TRANSFORMADORES

FEDERICO MILANO

DEPARTAMENTO DE INGENIERA ELCTRICA, ELECTRNICA, AUTOMTICA Y COMUNICACIONES ESCUELA TCNICA SUPERIOR DE INGENIEROS INDUSTRIALES UNIVERSIDAD DE CASTILLA - LA MANCHA

CAMPUS UNIVERSITARIO S/N E-13071 CIUDAD REAL ESPAA

CURSO 2010/11

MQUINAS ELCTRICAS

TRANSFORMADORES

CONTENIDOS
1. INTRODUCCIN 2. CARACTERSTICAS CONSTRUCTIVAS 3. FUNCIONAMIENTO DE UN TRANSFORMADOR MONOFSICO REAL 4. TRANSFORMADORES TRIFSICOS EN RGIMEN EQUILIBRADO 5. TRANSFORMADORES EN PARALELO 6. AUTOTRANSFORMADOR 7. TRANSFORMADORES CON TOMAS 8. TRANSFORMADORES DE MEDIDA (TENSIN, INTENSIDAD)

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

INTRODUCCIN

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


A) NCLEO

CHAPAS DE ACERO AL SILICIO LAMINADAS EN FRO (GRANO ORIENTADO) CAPA AISLANTE (0,01 mm) CARLITE COLUMNAS, CULATAS, VENTANAS DEL NCLEO, JUNTAS SEGN LA POSICIN RELATIVA NCLEO - DEVANADO
!

ACORAZADAS (NCLEO ABRAZA DEVANADO) DE COLUMNAS (DEVANADO ABRAZA NCLEO)

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

SECCIN TRANSVERSAL
!

PEQUEA POTENCIA: SECCIN CUADRADA GRAN POTENCIA: POLGONO ESCALONADO (CRUCIFORME)

CANALES DE VENTILACIN
8

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


FIJACIN MECNICA DE CHAPA (VIBRACIONES)

B) DEVANADOS

HILOS DE COBRE (BARNIZ) PLETINA DE COBRE (FIBRA DE ALGODN O CINTA DE PAPEL) SEGN LA DISPOSICIN DE LOS ARROLLAMIENTOS:
!

CONCNTRICOS ALTERNADOS (DISMINUCIN FLUJO DISPERSO)

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

B.T. A.T. B.T. A.T. B.T. A.T. B.T.

C) SISTEMAS DE REFRIGERACIN

PRDIDAS " CALOR " # TEMPERATURA MQUINA PEQUEAS POTENCIAS: TRANSFORMADORES EN SECO

10

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


POTENCIAS ELEVADAS: $ TRANSFORMADORES EN BAO DE ACEITE
!

MAYOR CONDUCTIVIDAD TRMICA QUE EL AIRE MAYOR RIGIDEZ DIELCTRICA QUE EL AIRE ENVEJECIMIENTO INHIBIDORES DEPSITO DE EXPANSIN (% 8%)

ACEITE MINERAL: INFLAMABLE Y VAPORES MEZCLAS EXPLOSIVAS

11

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


!

ACEITE SINTTICO (ASKAREL) " IMPACTO ECOLGICO ACEITES DE SILICONA

$ ALETAS, VENTILADORES, INTERCAMBIADORES DE CALOR (MVA) D) AISLADORES PASANTES Y OTROS ELEMENTOS

PASATAPAS

12

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS

REL DE BUCHHOLTZ (GAS)


!

SOBRECARGAS, FALLOS DE AISLAMIENTO, ETC. CALENTAMIENTO ANMALO " VAPOR DE ACEITE SISTEMA DE DOS FLOTADORES: ALARMA Y DESCONEXIN

13

MQUINAS ELCTRICAS

TRANSFORMADORES

PRINCIPALES ASPECTOS CONSTRUCTIVOS


E) PLACA DE CARACTERSTICAS DEL TRANSFORMADOR POTENCIA NOMINAL TENSIONES NOMINALES FRECUENCIA IMPEDANCIA EQUIVALENTE (%)

14

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL

$ %1 = % + %d1 SENTIDO ! # HORARIO ! "%2 = % & %d2


e1 = N1 d!1 dt = N1 d! dt + N1 d!d1 dt

15

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


e2 = N2 d! 2 dt = N2 d! dt " N2 d! dt d! d 2 dt d!d1 dt

v1 = R1i1 + e1 = R1i1 + N1 e2 = R2i2 + v 2 = N2

+ N1

d! dt

" N2

d! d 2 dt

SI SE DEFINEN LAS INDUCTANCIAS DE DISPERSIN:


L d1 = N1 d! d1 di1

X1 = Ld1&

L d 2 = N2

d! d 2 di 2
16

X2 = Ld2&

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL

v1 = e1 + R1i1 + L d1 e2 = v 2 + R2 i2 + L d 2

di1 dt di 2 dt

e1 = N1 e 2 = N2

d! dt d! dt

E1 = 4,44fN1%m $ E1 N1 ! " = =m # E N 2 2 E 2 = 4,44fN2 %m ! "


17

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


V1 = E1 + R1I1 + jX1I1 E2 = V2 + R2I2 + jX2I2 CADA TENSIN TRAFO INDUSTRIAL A PLENA CARGA: 1 - 10% UNOM

V1 % E1 $ V1 ! " !m # V 2 V2 % E 2 ! "

(APROXIMADAMENTE)

18

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


INTERRUPTOR S ABIERTO V1 = E1 + R1I0+ jX1I0 E2 = V2 I0: CORRIENTE DEL PRIMARIO EN VACO I0: 0.6 8 % I1 NOMINAL "
V1 = E1 $ V1 ! =m # " V 2 V2 = E2 ! "

19

MQUINAS ELCTRICAS

TRANSFORMADORES

FUNCIONAMIENTO DE UN TRANSFORMADOR REAL


INTERRUPTOR S CERRADO (EN CARGA) V1 EN VACO = V1 EN CARGA COMO V1 ! E1, 'm EN VACO % 'm EN CARGA F.M.M. EN VACO % F.M.M. EN CARGA N1 I0 = N1 I1 N2 I2

I1 = I0 +

N2 I I2 = I0 + 2 N1 m

20

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
REDUCCIN AL PRIMARIO: VALORES INSTANTNEOS: RGIMEN SENOIDAL: N1i1 N2i2 = () N1I1 N2I2 = ()ef
V1 = (R1 + jX1 )I1 + E 2 V1 = (R1 + jX1 )I1 + R 2I2 N1 N2

N1 N N + V2 1 + jX 2I2 1 N2 N2 N2

I1 #

! N2 I2 = " ef N1 N1

21

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
N2 I2 = I' 2 ! I2 REFERIDA AL PRIMARIO N1 # " ef = I0 ! CORRIENTE DE VACO O DE EXCITACIN N1

POR LO TANTO:
V1 = (R1 + jX1 )I1 + (R 2 + jX 2 )I2 N1 N + V2 1 N2 N2

2 N1 N N V1 = (R1 + jX1 )I1 + (R 2 + jX 2 ) 2 I2 2 + V2 1 N2 N1 N2

22

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
V1 = (R1 + jX1 )I1 + (R' 2 + jX' 2 )I' 2 + V ' 2
N1 V2 = V ' 2 ! V2 REFERIDA AL PRIMARIO N2

' N1 $ % %N " " R 2 = R' 2 ! R 2 REFERIDA AL PRIMARIO & 2# ' N1 $ % %N " " X 2 = X' 2 ! X 2 REFERIDA AL PRIMARIO & 2#
2

23

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
TRANSFORMADOR REAL " PRDIDAS MAGNTICAS " RFE
$IFE % PRDIDAS EN EL HIERRO ! I0 # !I % CORRIENTE DE MAGNETIZACIN "

I1 +

R1

X1 I0 IFE

X2

I2

R2 +

I X V2

V1

RFE

24

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO EQUIVALENTE
EN LA PRCTICA, DEBIDO A QUE I0 <<< I1, I2 SE SUELE TRABAJAR CON UN CIRCUITO APROXIMADO
R1 I0 IFE V1 RFE I X V2 X1 X2 R2 +

I1 +

I2

I1 + IFE V1 RFE I0

Rcc

Xcc

I2 +

I X V2

Rcc = R1 + R2 * RESISTENCIA DE CORTOCIRCUITO Xcc = X1 + X2 * REACTANCIA DE CORTOCIRCUITO

25

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR MONOFSICO


P0 ~ V10 I0 V20 i2 = 0

TRANSFORMADOR

MEDIDAS: V10, V20, P0, I0


I0 + V10 RFE IFE X I

IFE !0 I0 "

V10 = E10

26

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR MONOFSICO


2 V10

P0 =

RFE

! RFE

IFE =

V10 RFE
X =

2 2 I = I0 ! IFE

V10 I

Cos !0 =

P0 V10I0

m=

V10 V20

27

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
Pcc
TENSIN VARIABLE V1cc DE C.A.

I1cc

CORTOCIRCUITO

TRANSFORMADOR

MEDIDAS: V1cc, Pcc, I1cc


I1cc + V1cc Rcc Xcc

V1cc = ZccI1cc

XccI1cc

!cc

RccI1cc

I1cc

28

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
2 Pcc = RccI1 cc ! Rcc

Zcc =

V1cc I1cc

2 2 X cc = Z cc ! R cc

Cos !cc =

Pcc V1ccI1cc

R cc = R1 + R' 2 X cc = X1 + X' 2

29

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADOR MONOFSICO EN CARGA


I2 + 0 NDICE DE CARGA * C = C = 1 " PLENA CARGA C > 1 " SOBRECALENTAMIENTO (ADMITIDO NORMA UNE POCO TIEMPO) MAGNITUDES DE INTERS:

I2 I' I = 2 ! 1 I2N I' 2N I1N

CADA DE TENSIN RENDIMIENTO

30

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN
CADA DE TENSIN INTERNA * ,V2 = |V20| |V2| CADA DE TENSIN RELATIVA O REGULACIN * #c = REFERIDA AL PRIMARIO:
#c = V1N " V '2 V1N ! 100 % V20 " V2 V20 ! 100 %

EN CARGA:
#c = V1 " V '2 V1 ! 100 %

31

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN. APROXIMACIN DE KAPP


CIRCUITO EQUIVALENTE APROXIMADO. FACTOR DE POTENCIA INDUCTIVO
Rcc + V1N Xcc I2 + V2 ZL
O I2 !2 V2 V1N XccI2 !2 P !2 RccI2 Q M R N

T S

V1N = V2 + (Rcc + jXcc)I2 |V1N| |V'2|= |OS| |OP| = |PS| |V1N| |V'2| = |PS| % |PR|
32

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN. APROXIMACIN DE KAPP


|PR| = |PQ| + |QR| = |PQ| + |MN| |PR| = Rcc!I2!Cos(-2) + Xcc!I2!Sen(-2) |V1N| |V'2| = Rcc!I2!Cos(-2) + Xcc!I2!Sen(-2) |V1N| |V'2| = C!Rcc!I2N!Cos(-2) + C!Xcc!I2N!Sen(-2) APROXIMACIN DE KAPP: .c = C!. Rcc Cos(-2) + C!. Xcc!Sen(-2)
33

MQUINAS ELCTRICAS

TRANSFORMADORES

CADA DE TENSIN
" cc = Z ccI1N ! 100 V1N

# Rcc = # Xcc =

R ccI1N R I' ! 100 " cc 2N ! 100 V1N V1N X ccI1N X I' ! 100 " cc 2N ! 100 V1N V1N

EFECTO FERRANTI: CON F.D.P. CAPACITIVO " .c PUEDE SER NEGATIVA .c = C!. Rcc Cos(-2) C!. Xcc!Sen(-2)

34

MQUINAS ELCTRICAS

TRANSFORMADORES

PRDIDAS Y RENDIMIENTO
PRDIDAS 1) 2) HIERRO: COBRE: PFE = P0
2 2 2 PCU = I' 2 2 Rcc = C I' 2N Rcc = C Pcc

RENDIMIENTO * /
"= P2 P PPERD = 1 ! PERD = 1 ! P1 P1 P2 + PPERD

P0 + C 2Pcc " = 1! P2 + P0 + C 2Pcc

35

MQUINAS ELCTRICAS

TRANSFORMADORES

PRDIDAS Y RENDIMIENTO
POTENCIA DEL SECUNDARIO ( * P2) P2 = V2I2Cos(-2) = CV2I2NCos(-2) POR LO TANTO:

P0 + C 2Pcc CV2I2NCos(! 2 ) # = 1" = CV2I2NCos(! 2 ) + P0 + C 2Pcc CV2I2NCos(! 2 ) + P0 + C 2Pcc


RENDIMIENTO MXIMO:
2 Pcc P0 = C OPT

C OPT =

P0 Pcc

36

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
BANCOS TRIFSICOS
!A A iA ia a

!B B iB ib b

!C C iC ic c

37

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
CONDICIONES EQUILIBRADAS:

LAS TRES MQUINAS IDNTICAS TRABAJANDO EN IDNTICAS CONDICIONES DESFASE ENTRE MAGNITUDES DE 120

38

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
PROPIEDADES EN RGIMEN EQUILIBRADO: 1) 2) TRAFOS TRIFSICOS " UNIN DE 3 MQUINAS )A + )B + )C = 0 " AHORRO DE MATERIAL

TRANSFORMADOR DE 3 COLUMNAS (CORE - TYPE) FASES LATERALES (a, c) MAYOR LONGITUD FASE CENTRAL (b) DESEQUILIBRIOS INTENSIDADES MAGNETIZANTES POCA IMPORTANCIA " FORMA CONSTRUCTIVA MUY EXTENDIDA

39

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
OTRAS FORMAS CONSTRUCTIVAS: 1)

TRANSFORMADORES DE 5 COLUMNAS ARROLLAMIENTOS EN LAS COLUMNAS CENTRALES EL FLUJO SE CIERRA POR LAS LATERALES " MENOR SECCIN CULATA (MENOR ALTURA TOTAL) TRANSFORMADORES ACORAZADOS (SHELL - TYPE)

2)

40

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
CLASIFICACIN SEGN EL TIPO DE CIRCUITO MAGNTICO A) FLUJOS LIBRES HAY MALLAS DONDE SLO ACTA 0 DE UNA FASE B) FLUJOS LIGADOS EN CADA MALLA ACTAN 0 DE VARIAS FASES BANCO TRIFSICO TRES COLUMNAS CINCO COLUMNAS ACORAZADOS

41

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
COMPARACIN TRIFSICOS

BANCOS

TRIFSICOS

VS.

TRANSFORMADORES

COMPORTAMIENTO ELCTRICO IDNTICO TRANSFORMADORES TRIFSICOS: $ MENOR PESO $ MENORES PRDIDAS $ MENOR VOLUMEN DE MQUINA Y PARQUE $ AVERA: OTRO TRANSFORMADOR TRIFSICO

42

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
BANCOS TRIFSICOS: $ AVERA: RESERVA DEL 33% $ MEJORES CONDICIONES DE TRANSPORTE UTILIZACIN TPICA: TRANSFORMADORES TRIFSICOS SALVO TRANSFORMACIN DE GRANDES POTENCIAS CENTROS DE

43

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
MAGNITUDES NOMINALES Y PARMETROS POTENCIA NOMINAL, SN (kVA), TRIFSICA TENSIN NOMINAL PRIMARIA (VN1) (TENSIN COMPUESTA) TENSIN NOMINAL SECUNDARIA (VN2) (TENSIN COMPUESTA) INTENSIDAD NOMINAL:
IN = SN 3 ! UN

44

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES TRIFSICOS
RELACIN DE TRANSFORMACIN (k) + RELACIN NMERO DE ESPIRAS GRUPO DE CONEXIN Dd, Yy Dy Yd Dz Yz RELACIN DE TRANSFORMACIN (k)

N1 N2 1 N1 ! 3 N2 N 3! 1 N2 2 N1 ! 3 N2 2 N1 ! 3 N2

45

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO
DISTINTOS TIPOS DE CONEXIN ORIGINAN DIFERENCIAS DE FASE ENTRE TENSIONES COMPUESTAS DE PRIMARIO Y SECUNDARIO NDICE HORARIO * RETRASO DEL LADO DE MENOR TENSIN (R) RESPECTO AL DE TENSIN MS ELEVADA (R) MEDIDO EN MLTIPLOS DE 30 AGUJA GRANDE (ALTA TENSIN) 1 12 AGUJA PEQUEA (BAJA TENSIN) 1 HORA CORRESPONDIENTE
R R YNd1 R YNd11 R R YNyn0 R

46

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ESTRELLA


R + ! UU S + ! UV + ! U' V + ! U'U S R

N T

N T

+ ! UW

+ ! U' W

47

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ESTRELLA


! UU R S T ! UV ! UW N N ! U'U ! U'V ! U' W R S T

HIPTESIS: SISTEMA EQUILIBRADO, SECUENCIA DIRECTA

! U u = U20 ! U u = U20

! U v = U2-120 ! U v = U2-120

! U w = U2120 ! U w = U2120

48

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ESTRELLA


TRANSFORMADOR IDEAL:

U N = U' N' ! ! ! URS = Uu ! UV

! ! ! U'RS = U'u !U' V


! URS U( 1!0 " 1! " 120 ) U N ! = = !0 = !0 1!0 " 1! " 120 ) U' N' U'RS U' (

49

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ESTRELLA


DESFASE 0 " CONEXIN YNyn0

! ! U W = UT ! ! U' W = U' T ! ! U'U = U'R ! ! U' V = U'S ! ! U V = US


50

! ! UU = UR ! ! UU = UR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-TRINGULO


R + ! UU S + ! UV + ! U'V T + ! UW + ! U' W + ! U'U S R

N T

51

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-TRINGULO


! UU R ! UV S ! UW T N ! U' W T ! U'V S ! U'U R

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA DIRECTA

52

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN ESTRELLA-TRINGULO


! ! ! URS = UU ! UV
! ! U'RS = !U' V

! URS U( 1"0 ! 1" ! 120 ) 3U"30 N ! = = = 3 " ! 30 1" ! 120 + 180 ) U' "60 N' U'RS U' (
! ! UW = UT ! ! U' W = U'TS ! U'R ! U'S
N

CONEXIN YNd11

! U'T ! ! U' V = U'SR

30

! ! UU = UR

! ! U'U = U'RT

! ! UV = US

53

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-TRINGULO


! UU R ! UV S ! UW T N ! U' W T ! U'V S ! U'U R

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA DIRECTA

54

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN ESTRELLA-TRINGULO


! ! ! URS = UU ! UV

! ! U'RS = U'U
! URS U(1!0 " 1! " 120 ) 3U!30 N ! = = = 3 !30 U' !0 U' !0 N' U'RS
! ! UW = UT ! ! U' W = U' TR ! U'T
N!

CONEXIN YNd1

! U'S ! ! U' V = U'ST

! ! U'U = U'RS
30

U'R

! ! UU = UR

! ! UV = US

55

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN TRINGULO-ESTRELLA


! UU R ! UV S ! UW T N ! U'W T ! U'V S ! U'U R

HIPTESIS: TRANSFORMADOR IDEAL, SISTEMA EQUILIBRADO, SECUENCIA DIRECTA

56

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO. CONEXIN TRINGULO-ESTRELLA


! ! URS = UU

! ! ! U'RS = U'U !U' V


! URS U"0 U"0 N ! = = = " ! 30 3U' "30 3N' U' RS U' (1"0 ! 1" ! 120 )
! ! UW = UTR ! ! U' W = U'T ! UT

CONEXIN Dyn11
! US

! ! U'U = U'R
N 30

! ! UU = URS ! UR

! ! U' V = U'S ! ! UV = UST

57

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN TRINGULO-TRINGULO


! UU R ! UV S ! UW ! U'W T ! U'V S ! U'U R

HIPTESIS: SECUENCIA DIRECTA, EQUILIBRADO

TRANSFORMADOR

IDEAL,

SISTEMA

58

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN TRINGULO-TRINGULO


! ! URS = UU
! ! U'RS = U'U

! URS U!0 N ! = = !0 U'RS U' !0 N'

T
! ! U V = UST ! ! U W = UTR ! ! UU = URS ! ! U' V = U' ST

CONEXIN Dd0

! ! U' W = U' TR

! ! R S U 'U = U'RS

59

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN TRINGULO-TRINGULO


! UU R ! UV S ! UW ! U'W T ! U'V S ! U'U R

HIPTESIS: SECUENCIA DIRECTA, EQUILIBRADO

TRANSFORMADOR

IDEAL,

SISTEMA

60

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN TRINGULO-TRINGULO


! ! URS = UU
! ! U' RS = !U' V

! URS U"0 N ! = = " ! 60 U' RS U' "180 ! 120 N'

T
! ! U V = UST ! ! U W = UTR ! ! UU = URS R
61

! ! U'U = U'RT

CONEXIN Dd10

30

30

! ! U' W = U'TS

! ! U'V = U'SR

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ZIGZAG


! UU R ! U' V 2 N ! U' W 2 N ! U'W 2 T ! U' V 2 S
! U'U 2 ! U'U 2

R ! UV

! UW T

HIPTESIS: SECUENCIA DIRECTA, EQUILIBRADO

TRANSFORMADOR

IDEAL,

SISTEMA

62

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ZIGZAG


! ! ! URS = UU ! U V

! ! ! ! ! ! U' U U' V U' W U' V 3 ! U' RS = + ! + = U' V 2 2 2 2 2

! URS U( 1!0 " 1! " 120) 3U!30 2 N ! = = = !150 3 3 3 N' U'RS U' ! " 120 U' ! " 120 2 2
CONEXIN YNzn5

63

MQUINAS ELCTRICAS

TRANSFORMADORES

NDICE HORARIO CONEXIN ESTRELLA-ZIGZAG


! ! UW = UT ! ! U' V 2 ! U' W 2 ! U'R ! ! U'U 2 ! ! UV = US ! U'S ! U'U

N
! U' V 2

! ! UU = UR ! ! U' W

150

! U'T

64

MQUINAS ELCTRICAS

TRANSFORMADORES

ESQUEMA EQUIVALENTE
ESQUEMA EQUIVALENTE POR FASE REFERIDO A UN LADO TRANSFORMADOR TRIFSICO: ESTRELLA DE IMPEDANCIAS ! I1 + ! V1
! ! V1 , V' 2

! Z1 ! Z0 ! I0

! Z'2

! I '2 + ! V '2

TENSIONES SIMPLES

! ! ! I1, I '2 , I0 INTENSIDADES SIMPLES

65

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO
CONEXIN:

TENSIN NOMINAL " DEVANADO DE MAYOR TENSIN ABIERTO " DEVANADO DE MENOR TENSIN

LECTURAS:

POTENCIA TOTAL ABSORBIDA (TRIFSICA) * P0 INTENSIDAD DE FASE * I0A, I0B, I0C

POR DESEQUILIBRIO EN EL CIRCUITO MAGNTICO:

I0 =

1 (I0 A + I0B + I0C ) 3


66

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE VACO: TRANSFORMADOR TRIFSICO


P0 = 3R I
2 FE FE

2 3 V10

RFE

! RFE

V10 % VSIMPLE

$ VLNEA ! =# 3 !V " LNEA

CONEXIN EN ESTRELLA CONEXIN EN TRINGULO


" "

I0 % ISIMPLE

$ILNEA ! = #I LNEA ! " 3

CONEXIN EN ESTRELLA CONEXIN EN TRINGULO

67

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
CONEXIN:

INTENSIDADES NOMINALES TENSIN REDUCIDA " DEVANADO DE MAYOR TENSIN CORTOCIRCUITO " DEVANADO DE MENOR TENSIN

LECTURAS:

TENSIN DE CORTOCIRCUITO, Vcc, COMPUESTA POTENCIA TOTAL ABSORBIDA, Pcc, TRIFSICA

68

MQUINAS ELCTRICAS

TRANSFORMADORES

ENSAYO DE CORTOCIRCUITO
2 Pcc = 3RccI1 cc ! R cc

Icc % ISIMPLE

$ILNEA ! = #I LNEA ! " 3

CONEXIN EN ESTRELLA CONEXIN EN TRINGULO

Z cc =
$ VLNEA ! =# 3 !V " LNEA

V1cc 2 2 " X cc = Z cc ! R cc I1N

Vcc % VSIMPLE

CONEXIN EN ESTRELLA CONEXIN EN TRINGULO

R cc = R1 + R' 2

X cc = X1 + X' 2

69

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE ESTRELLA-ESTRELLA


R A C A B t B c r a a c' b' b ZL IL Z
c

T S

! I1 + ! V1

! Z1 ! Z0 ! I0

! Z' 2

! Z'L +

! ! I '2 = I 'L ! V '2


! Z'

70

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE ESTRELLA-TRINGULO


R A C A B a B t c r a T S C ZL b' b c' s Z IL

! I1 + ! V1

! Z1 ! Z0 ! I0

! Z' 2

! 3Z'L +

! ! I '2 = I 'ab ! V '2


! Z'

71

MQUINAS ELCTRICAS

TRANSFORMADORES

CIRCUITO MONOFSICO EQUIVALENTE TRINGULO-ESTRELLA / ESTRELLA-TRINGULO


RECOMENDACIN: CONVERTIR LA CARGA A LA CONEXIN DEL DEVANADO DEL TRANSFORMADOR DOS POSIBILIDADES: CONVERSIN DEL TRINGULO A ESTRELLA CONVERSIN DE LA ESTRELLA A TRINGULO

72

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
SITUACIONES PRCTICAS: 1) 2)

AMPLIACIN DE INSTALACIONES (SOLUCIN MS ECONMICA) FLEXIBILIDAD DE OPERACIN 1 NICO TRANSFORMADOR " PRDIDA DE SUMINISTRO EN AVERA O REVISIN 2 TRANSFORMADORES " LIMITACIN DE POTENCIA POTENCIAS ELEVADAS

3)

FIABILIDAD (SALIDA DE GENERADORES) TAMAO (TRANSPORTE)

73

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO CONDICIONES DE FUNCIONAMIENTO

CONDICIONES CONVENIENTES:
!

IGUAL RELACIN DE TRANSFORMACIN CORRECTO FUNCIONAMIENTO EN VACO

IGUAL TENSIN DE CORTOCIRCUITO EN p.u.

Vcc VN
!

ZccIN VN

= !cc

" EQUILIBRIO DE LA CARGA (CI = CII)

IGUAL POTENCIA DE CORTOCIRCUITO EN p.u.

Pcc SN

2 RccIN

VNIN

RccIN VN

= !Rcc

" SI .ccI = .ccII " Zcc CON IGUAL ARGUMENTO

74

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO

CONDICIONES OBLIGATORIAS
!

TRAFOS MONOFSICOS: CONEXIN BORNAS HOMLOGAS ENTRE S TRAFOS TRIFSICOS: $ CONEXIN BORNAS HOMLOGAS ENTRE S $ IGUAL NDICE HORARIO

$ IGUAL SECUENCIA DE FASES


INCONVENIENTES:

AUMENTA LA INTENSIDAD DE CORTOCIRCUITO AUMENTA COSTE DEL APARELLAJE ELCTRICO

75

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
INCUMPLIMIENTO DE CONDICIONES

CONDICIONES PTIMO)

CONVENIENTES:

FUNCIONAMIENTO

POSIBLE

(NO

CONDICIONES OBLIGATORIAS: IMPOSIBILIDAD DE FUNCIONAMIENTO (CORTOCIRCUITO)


+

AI V1 A'I II A'II

AII

III ZccII aII a'II I

TRANSFORMADOR I

TRANSFORMADOR II
aI V'2 a'I

ZccI

CARGA

76

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES EN PARALELO
ZccI!II = ZccII!III
II Z ccIIIN I Z I ! ! 100 = II ! ccII IIN ! 100 IIN V1N IIIN V1N

CI!.ccI = CII!.ccII
CI ! ccII = CII ! ccI
R S T

C B A c b a

II

C B A c b a

77

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR

DIVISOR DE TENSIN NICO ARROLLAMIENTO PRIMARIO Y SECUNDARIO UNIDOS GALVNICAMENTE

78

MQUINAS ELCTRICAS

HIPTESIS IDEAL

TRANSFORMADORES

AUTOTRANSFORMADOR
ARROLLAMIENTO SERIE: CIRCULA I1 (MENOS LONGITUD POR TRAFO) ARROLLAMIENTO COMN: CIRCULA I2 - I1 (MENOS SECCIN POR TRAFO) MENOR CANTIDAD DE COBRE

RELACIN DE TRANSFORMACIN:
k= N1 Ns + Nc U1 = = N2 Nc U2

DESPRECIANDO (m LA ECUACIN MAGNTICA: NsI1 - Nc(I2 - I1) = 0


79

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
I2 Ns + Nc N1 = = I1 Nc N2
COMPORTAMIENTO COMO EL DEL TRANSFORMADOR ARROLLAMIENTOS DE FORMA INDIVIDUALIZADA:

Us Ns = Uc Nc

I s Nc = Ic Ns

EL AUTOTRANSFORMADOR PUEDE ENTENDERSE COMO UNA FORMA ESPECIAL DE CONECTAR UN TRANSFORMADOR COINCIDE CON SUS CARACTERSTICAS CONSTRUCTIVAS

80

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
COMPARACIN ENTRE TRANSFORMADOR Y AUTOTRANSFORMADOR BASES: DOS MQUINAS CON: 1) 2) 3) IGUALES CARACTERSTICAS NOMINALES (TENSIN, POTENCIA) IGUALES PRDIDAS POR UNIDAD DE PESO (Bmax) IGUAL DENSIDAD DE CORRIENTE

PARMETROS DE CORTOCIRCUITO:
2 2 TRAFO " PccT = I1 R1 + I2 2R 2 = I1 Rcc
2 AUTOTRAFO " Pcc A = I1 R s + (I2 ! I1 ) R c 2

81

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
I1 + U1
N
' ! ! ! ! 1& ! ! ! ! %

I1

I2
$ ! ! # ! ! "

NS = N1 $N2 # "
!

I2
( % % ' % % &

N2

+ U2

U1

+
NC = N2

U2

I2 I1

R s = R1

Ns N ' N2 1# & = R1 1 = R1 $ 1 ' ! N1 N1 % k"

& I1 # & 1# ! I2 ' I1 = I2 $ 1 ' = I $ I ! 2 $1 ' k ! % " % 2 "


82

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
I ' 1$ R c = R 2 2 = R 2 %1 ! " I2 ! I1 & k#
2

!1

(BASE 3)

Pcc A

1# 1# 1# & & & = I R 1 $ 1 ' ! + I2 1 ' R 1 ' ! 2$ ! 2$ % k" % k" % k"


2 1

'1

1# & = Pcc T $1 ' ! % k"

BASE 1 " MISMA POTENCIA NOMINAL

1# & p cc % A = p cc % T $1 ' ! % k"

& 1# (Rcc A = (Rcc T $1 ' ! % k"

83

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
$MENORES VENTANAS ! MENOR NECESIDAD DE COBRE " # " !MENORES BOBINAS (DIMENSIN) " 33REACTANCIA DE DISPERSIN
EN GENERAL:

1# & X cc A ( X cc T $1 ' ! % k" & 1# u cc % A = u cc %T $1 ' ! % k"


1

& 1# (cc A = (cc T $1 ' ! % k"

84

MQUINAS ELCTRICAS

IGUAL B (BASE 2)

TRANSFORMADORES

AUTOTRANSFORMADOR
PARMETROS DE VACO

MAGNTICO

$VACO ! # !IGUAL TENSIN "

"

MISMO

FLUJO

"

MISMA

SECCIN

CIRCUITO

$LA MISMA H ! AUNQUE TRABAJEN CON # AL SER !LAS MISMAS PRDIDAS ESPECFICAS " MENOR SECCIN LA VENTANA:

85

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
MENOR LONGITUD MAGNTICA " 33 INTENSIDAD MAGNETIZANTE MENOR PESO " 33 PRDIDAS TOTALES NECESARIO CONOCER LAS DIMENSIONES DEL CIRCUITO EN GENERAL:
i0 % A < i0 % T p 0 % A < p 0 %T

PESO DE COBRE IGUAL DENSIDAD CORRIENTE (BASE 3) " IGUALES PRDIDAS POR UNIDAD DE PESO

86

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
FACTOR DE REDUCCIN DE PRDIDAS EN EL COBRE

1!

1 k

SE PUEDE APLICAR AL PESO DE COBRE

& 1# PESO CU,A = PESO CU,T $1 ' ! % k"


VENTAJAS DE LOS AUTOTRANSFORMADORES

MENORES PRDIDAS (COBRE, HIERRO) MEJOR RENDIMIENTO

87

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
MENORES CADAS DE TENSIN MENOR INTENSIDAD DE VACO MENOR COSTE: 3 COBRE, 3 HIERRO MENOR TAMAO (ESPACIO EN SUBESTACIONES)

INCONVENIENTES DE LOS AUTOTRANSFORMADORES

MAYOR INTENSIDAD DE CORTOCIRCUITO " # COSTE APARELLAJE NO EXISTE AISLAMIENTO GALVNICO ENTRE PRIMARIO Y SECUNDARIO " APARICIN DE TENSIONES PRIMARIAS EN EL SECUNDARIO

88

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
AVERA:

15 kV ! [500 V] + 500 V N Rt [0 V] FUNCIONAMIENTO NORMAL

89

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
CORTOCIRCUITO A TIERRA EN ALTA TENSIN:

[0 V] ! [14,5 kV] + 500 V [15 kV] Rt N [15 kV]

90

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
AVERA:

[0 V] I=0 E ! + 0V [0 V] -

BORNA COMN: CONEXIN RGIDA A TIERRA

91

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
[15 kV] !

Zs

[15 kV] - CADA TENSIN Zs " A.T.

[0 V] RUPTURA DEL CABLE

REGLAMENTACIN: k < 1,25 CON POTENCIALES POR DEBAJO DE 250 V, NO REGULADO ACONSEJABLE (GENERAL) 1 < k < 2
92

MQUINAS ELCTRICAS

! Sc

$ ! # ! " Si

TRANSFORMADORES

AUTOTRANSFORMADOR
POTENCIA EN LOS AUTOTRANSFORMADORES POTENCIA NOMINAL: POTENCIA MXIMA QUE PUEDE TRANSFERIR DEL PRIMARIO AL SECUNDARIO

POTENCIA CEDIDA AL SECUNDARIO: S2 = V2I2 = V2I1 + V2(I2 - I1) Sc * POTENCIA DE CIRCULACIN Si * POTENCIA INTERNA (TRANSFERENCIA ELECTROMAGNTICA)

93

MQUINAS ELCTRICAS

TRANSFORMADORES

AUTOTRANSFORMADOR
& 1# & 1# Si = V2(I2 - I1) = V2I2 $1 ' ! = Sp $1 ' ! % k" % k"
Sp * POTENCIA DE PASO

& 1# AUTOTRAFO SOLO TRANSFORMA EL $1 ' ! !100 % DE LA POTENCIA TOTAL % k" TRANSFERIDA AL SECUNDARIO
EJEMPLO: TRAFO 100 kVA, k = 2, TRANSF. ELECTROMAGNTICA = 100 kVA AUTOTRAFO 100 kVA, k = 2, TRANSF. ELECTROMAGNTICA = 50 kVA

94

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES CON TOMAS


CONTROL DE LA TENSIN

REGULAR TENSIN SERVIDA DENTRO LMITES LEGALES CONTROLAR FLUJOS DE P Y Q EN LA RED AJUSTE TENSIN FRENTE A INCREMENTO EN LA CARGA MONOFSICO TRIFSICO

95

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES CON TOMAS


CONMUTACIN A ALTA TENSIN

ECONMICO: EN BAJA TENSIN CONMUTADORES DE ALTA INTENSIDAD TCNICO: EN ALTA TENSIN MAYOR NMERO DE ESPIRAS " MAYOR CAPACIDAD DE REGULACIN SI AMBOS ARROLLAMIENTOS ESTN A ALTA TENSIN LA REGULACIN EN EL ARROLLAMIENTO QUE VAYA A TENER TENSIN VARIABLE (B CTE.)

TRANSFORMACIN A I CTE. VERSUS TRANSFORMACIN A P CTE. CONMUTACIN EN VACO VERSUS CONMUTACIN EN CARGA

96

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
TRANSFORMADOR DE TENSIN

FUNCIONA CASI EN VACO CADA DE TENSIN INTERNA MUY PEQUEA BORNE DE SECUNDARIO A TIERRA " PELIGRO CONTACTO PRIMARIO Y SECUNDARIO
RED !

TRANSFORMADOR DE TENSIN V VOLTMETRO

97

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
V1 - V2 = RccI2Cos(-cc) + XccI2Sen(-cc) IDEALMENTE: V1 = V2 " V2 = ERROR DE RELACIN O DE TENSIN

V1 KV

V2 " #V =

V1 KV

V1 KV

! 100

98

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
ERROR DE FASE O DE NGULO * DIFERENCIA DE FASE ENTRE V1 Y V2 (MIN) CLASES DE PRECISIN: 0,1, 0,2, 0,5, 1, 3 " VALOR MXIMO DE .V A POTENCIA NOMINAL Y F.D.P. 0,8 INDUCTIVO APARATO VOLTMETROS BOBINA VOLTIMTRICA VATMETRO BOBINA VOLTIMTRICA CONTADOR FASMETROS SINCRONOSCOPIOS RELS CONSUMO (VA) 2-8 1-8 2-6 2-12 5-15 5-50

99

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
TRANSFORMADOR DE CORRIENTE

FUNCIONA CASI EN CORTOCIRCUITO EN A.T. BORNE DE SECUNDARIO A TIERRA " PELIGRO CONTACTO PRIMARIO Y SECUNDARIO
RED !

RED ! TRANSFORMADOR DE INTENSIDAD A AMPERMETRO

TRANSFORMADOR DE INTENSIDAD

AMPERMETRO

100

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
I1 = I2 + I0 " I' 2 = IDEALMENTE: I1 = I2 = KiI2 B.T. " TRANSFORMADOR DE TENAZA O PINZAS (NO SE CORTA LA LNEA)

I2 m

101

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
SI SE DEJA EN CIRCUITO ABIERTO EL SECUNDARIO " I1 = I0 I1 ES CTE. (RED) Y MUY ELEVADA " FLUJO CRECE PELIGROSAMENTE " ##PFE Y V2 " PELIGRO EN LA VIDA DE LOS AISLANTES Y LA SEGURIDAD DEL PERSONAL SOLUCIONES: INTERRUMPIR EL SERVICIO DE LA LNEA CORTOCIRCUITAR PREVIAMENTE EL SECUNDARIO

102

MQUINAS ELCTRICAS

TRANSFORMADORES

TRANSFORMADORES DE MEDIDA
ERROR DE RELACIN O DE INTENSIDAD

I2 " #i =

I1 Ki

I1 Ki

! 100

ERROR DE FASE * DIFERENCIA DE FASE ENTRE I1 E I2 (MIN) CLASES DE PRECISIN: IGUAL QUE LOS TRANSFORMADORES DE TENSIN APARATO AMPERMETRO BOBINA AMPERIMTRICA VATMETRO BOBINA AMPERIMTRICA CONTADOR FASMETROS RELS CONSUMO (VA) 1-4 1-8 1-2 2-12 5-20

103