CAPACIDAD DE LOS CONDUCTORES EN KVA x KM

A.- Voltaje = 13.2 KV 3


Conductor
de Cu.

Cos

= 0.8

Cos

= 0.9

Cos

=1

4/0

47.157

53.051

92.068

3/0

42.235

46.526

73.421

2/0

37.341

40.094

58.003

1/0

32.647

34.388

46.156

28.248

29.097

36.556

24.167

24.371

29.001

20.520

20.327

23.047

17.401

16.976

18.551

14.525

13.965

14.746

11.958

11.350

11.639

9.886

9.284

9.305

7.931

7.481

7.342

B.- Voltaje = 23 KV 3
Conductor
de Cu.

Cos

= 0.8

Cos

= 0.9

Cos

=1

4/0

143.295

161.208

279.772

3/0

128.340

141.381

223.109

2/0

113.467

121.835

176.256

1/0

99.203

104.498

140.257

85.837

88.422

111.086

73.438

74.056

88.128

62.353

61.771

70.035

52.876

51.586

56.372

44.136

42.436

44.811

36.340

34.492

35.368

30.042

28.215

28.276

24.445

22.732

22.310

NOTA : SE HA CONSIDERADO UN PORCENTAJE MAXIMO DE REGULACION DE 10 % EN LA LINEA

Control

Aprob

EMPRESA NACIONAL DE ELECTRICIDAD S.A.


CAPACIDAD DE LOS CONDUCTORES
EN KVA x KM.

PLANO :
Tm-G 1-11.1
NORMAS DE DISTRIBUCION