Está en la página 1de 4

ANALISIS A CAUDAL MAXIMO HORARIO - SIN COMPRESOR

l/s

CAUDAL DE BOMBEO

QSB =

23.53

l/s

NUMERO DE CICLOS

U=

4.00

HORA

TIEMPO DE BOMBEO

Tc =

900.00

4.41

m3

PRESION MINIMA

Vu =
PMIN =

30.00

PRESION MAXIMA

PMAX =

45.00

PORCENTAJE DE VOLUMEN
VULUMEN TOTAL
DIAMETRO

%Vu =
Vt =
D=

30%
14.71
3.00

m3
m

ALTURA DE TANQUE

H=

4.50

AREA DE TANQUE

A=

7.07

m2

TLL =
TV=
TLL/(TLL+TV)=

3.13
3.75

min
min

VOLUMEN UTIL

TIEMPO DE BOMBEO
TIEMPO DE VACIADO
% DE ENERGIA POR CICLO
TIEMPO DE CICLO
CICLOS HORA A CMH
TIEMPO USO BOMBA

Tc =
Nc =
Tu =
PSB =

POTENCIA SISTEMA DE BOMBEO

PSB =

POTENCIA SISTEMA DE BOMBEO


FACTOR DE ARRANQUE
ENERGIA HORA

F=
E=

0.45
6.88
8.73
27.27

0.75

19.61

Ve =3.53

3.00

QB =

Ve =21.21

0.75

CAUDAL MAXIMO HORARIO

4.50

3.00

Ve =3.53

min
min

20

HP

15
0.55
9.00

Kw
Kw/HORA

ANALISIS A CAUDAL MEDIO DIARIO - SIN COMPRESOR


CAUDAL MEDIO DIARIO

QB =

13.07 l/s

CAUDAL DE BOMBEO

QSB =

23.53 l/s

NUMERO DE CICLOS

U=

4.00 HORA

0.75

3.00

Ve =3.53

PRESION MINIMA

Vu =
PMIN =

30.00 m

PRESION MAXIMA

PMAX =

45.00 m

PORCENTAJE DE VOLUMEN
VULUMEN TOTAL
DIAMETRO

%Vu =
Vt =
D=

30%
14.71 m3
3.00 m

ALTURA DE TANQUE

H=

4.50 m

AREA DE TANQUE

A=

7.07 m2

TIEMPO DE BOMBEO
TIEMPO DE VACIADO

TLL =
TV=
TLL/(TLL+TV)=

3.13 MIM
5.63 MIM

% DE ENERGIA POR CICLO


TIEMPO DE CICLO
CICLOS HORA A CMH
TIEMPO USO BOMBA
POTENCIA SISTEMA DE BOMBEO
POTENCIA SISTEMA DE BOMBEO
FACTOR DE ARRANQUE
ENERGIA HORA

Tc =
Nc =
Tu =
PSB =
PSB =
F=
E=

0.75
VOLUMEN UTIL

3.00

Tc =

Ve =21.21

0.75

TIEMPO DE BOMBEO

Ve =3.53

Ve =3.53

900.00 s

0.36
8.75 MIM
6.86
21.43 MIN
20 HP
14.8 Kw
0.70
7.00 Kw/HORA

4.50

4.41 m3

ANALISIS A CAUDAL MAXIMO HORARIO - CON COMPRESOR


3.00

Ve =3.53

Ve =21.21

CAUDAL MAXIMO HORARIO

QB =

19.61

l/s

CAUDAL DE BOMBEO

QSB =

23.53

l/s

QAireyAgua =

16.16

l/s

VOLUMEN DE AIRE

VE =

3.53

m2

VOLUMEN DE UTIL DE AGUA

Vc =

21.21

m3

TIEMPO DE BOMBEO

TLL =

9.88

min

TIEMPO DE VACIADO

TV =

18.03

MIM

TLL/(TLL+TV) =

0.35
27.91
2.15

MIM

Tu =
PSB =

21.25

MIN

30.00

HP

PSB =

Kw

F=

22.20
0.28

E=

8.08

Kw/HORA

CAUDAL DE AGUA + AIRE

% DE ENERGIA POR CICLO


TIEMPO DE CICLO
CICLOS HORA A CMH
TIEMPO USO BOMBA+ COMPRES
Ve =3.53

POTENCIA BOMBA + COMPRES


POTENCIA BOMBA + COMPRES
FACTOR DE ARRANQUE
ENERGIA HORA

Tc =
Nc =

ANALISIS A CAUDAL MEDIO DIARIO - CON COMPRESOR


3.00

Ve =3.53

CAUDAL MAXIMO HORARIO

QB =

19.61

l/s

CAUDAL DE BOMBEO

QSB =

23.53

l/s

QAireyAgua =

16.16

l/s

CAUDAL DE AGUA + AIRE

Ve =3.53

Ve =21.21

VOLUMEN DE AIRE

VE =

3.53

m2

VOLUMEN DE UTIL DE AGUA

Vc =

21.21

m3

TIEMPO DE BOMBEO

TLL =

12.09

min

TIEMPO DE VACIADO

TV =

27.04

min

TLL/(TLL+TV) =

0.31
39.13
1.53

min

Tu =
PSB =

18.54

min

30.00

HP

PSB =

Kw

F=

22.20
0.32

E=

7.01

Kw/HORA

% DE ENERGIA POR CICLO


TIEMPO DE CICLO
CICLOS HORA A CMH
TIEMPO USO BOMBA+ COMPRES
Ve =3.53

POTENCIA BOMBA + COMPRES


POTENCIA BOMBA + COMPRES
FACTOR DE ARRANQUE
ENERGIA HORA

Tc =
Nc =

También podría gustarte