PROFIS Anchor 2.4.2


1 GATE HOUSE HILTI BO 3/13/2014

-|-

1. Input data

Anchor type and diameter: Effective embedment depth: Material: Evaluation Service Report: Issued I Valid: Proof: Stand-off installation: Anchor plate: Profile Base material: Installation: Reinforcement:

HIT-RE 500-SD + HIT-V-F (8.8), M24 h ef,opti = 440 mm (hef,limit = 480 mm) 8.8 ETA 07/0260 6/26/2013 | 5/16/2018 design method Engineering judgement SOFA BOND - based on ETAG BOND testing e b = 0 mm (no stand-off); t = 20 mm lx x l y x t = 500 x 400 x 20 mm (Recommended plate thickness: not calculated) IPE; (L x W x T x FT) = 100 mm x 55 mm x 6 mm x 6 mm uncracked concrete , C30/37, fcc = 37.00 N/mm; h = 1500 mm, Temp. short/long: 30/40C hammer drilled hole, installation condition: dry no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm) no longitudinal edge reinforcement

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


2 GATE HOUSE HILTI BO 3/13/2014

-|-

2. Load case/Resulting anchor forces


Load case (Design loads): Anchor reactions [kN] Tension force: (+Tension, -Compression) Anchor 1 2 3 4 5 6 7 8 Tension force 46.750 46.750 46.750 46.750 46.750 46.750 46.750 46.750 Shear force 0.923 0.923 0.923 0.923 0.923 0.923 0.923 0.923 Shear force x 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 Shear force y -0.923 -0.923 -0.923 -0.923 -0.923 -0.923 -0.923 -0.923 6 1 2 5 3

y 4 x 8 7

Tension

max. concrete compressive strain []: 0.00 max. concrete compressive stress [N/mm]: 0.00 resulting tension force in (x/y)=(0/0) [kN]: 374.000 resulting compression force in (x/y)=(0/0) [kN]: 0.000

3. Tension load (EOTA TR 029, Section 5.2.2)


Proof Steel Strength* Combined pullout-concrete cone failure** Concrete Breakout Strength** Splitting failure** * anchor having the highest loading Steel Strength NRk,s [kN] 282.000 g M,s 1.500 NRd,s [kN] 188.000 NSd [kN] 46.750 374.000 N/A 374.892 N/A 100 N/A OK N/A Load [kN] 46.750 374.000 Capacity [kN] 188.000 423.496 Utilization bN [%] 25 88 Status OK OK

**anchor group (anchors in tension)

Combined pullout-concrete cone failure Ap,N [mm ] 480828 yc 1.040 e c1,N [mm] 0 NRk,p [kN] 241.516
0 2

Ap,N [mm ] 215040 t Rk,ucr [N/mm ] 7.28 y ec1,Np 1.000 NRk,p [kN] 889.341
2

t Rk,ucr,25 [N/mm ] 7.00 k 3.200 e c2,N [mm] 0 g M,p 2.100

s cr,Np [mm] 464 y g,Np 2.317 y ec2,Np 1.000 NRd,p [kN] 423.496
0

c cr,Np [mm] 232 y g,Np 1.647 y s,Np 1.000 NSd [kN] 374.000

c [mm] 820

y re,Np 1.000

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


3 GATE HOUSE HILTI BO 3/13/2014

-|-

Concrete Breakout Strength Ac,N [mm ] 2419200 e c1,N [mm] 0 NRk,c [kN] 567.024
0 2

Ac,N [mm ] 1742400 y ec1,N 1.000 g M,c 2.100

c cr,N [mm] 660 e c2,N [mm] 0 NRd,c [kN] 374.892

s cr,N [mm] 1320 y ec2,N 1.000 NSd [kN] 374.000 y s,N 1.000 y re,N 1.000 k1 10.100

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


4 GATE HOUSE HILTI BO 3/13/2014

-|-

4. Shear load (EOTA TR 029, Section 5.2.3)


Proof Steel Strength (without lever arm)* Steel failure (with lever arm)* Pryout Strength** Concrete edge failure in direction y-** * anchor having the highest loading Steel Strength (without lever arm) VRk,s [kN] 141.000 g M,s 1.250 V Rd,s [kN] 112.800 VSd [kN] 0.923 **anchor group (relevant anchors) Load [kN] 0.923 N/A 7.380 7.380 Capacity [kN] 112.800 N/A 1049.697 289.604 Utilization bV [%] 1 N/A 1 3 Status OK N/A OK OK

Pryout Strength (Concrete Breakout Strength controls) Ac,N [mm ] 2419200 e c1,V [mm] 0 NRk,c [kN] 567.024
0 2

Ac,N [mm ] 1742400 y ec1,N 1.000 g M,c,p 1.500

c cr,N [mm] 660 e c2,V [mm] 0 VRd,c1 [kN] 1049.697

s cr,N [mm] 1320 y ec2,N 1.000 VSd [kN] 7.380

k-factor 2.000 y s,N 1.000 y re,N 1.000 k1 10.100

Concrete edge failure in direction yh ef [mm] 440 c 1 [mm] 940 y s,V 0.874 VRk,c [kN] 700.439
0

d nom [mm] 24 Ac,V [mm ] 2820000 y h,V 1.000 g M,c 1.500


2

k1 2.400 A c,V [mm ] 3976200 y a,V 1.000 V Rd,c [kN] 289.604


0 2

a 0.068

b 0.048

e c,V [mm] 0 VSd [kN] 7.380

y ec,V 1.000

y re,V 1.000

5. Combined tension and shear loads (EOTA TR 029, Section 5.2.4)


bN 0.998 (bN + bV) / 1.2 <= 1 bV 0.025 a Utilization bN,V [%] 85 Status OK

6. Displacements
The displacement of the highest loaded anchor should be calculated according to the relevant approval under the effect of the following characteristic loads. NSk VSk = = 34.630 [kN] 0.680 [kN]

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


5 GATE HOUSE HILTI BO 3/13/2014

-|-

7. Warnings
The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means. The compliance with current standards (e.g. EC3) is the responsibility of the user An SLS-check is not performed for SOFA and has to be provided by the user! Characteristic bond resistances depend on short- and long-term temperatures. Please contact Hilti to check feasibility of HIT-V rod supply. Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7! To avoid failure of the anchor plate the required thickness can be calculated in PROFIS Anchor. Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the loading! The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger diameters of the clearance hole see Chapter 1.1. of EOTA TR029! The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be followed to ensure a proper installation.

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


6 GATE HOUSE HILTI BO 3/13/2014

-|-

8. Installation data
Anchor plate, steel: Anchor type and diameter: HIT-RE 500-SD + HIT-V-F (8.8), M24 Profile: IPE, 100 mm x 55 mm x 6 mm x 6 mm Installation torque: 0.200 kNm Hole diameter in the fixture: df = 26 mm Hole diameter in the base material: 28 mm Plate thickness (input): 20 mm Hole depth in the base material: 440 mm Recommended plate thickness: not calculated Minimum thickness of the base material: 496 mm Cleaning: Premium cleaning of the drilled hole is required Annular gap must be removed by e.g. filling the holes with mortar of sufficient compressive strength. 8.1. Required accessories Drilling Suitable Rotary Hammer Properly sized drill bit Cleaning Compressed air with required accessories to blow from the bottom of the hole Proper diameter wire brush y Setting Dispenser including cassette and mixer Dynamic set Torque wrench

140.0 5 3 4 7

200.0

70.0 250.0 250.0

70.0

Coordinates Anchor [mm] Anchor x y c -x 1 -60 -60 940 2 60 -60 1060 3 -60 60 940 4 60 60 1060

c +x 1060 940 1060 940

c -y 940 940 1060 1060

c +y 1060 1060 940 940

Anchor 5 6 7 8

x -180 -180 180 180

y 60 -60 60 -60

c -x 820 820 1180 1180

140.0

200.0 c +x 1180 1180 820 820

c -y 1060 940 1060 940

c +y 940 1060 940 1060

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

www.hilti-me.com Company: Specifier: Address: Phone I Fax: E-Mail: Page: Project: Sub-Project I Pos. No.: Date:

PROFIS Anchor 2.4.2


7 GATE HOUSE HILTI BO 3/13/2014

-|-

9. Remarks; Your Cooperation Duties


Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific application. You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility! PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan