DESCRIPTION
ASHRAE 90.1 COMPLIANT
YORK

Predator heat pump units are convertible single pack-
ages with a common footprint cabinet and common roof curb for
all 7-1/2 through 10 ton models. The units were designed for
light commercial applications and can be easily installed on a roof
curb, slab, or frame.
All Predator heat pump units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift access
and overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow. Indepen-
dent economizer designs are used on side and down discharge
applications, as well as all tonnage sizes.
RETURN HOME
Unitary Products Group 2
B P 120 C 00 A 7 A AA 1 A
TABLE 1: PRODUCT NOMENCLATURE
Model #
Model Number
Description
Options
B Product Category B = Single Package Heat Pumps
P Product Identifier P = High Efficiency
120
Nominal Cooling Capacity
MBH
090 = 7-1/2 Ton 120= 10 Ton
C Heat Type C = Cooling Only
00
Nominal Heating
Capacity
00 = No Heat Installed
A Airflow
A = SM
B = SM/EC/BR
C = SM/EC/PE
D = SM/MD
N = High Static Motor
P = High Static Motor/EC/BR
Q = High Static Motor/EC/PE
R = High Static Motor/MD
7 Voltage 7 = 380/415-3-50
A Installation Options
A= None
B = 1
C = 2
D = 1 & 2E = 3
F = 4
G = 1 & 3
H = 1 & 4
J = 1, 2 & 3
K = 1, 2 & 4
L = 1, 3 & 4
M = 1, 2, 3 & 4
N = 2 & 3
P = 2 & 4
Q = 2, 3 & 4
R = 3 & 4
AA Additional Options
AA = None
AB = PM
AC = CG
AD = DFS
AE = PM & CG
AF = PM & DFS
AG = CG & DFS
AH = PM, CG & DFS
RC = CG & AM
TA = TCC
TB = TCC & PM
TC = TCC & CG
TD = TCC & DFS
TE = TCC, PM & CG
TF = TCC, PM & DFS
TG = TCC, CG & DFS
TH = TCC, PM, CG & DFS
1 Product Generation 1 = First Generation
A Product Style A = Style A
TABLE 2: AIRFLOW ABBREVIATIONS
ABBREVIATION MEANING
BR Barometric Relief
EC Economizer
MD Motorized Damper
PE Power Exhaust
SM Standard Motor
TABLE 3: INSTALLATION ABBREVIATIONS
ABBREVIATION MEANING
1 Disconnect
2 Convenience Outlet
3 Smoke Detector Supply Air
4 Smoke Detector Return Air
TABLE 4: ADDITIONAL OPTIONS ABBREVIATIONS
ABBREVIATION MEANING
AM American Flag
CG Coil Guard
DFS Dirty Filter Switch
PM Phase Monitor
TCC Technicoat Condenser Coil
Unitary Products Group 3
FEATURES
High Efficiency High efficiency units reach as high as
10.7 EER.
Service Friendly The Predator incorporates a num-
ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged, tool-
less panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unautho-
rized persons. It is recommended that the panels be
secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
The unit control board utilizes flash codes to aid in diag-
nosis of unit malfunctions. Unique flash codes quickly
identify the source of the unit alarm.
All units use the same standard filter size. This stan-
dardization removes any confusion on which filter sizes
are needed for replacement.
The non-corrosive drain pan slides out of the unit to per-
mit easy cleaning. The drain pan is accessed by remov-
ing the drain pan cover plate on the rear of the unit.
FIGURE 1 : PREDATOR COMPONENT LOCATION
Compressor #1 Access
(High-Eff Compressor)
Tool-less
Door Latch
Side entry power
and control wiring
knockouts
Slide-out drain pain
with steel 3/4 FPT
Connection
Belt-drive
blower
motor
Condenser
section
Filter drier (solid core)
Filter access
(2 throw-away)
Disconnect location
(optional disconnect switch)
Compressor #2
Access (High-Eff
Compressor)
Simplicity
TM
Control
board w/screw connec-
tors for T-stat wiring and
network connection
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
Sunline footprint to the
BP series footprint are also
available (field installed
accessory)
ase Rails w/ Fork-
ift Slots (3 Sides)
Lifting Holes
Terminal block
for hi-voltage
connection
Dual stage cool-
ing for maximum
comfort (7-1/2 -
10 Only)
Second Model
Nameplate Inside
Control Door
Slide-out motor and
blower assembly for
easy adjustment and
service.
4 Unitary Products Group
Once the plate is removed, the drain pan slides out
through the rear of the unit.
All Predator units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
Environmentally Aware For improved Indoor Air
Quality, foil faced insulation is used exclusively through-
out the units.
Convertible Airflow Design The side duct openings
are covered when they leave the factory. If a side sup-
ply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
System Protection Suction line freezestats are sup-
plied on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and
low-pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compres-
sors do not require crankcase heaters.
Advanced Controls - Predator control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heating.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats and
the temperature limit switch on electric heat units.
The unit control board will alarm on compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
three times, youre out philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
Reliable From the beginning All units undergo com-
puter automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. All Predator units
are painted with a long lasting, powder paint that stands
up over the life of the unit. The paint used has been
proven by a 750 hour salt spray test.
Flexible Placement All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size after the internal loads have
been determined.
To further simplify planning and installation, Predator
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24
on-center joists or between 48 on-center joists.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
Full Perimeter Base Rails The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer fork-
lift access from 3 sides, and rigging holes are available
so that an overhead crane can be used to place the units
on a roof.
Easy Installation Electric utility knockouts are sup-
plied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections
can be made quickly and with a minimum amount of field
labor.
All units are shipped with 2 throw-away filters installed.
Wide Range of Indoor Airflows All indoor fan motors
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units can
supply nominal airflow at up to 1.5 ESP.
Unitary Products Group 5
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty.
FACTORY INSTALLED OPTIONS
YORK

offers several equipment options/accessories factory


installed, for the Predator

line.
Alternate Indoor Blower Motor - For applications with
high restrictions, units are offered with optional indoor
motors that provide higher static output and/or higher air-
flow, depending upon the installers needs.
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
Convenience Outlet - (Non-Powered) - This option
locates a 120V GFCI single-phase outlet with cover on
the corner of the unit housing the compressors. The
installer must provide the 120V single-phase power
source and wiring. Factory installed option only.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
Disconnect Switch - For gas heat units, a HACR
breaker sized to the unit is provided. For cooling units
with electric heat, a switch sized to the largest electric
heat available for the particular unit is provided. Factory
installed option only.
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizers
are shipped installed and wired. The installer needs only
assemble and mount the outdoor air hood. The econo-
mizer has spring return, fully modulating damper actua-
tors and is capable of introducing up to 100% outdoor air.
As the outdoor air intake dampers open, the return air
dampers close. The changeover from mechanical refrig-
eration to economizer operation is regulated by the stan-
dard single enthalpy input. There is an optional input
dual dry bulb available. To meet regulated air standards,
the economizer control accepts an optional CO
2
input for
demand ventilation.
With single enthalpy input, the economizer control moni-
tors outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
Sideflow Economizer - (Without barometric relief) - All
features as the downflow economizer exist except you
must order the barometric relief separately. You must
order a 1EH0408 if you are installing a power
exhaust. You can order a 1RD0411 Barometric Relief
kit for sideflow economizer only.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer. Power
exhaust plugs into the connector in the unit bulkhead.
Phase Monitors - This accessory monitors the incoming
power to the unit and protects the unit from phase loss
and reversed phase rotation (Standard on units with
scroll compressors).
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
Stainless Steel Heat Exchanger - For applications in
corrosive environments, this option provides a full stain-
less steel heat exchanger assembly.
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coil is
coated with a phenolic coating for protection against
harsh environments.
Novar BAS Control - The Novar ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
BAS Ready Economizer - The economizer is provided
with a Belimo actuator that requires a 0-10V DC input
from an external source (i.e., field installed building auto-
mation system controller). Barometric relief or power
6 Unitary Products Group
exhaust options are available. The economizer is 2% low
leakage type with spring return and fully modulating
dampers capable of introducing up to 100% outside air.
Also include 2 pleated filters.
FIELD INSTALLED ACCESSORIES
YORK offers several equipment options/accessories for
field installation, for the Predator

Magnum line.
Barometric Relief - Zero to 100% capacity barometric
relief damper for use with sideflow economizer.
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
CO
2
Sensor - Senses CO
2
levels and automatically
overrides the economizer when levels rise above the
preset limits.
Coil Guard - Field installed decorative wire coil guard.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters.
Enthalpy Accessory Control Kit - This kit contains the
required components to convert a single enthalpy econo-
mizer to dual enthalpy.
Economizer (Downflow with barometric relief) - Econo-
mizer with relief damper and single enthalpy input (2%
low leakage damper).
Spring return fully modulating motor capable of introduc-
ing up to 100% outside air. For power exhaust, add the
power exhaust accessory.
Economizer (Horizontal) - Horizontal economizers are
designed to install in the lower return section on the side
of the unit. It is specifically designed for horizontal return
applications. A 1EH0408 barometric relief/power
exhaust hood must be purchased separately. You
may also order a 1RD0411 Barometric Relief if a
power exhaust isnt being installed. The horizontal
economizer is available with standard single enthalpy
control. Dual enthalpy may be added by installing the
dual enthalpy kit.
Electric Heaters - The electric heaters range from 18
kW to 54kW and are available in all the voltage options
of the base units. All heaters are dual staged. Cooling
units include an adapter panel for easy installation of the
electric heaters. Necessary hardware and connectors
are included with the heaters. All heaters are intended
for single point power supply.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when
applying to a sideflow application.
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8 and 14 heights.
For applications with security concerns, burglar bars are
available for the duct openings of the roof curbs.
Roof Curb Adaptor Single Piece Adapter (10 High) -
Roof curbs for transitioning from Sunline units to Pred-
ator Magnum. Fits 7.5 to 12.5 Sunline roof curbs
only.
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
Unitary Products Group 7
TABLE 5: ACCESSORIES
Part Number Description
1RC0470 Roof Curb, 8" Height
1RC0471 Roof Curb, 14" Height
1RC0472
Roof Curb, Adapter (6-1/2 ton through
12-1/2 ton) (1 Piece)
2TP04510925 Electric Heat 9kW 230V
2TP04511825 Electric Heat 18kW 230V
2TP04512425 Electric Heat 24kW 230V
2TP04513625 Electric Heat 36kW 230V
2HP04505425 Electric Heat 54KW 230V (10 ton only)
2HP04515425 Electric Heat 54kW 230V (12-1/2 ton only)
2TP04510946 Electric Heat 9kW 460V
2TP04511846 Electric Heat 18kW 460V
2TP04512446 Electric Heat 24kW 460V
2TP04513646 Electric Heat 36kW 460V
2HP04515446 Electric Heat 54kW 460V
2TP04510958 Electric Heat 9kW 575V
2TP04511858 Electric Heat 18kW 575V
2TP04512458 Electric Heat 24kW 575V
2TP04513658 Electric Heat 36kW 575V
2HP04515458 Electric Heat 54kW 575V
1FA0411 Manual Outside Damper 6.5-12.5 T 0-35%
1FA0412 Manual Outside Damper 6.5-12.5 T 0-100%
2MD04702724
Motorized Damper Accessory
(6-1/2 ton to 12-1/2 ton)
2EE04705124
Economizer Downflow Accy
6-1/2 - 12-1/2T w/ Baro Relief (124 LBS)
2PE04703246 Power Exhaust Accy 6-1/2 - 12-1/2T 460V
2PE04703258 Power Exhaust Accy 6-1/2 - 12-1/2T 575V
2PE04703225 Power Exhaust Accy 6-1/2 - 12-1/2T 230V
2EC04700924 Dual Enthalpy Control Accy
1EH0407 Power Exhaust Hood with Barometric Relief Downflow (25 LBS)
1EH0408 Power Exhaust (Duct Mount) Hood w/Barometric Relief (Sideflow)
1RD0411 Barometric Relief (Duct Mount for Sideflow)
2EE04700514
Economizer, Sideflow Accessory without Barometric Relief (6-1/2T to
12-1/2T) (97 LBS)
2AQ04700424 Sensor, CO2 Duct Accessory
2AQ04700324 CO2 Space Accessory
2SD04700224 Sensor, Duct Smoke Detector Accy for Supply or Return
2DF0401 Dirty Filter Switch
1CG0419
Coil Guard (3 Pieces for
Electric / Electric / Heat Pump)
1BD0408 Burglar Bars
1HG0411 Hail Guard Kit
1FL0402 Permanent Filter Kit
2ET0770010024 Programmable Thermostat 2H, 2C
2ET0770010124 Non-programmable Thermostat 2H, 2C
TABLE 6: PHYSICAL DATA
Component
Models
090 120
Evaporator Blower
Blower, Centrifugal Dia. X Wd. in. (Dia. X Wd. mm) 15 x 15 (381 x 381) 15 x 15 (381 x 381)
Motor, Standard HP (kW) 1-1/2 (1.1) 2 (1.5)
Motor, Optional HP (kW) 2 (1.5) 4 (3)
Evaporator Coil
Rows 3 4
Fins per Inch (2.54 cm.) 15 15
Height in. (mm) 40 (1020) 40 (1020)
Face Area ft.
2
each (m
2
)
13.2 (1.23) 13.2 (1.23)
Condenser Fan
(2 per Unit)
Propeller Dia. in., each (mm) 24 (610) 24 (610)
Motor HP, each (kW) 3/4 (.56) 3/4 (.56)
CFM, Nominal (each) 4000 4000
Condenser Coil
(2 per unit)
Rows (each) 1 2
Fins per Inch (2.54 cm) 20 20
Height in., each (mm) 44 (1120) 44 (1120)
Face Area ft.
2
each (mm)
14.5 (1.35) 14.5 (1.35)
Refrigerant
Charge
System 1 lb./oz. (kg) 9 lbs. 4 oz. (4.20) 15 lbs. 12 oz. (7.14)
System 2 lb./oz. (kg) 9 lbs. 0 oz. (4.06) 16 lbs. 8 oz. (7.48)
Compressors
Quantity 2 2
Type Recip Recip
Air Filters
Size Wd. x Ht. x Thickness in. (Wd. x Ht x Thickness mm)
25x20x2
(635 x 508 x 51)
25x20x2
(635 x 508 x 51)
Number Per Unit 4 4
TABLE 7: COOLING CAPACITY 7-1/2 TON UNIT
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (F): 85 OUTDOOR AMBIENT TEMPERATURE (F): 95
W.B. GROSS
*
INPUT Sensible Capacity (MBH) GROSS
*
INPUT Sensible Capacity (MBH)
CFM TEMP CAP. POWER

Return Dry Bulb (F) CAP. POWER

Return Dry Bulb (F)


(F) (MBh) (kW) 86 83 80 77 74 71 68 (MBh) (kW) 86 83 80 77 74 71 68
2250 72 109,0 8,71 61,0 54,6 48,2 41,7 35,3 103,6 9,41 58,2 51,8 45,4 39,0 32,5
67 98,4 8,36 74,4 68,0 61,6 55,2 48,8 42,4 35,9 92,1 8,94 72,1 65,7 59,3 52,9 46,5 40,1 33,6
62 89,2 8,02 87,8 81,3 74,9 68,5 62,1 55,7 49,3 83,4 8,60 83,4 79,1 72,7 66,2 59,8 53,4 47,0
57 94,9 7,97 93,3 86,8 80,4 74,0 67,6 61,2 54,8 84,2 8,55 84,2 81,7 75,3 68,8 62,4 56,0 49,6
2625 72 111,9 8,81 66,8 59,2 51,6 44,0 36,5 106,2 9,51 63,9 56,3 48,7 41,2 33,6
67 101,0 8,45 81,2 73,6 66,0 58,5 50,9 43,3 35,7 94,4 9,03 78,9 71,3 63,7 56,1 48,5 41,0 33,4
62 91,6 8,11 90,9 87,7 80,3 72,7 65,2 57,6 50,0 85,4 8,69 85,4 83,3 78,0 70,5 62,9 55,3 47,7
57 97,4 8,06 96,6 93,4 86,2 78,6 71,1 63,5 55,9 86,3 8,64 86,3 85,1 80,8 73,3 65,7 58,1 50,5
3000 72 114,8 8,90 72,6 63,8 55,1 46,3 37,6 108,8 9,61 69,6 60,8 52,1 43,4 34,6
67 103,6 8,54 88,0 79,2 70,5 61,7 53,0 44,2 35,5 96,7 9,13 85,6 76,8 68,1 59,3 50,6 41,8 33,1
62 94,0 8,20 94,0 94,0 85,7 77,0 68,2 59,5 50,7 87,5 8,78 87,5 87,5 83,4 74,7 65,9 57,2 48,4
57 99,9 8,14 99,9 99,9 92,0 83,3 74,5 65,8 57,0 88,4 8,73 88,4 88,4 86,4 77,7 68,9 60,2 51,4
3375 72 117,3 8,95 77,8 67,9 57,9 47,9 38,0 111,7 9,69 74,9 64,9 55,0 45,0 35,0
67 105,9 8,58 94,0 84,0 74,1 64,1 54,1 44,2 34,2 99,4 9,21 91,8 81,8 71,8 61,9 51,9 41,9 32,0
62 96,0 8,23 96,0 96,0 90,1 80,1 70,1 60,2 50,2 89,9 8,86 89,9 89,9 87,9 77,9 67,9 58,0 48,0
57 102,1 8,18 102,1 102,1 96,7 86,7 76,8 66,8 56,8 90,9 8,80 90,9 90,9 89,8 79,9 69,9 59,9 50,0
3750 72 119,7 8,99 83,0 71,9 60,7 49,5 38,3 114,7 9,77 80,2 69,0 57,8 46,6 35,5
67 108,1 8,62 100,0 88,8 77,6 66,5 55,3 44,1 32,9 102,0 9,29 97,9 86,8 75,6 64,4 53,2 42,0 30,9
62 98,1 8,27 98,1 98,1 94,4 83,3 72,1 60,9 49,7 92,3 8,93 92,3 92,3 92,3 81,1 70,0 58,8 47,6
57 104,2 8,22 104,2 104,2 101,4 90,2 79,0 67,8 56,7 93,3 8,88 93,3 93,3 93,3 82,1 70,9 59,7 48,5
OUTDOOR AMBIENT TEMPERATURE (F): 105 OUTDOOR AMBIENT TEMPERATURE (F): 115
2250 72 101,0 10,15 59,6 53,2 46,8 40,3 33,9 98,5 10,89 61,0 54,6 48,1 41,7 35,3
67 87,9 9,64 73,7 67,3 60,9 54,5 48,1 41,6 35,2 83,7 10,35 75,3 68,9 62,5 56,1 49,6 43,2 36,8
62 78,9 9,24 78,9 76,7 73,5 67,1 60,7 54,3 47,9 74,4 9,89 74,4 74,4 74,4 67,9 61,5 55,1 48,7
57 79,1 9,20 79,1 77,8 74,6 68,2 61,8 55,4 48,9 73,9 9,86 73,9 73,9 73,9 67,5 61,1 54,7 48,3
2625 72 102,5 10,20 63,6 56,0 48,5 40,9 33,3 98,7 10,89 63,3 55,8 48,2 40,6 33,0
67 89,2 9,69 78,3 70,7 63,1 55,5 47,9 40,4 32,8 84,0 10,35 77,7 70,1 62,5 54,9 47,4 39,8 32,2
62 80,0 9,29 80,0 78,9 76,3 68,7 61,1 53,6 46,0 74,6 9,89 74,6 74,6 74,6 67,0 59,4 51,8 44,2
57 80,2 9,25 80,2 79,6 77,5 69,9 62,3 54,7 47,2 74,2 9,86 74,2 74,2 74,2 66,6 59,0 51,4 43,8
3000 72 103,9 10,25 67,7 58,9 50,2 41,4 32,7 99,0 10,89 65,7 57,0 48,2 39,5 30,7
67 90,5 9,74 82,8 74,1 65,3 56,6 47,8 39,1 30,3 84,2 10,35 80,1 71,3 62,6 53,8 45,1 36,3 27,6
62 81,2 9,34 81,2 81,2 79,1 70,4 61,6 52,9 44,1 74,8 9,90 74,8 74,8 74,8 66,0 57,3 48,5 39,8
57 81,4 9,30 81,4 81,4 80,4 71,6 62,9 54,1 45,4 74,4 9,86 74,4 74,4 74,4 65,6 56,9 48,1 39,4
3375 72 106,0 10,32 73,2 63,2 53,3 43,3 33,3 100,3 10,96 71,5 61,6 51,6 41,6 31,7
67 92,3 9,81 87,5 79,3 69,4 59,4 49,5 39,5 29,5 85,3 10,41 83,3 76,9 66,9 57,0 47,0 37,1 27,1
62 82,8 9,41 82,8 82,8 81,8 71,9 61,9 51,9 42,0 75,8 9,95 75,8 75,8 75,8 65,8 55,8 45,9 35,9
57 83,1 9,36 83,1 83,1 82,6 72,6 62,7 52,7 42,7 75,3 9,92 75,3 75,3 75,3 65,4 55,4 45,5 35,5
3750 72 108,2 10,40 78,7 67,6 56,4 45,2 34,0 101,6 11,02 77,3 66,1 55,0 43,8 32,6
67 94,2 9,88 92,2 84,6 73,4 62,3 51,1 39,9 28,7 86,4 10,47 86,4 82,5 71,3 60,1 49,0 37,8 26,6
62 84,5 9,47 84,5 84,5 84,5 73,4 62,2 51,0 39,8 76,8 10,01 76,8 76,8 76,8 65,6 54,4 43,2 32,0
57 84,8 9,43 84,8 84,8 84,8 73,6 62,4 51,3 40,1 76,3 9,98 76,3 76,3 76,3 65,1 54,0 42,8 31,6
*
These capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW.
Refer to the appropriate Blower Perfomance Table for the kW of the supply blower motor.
These ratings include condenser fan motors and the compressor motors but not the supply air blower motor.
TABLE 8: COOLING CAPACITY 10 TON UNIT
RETURN AIR OUTDOOR AMBIENT TEMPERATURE (F): 85 OUTDOOR AMBIENT TEMPERATURE (F): 95
W.B. GROSS
*
INPUT Sensible Capacity (MBH) GROSS
*
INPUT Sensible Capacity (MBH)
CFM TEMP CAP. POWER

Return Dry Bulb (F) CAP. POWER

Return Dry Bulb (F)


(F) (MBh) (kW) 86 83 80 77 74 71 68 (MBh) (kW) 86 83 80 77 74 71 68
3000 72 132,5 10,59 80,7 72,2 63,6 55,1 46,5 128,2 11,47 77,3 68,8 60,2 51,7 43,1
67 123,2 10,29 97,9 89,3 80,8 72,2 63,7 55,1 46,6 117,4 11,03 96,0 87,5 78,9 70,4 61,8 53,3 44,7
62 114,9 9,95 114,9 108,7 100,2 91,6 83,0 74,5 65,9 110,5 10,73 110,5 104,5 95,9 87,3 78,8 70,2 61,7
57 110,0 9,94 110,0 110,0 102,6 94,0 85,5 76,9 68,4 105,6 10,72 105,6 105,6 97,3 88,7 80,2 71,6 63,0
3500 72 137,3 10,70 88,1 78,0 67,9 57,8 47,7 132,6 11,57 85,0 74,9 64,8 54,7 44,5
67 127,6 10,40 106,5 96,3 86,2 76,1 66,0 55,9 45,8 121,5 11,14 105,1 95,0 84,9 74,8 64,7 54,6 44,5
62 119,1 10,05 119,1 116,0 106,9 96,8 86,7 76,6 66,5 114,3 10,82 114,3 111,3 103,2 93,1 82,9 72,8 62,7
57 114,0 10,04 114,0 114,0 109,5 99,4 89,3 79,2 69,1 109,3 10,82 109,3 109,3 104,6 94,5 84,4 74,3 64,2
4000 72 142,2 10,81 95,6 83,9 72,2 60,6 48,9 137,0 11,68 92,7 81,0 69,3 57,7 46,0
67 132,1 10,51 115,0 103,4 91,7 80,0 68,4 56,7 45,0 125,5 11,24 114,2 102,5 90,9 79,2 67,5 55,9 44,2
62 123,3 10,16 123,3 123,3 113,7 102,0 90,3 78,7 67,0 118,1 10,92 118,1 118,1 110,4 98,8 87,1 75,4 63,8
57 118,0 10,15 118,0 118,0 116,4 104,8 93,1 81,5 69,8 112,9 10,92 112,9 112,9 112,0 100,3 88,7 77,0 65,3
4500 72 145,1 10,87 103,9 90,6 77,3 64,0 50,7 140,5 11,77 100,9 87,6 74,3 61,0 47,7
67 134,8 10,57 124,7 111,4 98,2 84,9 71,6 58,3 45,0 128,7 11,33 123,0 110,7 97,4 84,1 70,8 57,5 44,3
62 125,8 10,22 125,8 125,8 121,0 107,7 94,4 81,1 67,8 121,1 11,01 121,1 121,1 117,2 104,0 90,7 77,4 64,1
57 120,4 10,21 120,4 120,4 119,6 106,3 93,0 79,8 66,5 115,7 11,01 115,7 115,7 115,3 102,0 88,7 75,4 62,2
5000 72 147,9 10,94 112,2 97,3 82,4 67,5 52,6 143,9 11,86 109,1 94,2 79,3 64,4 49,5
67 137,5 10,63 134,4 119,5 104,6 89,7 74,8 59,9 45,0 131,9 11,41 131,9 118,8 103,9 89,0 74,1 59,2 44,3
62 128,3 10,28 128,3 128,3 128,3 113,4 98,5 83,6 68,7 124,1 11,09 124,1 124,1 124,1 109,2 94,3 79,3 64,4
57 122,8 10,27 122,8 122,8 122,8 107,9 93,0 78,1 63,2 118,6 11,09 118,6 118,6 118,6 103,7 88,8 73,9 59,0
OUTDOOR AMBIENT TEMPERATURE (F): 105 OUTDOOR AMBIENT TEMPERATURE (F): 115
3000 72 121,4 12,22 74,5 65,9 57,4 48,8 40,3 114,6 12,97 71,7 63,1 54,6 46,0 37,5
67 109,6 11,71 92,6 84,0 75,5 66,9 58,4 49,8 41,3 101,9 12,38 89,1 80,6 72,0 63,5 54,9 46,3 37,8
62 103,4 11,40 103,4 100,0 91,4 82,9 74,3 65,8 57,2 96,2 12,08 96,2 95,5 86,9 78,4 69,8 61,3 52,7
57 102,0 11,44 102,0 98,4 89,9 81,4 72,8 64,2 55,7 98,3 12,16 98,3 91,1 82,6 74,0 65,5 56,9 48,3
3500 72 125,5 12,33 82,3 72,2 62,1 52,0 41,9 118,4 13,09 79,7 69,6 59,5 49,4 39,3
67 113,4 11,82 101,9 91,8 81,7 71,6 61,5 51,4 41,3 105,3 12,50 98,7 88,6 78,5 68,4 58,3 48,2 38,1
62 106,9 11,51 106,9 105,2 99,0 88,8 78,7 68,6 58,5 99,5 12,19 99,5 99,1 94,7 84,6 74,5 64,4 54,3
57 105,4 11,55 105,4 103,6 97,3 87,2 77,1 67,0 56,9 101,6 12,27 101,6 98,0 90,0 79,9 69,8 59,7 49,6
4000 72 129,6 12,45 90,2 78,5 66,9 55,2 43,5 122,2 13,22 87,7 76,1 64,4 52,7 41,1
67 117,1 11,93 111,3 99,6 87,9 76,3 64,6 52,9 41,3 108,7 12,62 108,3 96,6 85,0 73,3 61,6 50,0 38,3
62 110,4 11,61 110,4 110,4 106,5 94,8 83,2 71,5 59,8 102,7 12,31 102,7 102,7 102,6 90,9 79,2 67,6 55,9
57 108,9 11,65 108,9 108,9 104,7 93,0 81,4 69,7 58,1 104,9 12,38 104,9 104,9 97,4 85,8 74,1 62,4 50,8
4500 72 132,3 12,55 97,8 84,5 71,3 58,0 44,7 124,2 13,33 94,8 81,5 68,2 54,9 41,7
67 119,6 12,03 116,7 107,0 93,7 80,4 67,1 53,9 40,6 110,5 12,73 110,3 103,3 90,0 76,7 63,5 50,2 36,9
62 112,7 11,71 112,7 112,7 110,8 97,5 84,2 70,9 57,6 104,4 12,42 104,4 104,4 104,3 91,0 77,7 64,5 51,2
57 111,2 11,75 111,2 111,2 109,1 95,8 82,5 69,2 55,9 106,6 12,49 106,6 106,6 102,9 89,6 76,3 63,0 49,7
5000 72 135,1 12,66 105,5 90,6 75,7 60,8 45,9 126,2 13,45 101,9 87,0 72,1 57,2 42,3
67 122,0 12,13 122,0 114,4 99,5 84,6 69,7 54,8 39,9 112,2 12,84 112,2 110,0 95,1 80,2 65,3 50,4 35,5
62 115,1 11,81 115,1 115,1 115,1 100,2 85,3 70,3 55,4 106,1 12,53 106,1 106,1 106,1 91,2 76,3 61,4 46,4
57 113,5 11,85 113,5 113,5 113,5 98,6 83,7 68,7 53,8 108,3 12,61 108,3 108,3 108,3 93,4 78,5 63,6 48,7
*
These capacities are gross ratings. For net capacity, deduct air blower motor, MBH = 3.415 x kW.
Refer to the appropriate Blower Perfomance Table for the kW of the supply blower motor.
These ratings include condenser fan motors and the compressor motors but not the supply air blower motor.
Unitary Products Group 11
TABLE 9: HEATING APPLICATION DATA 7-1/2 TON UNIT
CFM ID DB CAP & kW
OUTDOOR TEMPERATURE (F) (72% RH)
-10 0 10 20 30 40 50 60
2250
55
MBH
15.161 26.385 37.609 48.833 60.057 71.281 82.505 93.729
KW
3.755 4.253 4.752 5.251 5.750 6.248 6.747 7.246
70
MBH
13.702 24.926 36.150 47.374 58.598 69.822 81.046 92.270
KW
4.342 4.840 5.339 5.838 6.337 6.835 7.334 7.833
80
MBH
11.610 22.834 34.058 45.282 56.506 67.730 78.954 90.178
KW
4.722 5.220 5.719 6.218 6.717 7.215 7.714 8.213
3000
55
MBH
17.179 28.403 39.627 50.851 62.075 73.299 84.523 95.747
KW
3.420 3.918 4.417 4.916 5.415 5.913 6.412 6.911
70
MBH
15.720 26.944 38.168 49.392 60.616 71.840 83.064 94.288
KW
4.007 4.505 5.004 5.503 6.002 6.500 6.999 7.498
80
MBH
13.628 24.852 36.076 47.300 58.524 69.748 80.972 92.196
KW
4.387 4.885 5.384 5.883 6.382 6.880 7.379 7.878
3750
55
MBH
18.177 29.401 40.625 51.849 63.073 74.297 85.521 96.745
KW
2.889 3.387 3.886 4.385 4.884 5.382 5.881 6.380
70
MBH
16.718 27.942 39.166 50.390 61.614 72.838 84.062 95.286
KW
3.476 3.974 4.473 4.972 5.471 5.969 6.468 6.967
80
MBH
14.626 25.850 37.074 48.298 59.522 70.746 81.970 93.194
KW
3.856 4.354 4.853 5.352 5.851 6.349 6.848 7.347
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)
Unitary Products Group 12
TABLE 10: HEATING APPLICATION DATA 10 TON UNIT
CFM ID DB CAP & kW
OUTDOOR TEMPERATURE (F) (72% RH)
-10 0 10 20 30 40 50 60
3000
55
MBH
17.601 32.584 47.567 62.549 77.532 92.515 107.498 122.480
KW
5.642 6.082 6.522 6.962 7.401 7.841 8.281 8.721
70
MBH
18.204 33.187 48.170 63.152 78.135 93.118 108.101 123.083
KW
6.590 7.030 7.469 7.909 8.349 8.789 9.228 9.668
80
MBH
15.834 30.817 45.800 60.782 75.765 90.748 105.731 120.713
KW
7.118 7.558 7.997 8.437 8.877 9.317 9.756 10.196
4000
55
MBH
18.040 33.023 48.006 62.989 77.971 92.954 107.937 122.920
KW
5.215 5.655 6.095 6.535 6.974 7.414 7.854 8.294
70
MBH
18.643 33.626 48.609 63.592 78.574 93.557 108.540 123.523
KW
6.163 6.603 7.042 7.482 7.922 8.362 8.801 9.241
80
MBH
16.273 31.256 46.239 61.222 76.204 91.187 106.170 121.153
KW
6.691 7.131 7.570 8.010 8.450 8.890 9.329 9.769
5000
55
MBH
16.305 31.287 46.270 61.253 76.236 91.218 106.201 121.184
KW
5.090 5.530 5.970 6.410 6.849 7.289 7.729 8.169
70
MBH
16.908 31.890 46.873 61.856 76.839 91.821 106.804 121.787
KW
6.038 6.478 6.917 7.357 7.797 8.237 8.676 9.116
80
MBH
14.538 29.520 44.503 59.486 74.469 89.451 104.434 119.417
KW
6.566 7.006 7.445 7.885 8.325 8.765 9.204 9.644
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x KW)
Unitary Products Group 13
TABLE 11: ELECTRICAL DATA 7-1/2 TON
Voltage
Compressors
OD Fan
Motors
FLA ea.
Blower Motor
Supply FLA
Electric Heater
Min. Circuit
Ampacity
(Amps)
Max Fuse
*
Size (Amps)
RLA ea. LRA ea.
1.5
HP
2
HP
Model
#
Rated kW Heater Amps 1.5 HP 2 HP 1.5 HP 2 HP
380 8.0 62 1.1 4.3 5.2
None - - 24.5 25.4 30 30
2TP04510950 5.6 15.5 35.1 36.0 40 40
2TP04511850 11.3 31.4 46.0 46.9 50 50
2TP04512450 15.0 41.6 53.0 53.9 60 60
2TP04513650 21.3 70.8 65.0 65.9 70 70
415 8.0 62 1.1 4.3 5.2
None - - 24.5 25.4 30 30
2TP04510950 6.7 16.1 36.2 37.1 40 40
2TP04511850 13.5 32.5 48.0 48.9 50 50
2TP04512450 17.9 43.1 55.6 56.5 60 60
2TP04513650 25.4 61.1 68.7 69.6 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 12: ELECTRICAL DATA 10 TON
Voltage
Compressors
OD Fan
Motors
FLA ea.
Blower Motor
Supply FLA
Electric Heater
Min. Circuit
Ampacity
(Amps)
Max Fuse
*
Size (Amps)
RLA ea. LRA ea. 2 HP 3 HP Model # Rated kW Heater Amps 2 HP 3 HP 2 HP 3 HP
380 9.6 79 1.1 5.2 5.4
None - - 29.0 29.2 35 35
2TP04511850 11.3 31.4 50.5 50.7 60 60
2TP04512450 15.0 41.6 57.5 57.7 60 60
2TP04513650 21.3 59.1 69.5 69.7 70 70
2HP04515450

33.8 93.8 70.7 70.9 80 80


415 9.6 79 1.1 5.2 5.4
None - - 29.0 29.2 35 35
2TP04511850 13.5 32.5 52.5 52.7 60 60
2TP04512450 17.9 43.1 60.1 60.3 70 70
2TP04513650 25.4 61.1 73.2 73.4 80 80
2HP04515450

40.4 97.2 76.8 77.0 80 80


*
Maximum HACR breaker of the same AMP size is applicable.

Only 25.4kW of electric heat can be simultaneously energized with the mechanical heating. The full 40.4kW operates only if both
compressors are locked-out
14 Unitary Products Group
TABLE 13: ADDITIONAL STATIC RESISTANCE
CFM
Cooling Only
*
Economizer

Electric Heat KW

9 18 24 36 54
1900 0.06 0.02 0.05 0.06 0.07 0.08 0.10
2100 0.07 0.02 0.06 0.07 0.08 0.09 0.11
2300 0.08 0.02 0.07 0.08 0.09 0.10 0.13
2500 0.09 0.02 0.08 0.09 0.10 0.11 0.14
2700 0.11 0.03 0.09 0.10 0.12 0.13 0.16
2900 0.12 0.03 0.10 0.11 0.13 0.14 0.18
3100 0.14 0.03 0.12 0.13 0.15 0.16 0.20
3300 0.16 0.03 0.13 0.14 0.17 0.18 0.22
3500 0.18 0.04 0.15 0.16 0.19 0.20 0.24
3700 0.20 0.04 0.17 0.18 0.21 0.22 0.26
3900 0.23 0.04 0.19 0.20 0.23 0.24 0.28
4100 0.25 0.04 0.21 0.22 0.25 0.26 0.31
4300 0.28 0.05 0.23 0.24 0.28 0.29 0.34
4500 0.30 0.05 0.25 0.26 0.30 0.31 0.37
4700 0.33 0.05 0.28 0.29 0.33 0.34 0.40
4900 0.36 0.05 0.30 0.31 0.35 0.37 0.43
5100 0.39 0.06 0.33 0.34 0.38 0.40 0.46
5300 0.42 0.06 0.35 0.37 0.41 0.43 0.49
5500 0.45 0.06 0.38 0.40 0.44 0.46 0.53
5700 0.48 0.06 0.41 0.43 0.47 0.49 0.56
5900 0.52 0.07 0.44 0.46 0.50 0.53 0.59
6100 0.56 0.07 0.47 0.49 0.53 0.56 0.62
6300 0.60 0.07 0.50 0.53 0.56 0.59 0.65
*
Add these resistance values to the available static resistance in the respective Blower Performance Tables.

Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 14: 7-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.2 - - - 3715 1573 1.69 3634 1434 1.54 3431 1265 1.36 3218 901 0.97 3024 976 1.05
0.4 3650 1657 1.78 3510 1490 1.60 3320 1313 1.41 3079 1145 1.23 2832 810 0.87 2586 860 0.92
0.6 3334 1522 1.63 3146 1351 1.45 2910 1169 1.25 2621 1005 1.08 2307 706 0.76 - - -
0.8 2903 1352 1.45 2622 1167 1.25 2404 1013 1.09 2054 858 0.92 - - - - - -
1.0 2356 1159 1.24 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
Unitary Products Group 15
TABLE 15: 7-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.2 - - - - - - - - - - - - 3992 1904 2.04 3798 1679 1.80
0.4 - - - - - - - - - 3930 2017 2.16 3734 1786 1.92 3486 1552 1.66
0.6 - - - - - - 3947 2176 2.33 3670 1895 2.03 3394 1641 1.76 3084 1401 1.50
0.8 - - - 4138 2384 2.56 3623 2009 2.15 3323 1742 1.87 2971 1477 1.58 2591 1236 1.33
1.0 4126 2430 2.61 3643 2145 2.30 3224 1820 1.95 2889 1569 1.68 2466 1306 1.40 - - -
1.2 3613 2238 2.40 3143 1921 2.06 2748 1621 1.74 2369 1385 1.49 - - - - - -
1.4 3099 2039 2.19 2636 1714 1.84 2195 1424 1.53 - - - - - - - - -
1.6 2586 1833 1.97 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
TABLE 16: 10 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.2 - - - - - - - - - 3896 1639 1.76 3688 1453 1.56 3447 1268 1.36
0.4 4040 2076 2.23 4005 1934 2.07 3790 1698 1.82 3569 1508 1.62 3333 1330 1.43 3057 1147 1.23
0.6 3890 2006 2.15 3697 1790 1.92 3427 1550 1.66 3152 1356 1.45 - - - - - -
0.8 3620 1882 2.02 3324 1629 1.75 2972 1380 1.48 - - - - - - - - -
1.0 3227 1708 1.83 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
16 Unitary Products Group
TABLE 17: 10 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.4 4965 3485 3.74 4875 3150 3.38 4613 2739 2.94 4322 2374 2.55 4156 2106 2.26 3907 1860 1.99
0.6 4876 3416 3.66 4651 2997 3.21 4359 2582 2.77 4038 2220 2.38 3860 1966 2.11 3590 1724 1.85
0.8 4713 3291 3.53 4387 2823 3.03 4077 2417 2.59 3719 2059 2.21 3541 1827 1.96 3242 1584 1.70
1.0 4476 3116 3.34 4084 2632 2.82 3768 2245 2.41 3365 1892 2.03 3197 1691 1.81 - - -
1.2 4165 2898 3.11 3741 2427 2.60 3432 2070 2.22 - - - - - - - - -
1.4 3779 2646 2.84 3359 2212 2.37 3069 1895 2.03 - - - - - - - - -
1.6 3319 2372 2.54 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
TABLE 18: 7-1/2 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.4 - - - - - - 3736 1476 1.58 3487 1284 1.38 3231 1109 1.19 3001 970 1.04
0.6 - - - 3572 1514 1.62 3389 1339 1.44 3094 1151 1.23 2764 972 1.04 2446 824 0.88
0.8 3422 1558 1.67 3179 1364 1.46 2889 1164 1.25 2554 985 1.06 - - - - - -
1.0 2891 1347 1.44 2372 1088 1.17 2050 922 0.99 - - - - - - - - -
1.2 2017 1051 1.13 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
17 Unitary Products Group

Blower performance includes dry coil and two-inch
filters.
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure
of the blower.
TABLE 19: 10 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.2 - - - - - - - - - - - - 5067 2614 2.80 4809 2290 2.46
0.4 - - - - - - 5179 3112 3.34 4884 2703 2.90 4729 2401 2.57 4459 2113 2.27
0.6 - - - - - - 4925 2943 3.16 4585 2521 2.70 4429 2244 2.41 4137 1964 2.11
0.8 - - - 4974 3220 3.45 4607 2727 2.92 4267 2342 2.51 4099 2080 2.23 3783 1809 1.94
1.0 4975 3453 3.70 4657 2995 3.21 4305 2550 2.73 3941 2171 2.33 3751 1919 2.06 3371 1630 1.75
1.2 4679 3423 3.67 4366 2808 3.01 4022 2373 2.54 3545 1978 2.12 3305 1741 1.87 - - -
1.4 4429 3065 3.29 4040 2607 2.80 3669 2673 2.87 2918 1700 1.82 - - - - - -
1.6 4107 2845 3.05 3620 2357 2.53 2931 1830 1.96 - - - - - - - - -
1.8 3553 2500 2.68 2756 1899 2.04 - - - - - - - - - - - -
2.0 2439 1939 2.08 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
TABLE 20: INDOOR BLOWER SPECIFICATIONS
MODEL
MOTOR MOTOR SHEAVE BLOWER SHEAVE
BELT
HP RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
BP090
1-1/2 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7.5 1 AK79 A55
2 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 6.5 1 AK69 A53
BP120
2 1725 80% 1.15 56 3.4 - 4.4 7/8 1VM50 7 1 AK74 A54
3 1725 80% 1.15 184T 4.3-5.3 1-1/8 1VP56 6.2 1 AK66 B55
Unitary Products Group 18
TABLE 21: 7-1/2 TON OPTIONAL MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.4 - - - - - - - - - - - - - - - 3910 1726 1.85
0.6 - - - - - - - - - - - - 3857 1842 1.98 3597 1430 1.53
0.8 - - - - - - - - - 3804 1957 2.10 3503 1689 1.81 3172 1430 1.53
1.0 - - - - - - 3774 2088 2.24 3406 1778 1.91 3032 1497 1.61 2248 1143 1.23
1.2 - - - - - - 3327 1866 2.00 2926 1578 1.69 2160 1217 1.31 - - -
1.4 - - - 3270 1971 2.11 2537 1544 1.66 2043 1296 1.39 - - - - - -
1.6 3196 2077 2.23 2460 1651 1.77 - - - - - - - - - - - -
1.8 2426 1768 1.90 - - - - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the
E.S.P. from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have
been deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
TABLE 22: 10 TON STANDARD MOTOR SIDE SHOT BLOWER PERFORMANCE
*
ESP

TURNS OPEN
**
0 1 2 3 4 5
CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP CFM
W

BHP
0.2 - - - - - - - - - 4368 1843 1.98 4132 1624 1.74 3870 1423 1.53
0.4 - - - 4515 2192 2.35 4213 1885 2.02 4020 1692 1.81 3791 1491 1.60 3499 1283 1.38
0.6 - - - 4192 2027 2.17 3905 1741 1.87 3657 1537 1.65 3383 1345 1.44 3062 1149 1.23
0.8 - - - 3838 1858 1.99 3534 1591 1.71 3236 1386 1.49 2934 1202 1.29 - - -
1.0 3755 1942 2.08 3489 1695 1.82 3081 1425 1.53 - - - - - - - - -
1.2 3337 1757 1.88 2918 1475 1.58 - - - - - - - - - - - -
*
Blower performance is for gas heat which includes maximum number of heat tubes available for each tonnage. Add the E.S.P.
from Table 17.

Blower performance includes two-inch throwaway filters.

ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
**
Turns Open refers to the setting of the variable pitch motor sheave, where 0 Turns Open is fully closed.

W = Watts
19 Unitary P roducts Group
FIGURE 2: UNIT DIMENSIONS
For Baserai l
Di mensi ons
See Detai l A
89 27
59
50-3/4
4-1 /4
6-3/1 6
1 7-3/1 6
24-3/1 6
30-3/1 6
Conveni ence
Power
Outl et
Entry
7/8
Power
Entry
2-1 /2
30-1 1 /32
Control
Entry
7/8
Power
Entry
2-1 /2
LEFT
FRONT
For Drai n
Di mensi ons
See Detai l B
TABLE 23: UNIT CLEARANCES
Top
*
* Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
72 Right 12
Front 36 Left 36
Rear

To remove the slide-out drain pan, a rear clearance of 60 is


required. If space is unavailable, the drain pan can be
removed through the front by separating the corner wall.
36
Bottom

Units may be installed on combustible floors made from


wood or class A, B or C roof covering materials.
0
3-3/4
3-9/1 6
2-3/8
DETAIL A
DETAIL B
5-3/8
3/4" Drain
Opening
036-21046-005-A-1102
Unitary Products Group 20
FIGURE 3: HORIZONTAL ECONOMIZER DETAIL
FIGURE 4: DOWNFLOW ECONOMIZER HOOD DETAIL
0A-1102
21 Unitary Products Group
FIGURE 5: PREDATOR ROOF CURB DIMENSIONS
FIGURE 6: SUNLINE TO PREDATOR TRANSITION ROOF CURBS
8 or 1 4
50-1 /2
30
20
20
80-5/8
6
2 TYP.
NSULATED DECK UNDER
COMPRESSOR SECT ON
NSULATED DECK UNDER
CONDENSER SECT ON
FRONT
R GHT
SUPPLY
RETURN
76-5/8
94
50-1 /2
30-1 /2
64-1 /4
59-1 /4
1 0
23
4
26
80-5/8
2 TYP
FRONT R GHT
SUPPLY
RETURN
Unitary Products Group 22
FIGURE 7: BOTTOM DUCT OPENINGS (FROM ABOVE)
FIGURE 8: REAR DUCT DIMENSIONS
32-1 1 /1 6
6-1 3/1 6
6-1 3/1 6
27-1 /2
1 8
21 -3/1 6
1 9-3/1 6
1 7-3/1 6
1 4-23/32
1 6-3/8
1 8-1 /1 6
6-1 3/1 6
24
21
LEFT
Bottom Power,
Control and
Conveni ence
Outl et Wi ri ng
Entry
SUPPLY
A R
RETURN
A R
FRONT
1 9-5/8
7-1 /8 Bottom Condensate
Locati on
1 8-1 /4
5-5/32
28-1 /4
31 -1 1 /1 6
2-31 /32
1 8-1 /1 6
28-1 /4
1 8-1 /4
Return
Ai r
Suppl y
Ai r
Patch Pl ate
For Sl i de-Out
Drai n Pan
Dot Pl ugs
JOB NAME:________________________________________LOCATION:________________________________________
PURCHASER:______________________________________ORDER NO:________________________________________
ENGINEER:__________________________________________________________________________________________
SUBMITTED TO:__________________FOR: _______REF: ________APPROVAL: ________ CONSTRUCTION: ________
SUBMITTED BY:____________________________________DATE:_____________________________________________
UNIT DESIGNATION: SCHEDULE NO. __________________MODEL NO:________________________________________
SINGLE PACKAGE HEAT PUMP UNITS
7-1/2 AND 10 TONS
MODEL BP 090, AND 120
036-22033-002 Rev A (0401) CD: 6-22033
Supersedes: 036-22033-001 Rev A (500)

COOLING PERFORMANCE
TOTAL CAPACITY _____ MBH
SENSIBLE CAPACITY _____ MBH
OUTDOOR DESIGN TMP. _________ F DB/WB
TOTAL SUPPLY AIR _____ CFM
TEMP. OF AIR ENTERING
EVAPORATOR COIL _____ F
POWER INPUT REQ. _____ KW
(LESS BLOWER MOTOR)
HEATING PERFORMANCE
CAPACITY @ 47F _____ MBH
@ 17F _____ MBH
COEFFICIENT OF PERFORMANCE
@ 47F _____ MBH
@ 17F _____ MBH
ELECTRIC HEAT _____ KW
SUPPLY AIR BLOWER PERFORMANCE
TOTAL SUPPLY AIR _____ CFM
EXT. STATIC PRESS. _____ IWG
BLOWER SPEED ____ RPM
POWER OUTPUT REQ. _____ BHP
MOTOR RATING _____ HP
POWER INPUT REQ. _____ KW
ELECTRICAL DATA
POWER SUPPLY __________
TOTAL UNIT AMPACITY _____ AMPS
MAX. OVERCURRENT DEVICE
__ FUSE __ BREAKER _____ AMPS
TOTAL UNIT WEIGHT
INCLUDING FACTORY- INSTALLED
OPTIONS _____ LBS
For Baserail
Dimensions
See Detail A
89 27
59
50-3/4
4-1/4
6-3/16
17-3/16
24-3/16
30-3/16
Convenience
Power
Outlet
Entry
7/8
Power
Entry
2-1/2
30-11/32
Control
Entry
7/8
Power
Entry
2-1/2
LEFT
FRONT
For Drain
Dimensions
See Detail B
FACTORY INSTALLED OPTIONS
ALTERNATE INDOOR BLOWER MOTOR - - - - - - - - - - - - - - - - !
BAS OPTION
Synthesys - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Novar

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
CONVENIENCE OUTLET - - - - - - - - - - - - - - - - - - - - - - - - - - - !
DIRTY FILTER SWITCH - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
DISCONNECT SWITCH - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
ECONOMIZER
Barometric Relief- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Power Exhaust - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Dual Enthalpy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
MOTORIZED AIR DAMPER- - - - - - - - - - - - - - - - - - - - - - - - - - !
PHASE MONITOR
1
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
SMOKE DETECTOR
Supply Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Return Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
TECHNICOAT CONDENSER COILS - - - - - - - - - - - - - - - - - - - - !
FIELD INSTALLED ACCESSORIES
COIL GUARD- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
DIRTY FILTER SWITCH - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
DISCONNECT SWITCH - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
ECONOMIZER
Barometric Relief- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Power Exhaust - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Dual Enthalpy - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
CO
2
Sensor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
ELECTRIC HEATER MODEL- - -________________________ !
HAIL GUARD- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
LOW AMBIENT KIT- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
MOTORIZED OUTDOOR AIR DAMPER- - - - - - - - - - - - - - - - - - !
MANUAL OUTDOOR AIR DAMPER - - - - - - - - - - - - - - - - - - - - !
PERMANENT FILTERS - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
PHASE MONITOR
1
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
ROOF CURB
8 Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
14 Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Transition Roof Curb - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Burglar Bars (Downflow Only)- - - - - - - - - - - - - - - - - - - - - - - - - - !
SMOKE DETECTOR
Supply Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
Return Air - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - !
1. Phase monitor standard on units with scroll compressors.
UNIT CLEARANCES
Top
1
1. Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
72 Right 12
Front 36 Left 36
Rear
2
2. To remove the slide-out drain pan, a rear clearance of 60 is
required. If space is unavailable, the drain pan can be
removed through the front by separating the corner wall.
36
Bottom
3
3. Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
0
HORIZONTAL DISCHARGE DIMENSIONS
ROOFCURB
CURB ADAPTOR
Dot Plugs
18-1/4
5-5/32
28-1/4
31-11/16
2-31/32
18-1/16
28-1/4
18-1/4
Return
Air
Supply
Air
8 or 1 4
50-1 /2
30
20
20
80-5/8
6
2 TYP.
NSULATED DECK UNDER
COMPRESSOR SECT ON
NSULATED DECK UNDER
CONDENSER SECT ON
FRONT
R GHT
SUPPLY
RETURN
76-5/8
94
50-1 /2
30-1 /2
64-1 /4
59-1 /4
1 0
23 4
26 80-5/8
2 TYP
FRONT R GHT
SUPPLY
RETURN
25-3/4
25-3/4
26 30-1 /4
35-3/4
88-1 /4
58-1 /4
47-1 /2
REL EF HOOD FOR
POWER EXHAUST OR
BAROMETR C REL EF
OUTS DE A R
NTAKE HOOD

También podría gustarte