Leakage Current Measurement Report of

Lightning Arrestors
Measurement Kit Used: Surge Arrestor leakage Current Meter
Model No. SA 30i, Make - Scope
Area of Measurement:

132 kV Switchyard

220 kV Switchyard

2x50 MW

20/25 MVA TR-01

100 MVA TR-01

GT-07

20/25 MVA TR-02

100 MVA TR-02

GT-08

20/25 MVA TR-03

GT-07 Bay

20/25 MVA TR-04

GT-08 Bay

132 kV Tie Line

132 kV Tie Line

132 kV Ras-Bwr Line

30/35 MVA Trafo (U-9)


30/35 MVA Trafo (U-10)
220 kV Merta Line
220 kV Beawar Line

Note: The graph has been plotted between the Ir (Corrected) in A & the test dates.

Brief Theory :
The resistive current (Ir) is only 15-25% of the total leakage current. Hence, a sharp increase in resistive current
due to degradation/ageing of Zinc Oxide blocks does not affect the total leakage current considerably. The
higher resistive leakage current may ultimately bring in the LA to thermal instability and may result in complete
failure/breakdown of the Arrester. Hence, the resistive leakage current is the true indicator of health of an LA in
service.
The resistive leakage current depends on the arrester temperature (in practice the ambient temperature) and
the operating voltage. If the temperature and voltage are not taken into account (uncorrected values), the
measured value of the resistive leakage current strongly varies. By taking account of the ambient temperature
and operating voltage, measurements performed under different conditions can be directly compared and the
measured values will be a reliable indicator of the arrester conditions.
The Ir (Corrected) value limit is 100 A.

and operating voltage, measurements performed under different conditions can be directly compared and the
measured values will be a reliable indicator of the arrester conditions.
The Ir (Corrected) value limit is 100 A.

LA Replacement History
Location
100 MVA TR-01
100 MVA TR-01
20/25 MVA TR-01
20/25 MVA TR-02
100 MVA TR-01
100 MVA TR-02
Ras-Bwr Line Incomer
132 kV Tie Line (132 kV SWYD)
132 kV Tie Line (132 kV SWYD)

Phase
Y
B
All 3 phase
All 3 phase
All 3 phase
All 3 phase
All 3 phase
All 3 phase
All 3 phase

Replacement Date
16.07.2011
16.07.2011
29.08.2011
25.01.2012
18.04.2012
23.04.2012
18.01.2013
30.03.2013
30.03.2013

LA Counter Replacement History


GT-7 Bay Y-phase (220kV S/Y)

11.08.2014

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

GT-07
R-Phase

GT-07 Bay

Y-Phase

B-Phase

R-Phase

81

Y-Phase

23

21
52

57

50

19

19

12

12

20

19

16
3
13
24

Test by Shanthala
on (04/12/2010)

B-Phase

44

17
8
9

16
9
8

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

17

19
10
11

16
9
9

14
10
8

In-house Test on
(28/08/2014)

Test by Shanthala
on (04/12/2010)

0
Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

Ir (Corr.) Limit: 100 A


LA Rating

120 kV Make - CGL

120 kV Make - CGL

GT-07
Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

In-house Test
Test by ABB on
on
(24/07/2012)
(03/07/2013)

GT-07 Bay

Phase

Test by
Shanthala on
(04/12/2010)

In-house Test In-house Test In-house Test In-house Test


on
on
on
on
(07/01/2014) (26/03/2014) (14/06/2014) (28/08/2014)

Test by
Shanthala on
(04/12/2010)

In-house Test
Test by ABB on
on
(24/07/2012)
(03/07/2013)

39

39

11

16

45

46

10

10

12

66

22

12

13

14

16

19

50

44

11

17

NA

24

20

19

57

52

10

10

13

NA

16

12

12

81

21

16

17

14

16

19

NA

23

19

19

849

753

982

985

1007

1007

970

764

877

873

872

831

937

938

940

920

979

1016

463

1100

1011

1003

932

973

816

814

802

856

808

927

904

837

877

0.2

0.2

0.3

0.4

0.2

0.2

0.6

0.2

0.3

NA

Readings not
available due
to TG-08
tripped on
Earth fault due
to RTD in LAVT
panel.

In-house Test
on
(07/01/2014)

In-house Test
on
(26/03/2014)

17

14

17

11

11

17

13

17

0.5

0.6

0.3

0.7

0.7

0.5

0.6

0.7

0.7

0.6

0.4

0.4

0.6

0.2

0.3

30

37

27

37

39

37

37

18

32

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

19

18
15

12

11

19

17

e Test on
3/2014)

In-house Test on
(14/06/2014)

16

In-house Test on
(28/08/2014)

In-house Test
In-house Test
on
on (28/08/2014)
(14/06/2014)
17

13

11

17

13

17

16

11

18

15

899

854

1058

1063

902

810

0.2

0.4

0.3

0.6

0.5

0.5

36

30

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

GT-08
R-Phase

GT-

Y-Phase

B-Phase

R-Phase

42
109

97

222
39

4
63

31
55

36

29

28
Test by Shanthala on
(04/12/2010)

78

11
9
7
In-house Test on
(03/07/2013)

Test by ABB on
(24/07/2012)

8
11
8

8
10
8

6
8
10
In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

27

8
16
9

8
11
8
In-house Test on
(08/07/2014)

In-house Test on
(28/08/2014)

Test by Shanthala on
(04/12/2010)

11
19

9
17

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

120 kV Make - CGL

120 kV Make - CGL

GT-08

GT-08 Bay

Phase

Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test In-house Test In-house Test In-house Test In-house Test
on
on
on
on
on
(07/01/2014) (26/03/2014) (14/06/2014) (08/07/2014) (28/08/2014)

168

24

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(07/01/2014)

19

72

17

13

84

47

10

11

10

16

45

36

10

33

27

90

23

25

222

28

10

27

78

17

19

109

55

10

11

11

16

63

39

11

42

31

11

97

29

36

552

935

953

968

978

1028

965

945

998

1192

1211

1100

798

979

959

951

969

1010

994

1089

851

960

1043

1006

869

984

976

951

995

1038

978

960

786

879

867

864

0.5

0.6

0.6

0.4

0.4

0.6

0.8

0.8

0.5

0.5

0.6

0.6

0.6

0.6

0.7

0.7

0.6

0.6

0.6

0.6

0.4

0.7

16

16

0.6

0.6

Counters

29

29

29

29

326

326

11

11

Ambient

31

36

27

37

39

36

38

34

37

19

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

GT-08 Bay
Y-Phase

B-Phase

36

32

35

33

30

11
19

11
19

12
17

13
17

11
16

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(8/07/2014)

120 kV Make - CGL


GT-08 Bay
In-house Test
on
(26/03/2014)

In-house Test
In-house Test In-house Test
on
on (8/07/2014) on (28/08/2014)
(14/06/2014)

17

16

16

15

10

12

12

10

30

34

30

29

19

17

17

16

11

12

13

11

32

35

33

30

1117

1160

1058

1103

1032

1052

1028

1069

893

906

874

827

0.8

0.8

0.8

0.8

0.7

0.8

0.8

0.7

0.6

0.6

0.6

0.7

16

16

16

16

11

11

11

11

18

20

32

36

36

35

In-house Test on
(28/08/2014)

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

100 MVA TR-01 (132 kV Side)


R-Phase

Y-Phase

100 MVA TR-01 (220 kV Side)

B-Phase

R-Phase

67
27

30

30
35

7
30

10
54
10
11
11

31

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

B-Phase

43

44

34

Y-Phase

In-house Test on
(03/07/2013)

12
11
10

10
10
10

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

21
32

23

8
9
4

In-house Test on
(28/08/2014)

22
25

18

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

16

19

12
13

19

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

132 kV Make - ELPRO

198 kV Make - CGL

100 MVA TR-01 (132 kV Side)

100 MVA TR-01 (220 kV Side)

Phase

Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
In-house Test on In-house Test on In-house Test on In-house Test on
on
(07/01/2014)
(26/03/2014)
(14/06/2014)
(28/08/2014)
(03/07/2013)

32

23

34

12

17

43

26

25

29

26

22

43

34

31

54

11

10

10

23

Test by Shanthala on
(04/12/2010)

Test by ABB on In-house Test on


(24/07/2012)
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

20

18

18

18

40

25

12

21

18

25

13

19

44

35

10

11

10

11

30

32

22

12

19

27

30

67

10

10

12

43

30

16

21

878

633

460

656

686

724

646

824

1060

996

819

942

862

617

638

613

653

660

633

739

891

886

727

847

754

635

698

637

677

674

600

789

920

968

831

954

0.2

0.3

0.3

0.4

0.5

0.6

0.6

0.7

0.4

0.4

0.4

0.4

0.4

0.6

0.5

0.6

0.2

0.2

0.2

0.2

0.4

0.8

0.7

0.8

Counters

Ambient

36

26

22

34

36

38

36

27

22

34

In-house Test on
(14/06/2014)

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

16

16

13

14

15

14

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

14

13

13

14

15

16

15

14

13

14

16

16

898

888

790

806

885

878

0.6

0.7

0.5

0.6

0.8

0.7

10

36

37

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

100 MVA TR-02 (132 kV Side)


R-Phase

Y-Phase

100 MVA TR-02 (220 kV Side)

B-Phase

R-Phase

Y-Phase

43

49

9
60

29

29
48

16

37
11
11
9

10
9
5

21

16
Test by Shanthala on
(04/12/2010)

28

13

33

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

9
11
10
In-house Test on
(26/03/2014)

10
9
10
In-house Test on
(14/06/2014)

9
9
6

16
16

13

In-house Test on
(28/08/2014)

Test by Shanthala
on (04/12/2010)

Test by ABB on
(24/07/2012)

14

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

132 kV Make - ELPRO

198 kV Make - CGL

100 MVA TR-02 (132 kV Side)

100 MVA TR-02 (220 kV Side)

Phase

Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
In-house Test
In-house Test
In-house Test
on
on (07/01/2014) on (26/03/2014) on (14/06/2014)
(03/07/2013)

16

16

In-house Test
on
(28/08/2014)

Test by
Shanthala on
(04/12/2010)

30

16

11

Test by ABB on In-house Test on In-house Test on


(24/07/2012)
(03/07/2013)
(07/01/2014)

35

37

32

15

27

12

28

37

39

26

10

16

21

10

10

13

33

16

14

37

48

11

11

60

16

28

16

29

49

10

11

10

43

29

13

859

621

649

625

662

669

599

761

917

962

805

872

601

633

619

641

657

591

750

953

957

794

864

617

662

636

668

654

650

786

948

1030

862

0.1

0.2

0.2

0.2

0.5

0.8

0.6

0.6

0.5

0.3

0.2

0.4

0.4

0.5

109

109

599

599

599

599

599

125

125

406

409

37

35

22

34

36

38

36

34

23

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

02 (220 kV Side)
Y-Phase

B-Phase

25

13

18

24

16
19

14
In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

22

17

17

14

16

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

198 kV Make - CGL


MVA TR-02 (220 kV Side)
In-house Test on In-house Test on
(26/03/2014)
(14/06/2014)

In-house Test on
(28/08/2014)

19

13

16

23

16

16

24

17

21

19

14

16

24

17

17

25

18

22

938

889

880

893

855

843

1003

956

969

0.7

0.7

0.7

0.6

0.6

0.6

0.1

0.1

109

109

109

125

125

156

409

409

1190

34

36

36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


20/25 MVA TR-01
R-Phase

Y-Phase

B-Phase

52

59

63

10
7
34

11
17
21

13
14
12

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

16
16
19

13
17
19
In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

132 kV Make - ELPRO


20/25 MVA TR-01
Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(07/01/2014)

In-house Test
on
(26/03/2014)

In-house Test
on
(14/06/2014)

25

47

12

12

14

44

10

10

11

12

39

10

12

34

63

12

21

19

19

59

14

17

17

16

10

52

13

11

13

16

688

865

782

794

866

842

412

776

765

737

770

793

551

784

773

754

798

813

0.5

0.3

0.5

0.4

0.8

0.3

0.5

0.6

0.5

0.3

0.5

0.6

299

299

299

299

149

149

149

149

2892

2892

2892

2892

34

35

26

37

37

Phase

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

10
14
16
In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
12
10
8
16
14
10
843
771
763
0.5
0.8
0.5
299
149
2892
36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT


REPORT
20/25 MVA TR-02
R-Phase

Y-Phase

B-Phase

43

52

11
23

39

17

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

13
16
15

11
15
15

13
14
13

10
13
11

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

132 kV Make - ELPRO


20/25 MVA TR-02
Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(07/01/2014)

In-house Test
on
(26/03/2014)

In-house Test
on
(14/06/2014)

14

32

10

11

19

37

10

10

12

32

10

17

39

11

13

15

15

23

52

13

14

15

16

11

43

10

13

11

13

721

803

812

814

825

833

945

759

781

767

780

815

742

865

898

861

905

870

0.5

0.3

0.5

0.6

0.5

0.5

0.6

0.6

0.5

0.5

0.5

0.6

299

299

299

299

12

12

12

12

33

33

33

33

33

36

26

37

37

Phase

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT


REPORT

11
15
13
In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
9
11
8
13
15
11
765
772
803
0.5
0.7
0.6
299
12
33
37

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


20/25 MVA TR-03
R-Phase

Y-Phase

B-Phase

51

21
30
47

0
Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

29
22
39

In-house Test on
(03/07/2013)

13
12
8

25

21

15
12

11

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

120 kV Make - ELPRO


20/25 MVA TR-03
Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(07/01/2014)

In-house Test
on
(26/03/2014)

In-house Test
on
(14/06/2014)

NA

44

29

NA

28

22

10

16

11

NA

47

16

10

17

18

NA

47

39

11

12

NA

30

29

12

21

15

NA

51

21

13

22

25

NA

765

496

805

832

839

NA

767

544

788

836

782

NA

700

640

811

867

835

NA

0.1

0.3

0.3

0.2

NA

0.3

0.5

0.6

0.6

NA

0.2

0.4

0.5

0.5

NA

372

372

372

372

NA

1839

1839

1839

1839

NA

1088

1089

1089

1089

NA

33

37

26

37

37

Phase

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

4
12
10
In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
7
12
3
10
12
4
749
642
789
0.4
0.5
0.5
372
1839
1089
37

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


20/25 MVA TR-04
R-Phase

Y-Phase

B-Phase

32
127

227

0
Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

13
2
6
In-house Test on
(03/07/2013)

14
13
13

10
12
12

8
9
9
In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

120 kV Make - ELPRO


20/25 MVA TR-04
Test by
Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(07/01/2014)

In-house Test
on
(26/03/2014)

In-house Test
on
(14/06/2014)

NA

198

10

NA

112

10

NA

29

10

NA

227

12

13

NA

127

12

13

NA

32

13

10

14

NA

425

778

783

791

803

NA

678

698

770

788

767

NA

756

783

780

788

801

NA

0.5

0.5

0.5

0.6

NA

0.5

0.1

0.5

0.4

NA

0.5

0.5

0.5

0.4

NA

399

399

399

399

NA

470

470

470

470

NA

NA

30

38

26

37

37

Phase

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

10
7
7
In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
5
5
11
7
7
10
782
748
818
0.6
0.7
0.6
399
470
0
37

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


30/35 MVA Unit-09
R-Phase

Y-Phase

B-Phase

7
4

0
Test by Shanthala on
(04/12/2010)

0
Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

120 kV Make - OBLUM


30/35 MVA Trafo (Unit-09)
Phase

Counters

Ambient

Test by ABB In-house Test In-house Test In-house Test In-house Test In-house Test
on
on
on
on
on
on
(24/07/2012) (03/07/2013) (07/01/2014) (26/03/2014) (14/06/2014) (28/08/2014)

955

860

964

1009

938

931

860

943

970

928

947

844

963

1112

932

0.5

0.4

0.45

0.45

0.45

0.4

0.3

0.4

0.4

0.4

0.3

0.3

0.35

0.35

0.35

1349

1349

1349

1349

1349

58

58

58

58

58

1093

1093

1093

1093

1093

29

19

33

36

36

Y
B

mA

Test by
Shanthala on
(04/12/2010)

35 MVA Trafo not


commissioned at the time of
testing

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


30/35 MVA Unit-10
Series1

0
Test by Shanthala on
(04/12/2010)

0
Test by ABB on
(24/07/2012)

0
In-house Test on
(03/07/2013)

0
In-house Test on
(07/01/2014)

Series2

Series3

0
In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(8/07/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

120 kV Make - OBLUM


30/35 MVA Trafo (Unit-10)
Phase

Test by
Shanthala on
(04/12/2010)

Test by ABB In-house Test In-house Test In-house Test In-house Test In-house Test
on
on
on
on
on
on
(24/07/2012) (03/07/2013) (07/01/2014) (26/03/2014) (14/06/2014) (8/07/2014)

999

952

981

956

976

946

0.4

0.4

0.4

0.4

36

36

Y
35 MVA Trafo not commissioned at the time of testing

mA

Counters

Ambient

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

5
6

In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
5
6
5
5
6
5
900
943
926
0.1
0.4
0.4
5
5
7
36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


132 kV Tie Line (220 kV SWYD)

132 kV Tie Line (132 kV SWYD)


R-Phase

Y-Phase

R-Phase

B-Phase

47

40

46

10
14
10

9
10
10

10
Test by Shanthala
on (04/12/2010)

Test by ABB on
(24/07/2012)

B-Phase

50

55

13
29

Y-Phase

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

64

10
24

13
17
11

12
17
11

9
14
10

In-house Test on
(28/08/2014)

Test by Shanthala on
(04/12/2010)

9
10
8

9
8
9

25
Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

8
10
9

In-house Test on
(07/01/2014)

9
9
8

8
8
7

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating

Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

Phase

Test by Shanthala Test by ABB on


on (04/12/2010)
(24/07/2012)

132 kV Make - ELPRO

132 kV Make - ELPRO

132 kV Tie Line (132 kV SWYD)

132 kV Tie Line (220 kV SWYD)

In-house Test
on
(03/07/2013)

In-house Test
In-house Test
In-house Test
In-house Test
on
on (26/03/2014) on (14/06/2014) on (28/08/2014)
(07/01/2014)

Test by
Shanthala on
(04/12/2010)

Test by ABB on In-house Test on In-house Test on In-house Test on In-house Test on
(24/07/2012)
(03/07/2013)
(07/01/2014)
(26/03/2014)
(14/06/2014)

In-house Test on
(28/08/2014)

44

24

85

24

53

10

11

13

13

23

36

10

45

10

10

46

10

46

10

10

10

11

11

25

64

29

55

10

14

14

17

17

24

40

10

10

13

47

10

12

13

10

50

780

811

677

750

714

751

701

805

860

607

516

560

554

596

817

831

588

659

626

647

615

801

801

554

572

469

475

530

764

790

642

676

667

715

654

815

794

562

578

543

505

551

0.3

0.3

0.4

0.2

0.6

0.3

0.5

0.3

0.2

0.3

0.2

0.3

0.3

0.2

0.4

0.2

0.2

0.1

0.3

0.1

0.3

0.3

0.2

0.3

0.2

0.2

0.2

0.1

0.2

34

35

24

37

36

36

32

37

18

29

36

36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


220 kV Merta Line
R-Phase

Y-Phase

B-Phase

28
98

42
26

54

29

22
20

21
Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

19
22
19

13
15
13
In-house Test on
(07/01/2014)

15
16
16

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating
Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

198 kV Make - CGL


220 kV Merta Line
In-house Test In-house Test
on
on
(03/07/2013) (07/01/2014)

In-house Test
on
(26/03/2014)

In-house Test
on
(14/06/2014)

10

19

15

20

11

23

16

26

24

19

15

21

54

20

13

19

16

29

98

22

15

22

16

42

28

26

13

19

15

766

1025

988

821

963

907

756

910

819

734

851

796

778

944

964

808

939

870

0.6

0.5

0.6

0.6

0.6

0.4

0.5

0.5

0.8

0.6

0.7

0.7

36

34

23

34

36

Phase

Test by Shanthala
on (04/12/2010)

Test by ABB on
(24/07/2012)

18

51

18

26

91

25

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

13
14
15
In-house Test on
(28/08/2014)

In-house Test
on
(28/08/2014)
15
14
13
15
14
13
893
730
800
0.6
0.4
0.7
10
9
6
36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


220 kV Beawar Line
R-Phase

Y-Phase

B-Phase

78

47
32

35

59

29

26

19
22

20
16
22

32

Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

21
17
24

24
32
In-house Test on
(26/03/2014)

21
17
24

In-house Test on
(14/06/2014)

In-house Test on
(14/06/2014)

Ir (Corr.) Limit: 100 A


LA Rating
Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

198 kV Make - CGL


220 kV Beawar Line
In-house Test In-house Test
on
on
(07/01/2014) (26/03/2014)

Phase

Test by Shanthala
on (04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test
on
(03/07/2013)

In-house Test
on
(14/06/2014)

20

54

30

17

32

22

10

44

24

12

25

16

19

72

32

16

29

20

22

59

32

22

32

24

19

47

26

16

24

17

32

78

35

20

29

21

721

926

849

715

823

781

776

935

865

758

882

801

743

857

828

713

829

791

0.5

0.5

0.6

0.6

0.6

0.5

0.6

0.6

0.6

0.4

0.6

0.6

14

14

14

14

36

34

24

34

36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT

21
17
24

22
17
23

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

In-house Test
on
(14/06/2014)

In-house Test
on
(28/08/2014)

22

24

16

18

20

22

24

23

17

17

21

22

781

775

801

825

791

754

0.6

0.6

0.6

0.6

0.6

0.6

14

14

36

36

LIGHTNING ARRESTOR LEAKAGE CURRENT MEASUREMENT REPORT


Ras-Bwr 132 kV Line
R-Phase

Y-Phase

B-Phase

48

17
23

26

23
0
Test by Shanthala on
(04/12/2010)

Test by ABB on
(24/07/2012)

17

10
4
28

In-house Test on
(03/07/2013)

9
11
11
In-house Test on
(07/01/2014)

33

9
10
10

7
11
9
In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

Ir (Corr.) Limit: 100 A


LA Rating
Parameters

Ir (A)

Ir(corr.) (A))

Itotal (A)

mA

Counters

Ambient

132 kV Make - ELPRO


Ras_Bwr 132 kV Line
Phase

Test by Shanthala
on (04/12/2010)

Test by ABB on
(24/07/2012)

In-house Test on
(03/07/2013)

In-house Test on
(07/01/2014)

In-house Test on
(26/03/2014)

In-house Test on
(14/06/2014)

In-house Test on
(28/08/2014)

24

19

25

21

12

18

44

12

26

28

11

10

33

23

11

11

10

17

23

48

10

17

81

690

382

645

662

569

766

63

652

603

651

650

693

861

672

895

588

688

681

741

882

0.2

0.5

0.4

0.2

0.5

0.4

0.4

0.3

0.2

0.5

0.3

0.4

0.3

0.2

0.4

34

32

24

37

36

36

También podría gustarte