SPEC.NO.

: IP060-45-23-05

REV. 0

PROJECT NO.

: IP060

SH. 1 OF 4

DESCRIPTION

: TURBINE FLOWMETER

CHEMTEX
AREA : INSTRUMENTATION

IP060
FINE PROJECT
TURBINE FLOWMETER
(BUYER'S SCOPE)

PT. INDORAMA VENTURES INDONESIA


BANTEN, INDONESIA

REFERENCE SPEC. NO. IP015-45-23-05, Rev.0


THIS DOCUMENT IS PROPRIETARY AND CONFIDENTIAL INFORMATION OF CHEMTEX AND ITS LICENSOR AND MAY BE USED ONLY WITH THEIR PRIOR WRITTEN CONSENT.

REV.

DESCRIPTION

ISSUED FOR ENQUIRY

PREP'D.

CHK'D

APPR'D.

DATE

RKM

VIM

SSG

AUG 29 2013

FILE NAME : IP060-45-23-05-0.XLS

CHEMTEX

SPEC NO. IP060-45-23-05 REV. 0

SHEET 2 OF 4

TURBINE FLOWMETER
REV.

SCOPE:
THIS SPECIFICATION COVERS THE MINIMUM REQUIREMENTS FOR DESIGN, FABRICATION, TESTING AND
GUARANTEES FOR OPERATION AND PERFORMANCE OF THE INSTRUMENTS LISTED HEREIN.
REFERENCE STANDARDS/ DESIGN CODES :
a)

ASME B16.5, 2009

PIPE FLANGES AND FLANGED FITTINGS AND FINISH.

CODES AND STANDARDS SHALL BE THE LATEST ISSUE TO THE DATE OF INQUIRY INCLUDING AGENDA,
REVISIONS OR SUPPLEMENTS.
3

TECHNICAL REQUIREMENTS :
ANY DEVIATIONS FROM THE REQUIREMENTS OF THIS SPECIFICATION SHALL BE STATED AS EXCEPTIONS IN
VENDOR'S PROPOSAL. UNLESS SPECIFIC EXCEPTIONS ARE STATED, IT SHALL BE UNDERSTOOD THAT THE
INSTRUMENTS ARE IN COMPLETE ACCORDANCE WITH THE SPECIFICATION.

NAMEPLATE :
EACH INSTRUMENT SHALL HAVE A CORROSION RESISTANT NAMEPLATE PERMANENTLY FASTENED TO IT
WITH DETAILS.

FOR ALL TAGS VENDOR TO CHECK THE SUITABILITY OF


TURBINE METER FOR THE GIVEN FLOW, VISCOSITY AND OTHER PROCESS CONDITIONS.

STD52305.00X

CHEMTEX

SPEC NO. IP060-45-23-05 REV. 0

SHEET 3 OF 4

TURBINE FLOWMETER

METER

SERVICE CONDITIONS

GENERAL

R
1 TAG NO.
2 SERVICE
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
43
44
45
46
47
48
49
50
51
52

LINE NO.
LINE SIZE & SCH.
FLUID
FLUID STATE
FLOW UNIT
FLOW NORMAL
FLOW
MIN. MAX.
PRESSURE KG/CM2G
NOR. MAX.
DEG C NOR. MAX.
TEMPERATURE
VISCOSITY
cP
NOR. MAX.
NOR. MAX.
DENSITY (kg/m3)
PERCENT SOLIDS & TYPE
MAX. ALLOW. PRES DROP KG/CM2
BACK PRESSURE
METER LOCATION
END CONNECTION SIZE & RATING
ACCURACY
EXCITATION
K-FACTOR(CYCLES PER UNIT VOL.)
PICKOFF TYPE
MATERIALS :
BODY
FLANGES
SUPPORT
SHAFT
ROTOR
BEARINGS
BEARINGS : TYPE
FLOW RANGE
OUTPUT VOLTAGE
MAXIMUM SPEED

OPTIONS

SECONDARY INST.

SECONDARY INST. TAG NO.


PRE AMPLIFIER
FUNCTION
POWER SUPPLY
OUTPUT
FLOW RANGE
MOUNTING
ENCLOSURE CLASS
AREA CLASSIFICATION
CONDUIT CONNECTION Signal Power
TOTALIZER TYPE
COMPENSATION TEMP. / VISC
STRAINER SIZE & MESH
STRAIGHTENING ASSEMBLY
JACKET:
FLUID
STATE
MAX. TEMP. PRESS.
JACKET CONN. :
INLET OUTLET
JACKET MATERIAL
PRESET COUNTER
MANUFACTURER
METER MODEL NO.
SECONDARY INST. MODEL NO.
P & ID. NO.
VENDOR TO SPECIFY / CONFIRM.
STD52305.00X

G
M
S
O

1840-FE/FT-65602

1850-FE/FT-65903

INDUSTRIAL WATER
SUPPLY HEADER FLOW

CHILLED WATER
SUPPLY FLOW TO AHU

6" IW(S)-65601 PS-1


6" SCH STD
INDUSTRIAL WATER
LIQUID
m3/hr
26.2
40.1
2
8
30
60
0.47
0.8
993
0.3

14" CW(S)-65901 PS-1


14" SCH STD
CHILLED WATER
LIQUID
m3/hr
894
1000
7.027
9.09
7
60
1.43
998.4
0.3

IN LINE
* ASME 150 # FF
+/-0.5% OR BETTER
*
*
*
SS 304
SS 304
SS 304
SS 304

IN LINE
* ASME 150 # FF
+/-0.5% OR BETTER
*
*
*
SS 304
SS 304
SS 304
SS 304

17-4 PH SS

TUNGSTEN CARBIDE

17-4 PH SS

TUNGSTEN CARBIDE

*
0 - 55 m3/hr
*
*

*
0 - 1300 m3/hr
*
*

1840-FT - 65602
MFR STD

1850-FT - 65903
MFR STD

TRANSMIT AND INDICATE

TRANSMIT AND INDICATE

220V AC, 50 HZ
4-20 mA DC
0 - 55 m3/hr
INTEGRAL
IP-65
SAFE
1/2"
3/4"
REQUIRED, *
-

220V AC, 50 HZ
4-20 mA DC
0 - 1300 m3/hr
INTEGRAL
IP-65
SAFE
1/2"
3/4"
REQUIRED, *
-

REQUIRED
*
*
*
503656-1840-060

REQUIRED
*
*
*
503659-1850-060

SPEC NO. IP060-45-23-05 REV. 0

CHEMTEX

SHEET 4 OF 4

TURBINE FLOWMETER
REV.

CHEMTEX
VENDOR DOCUMENT REQUIREMENT & SCHEDULE
INSTRUMENTATION
ITEM : FLOW METERS / TRANSMITTERS
PROJECT : IP060

SPECNO.: IP060-45-23-05

DESCRIPTION OF DOCUMENTATION

PO NO.:

----QUOTE---

VALIDATION DATE:

----------APPROVAL----------

QTY_P QTY_D QTY_P QTY_D

Outline Dimensional Drawings & Connections


Installation Drawings
Wiring / Termination Drawings
Specifications
Calculations (Sizing)
Calibration Procedures
Calibration Sheets (NIST Traceable)
FM Certificate (if applicable)
UL Certificate (if applicable)
Bill of Materials
I. O. M.
Inspection and Test Report
Quality Certificate
Certificate of Conformance (CFC)
Spare Parts List / Commissioning Spares

2
2

3
3
3
3
3

3
3
3

3
3
3

LEAD (wks)

(4) ARO

----------CERTIFIED---------QTY_R QTY_P QTY_D

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

LEAD (wks)

(4) ARO
(4) ARO
(4) ARO
(4) ARO
(4) ADA
(2) PTSR
(2) PTSR
(4) ARO
(4) ARO
(4) ARO
(4) ARO
(2) PTSR
(2) PTSR
(2) PTSR
(4) ARO

INSTRUCTIONS :
1. Vendor shall be responsible for the correctness of all Drawings and Documents.
2. Vendor must obtain written approval from Chemtex for any deviation from Drawings / Documents specifications.
3. Vendor shall identify Drawings by printing the following information in the title box on each Drawing :
a.
Customer name.
b.
Chemtex Purchase Order Number and Vendor Order Number.
c.
Equipment Item Number and Name to which the print applies.
4. All final Documents are to be bound together with an index. This is to include all applicable items shown in the
table above.
5. Drawings will not be accepted unless the above information is incorporated on all Documents furnished by vendor.
NOTES :
APPROVAL :
CERTIFIED :
ADA
ARO
PTSR
Qty_P
Qty_R
Qty_D
QUOTE

:
:
:
:
:
:
:

Drawings/Documents require Chemtexs approval prior to fabrication.


Vendor shall certify that the Drawings/Documents being furnished accurately describe the
equipment/items covered by this purchase order.
After Drawing/Document Approval
After Receipt of Order
Drawings/Documents required Prior To Shipment Release
Quantity of Prints or Copies
Quantity of Reproducibles
Quantity of Digital Documentation
Prints or copies of Drawings / Documents required With Quotation.

SCHEDULE : VD45-23
REVISION : 10/01/99 REV. 0

STD52304.00X