.
Transformers are 480 V primary with 208Y/120 V secondary.

Notes about using this Quick Reference Guide:

Selective Coordination Device Combinations (100 kA)

Branch Circuit Breakers

Transformer

Main Circuit Breaker

Input Circuit Breaker

Frame
Frame
Max.
Min.
Circuit
Ampere
Circuit
Ampere
General
Size /
InstantSize /
Min.
Min. Min. Min. Instant- Branch
Size
Catalog
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating2
Purpose
Rating
aneous
Rating
Settings Delay Pickup Delay aneous Size5
kVA
Numbers
ance
Frame
A
Type (Main)
(A)
Type
(A)
A
Plug
(% Z)1
HL
150
35

HL_U
60
25
25
2

8
3.2
Aluminum
EE15T3H
5.1
HD
150
60

30
HL_U
60
40
40

10

8
3.2S
HL__U
60
40
40
2
10
0
8
5.2/6.2
HD_U 3.2 150/150
60
60
2

15
30
15
HL
150
40

D-MC* 600/150
60
(0.5)(0.8)
4

30
HD_U 3.2 150/150
60
60
2

15
30
HL-U
60
25
25
2

8
3.2
D-MC* 600/150
60
(0.5)(0.8)
4

30
Copper
EE15T3HCU
4.6
HD_U 3.2 150/150
60
60
2

15
30
HL_U
60
45
45

10

8
3.2S
D-MC* 600/150
60
(0.5)(0.8)
4

30
HD_U 3.2 150/150
60
60
2

15
30
HL_U
60
45
45
2
10
0
8
5.2/6.2
D-MC* 600/150
60
(0.5)(0.8)
4

30
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 3:

Quick Reference Guide for Selective Coordination Based on 100 kA Available Fault Current on 480 Vac Primary

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

19

20

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (100 kA)

Long Time

Secondary Circuit Breaker


Short Time

Size
kVA

General
Purpose
Type

Catalog
Numbers

Frame
Frame
Max.
Min.
Circuit
Ampere
Circuit
Ampere
Size /
InstantSize /
Min.
Min. Min. Min. Instant- Branch
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating2
Rating
aneous
Rating
Settings Delay Pickup Delay aneous Size5
ance
Frame
A
Type (Main)
(A)
A
Plug
(% Z)1
(A)
HD_U 3.2 150/150 125
125
2

15
60
HD_U 3.2S 150/150 125
125

10

15
60
HL
150
70

HD_U
150/150 125
125
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.93) 4

60
HD_U 3.2 150/150 125
125
2

15
60
HD_U 3.2S 150/150 125
125

10

15
60
HL_U
100
50
50
2

8
HD_U
3.2
150/150 125
125
2
10
0
15
60
5.2/6.2
Aluminum
EE30T3H
5.5
D-MC* 600/150 125 (0.9)(0.93) 4

60
HD_U 3.2 150/150 125
125
2

15
60
HL_U
HD_U 3.2S 150/150 125
125

10

15
60
100
50
50

10

8
3.2S
HD_U
150/150 125
125
2
10
0
15
60
5.2/6.2
HD_U 3.2 150/150 125
125
2

15
60
HL_U
HD_U 3.2S 150/150 125
125

10

15
60
100
50
50
2
10
0
8
5.2/6.2
HD_U
150/150 125
125
2
10
0
15
60
5.2/6.2
30
HD_U 3.2 150/150 125
125
2

15
60
HD_U 3.2S 150/150 125
125

10

15
60
HL
150
80

HD_U
150/150 125
125
2
10
0
15
60
5.2/6.2
D-MC* 600/150 125 (0.9)(0.93) 4

60
HD_U 3.2 150/150 125
125
2

15
60
HD_U 3.2S 150/150 125
125

10

15
60
HL_U
100
50
50
2

10
HD_U
3.2
150/150 125
125
2
10
0
15
60
5.2/6.2
Copper
EE30T3H_Cu 4.6
D-MC* 600/150 125 (0.9)(0.93) 4

60
HD_U 3.2 150/150 125
125
2

15
60
HL_U
HD_U 3.2S 150/150 125
125

10

15
60
100
50
50

10

10
3.2S
HD_U
150/150 125
125
2
10
0
15
60
5.2/6.2
HD_U 3.2 150/150 125
125
2

15

HL_U
HD_U 3.2S 150/150 125
125

10

15

100
50
50
2
10
0
10
5.2/6.2
HD_U
150/150 125
125
2
10
0
15
50
5.2/6.2
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 3:

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)

QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)
QO(B)

QO(B)-VH

QO(B)

QO(B)
QO(B)

3P
15100
A

QO(B)

3P
110150
A

Continued on next page

2P
2P
15100 110150
A
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (100 kA)

Short Time

Max.
Min.
Min. Min. Min. Instant- Branch
Settings Delay Pickup Delay aneous Size5
(A)
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80
175
4

12
80
(0.7)(1)
8

80

Long Time

Secondary Circuit Breaker

Frame
Frame
Min.
Circuit
Ampere
Circuit
Ampere
General
Size /
InstantSize /
Size
Catalog
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating2
Purpose
Rating
aneous
Rating
kVA
Numbers
ance
Frame
A
Type (Main)
(A)
Type
1
A
Plug
(% Z)
JD_U 3.2
250
175
HL
150
150

D-MC* 600/250 175


JD_U 3.2
250
175
HL_U
100
70
70
4

12
3.2
D-MC* 600/250 175
Aluminum
EE45T3H
6.0
JD_U 3.2
250
175
HL-U
100
100
100

10

12
3.2S
D-MC* 600/250 175
JD_U 3.2
250
175
HL-U
100
100
100
2
10
0
12
45
5.2/6.2
D-MC* 600/250 175
JD_U 3.2
250
175
HL_U
100
70
70
4

12
3.2
D-MC* 600/250 175
JD_U 3.2
250
175
HL-U
100
100
100

10

12
Copper
EE45T3H_Cu 4.4
3.2S
D-MC* 600/250 175
JD_U 3.2
250
175
HL-U
100
100
100
2
10
0
12
5.2/6.2
D-MC* 600/250 175
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 3:

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)
QO(B)

20112013 Schneider Electric All Rights Reserved


QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

3P
15100
A

3P
110150
A

Continued on next page

2P
2P
15100 110150
A
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

21

22

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (100 kA)

Copper

EE75T3H_Cu

EE75T3H

3.5

3.7

250

250

JL_U
3.2S

JL_U
5.2/6.2

250

250

JL_U
5.2/6.2

JL_U
3.2

250

JL_U
3.2S

* NOTE: D-MC and L-MC circuit breakers are obsolete.

75

Aluminum

125

125

125

125

125

125

125

125

125

125

10

10

10

10

12

12

12

12

12

Long Time

Secondary Circuit Breaker


Short Time

250

225

225

225

225

225

225
225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

225250 (0.9)(1)
225300 (0.7)(0.8)
225300

225250
225
225250
225

225250

10
16

10

10
16

10

10
16

10

10

16

10

10

16

10

10

16

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

100
100
100

100

100

QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)4

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

QO(B)4
QO(B)
QO(B)

QO(B)-VH9

QO(B)

3P
110150
A

Continued on next page

QO(B)
QO(B)3

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)3
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)

3P
15100
A

2P
2P
15100 110150
A
A

Branch Circuit Breakers for


Total Selective Coordination

Frame
Max.
1P
Ampere
Size /
Min.
Min. Min. Min. Instant- Branch
1570
Rating2
Rating
Settings Delay Pickup Delay aneous Size5
A
(A)
(A)
Plug
250 225250
225
8

12
100
QO(B)
250 225250
225

10

12
100
QO(B)

600/250
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD-W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD-W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD-W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD-W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400
JD_W 3.2
250
JD_W 3.2S 250
JD-W
250
5.2/6.2
600/250
D-MC*
600/400
LA-MC
400

Frame
Trans- General
Min.
Circuit
Ampere
Circuit
Transformer
Size /
Instantformer Purpose
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Catalog
Rating
aneous
Size Transformer
ance
Frame
A
Type (Main)
Numbers
A
kVA
Type
(% Z)1
JD_W 3.2
JD_W 3.2S
JD-W
JL_U
250
125
125
4

12
5.2/6.2
3.2
D-MC*

Table 3:

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (100 kA)

Frame
Frame
Min.
Circuit
Ampere
Circuit
General
Size /
InstantSize /
Size
Catalog
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Purpose
Rating
aneous
Rating
kVA
Numbers
ance
Frame
A
Type (Main)
Type
1
A
Plug
(% Z)
LD_W 3.3
400
LD_W 3.3S 400
JL_U
250
175
175
4

12
LD_W
3.2
400
5.3/6.3
D-MC* 600/400
LD_W 3.3
400
LD_W 3.3S 400
JL_U
250
175
175

10

12
Aluminum
EE112T3H
5.1
LD_W
3.2S
400
5.3/6.3
D-MC* 600/400
LD_W 3.3
400
LD_W 3.3S 400
JL_U
250
175
175
4
10
0
12
LD_W
5.2/6.2
400
5.3/6.3
D-MC* 600/400
112.5
LD_W 3.3
400
LD_W 3.3S 400
LL_U
400
175
175
4

10
LD_W
3.3
400
5.3/6.3
D-MC* 600/400
LD_W 3.3
400
LD_W 3.3S 400
LL_U
400
225
225

10

10
Copper EE112T3H_Cu 5.4
LD_W
3.3S
400
5.3/6.3
D-MC* 600/400
LD_W 3.3
400
LD_W 3.3S 400
LL_U
400
225
225
4
10
0
10
LD_W
5.3/6.3
400
5.3/6.3
D-MC* 600/400
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 3:

20112013 Schneider Electric All Rights Reserved


0

10
10

10
10

10
10

10
10

300400 (0.8)(0.95) 16
400
400
4
400
400

300400 (0.8)(0.95) 16
400
400
4
400
400

300400 (0.8)(0.95) 16
400
400
4
400
400

4
300400 (0.8)(0.95) 16

400

400

400

400

400

400

400

400

10

400

300400 (0.8)(0.95) 16
400
400
4
400
400

400

10

300400 (0.8)(0.95) 16
400
400
4
400
400

10

400

400

400
400

Ampere
Rating2
(A)

Short Time

12

12
12

12

12
12

12

12
12

12

12
12

12

12
12

12

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min.
Min. Min. Min. Instant- Branch
Settings Delay Pickup Delay aneous Size5
(A)
400
4

12
150
400

10

12
150

Long Time

Secondary Circuit Breaker

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

1P
1570
A

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

3P
15100
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

QO(B)

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
2P
15100 110150
A
A

Branch Circuit Breakers for


Total Selective Coordination

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

23

24

Transformer

Long Time

Short Time

Primary Circuit Breaker

Selective Coordination Device Combinations (100 kA)

Short Time

2
2
2

600
(1)(1)
600
600

2
2
2

600
(1)(1)
600
600

2
2
2

600
(1)(1)
600
600

600

2
2

(1)(1)
600
600

(1)(1)

600

2
2
2

600
(1)(1)
600
600

11

11
11

11

11
11

11

11
11

11

11
11

11

11
11

11

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

Max.
Min.
Min. Min. Min. Instant- Branch
Settings Delay Pickup Delay aneous Size5
(A)
600
2

11
150
600

11
150

Long Time

Secondary Circuit Breaker

Frame
Frame
Min.
Circuit
Ampere
Circuit
Ampere
General
Size /
InstantSize /
Size
Catalog
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating2
Purpose
Rating
aneous
Rating
kVA
Numbers
ance
Frame
A
Type (Main)
(A)
Type
A
Plug
(% Z)1
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
400
225
225
4

10
LD_W
3.3
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
400
225
225

10

10
Aluminum
EE150T3H
6.0
LD_W
3.3S
600
600
5.3/6.3
D-MC*
600
600
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
400
225
225
4
10
0
10
LD_W
5.3/6.3
600
600
5.3/6.3
D-MC*
600
600
150
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
400
225
225
4

12
LD_W
3.3
600
600
5.3/6.3
D-MC* 600/600 600
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
Copper
EE150T3_Cu 4.7
400
250
250

10

12
LD_W
3.3S
600
600
5.3/6.3
D-MC* 600/600 600
LD_W 3.3
600
600
LD_W 3.3S 600
600
LL_U
400
250
250
4
10
0
12
LD_W
5.3/6.3
600
600
5.3/6.3
D-MC* 600/600 600
* NOTE: D-MC and L-MC circuit breakers are obsolete.

Table 3:

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)
QO(B)

QO(B)

QO(B)
QO(B)

QO(B)
QO(B)

QO(B)-

QO(B)
QO(B)

3P
15100
A

QO(B)-VH

QO(B)-VH
QO(B)-VH

3P
110150
A

QO(B)-

QO(B)-VH

QO(B)-

QO(B)-VH

QO(B)-

QO(B)-VH

QO(B)-

QO(B)-VH

QO(B)-

QO(B)-VH

Continued on next page

QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B) QO(B)-VH
QO(B)-VH QO(B) QO(B)-VH

QO(B)-VH

QO(B)-VH
QO(B)-VH

2P
2P
15100 110150
A
A

1P
1570
A

Branch Circuit Breakers for


Total Selective Coordination

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin
0100DB0902 R06/13
08/2013

20112013 Schneider Electric All Rights Reserved

20112013 Schneider Electric All Rights Reserved

Long Time

Short Time

Primary Circuit Breaker

General
Purpose
Type

Catalog
Numbers

600/600

6007

8
4

600
(1)(1)

11

11
11

11

11
11

11

11
11

11

11
11

11

150

150

150
150
150

150

150
150
150

150

150
150
150

150

150
150
150

150

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH


QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

to the minimum D-MC trip in column to the left.

10

10

10

8
4
8

600
(1)(1)
600
600

10

8
4
8

600
(1)(1)
600
600

8
4
8

600
(1)(1)
600
600

8
4
8

600
(1)(1)
600
600

1 Values representative of impedance values for Square D transformers.


2 Allow primary trip rating to increase to 250% of rated FLC (NEC 450.4); secondary main trip rating cannot exceed 125% of rated FLC.
3 Selective with 2 pole QO(B) through 80 A rating.
4 Selective with 3 pole QO(B) through 60 A rating.
5 Branch circuit breakers with ampere ratings of 50%, or less, of the D-MC main circuit breaker are selective. Values shown in this column correspond
6 Secondary main circuit breakers will not carry rated secondary current of 416 A.
7 Secondary main circuit breakers will not carry rated secondary current of 325 A.
8 Primary circuit breaker selections shown are for 35 kA SCCRs; if the system has <18 kA available, D-frame circuit breakers may be used.
9 Selective with 3 pole QO(B)-VH circuit breakers through 80 A rating.

D-MC*

Short Time

Branch Circuit Breakers for


Total Selective Coordination

Max.
1P
2P
2P
3P
3P
Min.
Min. Min. Min. Instant- Branch
1570
15100 110150 15100 110150
Settings Delay Pickup Delay aneous Size5
A
A
A
A
A
(A)
600
8

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH
600

11
150 QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH QO(B)-VH

Long Time

Secondary Circuit Breaker

Frame
Frame
Min.
Circuit
Ampere
Circuit
Ampere
Size /
InstantSize /
ImpedBreaker
Rating2 Setting Delay Setting Delay
Breaker
Rating2
Rating
aneous
Rating
ance
Frame
A
Type
(Main)
(A)
A
Plug
(% Z)1
LD_W 3.3
600
6007
LD_W 3.3S 600
6007
LL_U
400
350
350
4

12
LD_W
3.3
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3
600
6007
LD_W 3.3S 600
6007
LL_U
400
350
350

10

12
Aluminum EE225T3H
6.5
LD_W
3.3S
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3
600
6007
LD_W 3.3S 600
6007
LL_U
400
350
350
4
10
0
12
LD_W
5.3/6.3
600
6007
5.3/6.3
D-MC* 600/600 6007
LD_W 3.3
600
6007
LD_W 3.3S 600
6007
PL 3_
400
360
0.9
4

12
LD_W
600
6007
5.3/6.3
D-MC* 600/600 6007
Copper EE225T3H_Cu 3.7
LD_W 3.3
600
6007
LD_W 3.3S 600
6007
PL
400
400
1
4
10 INST 12
LD_W
5._/6.__
600
6007
5.3/6.3

Transformer

Selective Coordination Device Combinations (100 kA)

* NOTE: D-MC and L-MC circuit breakers are obsolete.

225

Size
kVA

Table 3:

0100DB0902 R06/13
08/2013
Guide to Low Voltage Transformer Protection and Selective Coordination
Data Bulletin

25

Guide to Low Voltage Transformer Protection and Selective Coordination


Data Bulletin

Schneider Electric USA, Inc.


1415 S. Roselle Road
Palatine, IL 60067 USA
1-888-778-2733
www.schneider-electric.us
26

0100DB0902 R06/13
08/2013

Electrical equipment should be installed, operated, serviced, and maintained only by


qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
20112013 Schneider Electric All Rights Reserved
Schneider Electric and Square D are trademarks owned by Schneider Electric
Industries SAS or its affiliated companies. All other trademarks are the property of
their respective owners.
20112013 Schneider Electric All Rights Reserved

También podría gustarte