Desarrollo del ejercicio 1ra Planta -Bao -Recamara -Cocina -Comedor -Sala 2da Planta -Bao -Recamara -Sala Tv

Area Total= 12m x 10m = 120 m2 Area Techada 1ra Planta = 98.19 m2 Area Techada 2da Planta = 104.19 m2 Area Total Techada = 202.38 m2 Area Libre (No techada)= 21.81 m2 Tabla de Valores -de los primeros 2000 W. -Los siguientes hasta 118000 W. -Exceso sobre 120000 W. Calculo de la Carga Instalada CI1 = Area Techada (m2) x Carga unitaria (W/m2) CI1 = 202.38 m2 x 25 W/m2 CI1 = 5059.5 W 100% 35% 25%

C2 = 1500 W/n.c. C2 = 1500 W

CI3 = Area Libre (m2) x 5 W/m2 CI3 = 21.81 m2 x 5 W/m2 CI3 = 109.05 W Cocina Electrica CI4 = 8000 W Calentador de Agua de 95 Lts. CI5 = 1200 W

CARGA INSTALADA TOTAL CIT= C1 + C2 + C3 + C4 + C5 CIT = 5059.5 + 1500 + 109.05 + 8000 + 1200 CIT = 15868.55 W CALCULO DE LA MAXIMA DEMANDA MD = CI X FACTOR DE DEMANDA MD1 = 2000 3059.5 MD2 = 1500 MD3 = 109.05 MD4 = 8000 MD5 = 1200 X X X X X X 1.00 = 2000 0.35 = 1070.83 1.00 = 1500 1.00 = 109.05 0.80 = 6400 1.00 = 1200

MDT = 2000 + 1070.83 + 1500 + 109.05 + 6400 + 1200 = 12279.88 W

Ahora hallaremos la Intensidad

Se multiplicara por un valor de 9% a 12% En este caso utilizaremos 12% I Diseo = 35.81 x 1.12 = 40.11 Amp. => 40 Amp.

Por lo tanto tendra que trabajarse con un conductor de calibre N8, pero por otra parte el conductor segn las normas deber trabajar al 80% de su capacidad, es por esto que utilizaremos un interruptor de 50 Amp. Y por consiguiente este conductor ser de un calibre N6.