Está en la página 1de 222

Technical Data

1756 ControlLogix I/O Specifications


Catalog Numbers 1756 series
Topic Additional Resources Available 1756 I/O Modules ControlLogix I/O Accessories Page 1 2 218

The ControlLogix architecture provides a wide range of input and output modules to span many applications, from high-speed digital to process control. The ControlLogix architecture uses Producer-Consumer technology, which allows input information and output status to be shared among multiple ControlLogix controllers. Each ControlLogix I/O module mounts in a ControlLogix chassis and requires either a removable terminal block (RTB) or a 1492 interface module (IFM) to connect all field-side wiring. RTBs and IFMs are not included with the I/O modules. They must be ordered separately.

Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

1756 ControlLogix I/O Specifications

Available 1756 I/O Modules


You can select these types of digital I/O modules.
Digital I/O Type Diagnostic Electronic fusing Individually isolated Description These modules provide diagnostic features to the point level. These modules have a D at the end of the catalog number. These modules have internal electronic fusing to prevent too much current from flowing through the module. These modules have an E at the end of the catalog number. These modules have individually isolated inputs or outputs. These modules have an I at the end of the catalog number.

I/O Type AC digital

Cat. No. 1756-IA8D 1756-IA16 1756-IA16I 1756-IA32 1756-IM16I 1756-IN16 1756-IB16 1756-IB16D 1756-IB16I 1756-IB16IF 1756-IB16IOSE 1756-IB32 1756-IC16 1756-IG16 1756-IH16I 1756-IH16ISOE 1756-IV16 1756-IV32 1756-OB8 1756-OB8EI

Page 3 6 9 12 75 78 15 18 21 25 28 31 34 66 69 72 94 97 117 121

Cat. No. 1756-LSC8XIB8I 1756-OA8D 1756-OA8E 1756-OA16 1756-OA16I 1756-ON8 1756-OB8I 1756-OB16D 1756-OB16E 1756-OB16I 1756-OB16IEF 1756-OB16IEFS 1756-OB16IS 1756-OB32 1756-OC8 1756-OG16 1756-OH8I 1756-OV16E 1756-OV32E 1756-OW16I 1756-OX8I

Page 209 103 106 109 113 182 125 128 132 135 138 142 146 150 154 176 179 186 190 194 197 158 162 165 169

DC digital

Contact Analog 1756-IF6CIS 1756-IF6I 1756-IF8 1756-IF16 1756-IF4FXOF2F 1756-IR6I 1756-IT6I 1756-IT6I2 1756-IF8H 1756-IF16H 1756-CFM 1756-HSC 38 42 47 55 62 81 86 90 51 59 200 205

1756-OF4 1756-OF6CI 1756-OF6VI 1756-OF8

HART interface Specialty

1756-OF8H 1756-LSC8XIB8I 1756-PLS

172 209 213

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IA8D
ControlLogix AC (79132V) diagnostic input module
Simplified Schematic +5V
Not Used

1756-IA8D
2 1

L1-0 Loss of Field Power


4 3

Input Display GND


+5V

Daisy Chain to Other RTBs

L2-0
6 5

IN-0 IN-1
8 7

L2-0

ControlLogix Backplane Interface Display

Group 0

L2-0
10 9

IN-2 IN-3
12 11

Group 0

Open Wire GND ControlLogix Backplane Interface


Group 1

L2-0 L2-1
14 13

47 k , 1/2 W 5% Resistor

IN-4 IN-5
16 15

L2-1 L2-1
18 17

IN-6 IN-7
20 19

Group 1

47 k , 1/2 W, 5% Resistor

L2-1

AC INPUT
ST 0 1 2 3 4 5 6 7 O FL T 012 345 67 K

L2-1 L2 L1

L1-1 Loss of Field Power

DIAG NO STIC

Table 1 - Diagnostic Specifications - 1756-IA8D


Attribute Open wire Loss of power Timestamp of diagnostics 1756-IA8D Off-state leakage current 1.5 mA min Transition range 4685V AC 1 ms

Table 2 - Technical Specifications - 1756-IA8D


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max 1756-IA8D 8 diagnostic (4 points/group) 120V AC 79132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 3 mA 0.58 W 4.5 W @ 60 C (140 F)

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 2 - Technical Specifications - 1756-IA8D (continued)


Attribute Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IA8D 15.35 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 16 mA @ 132V AC 250 mA 8.25 k @ 132V AC, 60 Hz 200 s750 ms Software configurable 200 s 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A None (open-style)

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 3 - Environmental Specifications - 1756-IA8D


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions 1756-IA8D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 3 - Environmental Specifications - 1756-IA8D (continued)


Attribute ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IA8D 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 Hz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 4 - Certifications - 1756-IA8D


Certification(1) UL CSA CE 1756-IA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IA16
ControlLogix AC (79132V) input module
1756-IA16
2 1

Simplified Schematic
Group 0

IN-1
4 3

IN-0 IN-2
6 5

IN-O L2-0 GND

+5V

Daisy Chain to Other RTBs

IN-3 IN-5
8 7

IN-4 IN-6
10 9

Group 0

IN-7 L2-0
12 11

L2-0 IN-8
14 13

ControlLogix Backplane Interface

Display

IN-9 IN-11
16 15

IN-10 IN-12
18 17

Group 1

IN-13 IN-15
20 19

Group 1

AC INPUT
ST 0 1 2 3 4 5 6 7 O FL T 012 345 67 K

IN-14 L2-1

L2-1

L2
DIAG NO STIC

L1

Table 5 - Technical Specifications - 1756-IA16


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IA16 16 (8 points/group) 120V AC 74132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 2 mA 0.58 W 5.8 W @ 60 C (140 F) 18.41 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 13 mA @ 132V AC

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 5 - Technical Specifications - 1756-IA16 (continued)


Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IA16 250 mA peak (decaying to <37% in 22 ms, without activation) 10.15 k @ 132V AC, 60 Hz 200 s750 ms Software configurable 200 s 125V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1200V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 None (open-style)

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 6 - Environmental Specifications - 1756-IA16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IA16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 6 - Environmental Specifications - 1756-IA16 (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1 1756-IA16 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

Table 7 - Certifications - 1756-IA16


Certification(1) UL CSA CE 1756-IA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IA16I
ControlLogix AC (79132V) isolated input module
Simplified Schematic IN-O L2-0 GND ControlLogix Backplane Interface Display
Jumper Bar (Cut to Length) Isolated Wiring L2-0 L2-2 L2-4 L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 L2-7 L2-8 L2-9 L2-10 L2-11

1756-IA161
2 4 6 8 10 1 3 5 7 9

+5V

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used

L1-0 L1-2 L1-4

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Additional jumper bars are available as cat. no. 1756-JMPR.

Nonisolated Wiring

L2-12 L2-13 L2-14 L2-15

L2

AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

L2-15 Not Used

L1

Daisy Chain to Other RTBs

Table 8 - Technical Specifications - 1756-IA16I


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max 1756-IA16I 16 individually isolated 120V AC 79132V AC, 4763 Hz 120V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 125 mA 3 mA 0.71 W 4.9 W @ 60 C (140 F) 16.71 BTU/hr 20V

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 8 - Technical Specifications - 1756-IA16I (continued)


Attribute Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type 1756-IA16I 2.5 mA 5 mA @ 79V AC, 4763 Hz 15 mA @ 132V AC, 4763 Hz 250 mA 8.8 k @ 132V AC, 60Hz 200 s750 ms Software configurable 200 s 125V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1200V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 9 - Environmental Specifications - 1756-IA16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IA16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

10

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 9 - Environmental Specifications - 1756-IA16I (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-IA16I 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1
,

Table 10 - Certifications - 1756-IA16I


Certification(1) UL CSA CE 1756-IA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

11

1756 ControlLogix I/O Specifications

1756-IA32
ControlLogix AC (74132V) input module
Simplified Schematic IN-O L2-0 GND ControlLogix Backplane Interface Display +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 L2-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 L2-1

1756-IA32
2 4 6 8 10 1 3 5 7 9

Group 0 Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 L2-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 L2-1

Group 0

Group 1

Group 1

AC INPUT
ST 0 1 2 3 4 5 6 7

1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6

1 1 1 9 2 7

1 2 2 0 2 8

1 3 2 1 2 9

1 4 2 2 3 0

1 O 5 K 2 3 3 1

L1

L2

Table 11 - Technical Specifications - 1756-IA32


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IA32 32 diagnostic (4 points/group) 120V AC 74132V AC, 4763 Hz 120V AC Hardware delay: 1.5 ms nom/10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 1 ms nom/8 ms max + filter time User-selectable filter time: 9 or 18 ms 165 mA 2 mA 0.9 W 6.1 W @ 60 C (140 F) 20.8 BTU/hr 20V 2.5 mA 5 mA @ 74V AC 15 mA @ 132V AC

12

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 11 - Technical Specifications - 1756-IA32 (continued)


Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IA32 390 mA 14.0 k @ 132V AC, 60 Hz 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4 None (open-style)

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 12 - Environmental Specifications - 1756-IA32


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IA32 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

13

1756 ControlLogix I/O Specifications

Table 12 - Environmental Specifications - 1756-IA32 (continued)


Attribute
EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

1756-IA32
4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

Table 13 - Certifications - 1756-IA32


Certification(1) UL CSA CE 1756-IA32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

14

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IB16
ControlLogix DC (1031.2V) input module
1756-IB16 Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
IN-1

IN-0 IN-2 IN-4 IN-6

Group 0
IN-3

Daisy Chain to Other RTBs

IN-5 IN-7 GND-0


Group 0

GND-0 IN-8

IN-9 IN-11

IN-10

DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15

Group 1
O K

IN-13

IN-12 IN14

Group 1

IN-15 GND-1

GND-1

DC COM

Table 14 - Technical Specifications - 1756-IB16


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IB16 16 (8 points/group) 12/24V DC sink 1031.2V DC 24V DC Hardware delay: 290 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 700 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 2 mA 0.56 W 5.1 W @ 60 C (140 F) 17.39 BTU/hr 5V 1.5 mA 2 mA @ 10V DC 10 mA @ 31.2V DC

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

15

1756 ControlLogix I/O Specifications

Table 14 - Technical Specifications - 1756-IB16 (continued)


Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IB16 250 mA peak (decaying to < 37% in 22 ms, without activation) 3.12 k @ 31.2V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T3C T3 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 15 - Environmental Specifications - 1756-IB16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IB16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

16

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 15 - Environmental Specifications - 1756-IB16 (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-IB16 10V/m with 1kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 16 - Certifications - 1756-IB16


Certification(1) UL CSA CE 1756-IB16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

17

1756 ControlLogix I/O Specifications

1756-IB16D
ControlLogix DC (1030V) diagnostic input module
Simplified Schematic Input IN-0 +5V ControlLogix Backplane Interface Display
Daisy Chain to Other RTBs GND-0 Group 0 GND-0 GND-0 GND-0 GND-1 GND-1 GND-1 GND-1
2 4 6 8 10 1 3 5 7 9

1756-IB16D
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used Group Leakage Resistor Group Leakage Resistor Group

GND-0 GND

Group 1

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group

Group 2

Open Wire

GND-2 GND-2 GND-2 GND-2 GND-3 GND-3

Group 3

GND-3 GND-3 GND-3 Not Used

DC INPUT
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 O K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

DC COM

Recommended Leakage Resistor Size 1/4 W, 5% 3.9K 5.6K 15K 20K

Supply Voltage 10V DC 12V DC 24V DC 30V DC

Table 17 - Diagnostic Specifications - 1756-IB16D


Attribute Open wire Timestamp of diagnostics 1756-IB16D Off-state leakage current 1.2 mA min 1 ms

Table 18 - Technical Specifications - 1756-IB16D


Attribute Inputs Voltage category Operating voltage range Input voltage, nom 1756-IB16D 16 diagnostic (4 points/group) 12/24V DC sink 1030V DC 24V DC

18

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 18 - Technical Specifications - 1756-IB16D (continued)


Attribute Input delay time (screw to backplane) Off to On 1756-IB16D Hardware delay: 340 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 740 s nom/4 ms max + filter time User-selectable filter time: 0, 1, 9, or 18 ms 150 mA 3 mA 0.84 W 5.8 W @ 60 C (140 F) 19.78 BTU/hr 5V 1.5 mA 2 mA @ 10V DC 13 mA @ 30V DC 250 mA 2.31 k @ 30V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T3C T3 None (open-style) Yes

On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

19

1756 ControlLogix I/O Specifications

Table 19 - Environmental Specifications - 1756-IB16D


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 20 - Certifications - 1756-IB16D


Certifications(1) UL CSA CE 1756-IB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick

20

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 20 - Certifications - 1756-IB16D


KC Ex Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16I
ControlLogix DC (1030V) isolated input module
1756-IB161 Simplified Schematic +5V IN-0
Source Input Wiring Isolated Wiring DC-0 (-) DC-1 (-) GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 Jumper Bar (Cut to Length) GND-8 GND-9 GND-10 GND-11 Nonisolated Wiring GND-12 GND-13 GND-14 GND-15 DC (-) GND-15 Not Used
10 1 3 5 7 9 2 4 6 8

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used

DC-0 (+) DC-1 (+)

GND-0 GND ControlLogix Backplane Interface Display

DC-5 (-) DC-6 (-)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

(+) (+)

DC-5 (+) DC-6 (+)

Sink Input Wiring

DC (+)

Additional jumper bars are available as cat. no. 1756-JMPR.

DC INPUT

Daisy Chain to Other RTBs

ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

21

1756 ControlLogix I/O Specifications

Table 21 - Technical Specifications - 1756-IB16I


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection 1756-IB16I 16 individually isolated 12/24V DC sink/source 1030V DC 24V DC Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 3 mA 0.58 W 5 W @ 60 C (140 F) 17.05 BTU/hr 5V 1.5 mA 2 mA @ 10 V DC 10 mA @ 30V DC 250 mA peak (decaying to < 37% in 22 ms, without activation) 3 k @ 30V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4 T4 None (open-style) Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

22

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 22 - Environmental Specifications - 1756-IB16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

23

1756 ControlLogix I/O Specifications

Table 23 - Certifications - 1756-IB16I


Certification(1) UL CSA CE 1756-IB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

24

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IB16IF
ControlLogix DC (1030V) sinking or sourcing, isolated, fast input module
Simplified Schematic IN-x Current Limiter Opto-isolator Display ControlLogix Backplane Interface

GND-x

Isolated Wiring
GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 DC (-) GND-15 Not Used

1756-IB16IF
2 4 6 8
10 1 3 5 7 9

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+) DC-1 (+) DC-2 (+)

DC-1 (-) DC-2 (-)

Source Input Wiring


DC-5 (-) DC-6 (-)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

(+) (+)

DC-5 (+) DC-6 (+)

Jumper Bar Cut to Length

Sink Input Wiring

Nonisolated Wiring

Additional jumper bars may be purchased by using catalog number 1756-JMPR.

Daisy Chain to Other RTBs DC INPUT


ST ST 01 2 3 4 5 6 7 8 9 10 11 12 13 14 15

O K

PEER DEVICE

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

25

1756 ControlLogix I/O Specifications

Table 24 - Technical Specifications - 1756-IB16IF


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IB16IF 16 individually isolated 12/24V DC sink/source 1030V DC 24V DC 14 s nom/23 s max + user-configurable filter time of 030,000 s 14 s nom/23 s max + user-configurable filter time of 030,000 s 275 mA 3 mA 1.47 W 3.8 W @ 60 C (140 F) 12.97 BTU/hr 5V 1.5 mA 2 mA @ 10 V DC 5 mA @ 30V DC 6 k @ 30V DC 200 s750 ms Software configurable 4 s for inputs < 4 kHz 13 s for inputs > 4 kHz 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 on signal ports(1) T4A T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

26

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 25 - Environmental Specifications - 1756-IB16IF


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16IF 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

27

1756 ControlLogix I/O Specifications

Table 26 - Certifications - 1756-IB16IF


Certification(1) c-UL-us CE 1756-IB16IF UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB16ISOE
ControlLogix DC (1055V) sequence of events input module
Simplified Schematic Electronic Current Limit Circuit IN-0
Isolated Wiring GND-0 GND-1 +5V GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 GND-6 DC-6 (-) GND-7 GND-8 Jumper Bar ControlLogix Display GND-9 (Cut to Length) Backplane GND-10 Interface GND-11 Nonisolated GND-12 Wiring GND-13 GND-14 Additional jumper bars are available GND-15 as cat. no. 1756-JMPR. GND-15 DC (-) Not Used DC-0 (-)
2 4 6 8 1 3 5 7

1756-IB16ISOE
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

GND-0

Daisy Chain to Other RTBs

SOE INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

28

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 27 - Technical Specifications - 1756-IB16ISOE


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On 1756-IB16ISOE 16 individually isolated, sequence of events 24/48V DC sink/source 1055V DC 24V DC Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 25 s nom/50 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) 320 mA 2 mA 1.7 W 5.5 W @ 60 C (140 F) 17.22 BTU/hr 5V 1.5 mA 2.0 mA @ 9V DC 4.5 mA @ 2431V DC 5.1 mA @ 4855V DC 10.8 k @ 55V DC 200 s750 ms Software configurable 100 s 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input-to-input Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4 T4 None (open-style) Yes

On to Off

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, nom On-state current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

29

1756 ControlLogix I/O Specifications

Table 28 - Environmental Specifications - 1756-IB16ISOE


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB16ISOE 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 2.5 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

30

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 29 - Certifications - 1756-IB16ISOE


Certification(1) UL CSA CE 1756-IB16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IB32
ControlLogix DC (1031.2V) input module
Simplified Schematic IN-0 GND-0
Group 0

1756-IB32 +5V
IN-1 IN-3 IN-5 IN-7 IN-9 IN-11 IN-13 IN-15 GND-0 IN-17 IN-19 IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 GND-1
2 4 6 8 10 1 3 5 7 9

Current Limiter

GND ControlLogix Display Backplane Interface

Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group 1

DC INPUT
ST 0 1 2 3 4 5 6 7

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 GND-0 IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 GND-1

Group 0

Group 1

1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6

1 1 1 9 2 7

1 2 2 0 2 8

1 3 2 1 2 9

1 4 2 2 3 0

1 O 5 K 2 3 3 1

DC COM

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

31

1756 ControlLogix I/O Specifications

Table 30 - Technical Specifications - 1756-IB32


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IB32 32 (16 points/group) 12/24V DC sink 1031.2V DC 24V DC Hardware delay: 380 s max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 420 s max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 120 mA 2 mA 0.66 W 6.2 W @ 60 C (140 F) 21.1 BTU/hr @ 60 C (140 F) 5V 2.27 mA 4.8 mA @ 10V DC 5.5 mA @ 31.2V DC 250 mA (decaying to < 37% in 22 ms, without activation) 5.67 k @ 31.2V DC 200 s750 ms Software configurable 200 s 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 - on signal ports(1) T4 T4 None (open-style) Yes

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

32

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 31 - Environmental Specifications - 1756-IB32


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IB32 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

33

1756 ControlLogix I/O Specifications

Table 32 - Certifications - 1756-IB32


Certification(1) c-UL-us CSA CE 1756-IB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IC16
ControlLogix DC (3060V) input module
1756-IC16 Simplified Schematic IN-0 GND-0
Group 0
2 1

+5V

IN-1
4 3

IN-0 IN-2
6 5

IN-3 IN-5
8 7

IN-4 IN-6
10 9

Group 0

GND ControlLogix Backplane Interface Display

IN-7 GND-0
12 11

GND-0 IN-8
14 13

IN-9 IN-11
16 15

IN-10 IN-11
18 17

Group 1

IN-13 IN-15
20 19

Group 1

DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

IN-14 GND-1

GND-1

Daisy Chain to Other RTBs

DC COM

34

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 33 - Technical Specifications - 1756-IC16


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IC16 16 (8 points/group) 48V DC sink 3055V DC @ 60 C (140 F) 3060V DC @ 55 C (131 F) 48V DC Hardware delay: 1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 4 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 100 mA 3 mA 0.58 W 5.2 W @ 60 C (140 F) 17.73 BTU/hr 10V 1.5 mA 2 mA @ 30V DC 7 mA @ 60V DC 250 mA 8.57 k @ 60V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane 125V (continuous), basic insulation type, input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s, inputs-to-backplane Routine tested @ 924V AC for 2 s, input group-to-group Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

35

1756 ControlLogix I/O Specifications

Table 34 - Environmental Specifications - 1756-IC16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IC16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

36

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 35 - Certifications - 1756-IC16


Certification(1) UL CSA CE 1756-IC16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

37

1756 ControlLogix I/O Specifications

1756-IF6CIS
ControlLogix sourcing current loop analog input module
1756-IF6CIS 2-wire Transmitter Connected to the Module and the Module Providing 24V DC Loop Power
2 1

1756-IF6CIS 2-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1

VOUT-1
4 3

VOUT-0 IN-0/I
6 5

VOUT-1
4 3

VOUT-0 i
A

IN-1/I RTN-1
8 7

IN-1/I
6 5

IN-0/I RTN-0
8 7

RTN-0 VOUT-2
10 9

RTN-1 VOUT-3
10 9

24V DC +

2-wire Transmitter

VOUT-3 IN-3/I
12 11

VOUT-2 IN-2/I
12 11

IN-2/I RTN-2
14 13

Shield Ground

IN-3/I RTN-3
14 13

RTN-3 Not Used


16 15

RTN-2 Not Used


16 15

Shield Ground

Not Used VOUT-4


18 17

Not Used VOUT-5


18 17

VOUT-5 IN-5/I
20 19

VOUT-4 IN-4/I
20 19

IN-4/I RTN-4

IN-5/I RTN-5

RTN-5

RTN-4

Place additional loop devices (such as strip chart recorders) at either A location in the current loop. 1756-IF6CIS 4-wire Transmitter Connected to the Module and an External, User-provided Power Supply Providing 24V DC Loop Power
2 1

VOUT-1
4 3

VOUT-0 IN-0/I
6 5

i
A + +

IN-1/I RTN-1
8 7

RTN-0 VOUT-2
10 9

4-wire Transmitter

24V DC

ANALOG INPUT CAL OK

VOUT-3 IN-3/I
12 11

IN-2/I RTN-2
14 13

RTN-3 Not Used


16 15

Shield Ground

Not Used VOUT-4


18 17

VOUT-5 IN-5/I
20 19

IN-4/I RTN-4

RTN-5

Place additional loop devices (such as strip chart recorders) at either A location in the current loop. User-supplied power supply must not exceed 150VA.

38

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 36 - Signal and User Counts - 1756-IF6CIS


Range 020 mA Low Signal and User Counts 0 mA -32768 counts High Signal and User Counts 21.09376 mA 32767 counts

Table 37 - Technical Specifications - 1756-IF6CIS


Attribute Inputs Input range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Sourcing voltage, min Sourcing voltage, max Sourcing current, max Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F), nom Calibrated accuracy 25 C (77 F), max Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module input scan time, min On-board data alarming Scaling to engineering units Real-time channel sampling Data format 1756-IF6CIS 6 individually isolated current sourcing 021 mA (over-range indication when exceeded) 16 bits 0.34 A/bit 250 mA 275 mA 7.9 W 5.1 W @ 60 C (140 F) 17.4 BTU/hr 215 , approx 20V DC 30V DC Current limited to < 30 mA Zero reading within 5 s 30V AC/DC with PTC and sense resistor 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 3262 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 0.025% of range 12 months 200 nA/C 17 ppm/C 0.36 A/C 35 ppm/C max 0.74 A/C max 0.2% of range 25 ms min floating point 10 ms min integer Yes Yes Yes Integer mode (left justified, 2s complement) IEEE 32-bit floating point

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

39

1756 ControlLogix I/O Specifications

Table 37 - Technical Specifications - 1756-IF6CIS (continued)


Attribute Module conversion method Isolation voltage 1756-IF6CIS Sigma-Delta 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(2) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 38 - Environmental Specifications - 1756-IF6CIS


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF6CIS 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

40

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 38 - Environmental Specifications - 1756-IF6CIS (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-IF6CIS 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

Table 39 - Certifications - 1756-IF6CIS


Certification(1) UL CSA CE 1756-IF6CIS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

41

1756 ControlLogix I/O Specifications

1756-IF6I
ControlLogix isolated voltage/current analog input module
1756-IF6I Current 2-wire
2 1

1756-IF6I Current 4-wire


2 1

IN-1/V
4 3

IN-0/V IN-0/I
6 5

+
2-wire Transmitter

IN-1/V
4 3

IN-0/V

IN-1/I RET-1
8 7

i A A

+
IN-0/I

IN-1/I
6 5

A A

4-wire Transmitter

RET-0 IN-2/V
10 9

RET-1
8 7

RET-0 IN-2/V
10 9

IN-3/V IN-3/I
12 11

IN-3/V IN-3/I
12 11

IN-2/I RET-2
14 13

IN-2/I RET-2
14 13

RET-3 Not Used Not Used


16 15

Shield Ground

RET-3 Not Used


16 15

Not Used IN-4/V


18 17

IN-5/V IN-4/V IN-5/I IN-4/I


20 19

IN-5/V
18 17

IN-4/I RET-4

IN-5/I
20 19

RET-5 RET-4

RET-5

Place additional loop devices (such as strip chart recorders) at either A location.

42

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IF6I Voltage
Voltage Input
2 1

IN-1/V
4 3

IN-0/V IN-0/I
6 5

+
User Analog Input Device

IN-1/I RET-1
8 7

RET-0 IN-2/V
10 9

Device External Power

IN-3/V IN-3/I
12 11

ANALOG INPUT CAL OK

IN-2/I RET-2
14 13

RET-3 Not Used


16 15

Not Used IN-4/V


18 17

IN-5/V IN-5/I
20 19

IN-4/I RET-4

Shield Ground

RET-5

Table 40 - Signal and User Counts - 1756-IF6I


Range 10V 010V 05V 020 mA Low Signal and User Counts -10.54688V -32768 counts 0V -32768 counts 0V -32768 counts 0 mA -32768 counts High Signal and User Counts 10.54688V 32767 counts 10.54688V 32767 counts 5.27344V 32767 counts 21.09376V 32767 counts

Table 41 - Technical Specifications - 1756-IF6I


Attribute Inputs Input range 1756-IF6I 6 individually isolated 10.5V 010.5V 05.25V 021 mA (over-range indication when exceeded) 16 bits 10.5V: 343 V/bit 010.5V: 171 V/bit 05.25V: 86 V/bit 021 mA: 0.34 A/bit 250 mA 100 mA

Resolution

Current draw @ 5.1V Current draw @ 24V

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

43

1756 ControlLogix I/O Specifications

Table 41 - Technical Specifications - 1756-IF6I (continued)


Attribute Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage 1756-IF6I 3.7 W Voltage: 3.7 W Current: 4.3 W Voltage: 12.62 BTU/hr Current: 14.32 BTU/hr Voltage: > 10 M Current: 249 Positive full scale reading within 5 s Voltage: 120V AC/DC Current: 8V AC/DC (with on-board current resistor) 60 dB @ 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 2 V/C Voltage: 35 ppm/C, 80 ppm/C max Current: 45 ppm/C, 90 ppm/C max 0.54% of range 25 ms min floating point 10 ms min integer(1) Yes Yes Yes Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(2) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

44

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 42 - Environmental Specifications - 1756-IF6I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF6I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

45

1756 ControlLogix I/O Specifications

Table 43 - Certifications - 1756-IF6I


Certification(1) UL CSA CE 1756-IF6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

46

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IF8
ControlLogix voltage/current analog input module
1756-IF8 Differential Current
Channel 0 Channel 0

1756-IF8 Differential Voltage +


Jumper Wires Shield Ground IN-0 IN-1 IN-2 IN-3 RTN IN-4 Channel 3 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used
2 4 6 8 10 1 3 5 7 9

i
A

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground

Shield Ground Channel 3 2-wire Transmitter

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

i
A

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-)

All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.

All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 2 channel, High Speed mode, only use channels 0 and 2.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

47

1756 ControlLogix I/O Specifications

1756-IF8 Single-ended Current


Channel 0

1756-IF8 Single-ended Voltage

i
IN-0 IN-1 IN-2
2 4 6 8 10 1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Jumper Wires

Channel 0

+
IN-0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

Shield Ground Channel 5

IN-1 IN-2 IN-3

IN-3 RTN

Shield Ground Channel 1

i
2-wire Transmitter

IN-4 IN-5 IN-6 IN-7 Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

RTN IN-4 IN-5 IN-6 IN-7 Not Used Not Used

Shield Ground

Not Used Not Used Not Used Not Used Not Used Not Used Not Used

All terminals marked RTN are connected internally. For current applications, all terminals marked iRTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and i RTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop.

All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring.

ANALOG INPUT CAL OK

48

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 44 - Technical Specifications - 1756-IF8


Attribute Inputs 1756-IF8 8 single-ended 4 differential 2 high-speed differential 10.25V 010.25V 05.125V 020.5 mA 10.25V: 320 V/count (15 bits plus sign bipolar) 010.25V: 160 V/count (16 bits) 05.125V: 80 /V count (16 bits) 020.5mA: 0.32 A/count (16 bits) 150 mA 40 mA 1.73 W Voltage: 1.73 W Current: 2.33 W Voltage: 5.88 BTU/hr Current: 7.92 BTU/hr Voltage: >1 M Current: 249 Differential voltage: Positive full scale reading within 5 s Single-ended/diff. current: Negative full scale reading within 5 s Single-ended voltage: Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 45 V/C Voltage: 15 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 8 pt single-ended (floating point): 16488 ms 4 pt differential (floating point): 8244 ms 2 pt differential (floating point): 5122 m(1) Yes Yes Yes Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), reinforced insulation type, inputs-to-backplane. No isolation between individual inputs Routine tested at 1350V AC for 2 s

Input range

Resolution

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min

On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

49

1756 ControlLogix I/O Specifications

Table 44 - Technical Specifications - 1756-IF8 (continued)


Attribute Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IF8 Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 2(2) T4A T4 None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 45 - Environmental Specifications - 1756-IF8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

50

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 46 - Certifications - 1756-IF8


Certification(1) UL CSA CE 1756-IF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IF8H
ControlLogix voltage/current analog input module with HART protocol
1756-IF8H Current
Voltage Input
2 Wire Current Input
2 Wire XMTR

1756-IF8H Voltage
+V IN0+ -V IN0IN1+ IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN72 4 6 8 1 3 5 7 I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

24V DC Power Supply

+ -

+-

IN0+ IN0IN1+

2 4 6 8

1 3 5 7

I RTN-0 NC I RTN-1 NC RTN I RTN-2 NC I RTN-3 NC I RTN-4 NC I RTN-5 NC RTN I RTN-6 NC I RTN-7 NC

ANALOG INPUT CAL OK HART

4 Wire Current Input

IN1RTN IN2+ IN2IN3+ IN3IN4+ IN4IN5+ IN5RTN IN6+ IN6IN7+ IN7-

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

24V DC Power Supply

+ + + 4 Wire XMTR - - -

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

51

1756 ControlLogix I/O Specifications

Table 47 - Technical Specifications - 1756-IF8H


Attribute Inputs Input range 1756-IF8H 8 differential voltage or current 10V 05V 15V 010V 020 mA 420 mA 1621 bits 300 mA 135 mA 4.77 W Voltage: 3.21 W Current: 4.01 W Voltage: 11.0 BTU/hr Current: 13.7 BTU/hr > 1 M voltage 250 current Positive full scale reading within 5 s Voltage: 30V DC Current: 8V DC > 80 dB @ 50/60 Hz > 100 dB @ 50/60 Hz Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months 90 V/C Voltage: 10 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 18488 ms (filter dependent) Typically 1 s per HART channel enabled. Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time Integer mode (left justified, 2s complement) IEEE 32-bit floating point Successive approximation R-Ladder DAC, monotonicity with no missing codes 50V (continuous), basic insulation type, input channels-to-backplane, and input channelto-channel Type tested at 1500V AC for 60 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1

Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time

Data format Input conversion method Output conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width

52

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 47 - Technical Specifications - 1756-IF8H (continued)


Attribute Wire category North American temperature code IEC temperature code Enclosure type 1756-IF8H 2 - on signal ports(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 48 - Environmental Specifications - 1756-IF8H


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF8H 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

53

1756 ControlLogix I/O Specifications

Table 49 - Certifications - 1756-IF8H


Certification(1) c-UL-us CSA CE 1756-IF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR101622C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

54

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IF16
ControlLogix voltage/current analog input module
1756-IF16 Differential Current
Channel 0

1756-IF16 Differential Voltage


Channel 0

i
A IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

Shield Ground Channel 3 2-wire Transmitter

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

i
A

Channel 3

Shield Ground

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-), i RTN-0 IN-2 (+), IN-3 (-), i RTN-2 IN-4 (+), IN-5 (-), i RTN-4 IN-6 (+), IN-7 (-), i RTN-6 IN-8 (+), IN-9 (-), i RTN-8 IN-10 (+), IN-11 (-), i RTN-10 IN-12 (+), IN-13 (-), i RTN-12 IN-14 (+), IN-15 (-), i RTN-14

Use this table when wiring your module in Differential mode. This channel Channel 0 Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Uses these terminals IN-0 (+), IN-1 (-) IN-2 (+), IN-3 (-) IN-4 (+), IN-5 (-) IN-6 (+), IN-7 (-) IN-8 (+), IN-9 (-) IN-10 (+), IN-11 (-) IN-12 (+), IN-13 (-) IN-14 (+), IN-15 (-)

All terminals marked RTN are connected internally. A 249 current loop resistor is located between IN-x and i RTN-x terminals. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Place additional loop devices (such as strip chart recorders) at the A location in the current loop. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.

All terminals marked RTN are connected internally. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a RTN terminal to maintain the modules accuracy. Terminals marked RTN or i RTN are not used for differential voltage wiring. IMPORTANT: When operating in 4 channel, High Speed mode, only use channels 0, 2, 4, and 6.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

55

1756 ControlLogix I/O Specifications

1756-IF16 Single-ended Current i


IN-0 IN-1 IN-2 Shield Ground 2-wire Transmitter IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15
2 4 6 8 10 1 3 5 7 9

1756-IF16 Single-ended Voltage

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15 Jumper Wires Shield Ground

IN-0 IN-1 IN-2 IN-3 RTN IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 RTN IN-12 IN-13 IN-14 IN-15

2 4 6 8 10

1 3 5 7 9

i RTN-0 i RTN-1 i RTN-2 i RTN-3 RTN i RTN-4 i RTN-5 i RTN-6 i RTN-7 i RTN-8 i RTN-9 i RTN-10 i RTN-11 RTN i RTN-12 i RTN-13 i RTN-14 i RTN-15

i
A

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Shield Ground

All terminals marked RTN are connected internally. For current applications, all terminals marked i RTN must be wired to terminals marked RTN. A 249 current loop resistor is located between IN-x and iRTN-x terminals. Place additional loop devices (such as strip chart recorders) at the A location in the current loop.

All terminals marked RTN are connected internally. Terminals marked i RTN are not used for single-ended voltage wiring.

ANALOG INPUT CAL OK HART

56

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 50 - Technical Specifications - 1756-IF16


Attribute Inputs Input range 1756-IF16 16 single ended, 8 differential or 4 differential (high speed) 10.25V 010.25V 05.125V 020.5 mA 320 V/count (15 bits + sign bipolar) @ 10.25V 160 V/count (16 bits) @ 010.25V 80 V/count (16 bits) @ 05.125V 0.32 A/count (16 bits) @ 020.5 mA 150 mA 65 mA 2.33 W Voltage: 2.3 W Current: 3.9 W Voltage: 7.84 BTU/hr Current: 13.3 BTU/hr Voltage: >10 M Current: 249 Differential voltage - Positive full scale reading within 5 s Single-ended/differential current - Negative full scale reading within 5 s Single-ended voltage - Even numbered channels go to positive full scale reading within 5 s, odd numbered channels go to negative full scale reading within 5 s Voltage: 30V DC Current: 8V DC >80 dB @ 50/60 Hz(1) >100 dB @ 50/60 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Voltage: Better than 0.05% of range Current: Better than 0.15% of range 45 V/C Voltage: 15 ppm/C Current: 20 ppm/C Voltage: 0.1% of range Current: 0.3% of range 16 pt single-ended: 16488 ms 8 pt differential: 8244 ms 4 pt differential: 5122 ms(1) Yes Yes Yes Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), reinforced insulation type, inputs-to-backplane No isolation between individual inputs Routine tested at 1350V AC for 2 s Electronic, software configurable

Resolution

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy 25 C (77 F) Offset drift Gain drift with temperature Module error Module input scan time, min

On-board data alarming Scaling to engineering units Real-time channel sampling Data format Module conversion method Isolation voltage

Module keying

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

57

1756 ControlLogix I/O Specifications

Table 50 - Technical Specifications - 1756-IF16 (continued)


Attribute Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IF16 1756-TBCH 1756-TBS6H User-defined mechanical 1 2(2) T4A T4 None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 51 - Environmental Specifications - 1756-IF16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

58

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 52 - Certifications - 1756-IF16


Certification(1) 1756-IF16

UL CSA CE

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-IF16H
ControlLogix current analog input module with HART protocol
2 Wire HART Device
2 Wire XMTR 24V DC Power Supply

+ -

+-

IN0+ IN1+ IN2+ IN3+

2 4 6 8 10

1 3 5 7 9

IN0IN1IN2IN3RTN IN4IN5IN6IN7IN8IN9IN10IN11RTN IN12IN13IN14IN15-

When a common supply is used you should tie the IN- to RTN.

4 Wire HART Device


24V DC Power Supply

RTN IN4+ IN5+ IN6+ IN7+ IN8+ IN9+

+ + -

+ -

4 Wire XMTR

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

ANALOG INPUT CAL OK HART

IN10+ IN11+ RTN IN12+ IN13+ IN14+ IN15+

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

59

1756 ControlLogix I/O Specifications

Table 53 - Technical Specifications - 1756-IF16H


Attribute Inputs Input range Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Repeatability Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module input scan time, min Module HART scan time 1756-IF16H 16 differential, current 020 mA 420 mA 1621 bits 200 mA 125 mA 4.02 W 6W 12 BTU/hr 249 Positive full scale reading within 5 s 8V DC 74 dB @ 50/60 Hz (15 Hz filter) 90 dB @ 60 Hz (20 Hz filter) > 90 dB @ 50/60 Hz (15 and 20 Hz filters only) Better than 0.01% of range (15 and 20 Hz filters only) Better than 0.13% of range (all filters) 12 months 27 V/C 11ppm/C 0.3% of range 11328 ms (filter dependent) Typically 1 s Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time Integer mode (left justified, 2s complement) IEEE 32-bit floating point Successive approximation R-Ladder DAC, monotonicity with no missing codes 50V (continuous), basic insulation type, inputs-to-backplane No isolation between individual inputs Type tested at 1500V DC for 60 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 2 - on signal ports(1) T5 T4 None (open-style)

Data format Input conversion method Output conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

60

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 54 - Environmental Specifications - 1756-IF16H


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IF16H 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 3 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 55 - Certifications - 1756-IF16H


Certification(1) c-UL-us CE 1756-IF16H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

61

1756 ControlLogix I/O Specifications

1756-IF4FXOF2F
ControlLogix high-speed input/output analog module
1756-IF4FXOF2F Current
(+) (-) i +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

1756-IF4FXOF2F Voltage
(+) (+) User Analog Input Device (-) Shield Ground +IN-1/V IN-1/I -IN-1 +IN-3/V IN-3/I -IN-3 Not Used

2-wire A Transmitter
A

2 1 4 3 6 5 8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 24 26 28 21 23 25 27

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 i I OUT-0 RTN-0 Not Used Not Used Not Used Not Used Not Used Not Used Not Used
A

2 1 4 3 6 5 8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

+IN-0/V IN-0/I -IN-0 +IN-2/V IN-2/I -IN-2 Not Used Not Used V OUT-0 I OUT-0 RTN-0 Not Used (-) Not Used Not Used Not Used Not Used Not Used Not Used Shield Ground (+)

Curren Output Load Shield Ground

Not Used V OUT-1 I OUT-1 RTN-1 Not Used Not Used Not Used Not Used Not Used Not Used Not Used

30 29 32 31 34 33 36 35

A = Inline field device (such as a strip chart recorder or meter)

ANALOG INPUT ANALOG OUTPUT CAL OK

Table 56 - Technical Specifications - 1756-IF4FXOF2F


Attribute Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, max Thermal dissipation Data format Isolation voltage 1756-IF4FXOF2F 375 mA 100 mA 4.3 W Voltage: 4.3 W Current: 4.7 W Voltage: 14.66 BTU/hr Current: 16.02 BTU/hr Integer mode (left justified, 2s complement) IEEE 32-bit floating point 250V (continuous), basic insulation type, inputs and outputs to backplane No isolation between individual inputs or outputs Routine tested at 1350V AC for 2 s Electronic, software configurable

Module keying

62

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 56 - Technical Specifications - 1756-IF4FXOF2F (continued)


Attribute Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IF4FXOF2F 1756-TBCH 1756-TBS6H User-defined mechanical 1 2(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 57 - Input Specifications - 1756-IF4FXOF2F


Attribute Number Input range

1756-IF4FXOF2F
4 high-speed, sub-millisecond, differential 10.5V 010.5V 05.25V 021 mA (over-range indication when exceeded) Approx 14 bits across 10.5V DC (21V total) 10.5V range: 1.3 mV/bit, 14-bit effective 010.5V range: 1.3 mV/bit, 13-bit effective 05.25V range: 1.3 mV/bit, 12-bit effective Approx 12 bits across 21 mA 021 mA range: 5.25 A/bit 1 Least Significant Bit (LSB)(1) Voltage: >1 M Current: 249 Positive full-scale reading within 1 s Voltage: 30V DC Current: 8V AC/DC 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months Voltage: 25 ppm/C max Current: 35 ppm/C max 0.2% of range 300 s min(2) Successive approximation

Resolution

Repeatability Input impedance Open circuit detection Overvoltage protection Calibrated accuracy @ 25 C (77 F) Calibration interval Gain drift with temperature Module error Module scan time Input conversion method

(1) Repeatability is defined as the stability of the input channel reading when a steady state signal is applied, for example, 1 LSB is one count (1.3 mV) from the nominal reading. (2) 300 s min for 1756-IF4FXOF2F/B, firmware revision 3.x or greater. 400 s min for 1756-IF4FXOF2F/A, firmware revision 1.x.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

63

1756 ControlLogix I/O Specifications

Table 58 - Output Specifications - 1756-IF4FXOF2F


Attribute Number Output range Resolution Open circuit detection Overvoltage protection Short circuit protection Drive capability Output settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Update period for all channels (RPI), min Output conversion method

1756-IF4FXOF2F
2 high-speed voltage or current 10.4V 021 mA 13 bits across 21 mA = 2.8 A/bit 14 bits across 21.8V = 1.3 mV/bit Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: >2000 Current: 0750 < 2 ms to 95% of final value with resistive loads 0.05% of range immediately after calibration Better than 0.1% of range within calibration interval 12 months 50 V/ C 1 A/ C Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.2% of range Current: 0.3% of range 1 ms R-Ladder DAC, monotonicity with no missing codes

Table 59 - Environmental Specifications - 1756-IF4FXOF2F


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IF4FXOF2F 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

64

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 59 - Environmental Specifications - 1756-IF4FXOF2F (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-IF4FXOF2F 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 60 - Certifications - 1756-IF4FXOF2F


Certification(1) UL CSA CE 1756-IF4FXOF2F UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

65

1756 ControlLogix I/O Specifications

1756-IG16
ControlLogix TTL input module
Standard Wiring
1756-IG16
DC
2 1

CE Compliant Wiring
1756-IG16
I/O Wire

IN-1

IN-0
4 3

IN-1
4 3

IN-0 IN-2
6 5

IN-3
6 5

IN-2 IN-4
8 7

5V DC

IN-3 IN-5
8 7

IN-5

IN-4 IN-6
10 9

I/O Wire

+
TTL Input Device

IN-7
+ DC

DC Power Wire

IN-7
10 9

IN-6
DC COM 0
12 11

DC-0(+) IN-9
14 13

DC-0(+)
12 11

DC COM 0

IN-8 IN-10
16 15

IN-9
14 13

IN-8 IN-10
16 15

IN-11
5V DC Power

IN-11 IN-13
18 17

IN-13
18 17

IN-12 IN-14
20 19

IN-12
IN-15

Capacitor 0.01 F Typical (See notes below.)

IN-15
20 19

IN-14
DC COM 1

DC-1(+)

DC COM 1

DC-1(+)

Simplified Schematic
+5 DC 1.5 K IN 1K 74HCT14 560

IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.

DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

1.5 K IN 1K 74HCT14 560

DC COM

Low to True Format - 1756-IG16


-0.20.8V = Input guaranteed to be in on-state 0.82.0V = Input state not guaranteed 2.05.5V = Input guaranteed to be in off-state

66

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 61 - Technical Specifications - 1756-IG16


Attribute Inputs Voltage category Operating voltage range Input delay time (screw to backplane) Off to On (5-to-0V DC transition) On to Off (0-to-5V DC transition) Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max Input impedance, max Input current, nom Input current, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IG16 16 (8 points/group) 5V DC TTL source (Low=True)(1) 4.55.5V DC 50 mV P-P ripple max Hardware delay: 270 s nom/450 s max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 390 s nom/ 700 s max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 110 mA 2 mA 0.61 W 1.4 W @ 60 C (140 F) 4.8 BTU/hr @ 60 C (140 F) 2V 4.1 mA 1.4 k min 1.5 k typical 3.7 mA @ 5V DC 4.1 mA @ 5V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(2) T5 T5 None (open-style) No

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

67

1756 ControlLogix I/O Specifications

Table 62 - Environmental Specifications - 1756-IG16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IG16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 1 kV at 5 kHz on signal ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4


Conducted RF immunity IEC 61000-4-6

Table 63 - Certifications - 1756-IG16


Certification(1) UL CSA CE 1756-IG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

68

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IH16I
ControlLogix DC (90146V) isolated input module
Simplified Schematic +5V IN-0 GND-0 GND ControlLogix Backplane Interface Display
DC-7 (-) Jumper Bar (Cut to Length) DC-0 (-) Isolated Wiring DC-3 (-) GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 GND-8 GND-9 GND-10 GND-11 GND-12 GND-13 GND-14 GND-15 GND-15 Not Used

1756-IH161
2 4 6 8 1 3 5 7

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Ysed

DC-0 (+)

DC-3 (+)

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

D C-7 (+ )

Nonisolated Wiring

Additional jumper bars are available as cat. no. 1756-JMPR.

DC (-)

DC (+)

DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Daisy Chain to Other RTBs

Table 64 - Technical Specifications - 1756-IH16I


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max 1756-IH16I 16 individually isolated 125V DC sink/source 90146V DC(1) 125V DC Hardware delay: 2 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 6 max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 125 mA 3 mA 0.71 W 5 W @ 60 C (140 F) 17.05 BTU/hr 20V DC

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

69

1756 ControlLogix I/O Specifications

Table 64 - Technical Specifications - 1756-IH16I (continued)


Attribute Off-state current, max On-state current, min On-state current, max On-state voltage Derated as follows 1756-IH16I 0.8 mA 1 mA @ 90V DC 3 mA @ 146V DC 90146V DC 90146V DC @ 50 C (122 F), 12 Channels ON 90132V DC @ 55 C (131 F), 14 Channels ON 90125V DC @ 60 C (140 F), 16 Channels ON 90146V DC @ 30 C (86 F), 16 Channels ON 250 mA 48.67 k @ 146V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(2) T4 None (open-style) Yes

Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type Reverse polarity protection

(1) 90146V DC @ 50 C (122 F),12 channels on 90132V DC @ 55 C (131 F), 14 channels on 90125V DC @ 60 C (140 F), 16 channels on 90146V DC @ 30 C (86 F), 16 channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 65 - Environmental Specifications - 1756-IH16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) 1756-IH16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing

70

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 65 - Environmental Specifications - 1756-IH16I (continued)


Attribute Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IH16I 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 66 - Certifications - 1756-IH16I


Certification(1) UL CSA CE 1756-IH16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

71

1756 ControlLogix I/O Specifications

1756-IH16ISOE
ControlLogix DC (90140V) sequence of events input module
Simplified Schematic IN-0 +5V
Isolated Wiring GND-0 GND-1 GND-2 GND-3 Source Input Wiring GND-4 DC-5 (-) GND-5 ControlLogix Display DC-6 (-) GND-6 Backplane GND-7 Interface GND-8 Jumper Bar GND-9 (Cut to Length) GND-10 GND-11 Nonisolated Additional jumper bars are available GND-12 Wiring GND-13 as cat. no. 1756-JMPR. GND-14 GND-15 GND-15 DC (-) Not Used DC-0 (-)
2 4 6 8 1 3 5 7

1756-IH16ISOE
Sink Input Wiring IN-0 DC-0 (+) IN-1 DC-1 (+) IN-2 IN-3 Source Input Wiring IN-4 DC-5 (+) IN-5 IN-6 DC - 6 ( + ) IN-7 IN-8 Sink Input Wiring IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used DC (+)

GND-0

10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

SOE INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15

Daisy Chain to Other RTBs

O K

Table 67 - Technical Specifications - 1756-IH16ISOE


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On 1756-IH16ISOE 16 individually isolated, sequence of events 125V DC sink/source 90140V DC 125V DC Hardware delay: 10 s nom/20 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) Hardware delay: 50 s nom/75 s max + firmware scan: up to 25 s + filter time: 050 ms + ASIC delay: 175 s (FIFO) or 625 s (Coordinated System Time per point) 275 mA 2 mA 1.3 W 5.5 W @ 60 C (140 F)

On to Off

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max

72

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 67 - Technical Specifications - 1756-IH16ISOE (continued)


Attribute Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type Reverse polarity protection 1756-IH16ISOE 17.22 BTU/hr 20V 0.3 mA 1.15 mA @ 90V DC 1.85 mA @ 140V DC 74.8 k 200 s750 ms Software configurable 100 s 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s, inputs-to-backplane Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T3C None (open-style) Yes

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 68 - Environmental Specifications - 1756-IH16ISOE


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions 1756-IH16ISOE 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

73

1756 ControlLogix I/O Specifications

Table 68 - Environmental Specifications - 1756-IH16ISOE (continued)


Attribute ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IH16ISOE 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 69 - Certifications - 1756-IH16ISOE


Certification(1) UL CSA CE 1756-IH16ISOE UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

74

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IM16I
ControlLogix AC (159265V) input module
Simplified Schematic
Isolated Wiring

1756-IM161 +5V
L2-0 L2-2 L2-4 L2-0 L2-1 L2-2 L2-3 L2-4 L2-5 L2-6 Jumper Bar (Cut to Length) L2-7 L2-8 L2-9 L2-10 L2-11 Nonisolated Wiring L2-12 L2-13 L2-14 L2-15 L2 L2-15 Not Used
2 4 6 8 10 1 3 5 7 9

IN-O L2-0 GND

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 IN-8 IN-9 IN-10 IN-11 IN-12 IN-13 IN-14 IN-15 Not Used Not Used L1

L1-0 L1-2 L1-4

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

ControlLogix Backplane Interface

Display

Additional jumper bars are available as cat. no. 1756-JMPR.

AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Daisy Chain to Other RTBs

Table 70 - Technical Specifications - 1756-IM16I


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On Onto Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max 1756-IM16I 16 individually isolated 240V AC 159265V AC, 4763 Hz(1) 240V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 3 mA 0.58 W 5.8 W @ 60 C (140 F) 19.78 BTU/hr 40V

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

75

1756 ControlLogix I/O Specifications

Table 70 - Technical Specifications - 1756-IM16I (continued)


Attribute Off-state current, max On-state current, min On-state current, max On-state voltage 1756-IM16I 2.5 mA 5 mA @ 159V AC, 60 Hz 13 mA @ 265V AC, 60 Hz 159265V AC, 4763Hz @ 30 C (86 F) all channels ON 159265V AC, 4763Hz @ 40 C (104 F) 8 points ON 159253V AC, 4763Hz @ 45 C (113 F) all channels ON 159242V AC, 4763Hz @ 60 C (140 F) all channels ON 250 mA 20.38 k @ 265V AC, 60 Hz 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(2) T4 None (open-style)

Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code Enclosure type

(1) 159265V AC, 4763Hz @ 30 C (86 F) all channels on 159265V AC, 4763Hz @ 40 C (104 F) 8 points on 159253V AC, 4763Hz @ 45 C (113 F) all channels on 159242V AC, 4763Hz @ 60 C (140 F) all channels on. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 71 - Environmental Specifications - 1756-IM16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) 1756-IM16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz

76

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 71 - Environmental Specifications - 1756-IM16I (continued)


Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IM16I 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 72 - Certifications - 1756-IM16I


Certification(1) FM CSA CE 1756-IM16I FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

77

1756 ControlLogix I/O Specifications

1756-IN16
ControlLogix AC (1030V) input module
Simplified Schematic IN-O L2-0 GND
IN-5 L2 Group 0 IN-7
10 9 8 7

1756-IN16 +5V
IN-1 L1 IN-3
6 5 4 3 2 1

IN-0 IN-2 IN-4 Group 0 IN-6 L2-0


12 11

ControlLogix Backplane Interface

Display

L2-0 IN-9
14 13

IN-8 IN-10
16 15

IN-11 Group 1 IN-13


18 17

AC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

IN-12 IN-14
20 19

Group 1

IN-15 L2-1

L2-1

Daisy Chain to Other RTBs

Table 73 - Technical Specifications - 1756-IN16


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max Inrush current, max 1756-IN16 16 (8 points/group) 24V AC 1030V AC, 4763 Hz 24V AC Hardware delay: 10 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 10 ms max + filter time User-selectable filter time: 9 or 18 ms 100 mA 2 mA 0.56 W 5.1 W @ 60 C (140 F) 17.39 BTU/hr 5V 2.75 mA 5 mA @ 10V AC, 60 Hz 1.2 mA @ 30V AC, 60 Hz 250 mA

78

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 73 - Technical Specifications - 1756-IN16 (continued)


Attribute Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IN16 2.5 k @ 30V AC, 60 Hz 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T3C T3 None (open-style)

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 74 - Environmental Specifications - 1756-IN16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IN16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

79

1756 ControlLogix I/O Specifications

Table 74 - Environmental Specifications - 1756-IN16 (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-IN16 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

Table 75 - Certifications - 1756-IN16


Certification(1) UL CSA CE 1756-IN16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

80

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IR6I
ControlLogix temperature sensing analog input module
1756-IR6I 3-wire RTD
2 1

IN-1/A
4 3

IN-0/A IN-0/B
6 5

IN-1/B RTN-1/C
8 7

RTN-0/C 3-wire RTD IN-2/A


10 9

IN-3/A IN-3/B
12 11

IN-2/B RTN-2/C
14 13

RTN-3/C Not used


16 15

Shield Ground

Not used IN-4/A


18 17

IN-5/A IN-5/B
20 19

IN-4/B RTN-4/C

RTN-5/C

IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x/B and RTN-x/C are shorted together as shown.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

81

1756 ControlLogix I/O Specifications

1756-IR6I 4-wire RTD


2 1

IN-1/A
4 3

IN-0/A IN-0/B
6 5

IN-1/B RTN-1/C
8 7

RTN-0/C 4-wire RTD IN-2/A


10 9

IN-3/A IN-3/B
12 11

ANALOG INPUT
IN-2/B RTN-2/C

RTN-3/C
14 13

CAL
Shield Ground

OK
Not used IN-4/A

Not used
16 15

IN-5/A
18 17

IN-5/B
20 19

IN-4/B RTN-4/C

RTN-5/C

Wiring is exactly the same as the 3-wire RTD with one wire left open.

Table 76 - Signal and User Counts - 1756-IR6I


Range 1487 21000 42000 84020 Low Signal and User Counts 0.859068653 -32768 counts 2 -32768 counts 4 -32768 counts 8 -32768 counts High Signal and User Counts 507.862 32767 counts 1016.502 32767 counts 2033.780 32767 counts 4068.392 32767 counts

82

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 77 - Technical Specifications - 1756-IR6I


Attribute Inputs Input range 1756-IR6I 6 individually isolated RTD 1487 21000 42000 84020 16 bits 1487 : 7.7 m/bit 21000 :15 m/bit 42000 :30 m/bit 84020 :60 m/bit 100, 200, 500, 1000 Platinum, alpha=385 100, 200, 500, 1000 Platinum, alpha=3916 120 Nickel, alpha=672 100, 120, 200, 500 Nickel, alpha=618 10 Copper 250 mA 125 mA 4.25 W 4.3 W 14.66 BTU/hr Negative full scale reading within 5 s with any combination of lost wires, except input terminal A alone. If input terminal A is lost by itself, the module reads a positive full scale reading within 5 s 24V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 10 M/C 50 ppm/C 90 ppm/C 0.54% of range 25 ms min floating point (ohms) 50 ms min floating point (temperature) 10 ms min integer (ohms)(1) Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH

Resolution

Sensors supported

Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Open circuit detection time

Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time

Data format Module conversion method Isolation voltage

Module keying Removable terminal block

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

83

1756 ControlLogix I/O Specifications

Table 77 - Technical Specifications - 1756-IR6I (continued)


Attribute RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-IR6I User-defined mechanical 1 2(2) T4A T4 None (open-style)

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 78 - Environmental Specifications - 1756-IR6I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IR6I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

84

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 79 - Certifications - 1756-IR6I


Certification(1) UL CSA CE 1756-IR6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

85

1756 ControlLogix I/O Specifications

1756-IT6I
ControlLogix temperature sensing analog input module
1756-IT61
2 1

+
IN-0

IN-0
4 3

Not Used Cold Junction Sensor Lug


6 5

Not Used RTN-0


8 7

RTN-1

IN-2 Thermocouple

IN-3
10 9

ANALOG INPUT
CJC+

Not Used
12 11

CAL
RTN-3

RTN-2
14 13

OK
CJC-

Not Used
16 15

Wire

IN-5
18 17

IN-4 Not Used


20 19

Not Used RTN-5

RTN-4

One CJC, part number 94238301, is shipped with the module. A replacement can be ordered as RP-94238301.

Table 80 - Signal and User Counts - 1756-IT6I


Range -1230 mV -1278 mV Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts

Table 81 - Technical Specifications - 1756-IT6I


Attribute Inputs Input range Resolution 1756-IT6I 6 individually isolated thermocouple 1 CJC -1278 mV -1230 mV (high resolution range) 16 bits -1278 mV: 1.4 V/bit (typical) -1230 mV: 0.7 V/bit (high resolution range) B, E, J, K, R, S, T, N, C

Thermocouples

86

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 81 - Technical Specifications - 1756-IT6I (continued)


Attribute Thermocouple linearization Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time 1756-IT6I ITS-90 250 mA 125 mA 4.3 W 4.3 W 14.66 BTU/hr >10 M Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 120 dB @ 60 Hz 100 dB @ 50 Hz 15 Hz (-3 dB)(1) <80 ms to 5% of full scale(1) Better than 0.1% of range 6 months 0.33.2 C, depending on channel 0.3 C 0.5 V/C 65 ppm/C 80 ppm/C 0.5% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(2) T4A T4 None (open-style)

Data format Module conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

87

1756 ControlLogix I/O Specifications

Table 82 - Thermocouple Ranges - 1756-IT6I


Attribute Thermocouple temperature/millivolt input range Thermocouple Type B Thermocouple Type C Thermocouple Type E Thermocouple Type J Thermocouple Type K Thermocouple Type N Thermocouple Type R Thermocouple Type S Thermocouple Type T Thermocouple resolution over temperature range, nom Type B, R, S, C Type E, J, K, T, N Type D Type TXK/XK (L) 1756-IT6I2 -1278 mV range 3001820 C (5723308 F) 02315 C (324199 F) -2701000 C (-4541832 F) -2101200 C (-3462192 F) -2701372 C (-4542502 F) -2701300 C (-4542372 F) -501768 C (-583215 F) -501768 C (-583215 F) -270400 C (-454752 F) -1278 mV range ~0.15 C (~0.28 F) ~0.05 C (~0.09 F) ~0.07 C (~0.13 F) ~0.02 C (~0.04 F) -1230 mV range Full range 01725 C (323137 F) -270415 C (-454 779 F) -210550 C (-3461022 F) -270725 C (-4541337 F) -270840 C (-4541544 F) Full range Full range Full range -1230 mV range ~0.08 C (~0.15 F) ~0.03 C (~0.05 F) ~0.03 C (~0.05 F) ~0.01 C (~0.02 F)

Table 83 - Environmental Specifications - 1756-IT6I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IT6I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

88

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 83 - Environmental Specifications - 1756-IT6I (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-IT6I 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

Table 84 - Certifications - 1756-IT6I


Certification(1) UL CSA CE 1756-IT6I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

89

1756 ControlLogix I/O Specifications

1756-IT6I2
ControlLogix enhanced thermocouple analog input module
1756-IT6I Cold Junction Sensor
Wire Spade Lug

Not Used CJC RTN-0

Not Used CJC+

Thermocouple

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 CJC+ Not used

Analog Input
RTN-1 CAL OK RTNRTN-3 RTNRTN-5 CJC Not used

Wire

Cold Junction Sensor

Spade Lug

Two CJCs, part number 94286501, are shipped with the module. Replacements can be ordered as RP-94286501.

Table 85 - Signal and User Counts - 1756-IT6I2


Range -1230 mV -1278 mV Low Signal and User Counts -15.80323 mV -32768 counts -15.15836 mV -32768 counts High Signal and User Counts 31.396 mV 32767 counts 79.241 mV 32767 counts

Table 86 - Technical Specifications - 1756-IT6I2


Attribute Inputs Input range Resolution 1756-IT6I2 6 individually isolated thermocouple 2 CJC -1278 mV (1.4 V per bit) -1230 mV (0.7 V per bit high resolution range) 16 bits -1278 mV: 1.4 V/bit -1230 mV: 0.7 V/bit B, E, J, K, R, S, T, N, C, D, L (TXK/XK) ITS-90 200 mA

Thermocouples Thermocouple linearization Current draw @ 5.1V

90

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 86 - Technical Specifications - 1756-IT6I2 (continued)


Attribute Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Input impedance Open circuit detection time Overvoltage protection, max Normal mode noise rejection Common mode noise rejection Channel bandwidth Settling time Calibrated accuracy @ 25 C Calibration interval Local CJC sensor accuracy Remote CJC sensor accuracy Offset drift Gain drift with temperature, nom 1756-IT6I2 150 mA 4.6 W 4.6 W 15.7 BTU/hr >10 M Positive full scale reading within 2 s 120V AC/DC 60 dB at 60 Hz(1) 160 dB min, tested @ 600V AC/60 Hz applied with 100 differential resistance 15 Hz(1) <80 ms to 5% of full scale(1) 0.05% of full range @ 25 C (77 F) typical Better than 0.1% of range @ 25 C (77 F) worst case 12 months 0.3 C 0.3 C 0.5 V/C 15 ppm/C 1.4 V/C for -1278 mV 0.6 V/C for -1230 mV 25 ppm/C 2.3 V/C for -1278 mV 1.1 V/C for -1230 mV 0.15% of range 25 ms min floating point (millivolt) 50 ms min floating point (temperature) 10 ms min integer (millivolt)(1) Integer mode (left justified, 2s complement) IEEE 32-bit floating point Sigma-Delta 250V (continuous), basic insulation type, input channels-to-backplane, and input channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH only User-defined mechanical 1 2(2) T4A T4 None (open-style)

Gain drift with temperature, max

Module error Module scan time

Data format Module conversion method Isolation voltage

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Notch filter dependent. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

91

1756 ControlLogix I/O Specifications

Table 87 - Thermocouple Ranges - 1756-IT6I2


Attribute Thermocouple temperature/millivolt input range Thermocouple Type B Thermocouple Type C Thermocouple Type E Thermocouple Type J Thermocouple Type K Thermocouple Type N Thermocouple Type R Thermocouple Type S Thermocouple Type T Thermocouple Type D Thermocouple Type L (TXK/XK) Thermocouple resolution over temperature range, nom Type B, R, S, C Type E, J, K, T, N Type D Type TXK/XK (L) 1756-IT6I2 -1278 mV range 3001820 C (5723308 F) 02315 C (324199 F) -2701000 C (-4541832 F) -2101200 C (-3462192 F) -2701372 C (-4542502 F) -2701300 C (-4542372 F) -501768 C (-583215 F) -501768 C (-583215 F) -270400 C (-454752 F) 02320 C (324208 F) -200800 C (-3281472 F) -1278 mV range ~0.15 C (~0.28 F) ~0.05 C (~0.09 F) ~0.07 C (~0.13 F) ~0.02 C (~0.04 F) -1230 mV range Full range 01725 C (323137 F) -270415 C (-454 779 F) -210550 C (-3461022 F) -270725 C (-4541337 F) -270840 C (-4541544 F) Full range Full range Full range 01718 C (323124 F) 200399 C (392750 F) -1230 mV range ~0.08 C (~0.15 F) ~0.03 C (~0.05 F) ~0.03 C (~0.05 F) ~0.01 C (~0.02 F)

Table 88 - Environmental Specifications - 1756-IT6I2


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-IT6I2 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

92

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 88 - Environmental Specifications - 1756-IT6I2 (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-IT6I2 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

Table 89 - Certifications - 1756-IT6I2


Certification(1) UL CSA CE 1756-IT6I2 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

93

1756 ControlLogix I/O Specifications

1756-IV16
ControlLogix DC (1030V) sourcing input module
1756-IV16 Simplified Schematic +5V DC-0+
Group 0 IN-3
6 5 2 1

IN-1
4 3

IN-0 IN-2 Group 0 IN-4


8 7

IN-0 GND ControlLogix Display Backplane Interface

IN-5 IN-7
10 9

IN-6 DC-0 +
12 11

DC-0 + IN-9
14 13

IN-8 IN-10
16 15

IN-11 Group 1 IN-13


18 17

IN-12 IN-14
20 19

Group 1

DC INPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 1 01 11 21 31 41 5K

IN-15 DC-1 +

DC-1 +

+
Daisy Chain to Other RTBs

DC COM

Table 90 - Technical Specifications - 1756-IV16


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IV16 16 (8 points/group) 12/24V DC source 1030V DC 24V DC Hardware delay: 280 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 110 mA 2 mA 0.61 W 5.41 W @ 60 C (140 F) 18.47 BTU/hr 5V DC 1.5 mA 2 mA @ 10V DC 10 mA @ 30V DC

94

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 90 - Technical Specifications - 1756-IV16 (continued)


Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IV16 250 mA 3.2 k @ 30V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 91 - Environmental Specifications - 1756-IV16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IV16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

95

1756 ControlLogix I/O Specifications

Table 91 - Environmental Specifications - 1756-IV16 (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-IV16 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 92 - Certifications - 1756-IV16


Certification(1) UL CSA CE 1756-IV16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

96

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-IV32
ControlLogix DC (1030V) sourcing input module
Simplified Schematic +5V DC-0+
IN-1 IN-3 IN-5 Group 0 IN-7 IN-9 IN-11

1756-IV32
2 4 6 8 10 1 3 5 7 9

IN-0 IN-2 IN-4 IN-6 IN-8 IN-10 IN-12 IN-14 DC-0 (+) IN-16 IN-18 IN-20 IN-22 IN-24 IN-26 IN-28 IN-30 DC-1 (+) Group 1 Group 0

IN-0

GND ControlLogix Backplane Interface Display


Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

IN-13 IN-15 DC-0 (+) IN-17 IN-19

Jumper Wire

IN-21 IN-23 IN-25 IN-27 IN-29 IN-31 DC-1 (+)

DC INPUT
ST 0 1 2 1 ST 8 9 0 11 1 ST 6 7 8 22 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 1 3 2 1 2 9 6 1 4 2 2 3 0 7 1 O 5 K 2 3 3 1

Group 1

DC COM

Table 93 - Technical Specifications - 1756-IV32


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state voltage, max Off-state current, max On-state current, min On-state current, max 1756-IV32 32 (16 points/group) 12/24V DC source 1030V DC 24V DC Hardware delay: 350 s nom/1 ms max + filter time User-selectable filter time: 0, 1, or 2 ms Hardware delay: 540 s nom/2 ms max + filter time User-selectable filter time: 0, 1, 2, 9, or 18 ms 120 mA 2 mA 0.66 W 4.1 W @ 60 C (140 F) 14 BTU/hr @ 60 C (140 F) 5V 1.5 mA 2 mA @ 10V DC 3.5 mA @ 30V DC

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

97

1756 ControlLogix I/O Specifications

Table 93 - Technical Specifications - 1756-IV32 (continued)


Attribute Inrush current, max Input impedance, max Cyclic update time Change of state Timestamp of inputs Isolation voltage 1756-IV32 250 mA (decaying to <37% in 22 ms, without activation) 8.6 k @ 30V DC 200 s750 ms Software configurable 200 s 250V (continuous), basic insulation type, inputs-to-backplane, and input group-to-group No isolation between individual group inputs Routine tested @ 1350V AC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 - on signal ports(1) T4A T4 None (open-style) Yes

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 94 - Environmental Specifications - 1756-IV32


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-IV32 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

98

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 94 - Environmental Specifications - 1756-IV32 (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-IV32 10V/m with 1k Hz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 95 - Certifications - 1756-IV32


Certification(1) UL CSA CE 1756-IV32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

99

1756 ControlLogix I/O Specifications

1756-OA8
ControlLogix AC (74265V) output module
1756-OA8 Simplified Schematic +5V L1-0
L1-0
4 3 2 1

OUT-0 OUT-1
6 5

L1-0 Group 0 L1-0


8 7

OUT-2 OUT-3
10 9

OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 20 A Current Surge

Group 0

L1-0 L1-0
12 11

Not Used OUT-4


14 13

L1-1 L1-1
16 15

OUT-5 OUT-6
18 17

Group 1

L1-1 L1-1
20 19

Group 1

OUT-7 Not Used L2

2A 0 43 ms

L1-1

Time

Daisy Chain to Other RTBs L1

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

Table 96 - Technical Specifications - 1756-OA8


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power 1756-OA8 8 (4 points/group) 2A 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 2 mA 1.07 W

100

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 96 - Technical Specifications - 1756-OA8 (continued)


Attribute Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Commutating voltage Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OA8 5.1 W @ 60 C (140 F) 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ <50 mA 2 A @ 60 C (140 F) linear derating 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Zero crossing 60V peak Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 1(2) T4A None (open style)

Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added across the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

101

1756 ControlLogix I/O Specifications

Table 97 - Environmental Specifications - 1756-OA8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 98 - Certifications - 1756-OA8


Certification(1) UL CSA CE 1756-OA8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

102

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OA8D
ControlLogix AC (74132V) diagnostic output module
Simplified Schematic
2

1756-OA8D
1

ControlLogix Backplane Interface

Diagnostic Control Block with Opto and Transformer Isolation


Short Verify/ No Load VAC GATE

Not Used

L2-0
4 3

L1
Group 0

L1-0
6 5

OUT-0 OUT-1
8 7

L1-0 L1-0
10 9

Group 0

OUT L2 Loss of Field Power


Daisy Chain to Other RTBs

OUT-2 OUT-3
12 11

Display

L1-0 L1-1
14 13

OUT-4 OUT-5
16 15

Surge Current Chart 8A Current 5A 1A 500 mA 0 Time Surge @ 30 C (86 F) Surge @ 60 C (140 F) Continuous @ 30 C (86 F) Continuous @ 60 C (140 F) 43 ms

L1-1 L1-1

OUT-6
18 17

Group 1 L1-1

Group 1 OUT-7

20

19

L1-1

L2-1 L2 Daisy Chain to Other RTBs L1

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

FLT 0 1 2 3 4 5 6 7

DIAGNOSTIC

Table 99 - Diagnostic Specifications - 1756-OA8D


Attribute Short trip, min No load Output verification Pulse test Field power loss (zero cross) Time stamp of diagnostics 1756-OA8D 12 A for 500 s Off-state detection only On-state detection only Configurable maximum width and max time delay from zero cross Detects at 25V peak min (firmware phase locked loop) 1 ms

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

103

1756 ControlLogix I/O Specifications

Table 100 - Technical Specifications - 1756-OA8D


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On 1756-OA8D 8 diagnostic, electronic fusing (4 points/group) 120V AC 74132V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 175 mA 250 mA 6.89 W 5.3 W @ 60 C (140 F) 18.0 BTU/hr 3 mA per point 2.5V peak @ 0.5 A 3V peak @ 1 A 1 A @ 30 C (86 F) linear derating 0.5 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 8 A for 43 ms per point, repeatable every 2 s @ 30 C (86 F) 5 A for 43 ms per point, repeatable every 1 s @ 60 C (140 F) 10 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s Zero crossing 25V peak Electronic, software configurable Electronically fused per point 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A None (open style)

On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage

Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

104

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 101 - Environmental Specifications - 1756-OA8D


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA8D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 102 - Certifications - 1756-OA8D


Certification(1) UL CSA CE 1756-OA8D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

105

1756 ControlLogix I/O Specifications

1756-OA8E
ControlLogix AC (74132V) electronically-fused output module
Simplified Schematic ControlLogix Backplane Interface Opto and Transformer Isolation
VAC GATE

1756-OA8E L1
2 1

Not Used
4 3

L2-0 OUT-0
6 5

Short

L1-0

OUT L2 Display Loss of Field Power

Group 0

L1-0
8 7

OUT-1 OUT-2
10 9

Group 0

L1-0 L1-0

OUT-3
12 11

Surge Current Chart 20 A Current Surge


Daisy Chain to Other RTBs L1-1 L1-1

OUT-4
14 13

OUT-5
16 15

L1-1
18 17

OUT-6 OUT-7
20 19

Group 1

L1-1 L1-1

Group 1

2A 0 43 ms

L2-1 L2 Daisy Chain to Other RTBs L1

Time

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7K

ELECTRONICALLY FUSED

Table 103 - Diagnostic Specifications - 1756-OA8E


Attribute Short trip, min Field power loss (zero cross) Time stamp of diagnostics 1756-OA8E >20 A for 100 ms Detects at 25V peak min (firmware phase locked loop) 1 ms

106

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 104 - Technical Specifications - 1756-OA8E


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On 1756-OA8E 8 electronic fusing (4 points/group) 2A 120V AC 74132V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA 250 mA 7.02 W 5.5 W @ 60 C (140 F) 18.76 BTU/hr 3 mA per point 4V peak @ 2 A 2 A @ 60 C (140 F) 4 A @ 30 C (86 F) linear derating 2 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 125V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1200V AC for 2 s Zero crossing 25V peak Electronic, software configurable Electronically fused per point 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A None (open style)

On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage

Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

107

1756 ControlLogix I/O Specifications

Table 105 - Environmental Specifications - 1756-OA8E


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA8E 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1k V line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 106 - Certifications - 1756-OA8E


Certification(1) UL CSA CE 1756-OA8E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

108

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OA16
ControlLogix AC (74265V) output module
Simplified Schematic ControlLogix Backplane +5V Interface L1-0
2 1

1756-OA16

OUT-1 Group 0 Daisy Chain to Other RTBs


4 3

OUT-0 OUT-2
6 5

OUT-3 OUT-5
8 7

(Fused per Group) Display

L2-0

OUT-4 OUT-6
10 9

Group 0

OUT-7 L1-0

L2-0
12 11

OUT-0 ControlLogix Backplane Interface

OUT-9
14 13

OUT-8 OUT-10
16 15

OUT-11

Surge Current Chart Surge Per Group

Group 1

OUT-13
18 17

OUT-12

L1
OUT-14

Group 1

OUT-15
20 19

20 A Current 5A 2A 500 mA 0

L1-1

L2-1

Per Group

43 ms Time

L1

L2

AC OUTPUT
ST 0 1 2 3 4 5 6 7 FUSE ST 8 9 10 11 12 13 14 15 FUSE O K

Table 107 - Diagnostic Specifications - 1756-OA16


Attribute Time stamp of diagnostics Fuse blown 1756-OA16 1 ms 1 fuse and indicator/group

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

109

1756 ControlLogix I/O Specifications

Table 108 - Technical Specifications - 1756-OA16


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On 1756-OA16 16 mechanically fused/group (8 points/group) 0.5 A 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 400 mA 2 mA 2.1 W 6.5 W @ 60 C (140 F) 22.17 BTU/hr 3 mA per point 1.5V @ 0.5 A 5.7V @ load current < 50 mA 0.5 A @ 60 C (140 F) 2 A @ 60 C (140 F) 4 A @ 60 C (140 F) 5 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 15 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Zero crossing 60V peak Electronic, software configurable Mechanically fused/group, 3.15 A @ 250V AC slow blow, 1500 A interruption current, Littelfuse p/n H2153.15 1756-TBNH 1756-TBSH User-defined mechanical 1

On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Surge current per group Load current, min Commutating voltage Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage

Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width

110

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 108 - Technical Specifications - 1756-OA16 (continued)


Attribute Wire category North American temperature code Enclosure type 1756-OA16 1(2) T4 None (open style)

(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 109 - Environmental Specifications - 1756-OA16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

111

1756 ControlLogix I/O Specifications

Table 110 - Certifications - 1756-OA16


Certification(1) UL CSA CE 1756-OA16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

112

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OA16I
ControlLogix AC (74265V) isolated output module
Simplified Schematic +5V L1-0
Isolated Wiring L1-0 L1-0 L1-1 L1-2 L1-3 L1-4 L1-4 L1-5 L1-6 L1-7 Jumper Bar (Cut to Length) L1-8 L1-9 L1-10 Nonisolated Wiring L1-11 L1-12 L1-13 L1-14 L1-15 L1 L1-15 Not Used
2 4 6 8 10 1 3 5 7 9

1756-OA161

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used L2

L2-0 L2-2 L2-4

OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 20 A Current

L1-2

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

2A 1A 0 Time 43 ms

Continuous @ 30 C (86 F) Continuous @ 60 C (140 F)

Daisy Chain to Other RTBs

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15 K

Additional jumper bars are available as cat. no. 1756-JMPR.

Table 111 - Technical Specifications - 1756-OA16I


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On 1756-OA16I 16 individually isolated 2A 120/240V AC 74265V AC 4763 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz

On to Off

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

113

1756 ControlLogix I/O Specifications

Table 111 - Technical Specifications - 1756-OA16I (continued)


Attribute Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Commutating voltage Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Inhibit voltage, max Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type 1756-OA16I 300 mA 2.5 mA 1.59 W 5.5 W @ 60 C (140 F) 18.76 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ load current < 50 mA 2 A @ 30 (86 F) linear derating 1 A @ 60 C (140 F) linear derating 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Zero crossing 60V peak Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(2) T4A None (open style)

(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

114

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 112 - Environmental Specifications - 1756-OA16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OA16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

115

1756 ControlLogix I/O Specifications

Table 113 - Certifications - 1756-OA16I


Certification(1) UL CSA CE 1756-OA16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

116

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OB8
ControlLogix DC (1030V) output module
Simplified Schematic DC-0(+) +5V OUT-0
Group 0

1756-OB8
Daisy Chain to Other RTBs
2 1

DC-0 (+)
4 3

OUT-0 OUT-1
6 5

DC-0 (+) DC-0 (+)

Group 0

OUT-2
8 7

ControlLogix Backplane Interface Display

RTN OUT-0

DC-0 (+)
10 9

OUT-3 RTN OUT-0


12 11

RTN OUT-0

Surge Current Chart


DC-1 (+)

4A

Surge
DC-1 (+) Group 1

OUT-4
14 13

OUT-5
16 15

Group 1 OUT-6

Current

Continuous @ 60 C (140 F) 2A

DC-1 (+)
18 17

DC-1 (+)
20 19

OUT-7 RTN OUT-1

RTN OUT-1

0 Time

10 ms
Daisy Chain to Other RTBs

DC COM

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

Table 114 - Technical Specifications - 1756-OB8


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V 1756-OB8 8 (4 points/common) 2A 12/24V DC source 1030V DC 1 ms max 2 ms max 165 mA 2 mA

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

117

1756 ControlLogix I/O Specifications

Table 114 - Technical Specifications - 1756-OB8 (continued)


Attribute Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB8 0.89 W 2.5 W @ 60 C (140 F) 8.53 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4A T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

118

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 115 - Environmental Specifications - 1756-OB8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

119

1756 ControlLogix I/O Specifications

Table 116 - Certifications - 1756-OB8


Certification(1) UL CSA CE 1756-OB8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

120

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OB8EI
ControlLogix DC (1030V) electronically-fused, isolated output module
+5V Simplified Schematic DC-0(+)
+ Isolated Wiring +

1756-OB8EI

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1

2 4 6 8 10

1 3 5 7 9

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Surge Current Chart 4A Surge

Nonisolated Wiring

RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7

Daisy Chain to Other RTBs

Current

Continuous @ 60 C (140 F) 2A
Daisy Chain to Other RTBs

Not Used Not Used

0 Time

10 ms

DC COM

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE 0 1 2 3 4 5 6 7 K

ELECTRONICALLY FUSED

Table 117 - Diagnostic Specifications - 1756-OB8EI


Attribute Short trip Timestamp of diagnostics 1756-OB8EI > 4.5 A for 500 s max (output on, then short) > 4.5 A for 1.5 ms max (output on into short) 1 ms

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

121

1756 ControlLogix I/O Specifications

Table 118 - Technical Specifications - 1756-OB8EI


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type 1756-OB8EI 8 individually isolated 2A 12/24V DC source 1030V DC 1 ms max 5 ms max 250 mA 2 mA 1.30 W 4.7 W @ 60 C (140 F) 16.03 BTU/hr 1 mA per point 1.2V DC @ 2 A 2 A @ 60 C (140 F) 10 A @ 60 C (140 F) 16 A @ 55 C (131F) linear derating 4 A for 10 ms each, repeatable every 2 s 3 mA Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per point 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

122

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 119 - Environmental Specifications - 1756-OB8EI


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8EI 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

123

1756 ControlLogix I/O Specifications

Table 120 - Certifications - 1756-OB8EI


Certification(1) UL CSA CE 1756-OB8EI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

124

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OB8I
ControlLogix DC (1030V) isolated output module
+5V Simplified Schematic DC-0(+)
Isolated Wiring

1756-OB8I

OUT-0 OUT-0 Display ControlLogix Backplane Interface Output Device RTN OUT-0

Surge Current Chart 4A Surge


Nonisolated Wiring

Daisy Chain to Other RTBs

Current

Continuous @ 60 C (140 F) 2A

Daisy Chain to Other RTBs

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not Used Not Used

2 1 4 3 6 5 8 7 10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used

0 Time

10 ms

DC OUTPUT
ST 01234567 O K

Table 121 - Technical Specifications - 1756-OB8I


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V 1756-OB8I 8 individually isolated 2A 12/24V DC source 1030V DC 1 ms max 2 ms max 165 mA

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

125

1756 ControlLogix I/O Specifications

Table 121 - Technical Specifications - 1756-OB8I (continued)


Attribute Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB8I 2 mA 0.89 W 4.6W @ 60 C (140 F) 15.70 BTU/hr 0.5 mA per point 0.5V DC @ 2 A 2 A @ 60 C (140 F) 16 A @ 60 C (140 F) 4 A for 10 ms each, repeatable every 1 s @ 60 C (140 F) 2 mA Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 122 - Environmental Specifications - 1756-OB8I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) 1756-OB8I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz

126

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 122 - Environmental Specifications - 1756-OB8I (continued)


Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB8I 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8k V air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 123 - Certifications - 1756-OB8I


Certification(1) UL CSA CE 1756-OB8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

C-Tick

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

127

1756 ControlLogix I/O Specifications

1756-OB16D
ControlLogix DC (19.230V) diagnostic output module
Simplified Schematic +5V +5V Short Circuit Detect Optoisolation +5V
+DC-0 +DC-0 +DC-0 +DC-0
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

+ DC
Daisy Chain to Other RTBs

1756-OB16D

OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used Group 1 Group 0

OUT ControlLogix Backplane Interface RTN Display Output Verify/No Load Surge Current Chart 4A Surge

Group 0

+DC-0 +DC-0 +DC-0 GND-0 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 +DC-1 GND-1 GND-1 Not Used

Group 1

Current

2A

Continuous @ 30 C (86 F) Continuous @ 60 C (140 F)

32
34 36

0 Time

10 ms

Daisy Chain to Other RTBs

DC COM

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FLT 0 1 2 3 4 5 6 7 K ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15 DIAGNOSTIC

Table 124 - Diagnostic Specifications - 1756-OB16D


Attribute Short trip No load Output verification Pulse test Time stamp of diagnostics 1756-OB16D 8 A for 180 ms, min 10 A for 120 ms, min Off-state detection only On-state detection only Configurable maximum pulse width 1 ms

128

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 125 - Technical Specifications - 1756-OB16D


Attribute Outputs Pilot duty 1756-OB16D 16 diagnostic (8 points/group) 2 A @ 30 C (86 F) DC-13SQ 1 A @ 60 C (140 F) linear derating 8 A combined continuous max @ 30 C (86 F) 4 A @ 60 C (140 F) 24V DC source 19.230V DC 60 s nom/1 ms max 630 s nom/5 ms max 250 mA 140 mA 4.64 W 3.3 W @ 60 C (140 F) 11.25 BTU/hr 1 mA per point 1.2V DC @ 2A 2 A @ 30 C (86 F) linear derating 1 A @ 60 C (140 F) linear derating 8 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 4 A for 10 ms per point, repeatable every 1 s 3 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per point 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A T4 None (open-style)

Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

129

1756 ControlLogix I/O Specifications

Table 126 - Environmental Specifications - 1756-OB16D


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16D 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1k Hz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

130

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 127 - Certifications - 1756-OB16D


Certification(1) UL CSA CE 1756-OB16D UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

131

1756 ControlLogix I/O Specifications

1756-OB16E
ControlLogix DC (1031.2V) electronically-fused output module
Display Simplified Schematic Optoisolation 1756-OB16E DC-0(+)
OUT-1
4 3 2 1

OUT-0 OUT-2
6 5

Group 0

OUT-3 OUT-5
8 7

Group 0

OUT-0 ControlLogix Backplane Interface Electronic Fuse Circuitry RTN OUT-0

Daisy Chain to Other RTBs

OUT-4 OUT-6
10 9

OUT-7 DC-0(+)
12 11

RTN OUT-0 OUT-8


14 13

Surge Current Chart Surge Continuous @ 60 C (140 F) 1A 0 Time 10 ms


Group 1

OUT-9 OUT-11
16 15

OUT-10 OUT-12
18 17

2A Current

OUT-13 OUT-15
20 19

Group 1 OUT-14 RTN OUT-1

DC-1(+)

DC COM

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O FUSE K ST 8 9 10 11 12 13 14 15 FUSE ELECTRONICALLY FUSED

Table 128 - Technical Specifications - 1756-OB16E


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max 1756-OB16E 16 electronically fused (8 points/group) 12/24V DC source 1031.2V DC 70 s nom/1 ms max 360 s nom/1 ms max 250 mA 2 mA 1.32 W 4.1 W @ 60 C (140 F) 13.98 BTU/hr 1 mA per point

132

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 128 - Technical Specifications - 1756-OB16E (continued)


Attribute On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB16E 400 mV DC @ 1 A 1 A @ 60 C (140 F) 8 A @ 60 C (140 F) 2 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 3 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per group 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 129 - Environmental Specifications - 1756-OB16E


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions 1756-OB16E 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

133

1756 ControlLogix I/O Specifications

Table 129 - Environmental Specifications - 1756-OB16E (continued)


Attribute ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16E 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 130 - Certifications - 1756-OB16E


Certification(1) UL CSA CE 1756-OB16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

134

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OB16I
ControlLogix DC (1030V) isolated output module
Simplified Schematic DC-0(+) +5V
DC-2 (+) Isolated Wiring DC-0 (+) DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

1756-OB16I
Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)

OUT-0 ControlLogix Backplane Interface Display

Sinking Output Wiring DC-6 (+) Jumper Bar (Cut to Length)

DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)

Surge Current Chart 4A Surge

Nonisolated Wiring

Current

2A 1A 0 Time

Continuous @ 30 C (86 F) Continuous @ 60 C (140 F)

DC(+)

DC-15 (+) Not Used

Daisy Chain to Other RTBs

10 ms

Additional jumper bars are available as cat. no. 1756-JMPR.

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Table 131 - Technical Specifications - 1756-OB16I


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V 1756-OB16I 16 individually isolated 2 A (DC-13SQ) 12/24V DC sink/source 1030V DC 1 ms max 2 ms max 350 mA

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

135

1756 ControlLogix I/O Specifications

Table 131 - Technical Specifications - 1756-OB16I (continued)


Attribute Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB16I 2.5 mA 1.8 W 3.6 W @ 60 C (140 F) 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C (86 F) 1 A @ 60 C (140 F) (linear derating) 8 A @ 30 C (86 F) 4 A @ 60 C (140 F) (linear derating) 4 A for 10 ms per point, repeatable every 2 s 1 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane 125V (continuous), basic insulation type, output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 132 - Environmental Specifications - 1756-OB16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) 1756-OB16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing

136

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 132 - Environmental Specifications - 1756-OB16I (continued)


Attribute Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16I 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 133 - Certifications - 1756-OB16I


Certification(1) UL CSA CE 1756-OB16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

137

1756 ControlLogix I/O Specifications

1756-OB16IEF
ControlLogix DC (1030V) electronically-protected, sinking or sourcing, isolated, fast output module
1756-OB16IEF DC-0(+) Isolator
DC-2 (+) Isolated Wiring DC-0 (+) DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

Simplified Schematic

Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)

OUT-0 Fault Display ControlLogix Backplane Interface

Sinking Output Wiring DC-6 (+) Jumper Bar (Cut to Length)

DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)

Surge Current Chart 4A Surge

Nonisolated Wiring

Current

Continuous 2A @ 45 C (113 F) 2A 1A 0 Time Continuous 1A @ 60 C (140 F)

DC(+)

DC-15 (+) Not Used

Daisy Chain to Other RTBs

10 ms Additional jumper bars may be purchased by using catalog number 1756-JMPR.

DC OUTPUT
ST DIAG ST DIAG 01 2 3 4 56 7 01 2 3 4 5 6 7 8 9 10 11 12 13 14 15 8 9 10 11 12 13 14 15

O K

PEER DEVICE

138

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 134 - Technical Specifications - 1756-OB16IEF


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time (backplane to screw) Off to On On to Off PWM cycle time PWM On time PWM On time accuracy Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point Duration of Fault mode per point Final state after Fault mode duration per point States in Program mode per point Isolation voltage 1756-OB16IEF 16 individually isolated 4 A inrush 12/24V DC sink/source 1030V DC 14 s nom/23 s max 14 s nom/23 s max 1 ms min/1 hour max 200 s min/1 hour max 20 s 320 mA 3 mA 1.7 W 4.9 W max (16 channels @ 1 A or 4 channels @ 2 A) 16.71 BTU/hr < 0.1 mA per point 0.2V DC @ 1 A 0.4V DC @ 2 A 2 A @ 45 C (113 F) 4 channels max 1 A @ 60 C (140 F) 16 A @ 60 C (86 F) 1 A max per channel 8 A @ 45 C (113 F) 2 A max per channel 4 A for 10 ms per point, repeatable every 2 s 1 mA per point CIP Sync only Hold last state, On or Off (Off is default) 1, 2, 5, 10 s, Forever (Forever is default) On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output Electronic, software configurable Electronically fused per point No 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 on signal ports(1)

Module keying Fusing Reverse polarity protection Removable terminal block RTB keying Slot width Wire category

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

139

1756 ControlLogix I/O Specifications

Table 134 - Technical Specifications - 1756-OB16IEF (continued)


Attribute North American temperature code IEC temperature code Enclosure type 1756-OB16IEF T4 T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 135 - Environmental Specifications - 1756-OB16IEF


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16IEF 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

140

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 136 - Certifications - 1756-OB16IEF


Certification(1) c-UL-us CE 1756-OB16IEF UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

141

1756 ControlLogix I/O Specifications

1756-OB16IEFS
ControlLogix DC (1030V) scheduled, electronically-protected, sinking or sourcing, isolated, fast output module
1756-OB16IEFS DC-0(+) Isolator
DC-2 (+) Isolated Wiring DC-0 (+) DC-0 (+) DC-1 (+) DC-2 (+) DC-3 (+) DC-4 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

Simplified Schematic

Isolated Sourcing Output Wiring OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Nonisolated Sourcing Output Wiring DC-6 (-) DC-2 (-) DC-0 (-)

OUT-0 Fault Display ControlLogix Backplane Interface

Sinking Output Wiring DC-6 (+) Jumper Bar (Cut to Length)

DC-5 (+) DC-6 (+) DC-7 (+) DC-8 (+) DC-9 (+) DC-10 (+) DC-11 (+) DC-12 (+) DC-13 (+) DC-14 (+) DC-15 (+)

Surge Current Chart 4A Surge

Nonisolated Wiring

Current

Continuous 2A @ 45 C (113 F) 2A 1A 0 Time Continuous 1A @ 60 C (140 F)

DC(+)

DC-15 (+) Not Used

Daisy Chain to Other RTBs

10 ms Additional jumper bars may be purchased by using catalog number 1756-JMPR.

DC OUTPUT
ST 0 1 2 3 4 5 6 7 FLT 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 FLT 8 9 10 11 12 13 14 15

O K

SCHEDULED

Table 137 - Technical Specifications - 1756-OB16IEFS


Attribute Outputs Pilot duty Voltage category Operating voltage range Unscheduled output delay time (backplane to screw) Off to On On to Off 1756-OB16IEFS 16 scheduled, individually isolated 4 A inrush 12/24V DC sink/source 1030V DC 14 s nom/23 s max 14 s nom/23 s max

142

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 137 - Technical Specifications - 1756-OB16IEFS (continued)


Attribute Schedule accuracy PWM cycle time PWM On time PWM On-time accuracy Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point Duration of Fault mode per point Final state after Fault mode duration per point States in Program mode per point Isolation voltage 1756-OB16IEFS 10 s nom when all components are synchronized to the current CIP Sync Grandmaster 1 ms min/1 hour max 200 s min/1 hour max 20 s 320 mA 3 mA 1.7 W 4.9 W max (16 channels @ 1 A or 4 channels @ 2 A) 16.71 BTU/hr < 0.1 mA per point 0.2V DC @ 1 A 0.4V DC @ 2 A 2 A @ 45 C (113 F) 4 channels max 1 A @ 60 C (140 F) 16 A @ 60 C (86 F) 1 A max per channel 8 A @ 45 C (113 F) 2 A max per channel 4 A for 10 ms per point, repeatable every 2 s 1 mA per point CIP Sync only Hold last state, On or Off (Off is default) 1, 2, 5, 10 s, Forever (Forever is default) On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), reinforced insulation type, outputs-to-backplane 250V (continuous), basic insulation type, output-to-output Type tested at 2300V AC for 60 s outputs-to-backplane Type tested at 1500V AC for 60 s output-to-output Electronic, software configurable Electronically fused per point No 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 on signal ports(1) T4 T4 None (open-style)

Module keying Fusing Reverse polarity protection Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

143

1756 ControlLogix I/O Specifications

Table 138 - Environmental Specifications - 1756-OB16IEFS


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16IEFS 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

144

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 139 - Certifications - 1756-OB16IEFS


Certification(1) c-UL-us CE 1756-OB16IEFS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

145

1756 ControlLogix I/O Specifications

1756-OB16IS
ControlLogix DC (1030V) scheduled, isolated output module
Simplified Schematic DC-0(+) +5V
Isolated Wiring DC-0 (+) DC-1 (+) DC-2 (+) DC-2 (+) DC-3 (+) DC-4 (+) Sinking Output Wiring DC-5 (+) DC-6 (+) DC-6 (+) + DC-7 (+) Jumper Bar DC-8 (+) (Cut to Length) DC-9 (+) DC-10 (+) DC-11 (+) Nonisolated DC-12 (+) Wiring DC-13 (+) DC-14 (+) DC-15 (+) DC(+) DC-15 (+) Not Used DC-0 (+)
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35

1756-OB16IS
OUT-0 OUT-1 OUT-2 OUT-3 OUT-4 OUT-5 OUT-6 OUT-7 OUT-8 OUT-9 OUT-10 OUT-11 OUT-12 OUT-13 OUT-14 OUT-15 Not Used Not Used DC(-) Isolated Sourcing Output Wiring DC-0 (-) DC-2 (-)

OUT-0 ControlLogix Backplane Interface Display

DC-6 (-)

Surge Current Chart 4A


Surge

Nonisolated Sourcing Output Wiring

Current

Continuous @ 30 C (86 F) 2A Continuous @ 60 C (140 F)

Daisy Chain to Other RTBs

0 Time

10 ms

Additional jumper bars are available as cat. no. 1756-JMPR.

DC OUTPUT
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 O K

146

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 140 - Technical Specifications - 1756-OB16IS


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing 1756-OB16IS 16 individually isolated, 8 scheduled 2 A (DC-13SQ) 12/24V DC sink/source 1030V DC 1 ms max 2 ms max 350 mA 2.5 mA 1.8 W 3.6 W @ 60 C (140 F) 12.28 BTU/hr 0.5 mA per point 1.2V DC @ 2 A 2 A @ 30 C (86 F) 1 A @ 60 C (140 F) (linear derating) 8 A @ 30 C (86 F) 4 A @ 60 C (140 F) (linear derating) 4 A for 10 ms per point, repeatable every 2 s 1 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM can be used to protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application-specific approval by the certifying agency. 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) Copper T4A T4 None (open-style)

Removable terminal block RTB keying Slot width Wire category Wire type North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

147

1756 ControlLogix I/O Specifications

Table 141 - Environmental Specifications - 1756-OB16IS


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB16IS 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

148

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 142 - Certifications - 1756-OB16IS


Certification(1) UL CSA CE 1756-OB16IS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

149

1756 ControlLogix I/O Specifications

1756-OB32
ControlLogix DC (1031.2V) output module
Simplified Schematic +5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface Display
Group 0

DC-0(+)
OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 OUT-23 OUT-25 OUT-27 OUT-29 OUT-31 DC-1(+)

1756-OB32
2 4 6 8 10 1 3 5 7 9

Daisy Chain to Other RTBs

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1

Group 0

Surge Current Chart

1A Current 0.5 A 0

Surge Continuous @ 60 C (140 F)

Group 1

Group 1

10 ms Time + _
DC COM

DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 4 11 12 12 90 22 78 5 6 11 3 4 22 1 2 23 9 0 7 1 O 5 K 2 3 3 1

150

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 143 - Technical Specifications - 1756-OB32


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point, max Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OB32 32 (16 points/group) 12/24V DC source 1031.2V DC 60 s nom/1 ms max 200 s nom/1 ms max 300 mA 2 mA 1.58 W 4.8 W @ 60 C (140 F) 16.37 BTU/hr 0.5 mA per point 200 mV DC @ 0.5 A 0.5 A @ 50 C (122 F) linear derating 0.35 A @ 60 C (140 F) 16 A @ 50 C (122 F) linear derating 10 A @ 60 C (140 F) 1 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 3 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-togroup No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM can be used to protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application-specific approval by the certifying agency. 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T3C T3 None (open-style)

Module keying Fusing

Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

151

1756 ControlLogix I/O Specifications

Table 144 - Environmental Specifications - 1756-OB32


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OB32 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

152

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 145 - Certifications - 1756-OB32


Certification(1) UL CSA CE 1756-OB32 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T3 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

153

1756 ControlLogix I/O Specifications

1756-OC8
ControlLogix DC (3060V) output module
Simplified Schematic +5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface
DC-0 (+) DC-0 (+)
4 3

DC-0(+)

1756-OC8
Daisy Chain to Other RTBs
2 1

OUT-0 OUT-1
6 5

DC-0 (+) Group 0 DC-0 (+)


8 7

Group 0 OUT-2 OUT-3

Display
RTN OUT-0

10

RTN OUT-0
12 11

Surge Current Chart 4A Surge


Group 1

DC-1(+)
14 13

OUT-4 OUT-5
16 15

DC-1(+) DC-1(+)
18 17

Group 1 OUT-6 OUT-7

Current

2A

Continuous @ 60 C (140 F)

DC-1(+)
20 19

RTN OUT-1

RTN OUT-1

0 Time

10 ms

DC COM

Daisy Chain to Other RTBs

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

154

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 146 - Technical Specifications - 1756-OC8


Attribute Outputs Pilot duty Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OC8 8 (4 points/group) 2A 48V DC source 3060V DC 1 ms, max 2 ms, max 165 mA 2 mA 0.89 W 4.9 W @ 60 C (140 F) 16.71 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 1 s @ 60 C (140 F) 2 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested at 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

155

1756 ControlLogix I/O Specifications

Table 147 - Environmental Specifications - 1756-OC8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OC8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

156

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 148 - Certifications - 1756-OC8


Certification(1) UL CSA CE 1756-OC8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

157

1756 ControlLogix I/O Specifications

1756-OF4
ControlLogix voltage/current output analog module
1756-OF4 Current
2 1

1756-OF4 Voltage
2 1

+
VOUT-0 IOUT-0

Not Used
4 3

VOUT-0 IOUT-0
6 5

i
A Current Output Load

Not Used
4 3

Not Used RTN


8 7

Not Used
6 5

RTN VOUT-1
10 9

RTN
8 7

RTN VOUT-1
10 9

Not Used Not Used


12 11

Not Used Not Used


Shield Ground
12 11

IOUT-1 VOUT-2
14 13

IOUT-1 VOUT-2
14 13

Shield Ground

Not Used Not Used


16 15

Not Used Not Used


16 15

IOUT-2 RTN
18 17

IOUT-2 RTN
18 17

RTN Not Used


20 19

RTN Not Used


20 19

VOUT-3 IOUT-3

VOUT-3 IOUT-3

Not Used

Not Used

Place additional loop devices (such as strip chart recorders) at the A location noted above. All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

ANALOG OUTPUT CAL OK

Table 149 - Signal and User Counts - 1756-OF4


Range 020 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

158

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 150 - Technical Specifications - 1756-OF4


Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy Calibration interval Offset drift Gain drift with temperature Module error Module scan time Data format Module conversion method Isolation voltage 1756-OF4 4 voltage or current outputs 10.4V 021 mA Voltage: 15 bits across 10.5V, 320 V/bit Current: 15 bits across 21mA, 650 nA/bit 150 mA 120 mA 5.8 W 3.25 W, 4 channel current 10.91 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21mA or less Voltage: >2000 Current: 0750 <2 ms to 95% of final value with resistive loads Better than 0.05% of range from 421 mA, -10.410.4V 12 months typical 50 V/ C 100 nA/C Voltage: 25 ppm/C, 520 V/C Current: 50 ppm/C, 1050 A/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point 8 ms integer Integer mode (left justified, 2s complement) IEEE 32-bit floating point R-Ladder DAC, monotonicity with no missing codes 250V (continuous), reinforced insulation type, output channels-to-backplane No isolation between individual output channels Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(1) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

159

1756 ControlLogix I/O Specifications

Table 151 - Environmental Specifications - 1756-OF4


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OF4 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

160

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 152 - Certifications - 1756-OF4


Certification(1) UL CSA CE 1756-OF4 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

161

1756 ControlLogix I/O Specifications

1756-OF6CI
ControlLogix current loop output analog module
1756-OF6CI 0550
2 1

1756-OF6CI 5511000
2 1

OUT-1
4 3

OUT-0

i
User Analog Output Device

OUT-1
4 3

OUT-0

i
User Analog Output Device

ALT-1
6 5

ALT-0 RTN-0
8 7

ALT-1
6 5

ALT-0 RTN-0
8 7

RTN-1 OUT-3
10 9

RTN-1 OUT-3
10 9

OUT-2

OUT-2

ALT-3
12 11

ALT-2 RTN-2
14 13

ALT-3
12 11

ALT-2 RTN-2
14 13

RTN-3 Not Used


16 15

RTN-3
Shield Ground

Not Used

Shield Ground Not Used

Not Used
16 15

OUT-5
18 17

OUT-4 ALT-4
20 19

OUT-5
18 17

OUT-4 ALT-4
20 19

ALT-5 RTN-5

ALT-5 RTN-5

RTN-4

RTN-4

Place additional devices anywhere in the loop.

Place additional devices anywhere in the loop.

ANALOG OUTPUT CAL OK

Table 153 - Signal and User Counts - 1756-OF6CI


Range 020 mA Low Signal and User Counts 0 mA -32768 counts High Signal and User Counts 21.074 mA 32767 counts

162

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 154 - Technical Specifications - 1756-OF6CI


Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time, max Data format Module conversion method Isolation voltage 1756-OF6CI 6 individually isolated 021 mA 13 bits across 21 mA (2.7 A) 250 mA for 0550 loads terminated on OUTs and RTNs 250 mA for 5511000 loads terminated on OUTs and ALTs 225 mA for 0550 loads terminated on OUTs and RTNs 300 mA for 5511000 loads terminated on OUTs and ALTs 6.7 W for 0550 range 8.5 W for 5511000 range 5.5 W (0550 loads) 6.1 W (5511000 loads) 18.76 BTU/hr (0550 loads) 20.80 BTU/hr (5511000 loads) None 24V DC Electronically current limited to 21 mA or less 01000 Separate field terminations for 0550 and 5511000 < 2 ms to 95% of final value with resistive loads Better than 0.1% of range from 421 mA 6 months typical 1 A/C typical 60 ppm/C 100 ppm/C 0.6% of range 25 ms floating point 10 ms integer Integer mode (left justified, 2s complement) IEEE 32-bit floating point R-Ladder DAC, monotonicity with no missing codes 250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(1) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

163

1756 ControlLogix I/O Specifications

Table 155 - Environmental Specifications - 1756-OF6CI


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OF6CI 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

164

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 156 - Certifications - 1756-OF6CI


Certification(1) UL CSA CE 1756-OF6CI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-OF6VI
ControlLogix voltage loop output analog module
1756-OF6VI
2 1

+
OUT-0 Not Used User Analog Output Device

OUT-1
4 3 5

Not Used
6

RTN-1
8 7

RTN-0 OUT-2
10 9

ANALOG OUTPUT CAL OK


Shield Ground

OUT-3 Not Used


12 11

Not Used RTN-2


14 13

RTN-3 Not Used


16 15

Not Used OUT-4


18 17

OUT-5 Not Used


20 19

Not Used RTN-4

RTN-5

Place additional devices anywhere in the loop.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

165

1756 ControlLogix I/O Specifications

Table 157 - Signal and User Counts - 1756-OF6VI


Range 10V Low Signal and User Counts -10.517V -32768 counts High Signal and User Counts 10.517V 32767 counts

Table 158 - Technical Specifications - 1756-OF6VI


Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Output impedance Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, nom Gain drift with temperature, max Module error Module scan time, max Data format Module conversion method Isolation voltage 1756-OF6VI 6 individually isolated 10.5V 14 bits across 21V (1.3 mV) (13 bits across 10.5V +sign bit) 250 mA 175 mA 5.5 W 4.85 W 16.54 BTU/hr <1 None 24V DC Electronically current limited > 1000 loads, 10 mA < 2 ms to 95% of final value with resistive loads Better than 0.1% of range 6 months typical 60 V/ C typical 50 ppm/C 80 ppm/C 0.5% of range 25 ms floating point 10 ms integer Integer mode (left justified, 2s complement) IEEE 32-bit floating point R-Ladder DAC, monotonicity with no missing codes 250V (continuous), basic insulation type, output channels-to-backplane, and output channel-to-channel Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(1)

Module keying Removable terminal block RTB keying Slot width Wire category

166

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 158 - Technical Specifications - 1756-OF6VI (continued)


Attribute North American temperature code IEC temperature code Enclosure 1756-OF6VI T4A T4 None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 159 - Environmental Specifications - 1756-OF6VI


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OF6VI 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF Immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

167

1756 ControlLogix I/O Specifications

Table 160 - Certifications - 1756-OF6VI


Certification(1) UL CSA CE 1756-OF6VI UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

168

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OF8
ControlLogix voltage/current output analog module
1756-OF8 Current
2 1

1756-OF8 Voltage
2 1

VOUT-4
4 3

VOUT-0 IOUT-0
6 5

i
A

VOUT-4
4 3

VOUT-0 IOUT-0
6 5

IOUT-4 RTN
8 7

RTN VOUT-1
10 9

Current IOUT-4 Output RTN Load


VOUT-5

RTN
8 7

VOUT-5 IOUT-5
12 11

VOUT-1
10 9

Shield Ground IOUT-1

IOUT-1 Shield Ground VOUT-2


14 13

IOUT-5
12 11

VOUT-6 IOUT-6
16 15

VOUT-6
14 13

VOUT-2 IOUT-2
16 15

IOUT-2 RTN
18 17

IOUT-6 RTN
18 17

RTN VOUT-7
20 19

RTN VOUT-3
20 19

VOUT-3 IOUT-3

VOUT-7 IOUT-7

IOUT-7

IOUT-3

Place additional loop devices (such as strip chart recorders) at the A location noted above. All terminals marked RTN are connected internally.

All terminals marked RTN are connected internally.

ANALOG OUTPUT CAL OK

Table 161 - Signal and User Counts - 1756-OF8


Range 020 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

169

1756 ControlLogix I/O Specifications

Table 162 - Technical Specifications - 1756-OF8


Attribute Outputs Output range Resolution Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Open circuit detection Overvoltage protection Short circuit protection Drive capability Settling time Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature, max Module error Module scan time, min Data format Module conversion method Isolation voltage 1756-OF8 8 voltage or current 10.4V 021 mA 15 bits across 21 mA - 650 nA/bit 15 bits across 10.4V - 320 V/bit 150 mA 210 mA 5.8 W 4.92 W, 8 channel current 16.78 BTU/hr Current output only (Output must be set to >0.1 mA) 24V DC Electronically current limited to 21 mA or less Voltage: > 2000 Current: 0750 < 2 ms to 95% of final value with resistive loads Better than 0.05% of range from 421 mA, -10.410.4V 12 months typical 50 V/C typical (Voltage mode) 0.1 A/C typical (Current mode) Voltage: 25 ppm/C max Current: 50 ppm/C max Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point 8 ms integer Integer mode (left justified, 2s complement) IEEE 32-bit floating point R-Ladder DAC, monotonicity with no missing codes 250V (continuous), reinforced insulation type, output channels-to-backplane No isolation between individual output channels Routine tested at 1350V AC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(1) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

170

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 163 - Environmental Specifications - 1756-OF8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OF8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

171

1756 ControlLogix I/O Specifications

Table 164 - Certifications - 1756-OF8


Certification(1) UL CSA CE 1756-OF8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

1756-OF8H
ControlLogix voltage/current output analog module with HART protocol
1756-OF8H

ANALOG OUTPUT CAL OK HART

172

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 165 - Signal and User Counts - 1756-OF8H


Range 020 mA 10V Low Signal and User Counts 0 mA -32768 counts -10.4336V -32768 counts High Signal and User Counts 21.2916 mA 32767 counts 10.4336V 32767 counts

Table 166 - Technical Specifications - 1756-OF8H


Attribute Outputs Output range 1756-OF8H 8 voltage or current 10.4V 020 mA 420 mA 1516 bits 200 mA 230 mA 6.54 W 4.92 W, 8 channel current 16.78 BTU/hr Voltage: >2 k @ 10.4V Current: 50750 drive Current output only (output must be set to < 0.1mA) 24V DC Voltage: > 2000 @ 10.4V Current: 50750 with short circuit survival current Voltage: 1 F Current: 10 H Current (no HART): < 23 ms to 95% with resistive loads Current (with HART): < 37 ms to 95% with resistive loads Voltage: < 8.5 ms to 95% with resistive loads Voltage: Better than 0.05% of range Current: Better than 0.15% of range 12 months typical 100 V/C typical 200 nA/C typical Voltage: 20 ppm/C Current: 35 ppm/C Voltage: 0.15% of range Current: 0.3% of range 12 ms floating point Typically 1 s per HART channel enabled Estimate 10 s if all 8 channels have HART enabled Pass through messages, handheld communicators, secondary masters, communication errors, or configuration changes can significantly increase the update time Integer mode (left justified, 2s complement) IEEE 32-bit floating point Successive approximation

Resolution Current draw @ 5V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Output impedance Open circuit detection time Overvoltage protection, max Drive capability Load reactance, max Settling time

Calibrated accuracy @ 25 C (77 F) Calibration interval Offset drift Gain drift with temperature Module error Module output scan time, min Module HART scan time

Data format Input conversion method

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

173

1756 ControlLogix I/O Specifications

Table 166 - Technical Specifications - 1756-OF8H (continued)


Attribute Output conversion method Isolation voltage 1756-OF8H R-Ladder DAC, monotonicity with no missing codes 50V (continuous), basic insulation type, output channels-to-backplane No isolation between individual output channels Type tested at 1500V AC for 60 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical 1 2(1) T4A T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 167 - Environmental Specifications - 1756-OF8H


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OF8H 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

174

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 167 - Environmental Specifications - 1756-OF8H (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-OF8H 2 kV at 5 kHz on shielded signal ports 2 kV line-earth (CM) on shielded signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

Table 168 - Certifications - 1756-OF8H


Certification(1) c-UL-us CSA CE 1756-OF8H UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR101622C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

175

1756 ControlLogix I/O Specifications

1756-OG16
ControlLogix TTL output module
1756-OG16 Standard Wiring
DC
2 1

1756-OG16 CE Compliant Wiring


+ DC Power Wire
2 1 3

OUT-1
4 3

OUT-0 OUT-2
6 5

5V DC Power

OUT-1
4

OUT-0 OUT-2

+5 V DC

OUT-3 OUT-5
8 7

OUT-3
6 5

OUT-4 OUT-6
10 9

OUT-5
8 7 9

OUT-4
10

OUT-7 + DC DC-0(+)
12 11

DC COM 0 OUT-8
14 13

I/O Wire

OUT-7 DC-0(+)
12 11

OUT-6 DC COM 0 OUT-8

OUT-9 OUT-11
16 15 17 19

OUT-10
18 20

TTL Output Device

OUT-9
14 13

OUT-11
Capacitor 0.01 F Typical (See notes below.)
16 15

OUT-10 OUT-12
18 17

OUT-13 OUT-15 DC-1(+)

OUT-12 OUT-14 DC COM 1

OUT-13 OUT-15
20 19

OUT-14 DC COM 1

DC-1(+)

Simplified Schematic
+5 DC 74AC14 OUT

IMPORTANT: I/O cables must be shielded type and cable length must be <10 m (32.8 ft) for maximum EMI noise immunity.

DC OUTPUT
ST 0 1 2 3 4 5 6 7 ST 8 9 10 11 12 13 14 15 O K

74AC14 OUT

DC COM

Low to True Format - 1756-OG16


00.4V DC = Output guaranteed to be in on-state 0.44.5V DC = Output state not guaranteed 4.55.5V DC = Output guaranteed to be in off-state

176

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 169 - Technical Specifications - 1756-OG16


Attribute Outputs Voltage category Operating voltage range Output delay time (resistive load) Off to On (5V-to-0V DC transition) On to Off (0V-to-5V DC transition) Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Continuous current, max Load current per point, max Load current per module, max Load current Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OG16 16 (8 points/group) 5V DC TTL (Low=True(1) 4.55.5V DC source, 50 mV P-P ripple max 45 s nom/450 s max 145 s nom/700 s max 210 mA 2 mA 1.12 W 1.5 W @ 60 C (140 F) 5.2 BTU/hr @ 60 C (140 F) 0.1 mA per point 0.4V DC 24 mA 24 mA 384 mA 0.15 mA Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-togroup No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 2(2) T5 T5 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in your program to convert to traditional True - High logic. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

177

1756 ControlLogix I/O Specifications

Table 170 - Environmental Specifications - 1756-OG16


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OG16 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Conducted RF immunity IEC 61000-4-6

Table 171 - Certifications - 1756-OG16


Certification(1) UL CSA CE 1756-OG16 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T5 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

178

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OH8I
ControlLogix DC (90146V) isolated output module
Simplified Schematic +5V OUT-0 RTN OUT-0 ControlLogix Backplane Interface Display Surge Current Chart 4A Current Surge
Non-Isolated Wiring +

DC-0

1756-OH81
Isolated Wiring +

DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7 Not used Not used

2 4 6 8 10

1 3 5 7 9

OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not used Not used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Continuous @ 60 C (140 F) 2A

Daisy chain to other RTBs

Time

10 ms

Daisy chain to other RTBs

DC COM

DC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

Table 172 - Technical Specifications - 1756-OH8I


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V 1756-OH8I 8 individually isolated 120V DC sink/source 90146V DC 2 ms max 2 ms max 210 mA 2 mA

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

179

1756 ControlLogix I/O Specifications

Table 172 - Technical Specifications - 1756-OH8I (continued)


Attribute Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type 1756-OH8I 1.11 W 3.3 W @ 60 C (140 F) 11.25 BTU/hr 1 mA per point 2V DC @ 2 A 2 A @ 60 C (140 F) 8 A @ 60 C (140 F) 4 A for 10 ms per point, repeatable every 1 s @ 60 C (140 F) 2 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 173 - Environmental Specifications - 1756-OH8I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 1756-OH8I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g

180

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 173 - Environmental Specifications - 1756-OH8I (continued)


Attribute Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OH8I 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 1V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 174 - Certifications - 1756-OH8I


Certification(1) UL CSA CE 1756-OH8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

181

1756 ControlLogix I/O Specifications

1756-ON8
ControlLogix AC (1030V) output module
Simplified Schematic +5V L1-0
Daisy Chain to Other RTBs
2 1

1756-ON8

L1-0
4 3

OUT-0 OUT-1
6 5

L1-0

OUT-0
Group 0

ControlLogix Backplane Interface Display Surge Current Chart 20 A Current Surge

L1-0
8 7

OUT-2 OUT-3
10 9

Group 0

L1-0 L1-0
12 11

Not Used OUT-4


14 13

L1-1 L1-1 Group 1 L1-1


18 17 16 15

OUT-5 Group 1 OUT-6 OUT-7


20 19

2A 0 43 ms

L1-1 L1-1

Not Used

L2

Time

L1

AC OUTPUT
ST 0 1 2 3 4 5 6 7 O K

Table 175 - Technical Specifications - 1756-ON8


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On 1756-ON8 8 (4 points/group) 24V AC 1030V AC, current >50 mA, 4763Hz 1630V AC, current <50 mA, 4763Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 9.3 ms @ 60 Hz 11 ms @ 50 Hz 200 mA

On to Off Current draw @ 5.1V

182

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 175 - Technical Specifications - 1756-ON8 (continued)


Attribute Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Commutating voltage Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-ON8 2 mA 1.07 W 5.1 W @ 60 C (140 F) 17.39 BTU/hr 3 mA per point 1.5V peak @ 2 A 6V peak @ load current < 50 mA 2 A @ 60 C (140 F) 5 A @ 30 C (86 F) linear derating 4 A @ 60 C (140 F) linear derating 20 A for 43 ms per point, repeatable every 2 s @ 60 C (140 F) 10 mA per point 4V/s for loads > 50 mA 0.2V/s for loads < 50 mA(1) Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-togroup No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBNH 1756-TBSH User-defined mechanical 1 1(2) T4A T4 None (open style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loads under 50 mA. The commutating dv/dt rating of the module for loads 50500 mA (OUTPUT to L2) is 4V/ ms maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating dv/dt rating is exceeded in the 1050 mA range, a resistor may be added AC ross the output and L2. The purpose of this resistor is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50500 mA range, the L1 AC waveform could be at fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened sections. (2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

183

1756 ControlLogix I/O Specifications

Table 176 - Environmental Specifications - 1756-ON8


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-ON8 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

184

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 177 - Certifications - 1756-ON8


Certification(1) UL CSA CE 1756-ON8 UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick Ex

FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

185

1756 ControlLogix I/O Specifications

1756-OV16E
ControlLogix DC (1030V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation DC-0(+) OUT-0
Group 0 OUT-1
4 3

1756-OV16E
2 1

OUT-0 OUT-2
6 5

OUT-3 OUT-5
8 7

OUT-4 OUT-6
10 9

Group 0

ControlLogix Backplane Interface

Electronic Fuse Circuitry

RTN OUT-0

OUT-7 DC-0(+)
12 11

RTN OUT-0 OUT-8


14 13

OUT-9 OUT-11

OUT-10
16 15

Surge Current Chart


Group 1

OUT-13
18 17

OUT-12 OUT-14
20 19

Group 1

2A Current 1A 0

Surge Continuous @ 60 C (140 F)

OUT-15 DC-1(+)

RTN OUT-1

10 ms Time
Daisy Chain to Other RTBs

DC COM Daisy Chain to Other RTBs

DC O UTPUT
ST 0 1 2 3 4 5 6 7 FU SE FU SE E LE C TR O NIC ALLYFU SE D O K ST 8 9 1 01 11 21 31 41 5

Table 178 - Diagnostic Specifications - 1756-OV16E


Attribute Short trip Time stamp of diagnostics 1756-OV16E 5 A for 20 ms @ 24V DC (output on, then short) 5 A for 20 ms @ 24V DC (output on into short) 1 ms

186

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 179 - Technical Specifications - 1756-OV16E


Attribute Outputs Pilot duty Voltage category Output delay time Off to On On to Off Operating voltage range Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OV16E 16 electronically fused (8 points/group) 1 A (DC-13/SR) 12/24V DC sink 75 s nom/1 ms max 360 s nom/1 ms max 1030V DC 210 mA 2 mA 1.12 W 6.72 W @ 60 C (140 F) 22.94 BTU/hr 1 mA per point 700 mV DC @ 1 A 1 A @ 60 C (140 F) 8 A @ 60 C (140 F) 2 A for 10 ms per Point, repeatable every 2 s @ 60 C (140 F) 2 mA per point Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per group 1756-TBNH 1756-TBSH User-defined mechanical 1 1(1) T4 T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

187

1756 ControlLogix I/O Specifications

Table 180 - Environmental Specifications - 1756-OV16E


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OV16E 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

188

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 181 - Certifications - 1756-OV16E


Certification(1) UL CSA CE 1756-OV16E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

189

1756 ControlLogix I/O Specifications

1756-OV32E
ControlLogix DC (1030V) electronically-fused, sinking output module
Simplified Schematic Display Optoisolation DC-0(+) OUT-0
Daisy Chain to Other RTBs OUT-1 OUT-3 OUT-5 OUT-7 OUT-9 OUT-11 OUT-13 OUT-15 DC-0(+) OUT-17 OUT-19 OUT-21 Group 1 OUT-23 OUT-25 OUT-27 OUT-29 OUT-31 DC-1(+)
2 4 6 8 10 1 3 5 7 9

1756-OV32E
Daisy Chain to Other RTBs OUT-0 OUT-2 OUT-4 OUT-6 OUT-8 OUT-10 OUT-12 OUT-14 RTN OUT-0 OUT-16 OUT-18 OUT-20 OUT-22 OUT-24 OUT-26 OUT-28 OUT-30 RTN OUT-1

ControlLogix Backplane Interface

Electronic Fuse Circuitry

RTN OUT-0

Group 0

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Group 0

Surge Current Chart Surge Continuous @ 60 C (140 F) 1A 0 Time 10 ms

Group 1

2A Current

_
DC COM

DC OUTPUT
ST 0 1 2 1 ST 8 9 0 1 1 1 ST 6 7 8 2 2 2 ST 4 5 6 3 1 1 1 9 2 7 4 1 2 2 0 2 8 5 6 11 3 4 22 1 2 23 9 0 7 1 5 2 3 3 1 F 0 O K F 1

ELECTRONIC FUSING

Table 182 - Diagnostic Specifications - 1756-OV32E


Attribute Short trip Time stamp of diagnostics 1756-OV32E 5 A for 20 ms @ 24V DC (output on then short) 5 A for 20 ms @ 24V DC (output into short) 1 ms

190

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 183 - Technical Specifications - 1756-OV32E


Attribute Outputs Voltage category Operating voltage range Output delay time (24V to 0V DC transition) Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max On-state voltage drop, max Current per point, max Current per group, max Current per module, max Surge current per point Load current, min Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage 1756-OV32E 32 electronically fused (16 points/group) 12/24V DC sink 1030V DC 75 s nom/300 s max 230 s nom/1 ms max 390 mA 2 mA 2.04 W 5.88 W @ 60 C (140 F) 20.1 BTU/hr 1 mA per point 350 mV DC @ 0.5 A 0.5 A @ 50 C (122 F) linear derating 0.35 A @ 60 C (140 F) 8 A @ 50 C (122 F) linear derating 5 A @ 60 C (140 F) 16 A @ 50 C (122 F) linear derating 10 A @ 60 C (140 F) 2 A for 10 ms per point, repeatable every 2 s @ 60 C (140 F) 2 mA per output Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group No isolation between individual group outputs Routine tested @ 1350V AC for 2 s Electronic, software configurable Electronically fused per group 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4 T4 None (open-style)

Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

191

1756 ControlLogix I/O Specifications

Table 184 - Environmental Specifications - 1756-OV32E


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OV32E 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

192

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 185 - Certifications - 1756-OV32E


Certification(1) UL CSA CE 1756-OV32E UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

193

1756 ControlLogix I/O Specifications

1756-OW16I
ControlLogix AC (10265V) DC (5150V) isolated contact module
Simplified Schematic +24V Display ControlLogix Backplane Interface L1
Isolated Wiring L1-0 L1-1 L1-2 L1-2 L1-3 OUT DC-4 (+) L1-4 L1-5 L1-6 L1-7 Jumper Bar L1-8 (Cut to Length) L1-9 L1-10 L1-11 Nonisolated L1-12 Additional jumper bars are available Wiring L1-13 as cat. no. 1756-JMPR. L1-14 L1-15 L1-15 L1 Not Used L1-0
2 4 6 8 10 1 3 5 7 9

1756-OW161
OUT-0 OUT-1 N.O. OUT-2 N.O. OUT-3 N.O. OUT-4 N.O. OUT-5 N.O. OUT-6 N.O. OUT-7 N.O. OUT-8 N.O. OUT-9 N.O. OUT-10 N.O. OUT-11 N.O. OUT-12 N.O. OUT-13 N.O. OUT-14 N.O. OUT-15 N.O Not Used Not Used L2 L2-0 L2-2
DC-4 (-)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O ST 8 9 10 11 12 13 14 15K

Daisy Chain to Other RTBs

Table 186 - Technical Specifications - 1756-OW16I


Attribute Outputs Pilot duty Operating voltage range Output voltage range (load dependent) 1756-OW16I 16 N.O. individually isolated C300/R150 5125V DC 10240V AC 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 10 ms max 10 ms max 150 mA 150 mA 4.4 W 4.5 W @ 60 C (140 F)

Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max

194

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 186 - Technical Specifications - 1756-OW16I (continued)


Attribute Thermal dissipation Off-state leakage current per point, max Minimum load current Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing 1756-OW16I 15.35 BTU/hr 1.5 mA per point 10 mA per point 100 m @ 6V 1 A 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM can be used to protect outputs. See publication 1492-TD008. However, the ControlLogix system has been agency certified using only the ControlLogix RTBs, that is, 1756-TBCH, 1756-TBNH, 1756-TBSH, and 1756-TBS6H. Any application that requires agency certification of the ControlLogix system using other wiring termination methods may require application-specific approval by the certifying agency. 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 187 - Environmental Specifications - 1756-OW16I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) 1756-OW16I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

195

1756 ControlLogix I/O Specifications

Table 187 - Environmental Specifications - 1756-OW16I (continued)


Attribute Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OW16I 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 188 - Certifications - 1756-OW16I


Certification(1) UL CSA CE 1756-OW16I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick FM KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

196

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-OX8I
ControlLogix AC (10265V) DC (5150V) isolated contact module
Simplified Schematic +24V L1-0
L1-0 L1-0 L1-1 L1-1 OUT-0 N.C. DC-2 (+) L1-2 L1-2 L1-3 OUT-0 N.O. Jumper Bar L1-3 (Cut to Length) L1-4 L1-4 L1-5 L1-5 L1-6 Nonisolated Wiring L1-6 L1-7 L1-7 Additional jumper bars are available as cat. no. 1756-JMPR. L1-7 L1 Not Used L1-0 Isolated Wiring

1756-OX81
2 4 6 8 10 1 3 5 7 9

ControlLogix Backplane Interface Display

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

OUT-0 N.C. OUT-0 N.O. OUT-1 N.C. OUT-1 N.O. OUT-2 N.C. OUT-2 N.O. OUT-3 N.C. OUT-3 N.O. OUT-4 N.C. OUT-4 N.O. OUT-5 N.C. OUT-5 N.O. OUT-6 N.C. OUT-6 N.O. OUT-7 N.C. OUT-7 N.O Not Used Not Used L2

L2-0

DC-2 (-)

RELAY OUTPUT
ST 0 1 2 3 4 5 6 7 O K

Daisy Chain to Other RTBs

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

197

1756 ControlLogix I/O Specifications

Table 189 - Technical Specifications - 1756-OX8I


Attribute Outputs Pilot duty Operating voltage range Contact current rating 1756-OX8I 8 N.O. 8 N.C. individually isolated (2 points per group) C300/R150 5125V DC 10240V AC 2 A @ 530V DC 0.5 A @ 48V DC 0.25 A @ 125V DC 2 A @ 125/240V AC 13 ms max 13 ms max 100 mA 100 mA 2.9 W 3.1 W @ 60 C (140 F) 10.57 BTU/hr 0 mA 10 mA per point 100 m @ 6V 1 A 1 operation/3 s (0.3 Hz at rated load) 1.2 ms 300 K cycles resistive 100 K cycles inductive Synchronization within 16.7 s max, reference to the Coordinated System Time Hold last state, On or Off (Off is default) Hold last state, On or Off (Off is default) 250V (continuous), basic insulation type, outputs-to-backplane, and output-to-output Routine tested @ 1350V AC for 2 s Electronic, software configurable Not protected. A fused IFM is recommended to protect outputs 1756-TBCH 1756-TBS6H User-defined mechanical 1 1(1) T4A None (open-style)

Output delay time Off to On On to Off Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation, max Thermal dissipation Off-state leakage current per point, max Minimum load current Initial contact resistance, max Switching frequency, max Bounce time, mean Expected contact life Scheduled outputs States in Fault mode per point States in Program mode per point Isolation voltage Module keying Fusing Removable terminal block RTB keying Slot width Wire category North American temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

198

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 190 - Environmental Specifications - 1756-OX8I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-OX8I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 3 kV

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 Oscillatory surge withstand IEEE C37.90.1

Table 191 - Certifications - 1756-OX8I


Certification(1) UL CSA CE 1756-OX8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations

C-Tick FM

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

199

1756 ControlLogix I/O Specifications

1756-CFM
ControlLogix configurable flow meter module
1756-CFM Standard Magnetic Pickup
2 1

1756-CFM Standard Output


2 1

Z0 12-24V DC
4 3

Z1 12-24V DC Z1 5V DC
6 5

Z0 12-24V DC
4 3

Z1 12-24V DC Z1 5V DC
6 5

Z0 5V DC Z0 Return
8 7

Z0 5V DC Z0 Return
8 7

Z1 RET F1
10 9

Z1 RET F1
10 9

Input Device

+
Shield Ground

F0 F0 Return
12 11

F0 F0 Return
12 11

F1 Return Not Used


14 13

F1 Return Not Used


14 13

Not Used Not Used


16 15

Not Used Not Used

Not Used
16 15

Not Used
Output 0

Output 1
18 17 19

Output 0
18 17 19

Output 1
Customer VCC

Customer VCC
20

Customer Common Customer Common

+
Load

20

Customer Common Customer Common Load

Customer VCC

Customer VCC

This wiring diagram can be used in applications with 50 mV (magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds. You must use RSLogix 5000 software to choose the appropriate threshold level for your specific application.

200

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

The 1756-CFM module provides Totalizer mode for metering applications, or high-speed frequency measurements for speed or rate control applications, on two channels connected to flowmeters.
1756-CFM Standard Prover/Store Count
12-24V DC

1 3 5

Z0 12-24V DC
4

Z1 1224V DC Z1 5V DC

Z0 5V DC
6

Shield Ground

Z0 Return
8 7

Z1 RET

METERING
F1

Input Device

+
Shield Ground

F0
10 9

F 0

Z 0 O O 0 1

F 1

Z 1

F0 Return
12 11

F1 Return Not Used


14 13

O K

Not Used Not Used


16 15

Not Used Output 1


18 17 19

DC I/O

Output 0 Customer VCC


20

Customer Common Customer Common

Customer VCC

Detectors 1 and 2 must be wired in parallel. Customer VCC may be used to power detectors. In this case, though, the maximum current on the wiring arm must be less than 4 A. The wiring example above shows a 12-24V DC standard prover connected to the module. If you use a 5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such as Z0 5V DC).

Table 192 - Technical Specifications - 1756-CFM


Attribute Inputs Inputs per channel Outputs Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, max Thermal dissipation Isolation voltage 1756-CFM 4 (2 per channel) 2 flowmeter (F) inputs used for all modes 2 gate inputs used in Totalizer mode for prover/store count 2 current sourcing 300 mA 16 mA 1.7 W 6 W @ 60 C (140 F) 20.4 BTU/hr 250V (continuous), reinforced insulation type, I/O-to-backplane 250V (continuous), basic insulation type, I/O group-to-group Routine tested at 1900V DC for 2 s Electronic, software configurable 1756-TBNH 1756-TBSH User-defined mechanical

Module keying Removable terminal block RTB keying

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

201

1756 ControlLogix I/O Specifications

Table 192 - Technical Specifications - 1756-CFM (continued)


Attribute Slot width Wire category North American temperature code Enclosure type Totalizer fill and prover High resolution, max Frequency Reverse polarity protection 1756-CFM 1 2 on signal ports 1 on power ports(1) T4 None (open-style) Yes 100 kHz 0.0005 Hz resolution Outputs only

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 193 - Input Specifications - 1756-CFM


Attributes Inputs Inputs per channel Count range, max Input frequency, max Flowmeter input voltage 1756-CFM 4 (2 per channel) 2 flowmeter (F) inputs used for all modes 2 gate inputs used in Totalizer mode for prover/store count 2,147,483,647 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz) 30V, selectable input thresholds of 50 mV, 1.3V and 4V: 30V peak unterminated open circuit voltage, magnetic pickup TTL compatible, input voltage >1.3V DC is Logic 1 and -0.71.3V DC is Logic 0 1224V DC powered preamp output, 4V DC threshold 5 k 30% resistive Firmware selectable: High-speed 100 kHz or low-pass filter for frequencies < 70 Hz 5V operation: 4.55.5V DC 12/24V operation: 1031.2V DC 4 mA 15 mA Software selectable User selectable

Flowmeter input impedance Filtering (inputs F0 & F1) Gate input voltage range Gate input on-state current, min Gate input on-state current, nom Mechanical filter debouncing (Z0 & Z1 Inputs) Input sampling period

202

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 194 - Output Specifications - 1756-CFM


Attribute Outputs Output voltage source Output voltage range, nom Output type Output Current per point Surge current Off-state leakage current, max On-state voltage drop, max Output control Output switching time Overload current Output short circuit protection Output reverse polarity protection
(1) All outputs can be on simultaneously without derating.

1756-CFM 2 current sourcing Customer supplied 5V operation: 4.55.5V DC for 320 mA load per point 12/24V operation: 1031.2V DC for 40 mA1 A load per point IEC 1A 24V DC 1 A @ 1031.2V DC 20 mA @ 4.55.5V DC(1) 2 A for 50 ms, repeatable every 2 s < 300 A @ 31.2V DC 0.6 x current Any number of outputs is assignable to any of 2 flowmeter channels Each output can have 2 turn-on and turn-off preset values < 50 s turn on, <300 s turn off Outputs triggered by Total; all other turn-on and turn-off times <1ms Electronic (< 4A) Electronic (No indication of fault. Remove overload and toggle output on/off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.)

Table 195 - Environmental Specifications - 1756-CFM


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-CFM 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1k Hz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

203

1756 ControlLogix I/O Specifications

Table 195 - Environmental Specifications - 1756-CFM (continued)


Attribute EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6 1756-CFM 4 kV at 5 kHz on unshielded output and power ports 4 kV at 5 kHz on shielded input ports 1 kV line-line (DM) and 2 kV line-earth (CM) on unshielded output and power ports 2 kV line-earth (CM) on shielded input ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

Table 196 - Certifications - 1756-CFM


Certification(1) UL CSA CE 1756-CFM UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

204

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-HSC
ControlLogix high-speed counter module
1756-HSC to Allen-Bradley 845 Incremental Encoder
Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12..24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10 1 3 5 7 9

1756-HSC to Allen-Bradley Series 10,000 Photoelectric Sensor


Allen-Bradley Bulletin 845 Incremental Encoder
Whit Photoswitch Series 10,000

Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

Green Black Blue Black White Black

Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)

2 4 6 8 10

1 3 5 7 9

Z1 (12...24V)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Z1 (5V) Blue Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) Black A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+) 12...24V

10-30V DC Not Used

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

Differential Line Driver Output

Jumper

The 1756-HSC module provides four high-speed, output-switching, on-off windows. The module uses pulses for counting and frequency.
1756-HSC to Allen-Bradley 8723-wire DC Proximity Sensor
Allen-Bradley Bulletin 872 3-wire DC Proximity Jumpers Sensor Z0 (12...24V) Z0 (5V) Z0 (RET) B0 (12...24V) B0 (5V) Black Blue 12...24V DC Return B0 (RET) A0 (12...24V) A0 (5V) A0 (RET) Not Used Not Used Not Used Out 0 Out 1 COMMON 0 COMMON 0 COMMON 0 DC-0(+)
2 4 6 8 10 1 3 5 7 9

Z1 (12...24V) Z1 (5V) Z1 (RET) B1 (12...24V) B1 (5V) B1 (RET) A1 (12...24V) A1 (5V) A1 (RET) Not Used Not Used Not Used Out 2 Out 3 COMMON 1 COMMON 1 COMMON 1 DC-1(+)

COUNTER
A B Z 0 0 0 O O 0 1 A B Z 1 1 1 O K O O 2 3

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

12...24V DC

DC I/O

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

205

1756 ControlLogix I/O Specifications

Table 197 - Technical Specifications - 1756-HSC


Attribute Number of counters Inputs per counter Outputs Operating voltage range Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, max Thermal dissipation Isolation voltage 1756-HSC 2 3 (A, B, Z for gate/reset) 4 (2 points/group) 5V operation: 4.55.5V DC 12/24V operation: 1026.4V DC 300 mA 3 mA 1.6 W 5.6 W @ 60 C (140 F) 19.1 BTU/hr 125V (continuous), basic insulation type, input group-to-backplane 30V (continuous), basic insulation type, input group-to-input group Routine tested at 1900V DC for 2 s Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 2 on signal ports 1 on power ports(1) T4 T4 None (open-style)

Module keying Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Table 198 - Input Specifications - 1756-HSC


Attribute Number of counters Inputs per counter Input frequency, max 1756-HSC 2 3 (A, B, Z for gate/reset) 1 MHz in counter modes (A input) 500 kHz in rate measurement mode (A input) 250 kHz in encoder mode (A/B inputs, X1 or X4) 70 Hz with filter enabled 016, 777, 214 1000 kHz 4 mA 15 mA

Count range Counting frequency, max Input current, min Input current, nom

206

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 199 - Output Specifications - 1756-HSC


Attribute Outputs Output delay time Off to On On to Off Off-state leakage current per point, max On-state voltage drop, max Output current rating, per point Current limit Surge current per point Load current per point, min Output control Short circuit protection Reverse polarity protection Counter, max Rate measurement, max Encoder, max Debounce filter, max 1756-HSC 4 (2 per common) 20 s nom/50 s max 60 s nom/300 s max 300 A 0.55V 20 mA @ 4.55.5V DC 1.0 A @ 1031.2V DC <4A 2 A for 10 ms every 1s @ 60 C (140 F) 5V operation: 3 mA 12/24V operation: 40 mA Up to two outputs are assigned to each counter channel Each output can have two turn-on and turn-off preset values Electronic (Remove overload and toggle On/Off to restore.) Yes (If wired incorrectly, module outputs may be permanently disabled.) 1 MHz 500 kHz 250 kHz 70 Hz

Table 200 - Environmental Specifications - 1756-HSC


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 1756-HSC 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

207

1756 ControlLogix I/O Specifications

Table 200 - Environmental Specifications - 1756-HSC (continued)


Attribute Radiated RF immunity IEC 61000-4-3 1756-HSC 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on power ports 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on power ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 2 kV line-earth (CM) on shielded ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 201 - Certifications - 1756-HSC


Certification(1) UL CSA CE 1756-HSC UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

208

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-LSC8XIB8I
ControlLogix 24V low-speed counter module
Simplified Schematic Current Limiter IN-x or CTR-x GND-x or CTR GND-x Opto-isolator Display ControlLogix Backplane Interface

Isolated Wiring
GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 CTR-GND-0 CTR GND-1 CTR GND-2 CTR GND- 3

1756-LSC8XIB8I
2 4 6 8
10 1 3 5 7 9

IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 CTR-0 CTR-1 CTR-2 CTR-3 CTR-4 CTR-5 CTR-6 CTR-7 Not Used Not Used DC (+) DC-1 (+) DC-2 (+)

DC-1 (-) DC-2 (-)

Source Input Wiring


DC-5 (-) DC-6 (-)

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

(+) (+)

DC-5 (+) DC-6 (+)

Jumper Bar Cut to Length

Sink Input Wiring

Nonisolated Wiring

CTR GND-4 CTR GND- 5 CTR GND-6 CTR GND- 7

See page 210 for proximity sensor wiring.

DC (-)

CTR GND-7 Not Used

Additional jumper bars may be purchased by using catalog number 1756-JMPR.

Daisy Chain to Other RTBs COUNTER


ST CTR 01234567 01234567

O K

PEER DEVICE

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

209

1756 ControlLogix I/O Specifications

The following diagram shows how to wire a proximity sensor to the modules eight counters or eight hardware inputs. Counters use incoming pulses for counts and frequency with two user-configurable On/Off windows per counter. Hardware inputs provide standard input or counter control functionality.

Allen-Bradley Bulletin 872 3-wire DC Proximity SensorNormally Open PNP

1224V DC

Brown

Black 1756-LSC8XIB8I Module Sink Input Wiring


IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 CTR-0 CTR-1 CTR-2 CTR-3 CTR-4 CTR-5 CTR-6 CTR-7 Not Used Not Used

1224V DC Return

Blue

GND-0 GND-1 GND-2 GND-3 GND-4 GND-5 GND-6 GND-7 CTR-GND-0 CTR GND-1 CTR GND-2 CTR GND- 3 CTR GND-4

2 4 6 8
10

1 3 5 7 9

Counter Control Hardware Inputs 07

Allen-Bradley Bulletin 872 3-wire DC Proximity SensorNormally Open NPN

12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35

1224V DC

Brown

Counters 07

1224V DC Return

Blue

Black

CTR GND- 5 CTR GND-6 CTR GND- 7 CTR GND-7 Not Used

Module Source Input Wiring

Table 202 - Counter Specifications - 1756-LSC8XIB8I


Attribute Number of counters Counting frequency, max Count range Voltage category Operating voltage range Off-state voltage, max Off-state current, max On-state current, min On-state current, max Change of state 1756-LSC8XIB8I 8 individually isolated 40 kHz 02,147,483,648 (31-bit counter) 12/24V DC sink/source 1030V DC 5V 1.5 mA 2 mA @ 10 V DC 5 mA @ 30V DC Enter or exit user-configurable windows

210

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 203 - Hardware Input Specifications - 1756-LSC8XIB8I


Attribute Inputs Voltage category Operating voltage range Input voltage, nom Input delay time (screw to backplane) Off to On On to Off Off-state voltage, max Off-state current, max On-state current, min On-state current, max Change of state 1756-LSC8XIB8I 8 individually isolated, standard input or counter control functionality 12/24V DC sink/source 1030V DC 24V DC 14 s nom/23 s max + user-configurable filter time of 030,000 s 14 s nom/23 s max + user-configurable filter time of 030,000 s 5V 1.5 mA 2 mA @ 10 V DC 5 mA @ 30V DC Any transition

Table 204 - Module Specifications - 1756-LSC8XIB8I


Attribute Current draw @ 5.1V Current draw @ 24V Total backplane power Power dissipation Thermal dissipation Input impedance, max Cyclic update time Isolation voltage 1756-LSC8XIB8I 275 mA 3 mA 1.47 W 3.8 W @ 60 C (140 F) 12.97 BTU/hr 6 k @ 30V DC 200 s750 ms 250V (continuous), reinforced insulation type, inputs-to-backplane 250V (continuous), basic insulation type, input-to-input Type tested @ 2300V AC for 60 s inputs-to-backplane Type tested @ 1500V AC for 60 s input-to-input Electronic, software configurable 1756-TBCH 1756-TBS6H User-defined mechanical 1 1 on signal ports(1) T4A T4 None (open-style) Yes

Module keying Removable terminal block housing RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type Reverse polarity protection

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

211

1756 ControlLogix I/O Specifications

Table 205 - Environmental Specifications - 1756-LSC8XIB8I


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-LSC8XIB8I 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on signal ports 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Table 206 - Certifications - 1756-LSC8XIB8I


Certification(1) c-UL-us CE 1756-LSC8XIB8I UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3

C-Tick Ex

KC

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

212

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756-PLS
ControlLogix programmable limit switch module
1756-PLS InputsLeft Side
2 1

1756-PLS OutputsRight Side


2 1

OUTPUT 0
4 3

INPUT 0 INPUT 1
6 5

OUTPUT 8
4 3

INPUT 8 INPUT 9
6 5

OUTPUT 1 OUTPUT 2
8 7

OUTPUT 9

INPUT 2 INPUT 3
10 9

+ _
10...30V DC

OUTPUT 10
8 7

INPUT 10 INPUT 11
10 9

OUTPUT 3 DC PWR 0...3


12 11

OUTPUT 11 DC PWR 8...11


12 11

DC COM 0...3 INPUT 4


14 13

DC COM 8...11 INPUT 12


14 13

OUTPUT 4 OUTPUT 5
16 15

OUTPUT 12 OUTPUT 13

INPUT 5 INPUT 6
18 17

INPUT 13
16 15

OUTPUT 6 OUTPUT 7
20 19

+ _
+ _

OUTPUT 14
18 17

INPUT 14 INPUT 15
20 19

INPUT 7 DC COM 4-...7

OUTPUT 15 DC PWR 12...15

DC PWR 4...7

DC COM 12...15

The 1756-PLS module supports enhanced packaging applications. The module requires three contiguous slots in the chassis.
1756-PLS Resolver
2 1

Do Not Use
4 3

Do Not Use Do Not Use


6 5

Do Not Use Do Not Use


8 7

Do Not Use Do Not Use


10 9

Do Not Use Do Not Use


12 11

Do Not Use Do Not Use


14 13

Do Not Use

Allen-Bradley Resolver 846-SJDA1CG-R3-C

F (S3)
Sine +

Do Not Use
16 15

D (S1) E (S2) G (S4)

Sine
18 17

Do Not Use Reference +


20 19

Cosine + Cosine

A (R1) B (R2)

Reference

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

213

1756 ControlLogix I/O Specifications

Indicator for Left Slot I/O Module


PROG. LIMIT SWITCH

Indicator for Left Resolver Module


PROG. LIMIT SWITCH

Indicator for Right Slot I/O Module


PROG. LIMIT SWITCH

OUT 0 1 2 3 4 5 6 7

O IN 0 1 2 3 4 5 6 7 K

O K

OUT 8 9 10 11 12 13 14 15

O IN 8 9 10 11 12 13 14 15 K

DC I/O

RESOLVER

DC I/O

Table 207 - Technical Specifications - 1756-PLS


Attribute Module configuration 1756-PLS Left section: 2 groups of 4 outputs and 4 inputs each Center section: resolver interface and I/O control Right section: 2 groups of 4 outputs and 4 inputs each 1A 125 mA 8.1 W 22.62 W @ 30 C (86 F) 18.22 W @ 60 C (140 F) 25.7 W @ 30 C (86 F) 21.3 W @ 60 C (140 F) 77.23 BTU/hr @ 30 C (86 F) 62.2 BTU/hr @ 60 C (140 F) 87.74 BTU/hr @ 30 C (86 F) 72.72 BTU/hr @ 60 C (140 F) 250V (continuous), basic insulation type, I/O-to-backplane, I/O group-to-group, resolverto-backplane, and resolver-to-I/O Routine tested at 1900V DC for 2 s Requires 3 RTBs: 1756-TBNH or 1756-TBSH User-defined mechanical 3 2 on signal ports 1 on power ports(1) T4 T4 None (open style)

Current draw at 5.1V Current draw at 24V Total backplane power Power dissipation, nom Power dissipation, max Thermal dissipation, nom Thermal dissipation, max Isolation voltage

Removable terminal block RTB keying Slot width Wire category North American temperature code IEC temperature code Enclosure type

(1) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

214

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 208 - Resolver Specifications - 1756-PLS


Attribute Resolver location Compatible resolver Resolver interface Reference voltage Reference frequency Digital resolution Angular resolution Digital count range Maximum tracking rate Repeatability Accuracy 1756-PLS Center section Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer options) 2V rms, reference output (differential pair) 2V rms, sine and cosine inputs (2 differential pairs) 2V rms 20% 5 kHz 20% 12 bits (4096 counts from hardware) 0.088 /bit 04095 (decimal) 1800 RPM 0.0488% of full scale 0.0976% of full scale

Table 209 - Input Specifications - 1756-PLS


Attribute Inputs Voltage category Operating voltage range Input delay time (screw to backplane) Off to On 1756-PLS 16 (2 groups of 4 per I/O section) 12/24V DC 10.831.2V DC < 15 s @ 30 C (86 F) < 150 s @ 60 C (140 F) < 30 s @ 30 C (86 F) < 200 s @ 60 C (140 F) 1.86 W @ 60 C (140 F) 2.8 W @ 60 C (140 F) 6.35 BTU/hr 9.56 BTU/hr 10V DC 10.826.4V DC 31.2V DC 5V DC 1.5 mA 3 mA 10 mA 3.3 k @ 24V DC Yes

On to Off Power dissipation, inputs, nom Power dissipation, inputs, max Thermal dissipation, inputs, nom Thermal dissipation, inputs, max On-state voltage, min On-state voltage, nom On-state voltage, max Off-state voltage, max Off-state current, max On-state current, min On-state current, max Input impedance, max Reverse polarity protection

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

215

1756 ControlLogix I/O Specifications

Table 210 - Output Specifications - 1756-PLS


Attribute Outputs Voltage category Operating voltage range Output delay time Off to On On to Off Power dissipation, outputs, nom Power dissipation, outputs, max Thermal dissipation, outputs, nom Thermal dissipation, outputs, max Output power dissipation/slot thermal dissipation Off-state leakage current per point, nom Off-state leakage current per point, max On-state voltage, min On-state voltage, nom On-state voltage, max Output voltage drop, max Current per point, max Current per group, max Current per module, max Current limit Surge current per point Load current per point, min Output switching time Short circuit protection Reverse polarity protection
(1) Derate 16.7 mA/ C above 30 C (86 F): 0.5 A @ 60 C (140 F). (2) Derate 66.8 mA/ C above 30 C (86 F): 2 A @ 60 C (140 F). (3) Derate 133.6 mA/ C above 30 C (86 F): 4 A @ 60 C (140 F).

1756-PLS 16 (2 groups of 4 per I/O section) 12/24V DC 1031.2V DC < 15 s @ 60 C (140 F) < 25 s @ 60 C (140 F) 5.4 W @ 30 C (86 F) 3.2 W @ 60 C (140 F) 6 W @ 30 C (86 F) 3.8 W @ 60 C (140 F) 18.43 BTU/hr @ 30 C (86 F) 10.93 BTU/hr @ 60 C (140 F) 21.48 BTU/hr @ 30 C (86 F) 11.93 BTU/hr @ 60 C (140 F) 3.2 W @ 60 C (140 F) 10.93 BTU/hr @ 60 C (140 F) <10 A @ 60 C (140 F) 300 mA @ 60 C (140 F) 10V DC 10.826.4V DC 31.2V DC 0.55V DC 1 A @ 30 C(1) (86 F) 4 A @ 30 C(2) (86 F) 8 A @ 30 C(3) (86 F) <4A 2 A for 10 ms every 1 s @ 60 C (140 F) 40 mA Switching 1 A @ 24V DC Electronic (No indication of fault. Remove load and toggle on/off to restore.) Yes, current limited. (If wired incorrectly, outputs may be permanently disabled.)

216

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Table 211 - Environmental Specifications - 1756-PLS


Attribute Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat) Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3 1756-PLS 060 C (32140 F)

60 C (140 F) -4085 C (-40185 F)

595% noncondensing 2 g @ 10500 Hz 30 g 50 g CISPR 11 (IEC 61000-6-4): Class A 6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 80 2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on unshielded I/O and power ports 2 kV at 5 kHz on shielded resolver ports 1 kV line-line (DM) and 2 kV line-earth (CM) on unshielded I/O and power ports 2 kV line-earth (CM) on shielded resolver ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz on shielded signal ports

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5 Conducted RF immunity IEC 61000-4-6

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

217

1756 ControlLogix I/O Specifications

Table 212 - Certifications - 1756-PLS


Certification(1) UL CSA CE 1756-PLS UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. European Union 2004/108/IEC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/95/EC LVD, compliant with: EN 61131-2; Programmable Controllers (Clause 11) Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc

C-Tick Ex

(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

ControlLogix I/O Accessories


Place 1756 I/O modules in any slot in a 1756 chassis. Each chassis requires a power supply.
Product Chassis Power supply, standard Power supply, redundant Cat. No. 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1756-PC75/B, 1756-PH75/B 1756-PA75R, 1756-PB75R, 1756-PSCA2 1756-CPR2 cable

For more information on chassis, see ControlLogix Chassis Specifications Technical Data, publication 1756-TD006. For more information on power supplies, see ControlLogix Power Supply Specifications Technical Data, publication 1756-TD005.

218

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

1756 Removable Terminal Blocks


Removable terminal blocks (RTBs) provide a flexible interconnection between your plant wiring and 1756 I/O modules. The RTB plugs into the front of the I/O module. The type of module determines which RTB you need. You can choose screw-clamp or spring-clamp RTBs. RTBs are not shipped with I/O modules. You must order them separately. The standard housing on the front of the wiring arm is not deep enough for 2.5 mm2 (14 AWG) wiring. If you plan to use 2.5 mm2 (14 AWG) wiring, also order the extended housing. ATTENTION: If separate power sources are used, do not exceed the specified isolation voltage: referring to each individual modules specifications on the preceding pages.
Table 213 - RTB Specifications - 1756-TBNH, 1756-TBSH, 1756-TBCH, 1756-TBS6H, 1756-TBE
Attribute Description 1756-TBNH 20-position NEMA screw-clamp removable block 1.36 Nm (12 lbin) 0.332.1 mm2 (2214 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal. 1756-TBSH 20-pin spring-clamp removable terminal block with standard housing N/A 0.332.1 mm2 (2214 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal. 1756-TBCH 36-pin cage-clamp removable terminal block with standard housing 0.5 Nm (4.4 lbin) Single wire connection: 0.332.1 mm2 (2214 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max Double wire connection: 0.331.3 mm2 (2216 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal. 3.2 mm (1/8 in.) 1756-TBS6H 36-pin spring-clamp removable terminal block with standard housing N/A 0.332.1 mm2 (2214 AWG) solid or stranded copper wire rated at 90 C (194 F), or greater, 1.2 mm (3/64 in.) insulation max Do not wire more than two conductors on any single terminal. 1756-TBE Extended depth terminal block housing N/A

Screw torque Wire size(1)

Screwdriver width

8 mm (5/16 in.) max

N/A

N/A

N/A

(1) Maximum wire size requires extended housing, catalog number 1756-TBE.

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

219

1756 ControlLogix I/O Specifications

Wiring Systems

As an alternative to buying RTBs and connecting the wires yourself, you can buy a wiring system of the following: Interface modules (IFMs) that provide the output terminal blocks for digital I/O modules. Use the pre-wired cables that match the I/O module to the IFM. Analog interface modules (AIFMs) that provide the output terminal blocks for analog I/O modules. Use the pre-wired cables that match the I/O module to the AIFM. I/O module-ready cables. One end of the cable assembly is an RTB that plugs into the front of the I/O module. The other end has individually color-coded conductors that connect to a standard terminal block.
RTB Pre-wired Cable Connector I/O Module Factory-wired Field Wiring Interface Module (IFM)

220

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

1756 ControlLogix I/O Specifications

Notes:

Rockwell Automation Publication 1756-TD002F-EN-E - November 2012

221

Important User Information


Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this publication are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Allen-Bradley, ControlLogix, RSLogix 5000, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Publication 1756-TD002F-EN-E - November 2012


Supersedes Publication 1756-TD002E-EN-E - April 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

También podría gustarte