Design of two-way slab

Panel No = S1
Input data: ACI Moment Coefficients
Case No = 9
la = 16 ft m = 0.65
lb = 25 ft Ca
neg
= 0.083
f'c = 3 ksi Cb
neg
= 0.008
fy = 40 ksi Ca
dl
= 0.028
DL add = 0.035 k/ft
2
Cb
dl
= 0.005
LL = 0.06 k/ft
2
Ca
ll
= 0.540
h, cal = 5.47 in Cb
ll
= 0.009
h, used = 6 Wa = 0.920
Wb = 0.080
Loads Calculation: Moments Calculation:
DL wu = 0.154 k/ft
2
Ma(-ve) = 65.27 k-in
LL wu = 0.102 k/ft
2
Mb(-ve) = 15.36 k-in
TL wu = 0.256 k/ft
2
Ma(+ve) = 182.45 k-in
Mb(+ve) = 12.66 k-in
Steel Calculation:
d
a
= 5 in Moments As
req
#4(in c/c)#3(in c/c)
d
b
= 4.75 in Ma(-ve) 0.382 6.3 3.5
b
1
= 0.85 Mb(-ve) 0.144 12 9.2
As
max
= 1.587 in
2
Ma(+ve) 1.203 2 1.1
As
min
= 0.144 in
2
Mb(+ve) 0.144 12 9.2
S
max
= 12
Load Transfer:
Load Transfer To Longer Beam = 1.884 k/ft
Load Transfer To Shorter Beam = 0.256 k/ft