Update the options Bus 1) Press 0 Enter 9876 Note: Have all your Option Buss Devices connected

to the option buss and addressed including the DX4020 (*The DX4020 needs to be addressed as 250, all switches CLOSED.) connected to the panel. 2) Press 3 Program System 3) Press 4 Option Bus 4) Press 1 Update Bus The keypad will display Updating . . . TOT BUS DEVS: XX. XX = the total number of devices on the Option bus . If 00 or not the correct total number of devices on the bus, check the wiring and addressing of each device on the Option bus. Each Device needs to have it own address. Repeat steps 3 and 4 until all the devices learned in the panel. 5) Press the * / Back key Once the top line of the display should read PROG MODES. 6) Press 6 Program Accounts 7) Press 1 Phone / IP Number 8) Press 1 Phone / IP 1 9) Press 1 Enter 0 to tell the panel this is an IP Address (then the 12th digit IP Address of the CoBox, D6680) followed by 0130751#Enter 10) Press 2 Port Number Enter 07700#Enter 11) Press the * / Back key Once the top line of the display should read Phone / IP Number 12) Press 2 Phone / IP 2 13) Press 1 Enter 0 to tell the panel this is an IP Address (then the 12th digit IP Address of the CoBox, D6680) followed by 0130751#Enter 14) Press 2 Port Number Enter 07700#Enter 15) Press the * / Back key Once the top line of the display should read Phone / IP Number 16) Press 3 Computer Phone / IP 17) Press 1 Enter 0 to tell the panel this is an IP Address (then the 12 digit IP Address of the RSP Computer) followed by 0130751#Enter 18) Press 2 Port Number Enter 07700#Enter

19) Press the * / Back key 4 times to return to System Normal.

The FPD-7024 is programmed for the DX4020. Now the DX4020 needs to be programmed (telneted) to communicate on the network. Refer to the DX4020 Installation Guide for more detailed instructions on DX4020 programming. Channel 1 Parameters CH1: Baud rate - 9600 IF Mode - 4C Flow - 00 Port - 7700 Connect Mode - CC Data gram 02 Select (9) to Save changes

Set the program for Network communications: 1) Press 0 Enter 9876 2) Press 6 for program accounts, then 4 for Alter Comm. 3) Select 0 for Network, then press CMD (#) key 4) Press the (*) key three times to exit

También podría gustarte