Insight

Ducted Air Handler


Product Data
Heat Pump Split System Air Conditioning
30 to 50 MBh - 50 Hz

Air Handler Models

Condensing Models

TWE030CA
TWE040CA
TWE050CA

TWJ020-036CA
TWA030-060CD

TWE-PRC001-EN-10-15-99

Features and
Benefits

Air Handling Units

TWE

Features
Ships horizontal
Six way convertibility-horizontal (left and
right), upflow, downflow (front and rear
access)
Electrical, refrigerant, condensate and
blower access convertible to either side
Corrosion resistant galvanized steel
with attractive finish
Internally enhanced finned coil tubes
Direct drive motor
Standard filters
Multi-speed blower
220 volt primary and 24 volt secondary
transformer
Insulated cabinet
External access to heater circuit
breakers
Start kits are not required
Built-in indoor fan delay function for
increased efficiency. No kit required.

TWJ

TWA

New Features
Improved filter access and latch Eliminate current T-bar and shipping
bracket.
Provision for 1-1/8 inches thick field
supplied electrostatic filter
Reversible Duct Flanges - Fits up to
1-1/2 inches duct board
Improve controls access with control
box mounted next to blower.
40 VA transformer with 5 amp automotive style fuse on 3 tons and less
5 Amp automotive style fuse replaces
Bussman red cap fuse on 3.5 to 5 ton
models
Blower mounting brackets improved Front access to screw with power driver
Improved bottom carton cushioning
1 inch thick foil faced insulation for all
models

Condensing Units
Features:
Vertical Air Discharge
High Efficiency TRANE Climatuff
Compressor
Powder Paint finish
Brazed connections
Spine Fin Outdoor Coil
Switchover Valves

American Standard Inc. 1999

Benefits:
Flexibility in application
Quality and reliability
Uniform covering for a smooth, attractive
and corrosion-resistant finish

TWE5-PRC001-EN-10-15-99

Contents

Features and Benefits


Air Handling Units
Condensing Units

2
2
2

System Performance

Selection Procedure

4
4

Model Number Nomenclature

General Data
TWE030CA40B
TWE040CA40C
TWE050CA50D
TWJ020CA00A0
TWJ024CA00A0
TWJ030CA00A0
TWJ036CA00A0
TWA030CD00A0
TWA040CD00A0
TWA050CD00A0
TWA060CD00A0

Performance Data
TWJ/TWE Cooling
TWA/TWE Cooling
TWJ/TWE Heating
TWA/TWE Heating
Evaporator Fan Performance
Air Pressure Drop

TWE5-PRC001-EN-10-15-99

5
5
5
5
6
6
6
6
7
7
7
7
8
8
12
16
20
24
26

Supplementary Heaters

27

Electrical Data

28

Dimensions

29

Convertibility

31

Mechanical Specification Options

32

System
Performance

Outdoor Unit
Indoor Unit
Ducted Air Handlers
TWJ020CA00A
TWE030CA00A
TWJ024CA00A
TWE030CA00A
TWJ030CA00A
TWE030CA00A
TWJ030CA00A
TWE040CA00A
TWJ036CA00A
TWE030CA00A
TWJ036CA00A
TWE040CA00A
TWJ036CA00A
TWE050CA00A
TWA030CD00A
TWE030CA00A
TWA030CD00A
TWE040CA00A
TWA040CD00A
TWE040CA00A
TWA040CD00A
TWE050CA00A
TWA050CD00A
TWE050CA00A
TWA060CD00A
TWE050CA00A

CFM
700
900
1000
1100
1100
1325
1400
1000
1100
1300
1500
1800
1800

Cooling Capacity
95 F (35 C)
CMH
MBh
1185
1520
1690
1860
1860
2240
2360
1690
1860
2200
2535
3040
3040

20
27
31
33
38
40.5
41.6
32
34
42
43
51
63

Kw
6
8
9
9.5
11
11.5
12
9
9.6
12
12.5
14.5
18

Selection
Procedure

Model Number Nomenclature


1

10

11

12

PRODUCT TYPE
TW = Split System Component
Heat Pump Compatible

PRODUCT
SERVICE CHANGE

AIRFLOW CONFIGURATION
E = Convertible

MINOR DESIGN
MODIFICATION

REFRIGERANT CONNECTIONS
0 = Brazed

NOT USED
REFRIGERANT FLOW CONTROL
4 = Accutron Flow Control/Check Valve
5 = Bleed TXV

NOMINAL NET COOLING


CAPACITY
30 = 30 MBh
40 = 40 MBh
50 = 50 MBh

ELECTRICAL CHARACTERISTICS
A = 220V/1/50

MAJOR DESIGN MODIFICATION


4

TWE5-PRC001-EN-10-15-99

General
Data

TWE

TWE Product Specifications


Model
Power Conn. Volts/Ph/Hz
Indoor Coil - Type
Rows
Fins per inch (Fins per 25.4 mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant Control
Drain Conn. Size in. (mm)
Duct Connections
Indoor Fan - Type
No. Used
Diameter in. (mm)
Width in. (mm)
Type Drive - No. Speeds
Airflow (High)
CFM @ 0.0 in. w.g.
CMH @ 0.0 Pa
No. Motors - HP
Motor RPM
Volts/Ph/Hz
F.L. Amps
L.R. Amps
Filters
Vertical Applications
Filter Furnished
Type Furnished
No.-Size-Thickness
Horizontal Applications
Filter Furnished
Type Recommended
No.-Size-Thickness
Refrigerant Line Size
Line Size ID Gas in. (mm)
Line Size ID Liquid in. (mm)
Dimensions (H x W x D)
Crated - in.
- (mm)
Uncrated - in.
- (mm)
Weight Ibs. (kg)
Shipping
Net

TWE030CA40B
220/1/50
Plate Fin
3
14
3.21 (.30)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
8.0 (203.2)
Direct - 3

TWE040CA40C
220/1/50
Plate Fin
3
14
5.04 (.47)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
10.0 (254.0)
Direct - 3

TWE050CA50D
220/1/50
Plate Fin
3
14
6.19 (.58)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
11.0 (279.4)
10.0 (254.0)
Direct - 3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
1000
220/1/50
2.6
3.3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
900
220/1/50
2.1
4.2

See Fan Performance Table


See Fan Performance Table
1 - 3/4
900
220/1/50
4.5
10.1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
High Velocity
1 - 2 2 x 20 - 1

No
See Note Below
See Note Below

No
See Note Below
See Note Below

No
See Note Below
See Note Below

7/8 (22.23)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

44.5 x 24.0 x 23.5


(1130 x 610 x 597)
43.0 x 21.5 x 21.0
(1092 x 546 x 533)

53.25 x 26.0 x 23.5


(1353 x 660 x 597)
52.0 x 23.5 x 21.0
(1321 x 597x 533)

59.5 x 26.0 x 23.5


(1511 x 660 x 597)
58.0 x 23.5 x 21.0
(1473 x 597 x 533)

125 (56.7)
115 (52.2)

165 (74.8)
150 (68.0)

198 (898)
183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter: Face Area (sq ft) = CFM/300
High Velocity Filter: Face Area (sq ft) = CFM/500

TWE5-PRC001-EN-10-15-99

General
Data

TWJ

TWJ Product Specifications 12


TWJ020CA00A0
Model
200/230/1/60
Power Conn. - Volts/Ph/Hz
PER LOCAL CODES
Fuse Size - max. amps
CLIMATUFF
Compressor - Type
1-1
No. Used - No. Speeds
200/230/1/50
Volts/Ph/Hz
10 - 60
F.L. Amps - L.R. Amps
PROPELLER
Outdoor Fan - Type
1
No. Used
18 (457)
Diameter in. (mm)
DIRECT - 1
Type Drive - No. Speeds
1503
CFM @ 0.0 in. w.g. 3
709
(M) 3/HR. @ 0.0 mm w.g. 3
1 - 1/8
No. Motors - HP
690
Motor Speed (RPM)
200/230/1/60/50
Volts/Ph/Hz
0.90
F.L. Amps
SPINE FIN
Outdoor Coil - Type
1
No. Rows
24 (.945)
Fins/in. (mm)
12.22 (1.14)
Face Area sq ft (sq m)
3/8 (9.52)
Tube Size in. (mm)
Refrigerant
5 LBS., 4 OZ (2.38)
R-22 (O.D. Unit) 4 - lbs. (kg)
YES
Factory Supplied
3/4 (19.1)
Line Size - OD Gas 5 in. (mm)
5/16 (7.94)
Line Size - OD Liq. 5 in. (mm)
FCCV
0.051 (1.30)
Restrictor Orifice Size in. (mm)
Dimensions (H x W x D)
25 X 26-1/2 X 30
Crated - in.
(635 X 673 X 762)
- (mm)
SEE OUTLINE DRAWINGS
Uncrated
Weight lbs. (kg)
170 (77.1)
Shipping
162 (73.5)
Net

TWJ024CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
1-1
200/230/1/50
17.9 - 69
PROPELLER
1
18 (457)
DIRECT - 1
1987
938
1 - 1/5
1075
200/230/1/50
1.60
SPINE FIN
1
24 (.945)
16.84 (1.56)
3/8 (9.52)

TWJ030CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
1-1
200/230/1/50
19 - 94
PROPELLER
1
18 (457)
DIRECT - 1
1975
932
1 - 1/5
900
200/230/1/60/50
1.60
SPINE FIN
1
24 (.945)
16.84 (1.56)
3/8 (9.52)

TWJ036CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
1-1
200/230/1/60/50
21.9 - 95
PROPELLER
1
22 (559)
DIRECT - 1
2748
1297
1 - 1/4
900
200/230/1/50
1.40
SPINE FIN
1
24 (.945)
23.11 (2.15)
3/8 (9.52)

4 LBS, 13 OZ. (2.18)


YES
3/4 (19.1)
5/16 (7.94)

6 LBS., 12 OZ. (3.06)


YES
7/8 (22.2)
3/8 (9.52)

8 LBS., 2 OZ. (3.69)


YES
7/8 (22.2)
3/8 (9.52)

0.061 (1.55)

0.065 (1.65)

0.073 (1.85)

33-1/4 X 30 X 26-1/2
(845 X 762 X 673)
SEE OUTLINE DRAWINGS

33-1/4 X 26-1/2 X 30
(845 X 673 X 762)
SEE OUTLINE DRAWINGS

37-1/2 X 34-3/4 X 30-1/2


(953 X 883 X 775)
SEE OUTLINE DRAWINGS

187 (84.8)
178 (80.7)

214 (97.1)
205 (93.0)

252 (114)
238 (108)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.

TWE5-PRC001-EN-10-15-99

General
Data

TWA

TWA Product Specifications 12


TWA030CD00A0
Model
380/415/3/60
Power Conn. - Volts/Ph/Hz
PER LOCAL CODES
Fuse Size - max. amps
CLIMATUFF
Compressor - Type
1-1
No. Used - No. Speeds
380/415/3/50
Volts/Ph/Hz
5 - 51
F.L. Amps - L.R. Amps
PROPELLER
Outdoor Fan - Type
1
No. Used
18 (457)
Diameter in. (mm)
DIRECT - 1
Type Drive - No. Speeds
1976
CFM @ 0.0 in. w.g. 3
933
(M) 3/HR. @ 0.0 mm w.g. 3
1 - 1/4
No. Motors - HP
1075/900
Motor Speed (RPM)
460/1/60/50
Volts/Ph/Hz
0.80
F.L. Amps
SPINE FIN
Outdoor Coil - Type
1
No. Rows
24 (.945)
Fins/in. (mm)
16.84 (1.56)
Face Area sq ft (sq m)
3/8 (9.52)
Tube Size in. (mm)
Refrigerant
6 LBS.,12 OZ. (3.06)
R-22 (O.D. Unit) 4 - lbs. (kg)
YES
Factory Supplied
7/8 (22.2)
Line Size - OD Gas 5 in. (mm)
3/8 (9.52)
Line Size - OD Liq. 5 in. (mm)
FCCV
0.065 (1.65)
Restrictor Orifice Size in. (mm)
Dimensions (H x W x D)
33-1/4 X 30 X 26-1/2
Crated - in.
(845 X 762 X 673)
- (mm)
SEE OUTLINE DRAWINGS
Uncrated
Weight lbs. (kg)
219 (99.3)
Shipping
210 (95.3)
Net

TWA040CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
1-1
380/415/3/50
7 - 51
PROPELLER
1
22 (559)
DIRECT - 1
2738
1292
1 - 1/3
825/690
460/1/60/50
1.0
SPINE FIN
1
24 (.945)
20.32 (1.89)
3/8 (9.52)

TWA050CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
1-1
380/415/3/50
9 - 71
PROPELLER
1
26 (660)
DIRECT - 1
3141
1482
1 - 1/3
825/690
460/1/60/50
1.0
SPINE FIN
1
24 (.945)
28.91 (2.69)
3/8 (9.52)

TWA060CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
1-1
380/415/3/50
10.6 - 64
PROPELLER
1
26 (660)
DIRECT - 1
3931
1855
1 - 1/3
825
460/1/60/50
1.7
SPINE FIN
2
24 (.945)
35.39 (3.29)
3/8 (9.52)

8 LBS.,13 OZ. (4.00)


YES
1-1/8 (3.18)
3/8 (9.52)

10 LBS.,9 OZ. (4.79)


YES
1-1/8 (3.18)
3/8 (9.52)

16 LBS.,12 OZ. (7.60)


YES
1-1/8 (3.18)
3/8 (9.52)

0.075 (1.91)

0.086 (2.18)

0.086 (2.18)

33-1/4 X 34-3/4 X 30-1/2


(845 X 883 X 775)
SEE OUTLINE DRAWINGS

37-1/2 X 40-3/4 X 36-1/2


(953 X 1035 X 927)
SEE OUTLINE DRAWINGS

45-1/2 X 41 X 37
(1156 X 1041 X 940)
SEE OUTLINE DRAWINGS

251 (114)
239 (108)

308 (140)
293 (133)

395 (179)
376 (171)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.

TWE5-PRC001-EN-10-15-99

Performance
Data Cooling

English Units

TWJ020CA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
18.2
19.7
21.2
22.7
17.9
19.3
20.8
22.3
17.5
18.9
20.4
21.9
17.0
18.4
19.8
21.3
16.5
17.9
19.2
20.7
15.6
16.8
18.1
19.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
15.5
16.7
18.0
18.6*
19.1*
13.0
14.3
15.5
16.8
18.1
10.3
11.6
12.8
14.1
15.4
7.5
8.8
10.1
11.3
12.6
15.3
16.6
17.8
18.4*
18.8*
12.8
14.1
15.4
16.7
17.9
10.1
11.4
12.7
13.9
15.2
7.4
8.6
9.9
11.2
12.4
15.2
16.4
17.6*
18.1*
18.5*
12.7
14.0
15.2
16.5
17.8
10.0
11.3
12.5
13.8
15.1
7.2
8.5
9.8
11.0
12.3
15.0
16.2
17.2*
17.7*
18.1*
12.5
13.8
15.0
16.3
17.6
9.8
11.0
12.3
13.6
14.9
7.0
8.3
9.5
10.8
12.1
14.7
16.0
16.8*
17.3*
17.7*
12.3
13.6
14.8
16.1
17.4
9.6
10.8
12.1
13.4
14.6
6.8
8.1
9.3
10.6
11.9
14.3
15.6*
16.0*
16.4*
16.9*
11.9
13.1
14.4
15.7
16.9*
9.2
10.4
11.7
13.0
14.2
6.4
7.7
8.9
10.2
11.5

COMPR.
KW
1.34
1.39
1.44
1.49
1.40
1.45
1.50
1.55
1.46
1.51
1.56
1.62
1.53
1.58
1.63
1.68
1.59
1.64
1.70
1.75
1.72
1.78
1.83
1.89

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

625
X0.99
X0.95
X0.99

800
X1.01
X1.06
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 20400 BTUH
AIRFLOW = 700 CFM
COMPRESSOR POWER = 1562 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
S.E.E.R. = 10.30 BTUH/WATT
E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWJ024CA WITH TWE030CA4 AT 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
24.2
26.0
28.0
30.0
23.8
25.6
27.5
29.5
23.4
25.2
27.1
29.0
22.8
24.6
26.4
28.3
22.2
24.0
25.7
27.6
21.1
22.7
24.4
26.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
19.7
21.3
22.9
24.3*
24.9*
16.7
18.3
19.8
21.4
23.0
13.3
14.9
16.5
18.0
19.6
9.9
11.5
13.0
14.6
16.2
19.6
21.1
22.7
24.0*
24.6*
16.5
18.1
19.7
21.2
22.8
13.2
14.7
16.3
17.9
19.4
9.7
11.3
12.8
14.4
16.0
19.4
21.0
22.5
23.7*
24.3*
16.4
17.9
19.5
21.0
22.6
13.0
14.5
16.1
17.7
19.2
9.5
11.1
12.7
14.2
15.8
19.2
20.7
22.3
23.2*
23.8*
16.1
17.7
19.2
20.8
22.4
12.7
14.3
15.9
17.4
19.0
9.3
10.9
12.4
14.0
15.6
18.9
20.5
22.0
22.8*
23.3*
15.9
17.4
19.0
20.6
22.1
12.5
14.1
15.6
17.2
18.8
9.0
10.6
12.2
13.7
15.3
18.4
20.0
21.3*
21.8*
22.4*
15.4
16.9
18.5
20.1
21.6
12.0
13.6
15.1
16.7
18.3
8.6
10.1
11.7
13.3
14.8

COMPR.
KW
1.92
1.98
2.05
2.12
2.01
2.08
2.14
2.21
2.10
2.17
2.24
2.31
2.21
2.27
2.34
2.41
2.31
2.37
2.44
2.51
2.52
2.58
2.65
2.71

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

800
X0.99
X0.95
X0.99

1025
X1.01
X1.06
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 27100 BTUH
AIRFLOW = 900 CFM
COMPRESSOR POWER = 2239 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 180 WATTS
E.E.R. = 8.90 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWJ030CA WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
29.0
31.2
33.5
35.8
28.5
30.6
32.9
35.2
28.0
30.1
32.3
34.6
27.3
29.4
31.5
33.8
26.6
28.7
30.8
32.9
25.3
27.2
29.2
31.3

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
22.8
24.5
26.2
28.0
29.3*
19.4
21.2
22.9
24.6
26.3
15.7
17.4
19.2
20.9
22.6
11.9
13.6
15.3
17.1
18.8
22.6
24.3
26.0
27.7
28.9*
19.2
20.9
22.7
24.4
26.1
15.5
17.2
18.9
20.7
22.4
11.7
13.4
15.1
16.9
18.6
22.3
24.1
25.8
27.5
28.5*
19.0
20.7
22.4
24.2
25.9
15.3
17.0
18.7
20.4
22.2
11.5
13.2
14.9
16.6
18.4
22.1
23.8
25.5
27.2
28.0*
18.7
20.4
22.1
23.9
25.6
15.0
16.7
18.4
20.1
21.9
11.2
12.9
14.6
16.3
18.1
21.8
23.5
25.2
26.8*
27.4*
18.4
20.1
21.9
23.6
25.3
14.7
16.4
18.1
19.9
21.6
10.9
12.6
14.3
16.1
17.8
21.2
22.9
24.6
25.7*
26.3*
17.8
19.6
21.3
23.0
24.7
14.1
15.8
17.6
19.3
21.0
10.3
12.0
13.8
15.5
17.2

COMPR.
KW
2.57
2.66
2.75
2.85
2.69
2.78
2.88
2.97
2.82
2.91
3.00
3.10
2.95
3.04
3.13
3.23
3.08
3.17
3.26
3.36
3.35
3.43
3.52
3.62

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

875
X0.98
X0.95
X0.99

1125
X1.01
X1.05
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 32400 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 3002 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 8.30 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWE5-PRC001-EN-10-15-99

Performance
Data Cooling

Metric Units

TWJ020CA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
5.3
5.8
6.2
6.7
5.2
5.7
6.1
6.5
5.1
5.5
6.0
6.4
5.0
5.4
5.8
6.2
4.8
5.2
5.6
6.1
4.6
4.9
5.3
5.7

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
4.5
4.9
5.3
5.4*
5.6*
3.8
4.2
4.5
4.9
5.3
3.0
3.4
3.8
4.1
4.5
2.2
2.6
3.0
3.3
3.7
4.5
4.9
5.2
5.4*
5.5*
3.8
4.1
4.5
4.9
5.2
3.0
3.3
3.7
4.1
4.5
2.2
2.5
2.9
3.3
3.6
4.5
4.8
5.2*
5.3*
5.4*
3.7
4.1
4.5
4.8
5.2
2.9
3.3
3.7
4.0
4.4
2.1
2.5
2.9
3.2
3.6
4.4
4.7
5.0*
5.2*
5.3*
3.7
4.0
4.4
4.8
5.2
2.9
3.2
3.6
4.0
4.4
2.1
2.4
2.8
3.2
3.5
4.3
4.7
4.9*
5.1*
5.2*
3.6
4.0
4.3
4.7
5.1
2.8
3.2
3.5
3.9
4.3
2.0
2.4
2.7
3.1
3.5
4.2
4.6*
4.7*
4.8*
5.0*
3.5
3.8
4.2
4.6
5.0*
2.7
3.0
3.4
3.8
4.2
1.9
2.3
2.6
3.0
3.4

COMPR.
KW
1.3
1.4
1.4
1.5
1.4
1.5
1.5
1.5
1.5
1.5
1.6
1.6
1.5
1.6
1.6
1.7
1.6
1.6
1.7
1.8
1.7
1.8
1.8
1.9

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1061
X0.99
X0.95
X0.99

1358
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 5.98 KW
AIRFLOW = 1189 CMH
COMPRESSOR POWER = 1562 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
S.E.E.R. = 10.30 BTUH/WATT
E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWJ024CA WITH TWE030CA4 AT 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
7.1
7.6
8.2
8.8
7.0
7.5
8.1
8.6
6.9
7.4
7.9
8.5
6.7
7.2
7.7
8.3
6.5
7.0
7.5
8.1
6.2
6.7
7.1
7.7

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
5.8
6.2
6.7
7.1*
7.3*
4.9
5.4
5.8
6.3
6.7
3.9
4.4
4.8
5.3
5.7
2.9
3.4
3.8
4.3
4.7
5.7
6.2
6.7
7.0*
7.2*
4.8
5.3
5.8
6.2
6.7
3.9
4.3
4.8
5.2
5.7
2.8
3.3
3.8
4.2
4.7
5.7
6.2
6.6
6.9*
7.1*
4.8
5.2
5.7
6.2
6.6
3.8
4.2
4.7
5.2
5.6
2.8
3.3
3.7
4.2
4.6
5.6
6.1
6.5
6.8*
7.0*
4.7
5.2
5.6
6.1
6.6
3.7
4.2
4.7
5.1
5.6
2.7
3.2
3.6
4.1
4.6
5.5
6.0
6.4
6.7*
6.8*
4.7
5.1
5.6
6.0
6.5
3.7
4.1
4.6
5.0
5.5
2.6
3.1
3.6
4.0
4.5
5.4
5.9
6.2*
6.4*
6.6*
4.5
5.0
5.4
5.9
6.3
3.5
4.0
4.4
4.9
5.4
2.5
3.0
3.4
3.9
4.3

COMPR.
KW
1.9
2.0
2.0
2.1
2.0
2.1
2.1
2.2
2.1
2.2
2.2
2.3
2.2
2.3
2.3
2.4
2.3
2.4
2.4
2.5
2.5
2.6
2.7
2.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1358
X0.99
X0.95
X0.99

1741
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 7.94 KW
AIRFLOW = 1528 CMH
COMPRESSOR POWER = 2239 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 180 WATTS
E.E.R. = 8.90 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWJ030CA WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.5
9.1
9.8
10.5
8.4
9.0
9.6
10.3
8.2
8.8
9.5
10.1
8.0
8.6
9.2
9.9
7.8
8.4
9.0
9.6
7.4
8.0
8.6
9.2

TWE5-PRC001-EN-10-15-99

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.7
7.2
7.7
8.2
8.6*
5.7
6.2
6.7
7.2
7.7
4.6
5.1
5.6
6.1
6.6
3.5
4.0
4.5
5.0
5.5
6.6
7.1
7.6
8.1
8.5*
5.6
6.1
6.7
7.1
7.6
4.5
5.0
5.5
6.1
6.6
3.4
3.9
4.4
5.0
5.4
6.5
7.1
7.6
8.1
8.4*
5.6
6.1
6.6
7.1
7.6
4.5
5.0
5.5
6.0
6.5
3.4
3.9
4.4
4.9
5.4
6.5
7.0
7.5
8.0
8.2*
5.5
6.0
6.5
7.0
7.5
4.4
4.9
5.4
5.9
6.4
3.3
3.8
4.3
4.8
5.3
6.4
6.9
7.4
7.9*
8.0*
5.4
5.9
6.4
6.9
7.4
4.3
4.8
5.3
5.8
6.3
3.2
3.7
4.2
4.7
5.2
6.2
6.7
7.2
7.5*
7.7*
5.2
5.7
6.2
6.7
7.2
4.1
4.6
5.2
5.7
6.2
3.0
3.5
4.0
4.5
5.0

COMPR.
KW
2.6
2.7
2.8
2.8
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.1
3.0
3.0
3.1
3.2
3.1
3.2
3.3
3.4
3.3
3.4
3.5
3.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.95
X0.99

1910
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.49 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 3002 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 8.30 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

Performance
Data Cooling

English Units

TWJ030CA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
30.7
33.0
35.3
37.7
30.1
32.3
34.6
37.0
29.5
31.7
33.9
36.2
28.8
30.9
33.0
35.3
28.0
30.0
32.1
34.3
26.5
28.4
30.4
32.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.1
27.1
29.1
31.0*
31.6*
21.2
23.2
25.2
27.2
29.2
16.9
18.9
20.9
22.9
24.9
12.5
14.5
16.5
18.5
20.4
24.9
26.9
28.9
30.5*
31.2*
21.0
22.9
24.9
26.9
28.9
16.6
18.6
20.6
22.6
24.6
12.2
14.2
16.2
18.2
20.2
24.6
26.6
28.6
30.0*
30.7*
20.7
22.7
24.7
26.7
28.7
16.4
18.4
20.4
22.3
24.3
12.0
14.0
15.9
17.9
19.9
24.3
26.3
28.3
29.3*
30.0*
20.4
22.4
24.3
26.3
28.3
16.0
18.0
20.0
22.0
24.0
11.6
13.6
15.6
17.6
19.6
24.0
26.0
27.9
28.7*
29.4*
20.0
22.0
24.0
26.0
28.0
15.7
17.7
19.7
21.7
23.7
11.3
13.3
15.3
17.3
19.3
23.3
25.3
26.8*
27.4*
28.1*
19.4
21.4
23.4
25.4
27.3
15.1
17.1
19.0
21.0
23.0
10.7
12.7
14.6
16.6
18.6

COMPR.
KW
2.65
2.75
2.84
2.94
2.78
2.87
2.97
3.07
2.91
3.00
3.10
3.20
3.04
3.13
3.23
3.33
3.17
3.27
3.36
3.46
3.45
3.54
3.63
3.73

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

975
X0.98
X0.95
X0.99

1275
X1.02
X1.07
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 34100 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 3104 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 9.05 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE
VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWJ036CA WITH TWE030CA4 AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
33.9
36.7
39.5
42.5
33.4
36.1
38.9
41.8
32.8
35.5
38.3
41.2
32.1
34.7
37.4
40.2
31.3
33.9
36.5
39.3
29.8
32.2
34.8
37.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.9
27.8
29.7
31.6
33.4
22.4
24.3
26.1
28.0
29.9
18.4
20.3
22.1
24.0
25.9
14.3
16.2
18.0
19.9
21.8
25.7
27.6
29.4
31.3
33.2
22.1
24.0
25.9
27.8
29.6
18.1
20.0
21.9
23.8
25.6
14.0
15.9
17.8
19.7
21.5
25.4
27.3
29.2
31.1
32.9*
21.9
23.8
25.6
27.5
29.4
17.9
19.8
21.6
23.5
25.4
13.8
15.7
17.5
19.4
21.3
25.1
27.0
28.9
30.7
32.4*
21.5
23.4
25.3
27.2
29.0
17.6
19.4
21.3
23.2
25.1
13.5
15.3
17.2
19.1
21.0
24.8
26.7
28.5
30.4
31.8*
21.2
23.1
25.0
26.8
28.7
17.2
19.1
21.0
22.8
24.7
13.1
15.0
16.9
18.7
20.6
24.1
26.0
27.9
29.7
30.6*
20.5
22.4
24.3
26.2
28.0
16.5
18.4
20.3
22.2
24.0
12.5
14.3
16.2
18.1
19.9

COMPR.
KW
2.52
2.60
2.68
2.77
2.65
2.73
2.82
2.91
2.78
2.87
2.95
3.04
2.92
3.00
3.09
3.18
3.06
3.14
3.23
3.31
3.35
3.42
3.50
3.58

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

975
X0.98
X0.95
X0.99

1275
X1.02
X1.06
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 38500 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2957 WATTS
I.D. FAN POWER = 540 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWJ036CA WITH TWE040CA4-B AT 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
37.2
40.1
43.1
46.2
36.5
39.3
42.3
45.3
35.8
38.6
41.5
44.4
34.9
37.6
40.4
43.3
34.0
36.6
39.3
42.1
32.1
34.6
37.1
39.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
30.6
33.0
35.5
37.6*
38.5*
25.8
28.3
30.7
33.1
35.6
20.6
23.0
25.4
27.9
30.3
15.2
17.6
20.1
22.5
25.0
30.3
32.7
35.2
37.0*
37.9*
25.5
28.0
30.4
32.8
35.3
20.3
22.7
25.1
27.6
30.0
14.9
17.3
19.8
22.2
24.7
30.0
32.4
34.9
36.5*
37.3*
25.2
27.7
30.1
32.5
35.0
20.0
22.4
24.8
27.3
29.7
14.6
17.0
19.5
21.9
24.4
29.6
32.0
34.5
35.7*
36.5*
24.8
27.3
29.7
32.1
34.6
19.6
22.0
24.4
26.9
29.3
14.2
16.6
19.1
21.5
24.0
29.2
31.6
34.1*
34.9*
35.8*
24.4
26.9
29.3
31.7
34.2
19.2
21.6
24.0
26.5
28.9
13.8
16.2
18.7
21.1
23.6
28.4
30.8
32.6*
33.4*
34.2*
23.6
26.1
28.5
30.9
33.4
18.4
20.8
23.2
25.7
28.1
13.0
15.4
17.9
20.3
22.8

COMPR.
KW
2.63
2.71
2.80
2.89
2.76
2.85
2.94
3.03
2.90
2.99
3.07
3.17
3.04
3.13
3.22
3.31
3.19
3.27
3.36
3.45
3.48
3.56
3.64
3.73

10

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1175
X0.97
X0.92
X0.98

1525
X1.01
X1.04
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 41300 BTUH
AIRFLOW = 1350 CFM
COMPRESSOR POWER = 3066 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 10.80 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWE5-PRC001-EN-10-15-99

Performance
Data Cooling

Metric Units

TWJ030CA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.0
9.7
10.3
11.0
8.8
9.5
10.1
10.8
8.6
9.3
9.9
10.6
8.4
9.1
9.7
10.3
8.2
8.8
9.4
10.0
7.8
8.3
8.9
9.5

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.4
7.9
8.5
9.1*
9.3*
6.2
6.8
7.4
8.0
8.6
5.0
5.5
6.1
6.7
7.3
3.7
4.2
4.8
5.4
6.0
7.3
7.9
8.5
8.9*
9.1*
6.2
6.7
7.3
7.9
8.5
4.9
5.4
6.0
6.6
7.2
3.6
4.2
4.7
5.3
5.9
7.2
7.8
8.4
8.8*
9.0*
6.1
6.7
7.2
7.8
8.4
4.8
5.4
6.0
6.5
7.1
3.5
4.1
4.7
5.2
5.8
7.1
7.7
8.3
8.6*
8.8*
6.0
6.6
7.1
7.7
8.3
4.7
5.3
5.9
6.4
7.0
3.4
4.0
4.6
5.2
5.7
7.0
7.6
8.2
8.4*
8.6*
5.9
6.4
7.0
7.6
8.2
4.6
5.2
5.8
6.4
6.9
3.3
3.9
4.5
5.1
5.7
6.8
7.4
7.9*
8.0*
8.2*
5.7
6.3
6.9
7.4
8.0
4.4
5.0
5.6
6.2
6.7
3.1
3.7
4.3
4.9
5.4

COMPR.
KW
2.7
2.8
2.8
2.9
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.2
3.3
3.4
3.5
3.5
3.5
3.6
3.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1656
X0.98
X0.95
X0.99

2165
X1.02
X1.07
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.99 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 3104 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 9.05 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWJ036CA WITH TWE030CA4 AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.9
10.8
11.6
12.5
9.8
10.6
11.4
12.2
9.6
10.4
11.2
12.1
9.4
10.2
11.0
11.8
9.2
9.9
10.7
11.5
8.7
9.4
10.2
11.0

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.6
8.1
8.7
9.3
9.8
6.6
7.1
7.6
8.2
8.8
5.4
5.9
6.5
7.0
7.6
4.2
4.7
5.3
5.8
6.4
7.5
8.1
8.6
9.2
9.7
6.5
7.0
7.6
8.1
8.7
5.3
5.9
6.4
7.0
7.5
4.1
4.7
5.2
5.8
6.3
7.4
8.0
8.6
9.1
9.6*
6.4
7.0
7.5
8.1
8.6
5.2
5.8
6.3
6.9
7.4
4.0
4.6
5.1
5.7
6.2
7.4
7.9
8.5
9.0
9.5*
6.3
6.9
7.4
8.0
8.5
5.2
5.7
6.2
6.8
7.4
4.0
4.5
5.0
5.6
6.2
7.3
7.8
8.4
8.9
9.3*
6.2
6.8
7.3
7.9
8.4
5.0
5.6
6.2
6.7
7.2
3.8
4.4
5.0
5.5
6.0
7.1
7.6
8.2
8.7
9.0*
6.0
6.6
7.1
7.7
8.2
4.8
5.4
5.9
6.5
7.0
3.7
4.2
4.7
5.3
5.8

COMPR.
KW
2.5
2.6
2.7
2.8
2.7
2.7
2.8
2.9
2.8
2.9
3.0
3.0
2.9
3.0
3.1
3.2
3.1
3.1
3.2
3.3
3.3
3.4
3.5
3.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1656
X0.98
X0.95
X0.99

2165
X1.02
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 11.28 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2957 WATTS
I.D. FAN POWER = 540 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWJ036CA WITH TWE040CA4-B AT 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
10.9
11.7
12.6
13.5
10.7
11.5
12.4
13.3
10.5
11.3
12.2
13.0
10.2
11.0
11.8
12.7
10.0
10.7
11.5
12.3
9.4
10.1
10.9
11.7

TWE5-PRC001-EN-10-15-99

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
9.0
9.7
10.4
11.0*
11.3*
7.6
8.3
9.0
9.7
10.4
6.0
6.7
7.4
8.2
8.9
4.5
5.2
5.9
6.6
7.3
8.9
9.6
10.3
10.8*
11.1*
7.5
8.2
8.9
9.6
10.3
5.9
6.7
7.4
8.1
8.8
4.4
5.1
5.8
6.5
7.2
8.8
9.5
10.2
10.7*
10.9*
7.4
8.1
8.8
9.5
10.3
5.9
6.6
7.3
8.0
8.7
4.3
5.0
5.7
6.4
7.1
8.7
9.4
10.1
10.5*
10.7*
7.3
8.0
8.7
9.4
10.1
5.7
6.4
7.1
7.9
8.6
4.2
4.9
5.6
6.3
7.0
8.6
9.3
10.0*
10.2*
10.5*
7.1
7.9
8.6
9.3
10.0
5.6
6.3
7.0
7.8
8.5
4.0
4.7
5.5
6.2
6.9
8.3
9.0
9.6*
9.8*
10.0*
6.9
7.6
8.4
9.1
9.8
5.4
6.1
6.8
7.5
8.2
3.8
4.5
5.2
5.9
6.7

COMPR.
KW
2.6
2.7
2.8
2.9
2.8
2.8
2.9
3.0
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.2
3.3
3.4
3.5
3.5
3.6
3.6
3.7

11

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1995
X0.97
X0.92
X0.98

2590
X1.01
X1.04
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.10 KW
AIRFLOW = 2293 CMH
COMPRESSOR POWER = 3066 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 10.80 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

Performance
Data Cooling

English Units

TWA030CD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
28.8
31.0
33.3
35.7
28.3
30.4
32.7
35.1
27.7
29.9
32.1
34.4
27.0
29.1
31.3
33.5
26.3
28.3
30.4
32.6
24.9
26.8
28.8
30.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
22.6
24.4
26.1
27.8
29.2*
19.3
21.0
22.8
24.5
26.2
15.6
17.3
19.1
20.8
22.5
11.8
13.6
15.3
17.0
18.7
22.4
24.1
25.8
27.6
28.7*
19.1
20.8
22.5
24.2
26.0
15.4
17.1
18.8
20.5
22.3
11.6
13.3
15.0
16.8
18.5
22.2
23.9
25.6
27.3
28.3*
18.9
20.6
22.3
24.0
25.7
15.2
16.9
18.6
20.3
22.0
11.4
13.1
14.8
16.5
18.2
21.9
23.6
25.3
27.1*
27.7*
18.5
20.3
22.0
23.7
25.4
14.8
16.6
18.3
20.0
21.7
11.1
12.8
14.5
16.2
17.9
21.6
23.3
25.0
26.5*
27.2*
18.2
20.0
21.7
23.4
25.1
14.5
16.2
18.0
19.7
21.4
10.7
12.5
14.2
15.9
17.6
21.0
22.7
24.4
25.4*
26.0*
17.6
19.3
21.1
22.8
24.5
13.9
15.6
17.3
19.1
20.8
10.1
11.8
13.6
15.3
17.0

COMPR.
KW
2.13
2.21
2.29
2.37
2.24
2.32
2.40
2.48
2.35
2.42
2.51
2.59
2.46
2.54
2.62
2.70
2.57
2.65
2.73
2.81
2.80
2.87
2.95
3.02

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

875
X0.98
X0.95
X0.99

1125
X1.01
X1.05
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 32200 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 2505 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 9.55 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWA030CD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
30.8
33.0
35.4
37.9
30.1
32.3
34.7
37.0
29.5
31.6
33.9
36.2
28.6
30.8
32.9
35.2
27.8
29.9
32.0
34.2
26.2
28.1
30.1
32.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.2
27.1
29.1
31.0*
31.7*
21.2
23.2
25.2
27.2
29.2
16.9
18.9
20.9
22.9
24.9
12.5
14.5
16.5
18.5
20.5
24.9
26.9
28.9
30.5*
31.2*
21.0
23.0
24.9
26.9
28.9
16.7
18.6
20.6
22.6
24.6
12.3
14.2
16.2
18.2
20.2
24.6
26.6
28.6
29.9*
30.6*
20.7
22.7
24.7
26.7
28.6
16.4
18.4
20.4
22.3
24.3
12.0
14.0
16.0
17.9
19.9
24.2
26.2
28.2
29.3*
29.9*
20.3
22.3
24.3
26.3
28.3
16.0
18.0
20.0
22.0
24.0
11.6
13.6
15.6
17.6
19.6
23.9
25.9
27.9*
28.6*
29.2*
20.0
22.0
23.9
25.9
27.9
15.7
17.6
19.6
21.6
23.6
11.3
13.2
15.2
17.2
19.2
23.2
25.2
26.5*
27.2*
27.8*
19.3
21.2
23.2
25.2
27.2
14.9
16.9
18.9
20.9
22.9
10.6
12.5
14.5
16.5
18.5

COMPR.
KW
2.21
2.29
2.37
2.45
2.32
2.40
2.48
2.56
2.43
2.51
2.59
2.67
2.54
2.62
2.70
2.78
2.66
2.73
2.81
2.90
2.89
2.96
3.04
3.11

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

975
X0.98
X0.95
X0.99

1275
X1.02
X1.07
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 34100 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2594 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 10.45 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWA040CD WITH TWE040CA4-B AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
39.3
42.2
45.2
48.4
38.5
41.4
44.3
47.4
37.7
40.5
43.4
46.4
36.7
39.4
42.3
45.2
35.7
38.4
41.1
44.0
33.7
36.2
38.8
41.5

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
32.2
34.8
37.4
39.6*
40.5*
27.1
29.7
32.3
34.9
37.4
21.5
24.1
26.7
29.3
31.8
15.8
18.4
21.0
23.6
26.1
31.9
34.4
37.0
39.0*
39.9*
26.8
29.4
32.0
34.5
37.1
21.2
23.8
26.4
28.9
31.5
15.5
18.1
20.7
23.2
25.8
31.5
34.1
36.7
38.4*
39.2*
26.5
29.1
31.6
34.2
36.8
20.9
23.5
26.0
28.6
31.2
15.2
17.7
20.3
22.9
25.5
31.1
33.7
36.3
37.5*
38.4*
26.0
28.6
31.2
33.8
36.4
20.5
23.0
25.6
28.2
30.8
14.7
17.3
19.9
22.5
25.1
30.7
33.3
35.9*
36.7*
37.6*
25.6
28.2
30.8
33.4
35.9
20.0
22.6
25.2
27.8
30.3
14.3
16.9
19.5
22.1
24.6
29.9
32.4
34.2*
35.0*
35.9*
24.8
27.4
29.9
32.5
35.1
19.2
21.8
24.3
26.9
29.5
13.5
16.1
18.6
21.2
23.8

COMPR.
KW
2.79
2.90
3.01
3.13
2.93
3.04
3.16
3.29
3.07
3.18
3.31
3.44
3.21
3.33
3.46
3.59
3.36
3.48
3.61
3.75
3.65
3.78
3.92
4.06

12

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1325
X0.98
X0.95
X0.99

1700
X1.01
X1.06
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 43500 BTUH
AIRFLOW = 1500 CFM
COMPRESSOR POWER = 3309 WATTS
I.D. FAN POWER = 420 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.45 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWE5-PRC001-EN-10-15-99

Performance
Data Cooling

Metric Units

TWA030CD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.4
9.1
9.8
10.5
8.3
8.9
9.6
10.3
8.1
8.8
9.4
10.1
7.9
8.5
9.2
9.8
7.7
8.3
8.9
9.6
7.3
7.9
8.4
9.0

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.6
7.1
7.6
8.1
8.6*
5.7
6.2
6.7
7.2
7.7
4.6
5.1
5.6
6.1
6.6
3.5
4.0
4.5
5.0
5.5
6.6
7.1
7.6
8.1
8.4*
5.6
6.1
6.6
7.1
7.6
4.5
5.0
5.5
6.0
6.5
3.4
3.9
4.4
4.9
5.4
6.5
7.0
7.5
8.0
8.3*
5.5
6.0
6.5
7.0
7.5
4.5
5.0
5.4
5.9
6.4
3.3
3.8
4.3
4.8
5.3
6.4
6.9
7.4
7.9*
8.1*
5.4
5.9
6.4
6.9
7.4
4.3
4.9
5.4
5.9
6.4
3.3
3.8
4.2
4.7
5.2
6.3
6.8
7.3
7.8*
8.0*
5.3
5.9
6.4
6.9
7.4
4.2
4.7
5.3
5.8
6.3
3.1
3.7
4.2
4.7
5.2
6.2
6.7
7.1
7.4*
7.6*
5.2
5.7
6.2
6.7
7.2
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0

COMPR.
KW
2.1
2.2
2.3
2.4
2.2
2.3
2.4
2.5
2.3
2.4
2.5
2.6
2.5
2.5
2.6
2.7
2.6
2.7
2.7
2.8
2.8
2.9
3.0
3.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.95
X0.99

1910
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.43 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2505 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 9.55 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWA030CD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.0
9.7
10.4
11.1
8.8
9.5
10.2
10.8
8.6
9.3
9.9
10.6
8.4
9.0
9.6
10.3
8.1
8.8
9.4
10.0
7.7
8.2
8.8
9.4

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.4
7.9
8.5
9.1*
9.3*
6.2
6.8
7.4
8.0
8.6
5.0
5.5
6.1
6.7
7.3
3.7
4.2
4.8
5.4
6.0
7.3
7.9
8.5
8.9*
9.1*
6.2
6.7
7.3
7.9
8.5
4.9
5.4
6.0
6.6
7.2
3.6
4.2
4.7
5.3
5.9
7.2
7.8
8.4
8.8*
9.0*
6.1
6.7
7.2
7.8
8.4
4.8
5.4
6.0
6.5
7.1
3.5
4.1
4.7
5.2
5.8
7.1
7.7
8.3
8.6*
8.8*
5.9
6.5
7.1
7.7
8.3
4.7
5.3
5.9
6.4
7.0
3.4
4.0
4.6
5.2
5.7
7.0
7.6
8.2*
8.4*
8.6*
5.9
6.4
7.0
7.6
8.2
4.6
5.2
5.7
6.3
6.9
3.3
3.9
4.5
5.0
5.6
6.8
7.4
7.8*
8.0*
8.1*
5.7
6.2
6.8
7.4
8.0
4.4
5.0
5.5
6.1
6.7
3.1
3.7
4.2
4.8
5.4

COMPR.
KW
2.2
2.3
2.4
2.5
2.3
2.4
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.8
2.7
2.7
2.8
2.9
2.9
3.0
3.0
3.1

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1656
X0.98
X0.95
X0.99

2165
X1.02
X1.07
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.99 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2594 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 10.45 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWA040CD WITH TWE040CA4-B AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.5
12.4
13.2
14.2
11.3
12.1
13.0
13.9
11.0
11.9
12.7
13.6
10.8
11.5
12.4
13.2
10.5
11.3
12.0
12.9
9.9
10.6
11.4
12.2

TWE5-PRC001-EN-10-15-99

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
9.4
10.2
11.0
11.6*
11.9*
7.9
8.7
9.5
10.2
11.0
6.3
7.1
7.8
8.6
9.3
4.6
5.4
6.2
6.9
7.6
9.3
10.1
10.8
11.4*
11.7*
7.9
8.6
9.4
10.1
10.9
6.2
7.0
7.7
8.5
9.2
4.5
5.3
6.1
6.8
7.6
9.2
10.0
10.8
11.3*
11.5*
7.8
8.5
9.3
10.0
10.8
6.1
6.9
7.6
8.4
9.1
4.5
5.2
5.9
6.7
7.5
9.1
9.9
10.6
11.0*
11.3*
7.6
8.4
9.1
9.9
10.7
6.0
6.7
7.5
8.3
9.0
4.3
5.1
5.8
6.6
7.4
9.0
9.8
10.5*
10.8*
11.0*
7.5
8.3
9.0
9.8
10.5
5.9
6.6
7.4
8.1
8.9
4.2
5.0
5.7
6.5
7.2
8.8
9.5
10.0*
10.3*
10.5*
7.3
8.0
8.8
9.5
10.3
5.6
6.4
7.1
7.9
8.6
4.0
4.7
5.4
6.2
7.0

COMPR.
KW
2.8
2.9
3.0
3.1
2.9
3.0
3.2
3.3
3.1
3.2
3.3
3.4
3.2
3.3
3.5
3.6
3.4
3.5
3.6
3.8
3.7
3.8
3.9
4.1

13

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2250
X0.98
X0.95
X0.99

2887
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.75 KW
AIRFLOW = 2547 CMH
COMPRESSOR POWER = 3309 WATTS
I.D. FAN POWER = 420 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.45 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

Performance
Data Cooling

English Units

TWA040CD WITH TWE050CA5-C AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
40.1
43.1
46.1
49.3
39.1
42.0
44.9
48.0
38.1
40.9
43.7
46.7
37.0
39.7
42.5
45.3
35.9
38.5
41.2
44.0
33.6
36.1
38.6
41.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
33.2
35.9
38.6
40.6*
41.5*
28.0
30.7
33.3
36.0
38.7
22.2
24.9
27.5
30.2
32.9
16.3
18.9
21.6
24.3
27.0
32.8
35.5
38.2
39.8*
40.7*
27.5
30.2
32.9
35.6
38.2
21.7
24.4
27.1
29.8
32.4
15.8
18.5
21.2
23.8
26.5
32.4
35.0
37.7
38.9*
39.8*
27.1
29.8
32.4
35.1
37.8
21.3
24.0
26.6
29.3
32.0
15.4
18.0
20.7
23.4
26.1
31.9
34.6
37.2*
38.0*
38.9*
26.6
29.3
32.0
34.6
37.3
20.8
23.5
26.2
28.8
31.5
14.9
17.6
20.2
22.9
25.6
31.4
34.1
36.3*
37.1*
37.9*
26.1
28.8
31.5
34.2
36.8
20.3
23.0
25.7
28.4
31.0
14.4
17.1
19.8
22.4
25.1
30.5
33.2
34.4*
35.2*
36.0*
25.2
27.9
30.6
33.2
35.9
19.4
22.1
24.7
27.4
30.1
13.5
16.2
18.8
21.5
24.2

COMPR.
KW
2.78
2.89
3.01
3.13
2.91
3.02
3.14
3.27
3.04
3.15
3.28
3.41
3.16
3.29
3.41
3.55
3.30
3.42
3.55
3.69
3.56
3.69
3.82
3.96

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1325
X0.99
X0.95
X0.99

1700
X1.01
X1.06
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 43800 BTUH
AIRFLOW = 1500 CFM
COMPRESSOR POWER = 3279 WATTS
I.D. FAN POWER = 510 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.30 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWA050CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
48.8
52.3
55.9
59.6
47.6
51.0
54.5
58.1
46.4
49.7
53.1
56.6
45.1
48.2
51.5
54.9
43.7
46.8
50.0
53.2
41.1
43.9
46.9
49.9

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
39.6
42.7
45.8
49.0*
50.1*
33.4
36.5
39.6
42.7
45.9
26.6
29.7
32.8
35.9
39.0
19.6
22.7
25.8
29.0
32.1
39.1
42.2
45.3
48.0*
49.1*
32.9
36.0
39.1
42.2
45.3
26.0
29.2
32.3
35.4
38.5
19.1
22.2
25.3
28.4
31.5
38.5
41.6
44.8
47.0*
48.1*
32.3
35.5
38.6
41.7
44.8
25.5
28.6
31.7
34.9
38.0
18.6
21.7
24.8
27.9
31.0
38.0
41.1
44.2
45.9*
46.9*
31.8
34.9
38.0
41.1
44.2
24.9
28.1
31.2
34.3
37.4
18.0
21.1
24.2
27.3
30.4
37.4
40.5
43.6
44.8*
45.8*
31.2
34.3
37.4
40.5
43.7
24.4
27.5
30.6
33.7
36.8
17.4
20.5
23.6
26.8
29.9
36.3
39.4
41.6*
42.5*
43.5*
30.1
33.2
36.3
39.4
42.5
23.2
26.3
29.5
32.6
35.7
16.3
19.4
22.5
25.6
28.7

COMPR.
KW
3.60
3.72
3.84
3.96
3.77
3.88
4.00
4.13
3.93
4.05
4.17
4.30
4.10
4.21
4.33
4.46
4.27
4.38
4.50
4.62
4.61
4.71
4.83
4.94

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1575
X0.99
X0.95
X0.99

2025
X1.01
X1.05
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 53100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 4171 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 255 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWA060CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
57.2
61.6
66.1
70.8
55.9
60.1
64.6
69.1
54.6
58.7
63.1
67.5
53.2
57.2
61.4
65.8
51.8
55.7
59.8
64.0
48.9
52.6
56.5
60.5

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
43.7
46.8
50.0
53.1
56.3
37.6
40.7
43.9
47.0
50.2
30.8
34.0
37.1
40.2
43.4
23.8
27.0
30.1
33.3
36.4
43.1
46.3
49.4
52.6
55.7
37.0
40.2
43.3
46.5
49.6
30.2
33.4
36.5
39.7
42.8
23.2
26.4
29.5
32.7
35.8
42.5
45.7
48.8
52.0
55.0*
36.4
39.6
42.7
45.9
49.0
29.6
32.8
35.9
39.1
42.2
22.7
25.8
29.0
32.1
35.3
41.9
45.1
48.2
51.4
53.8*
35.8
38.9
42.1
45.2
48.4
29.0
32.1
35.3
38.4
41.6
22.0
25.2
28.3
31.5
34.6
41.3
44.4
47.6
50.7
52.7*
35.2
38.3
41.5
44.6
47.8
28.4
31.5
34.7
37.8
40.9
21.4
24.5
27.7
30.8
34.0
40.1
43.2
46.3
49.3*
50.4*
33.9
37.1
40.2
43.4
46.5
27.1
30.2
33.4
36.5
39.7
20.1
23.3
26.4
29.6
32.7

14

COMPR.
KW
4.61
4.77
4.93
5.10
4.80
4.96
5.13
5.30
5.00
5.16
5.33
5.50
5.23
5.38
5.55
5.71
5.45
5.61
5.77
5.93
5.91
6.06
6.20
6.36

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1575
X0.98
X0.95
X0.99

2025
X1.01
X1.05
X1.01

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 63100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 5326 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 395 WATTS
E.E.R. = 9.20 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

TWE5-PRC001-EN-10-15-99

Performance
Data Cooling

Metric Units

TWA040CD WITH TWE050CA5-C AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.7
12.6
13.5
14.4
11.5
12.3
13.2
14.1
11.2
12.0
12.8
13.7
10.8
11.6
12.5
13.3
10.5
11.3
12.1
12.9
9.8
10.6
11.3
12.1

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
9.7
10.5
11.3
11.9*
12.2*
8.2
9.0
9.8
10.5
11.3
6.5
7.3
8.1
8.8
9.6
4.8
5.5
6.3
7.1
7.9
9.6
10.4
11.2
11.7*
11.9*
8.1
8.8
9.6
10.4
11.2
6.4
7.1
7.9
8.7
9.5
4.6
5.4
6.2
7.0
7.8
9.5
10.3
11.0
11.4*
11.7*
7.9
8.7
9.5
10.3
11.1
6.2
7.0
7.8
8.6
9.4
4.5
5.3
6.1
6.9
7.6
9.3
10.1
10.9*
11.1*
11.4*
7.8
8.6
9.4
10.1
10.9
6.1
6.9
7.7
8.4
9.2
4.4
5.2
5.9
6.7
7.5
9.2
10.0
10.6*
10.9*
11.1*
7.6
8.4
9.2
10.0
10.8
5.9
6.7
7.5
8.3
9.1
4.2
5.0
5.8
6.6
7.4
8.9
9.7
10.1*
10.3*
10.5*
7.4
8.2
9.0
9.7
10.5
5.7
6.5
7.2
8.0
8.8
4.0
4.7
5.5
6.3
7.1

COMPR.
KW
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.3
3.0
3.2
3.3
3.4
3.2
3.3
3.4
3.5
3.3
3.4
3.5
3.7
3.6
3.7
3.8
4.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2250
X0.99
X0.95
X0.99

2887
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.83 KW
AIRFLOW = 2547 CMH
COMPRESSOR POWER = 3279 WATTS
I.D. FAN POWER = 510 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.30 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWA050CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
14.3
15.3
16.4
17.5
13.9
14.9
16.0
17.0
13.6
14.6
15.6
16.6
13.2
14.1
15.1
16.1
12.8
13.7
14.6
15.6
12.0
12.9
13.7
14.6

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
11.6
12.5
13.4
14.4*
14.7*
9.8
10.7
11.6
12.5
13.4
7.8
8.7
9.6
10.5
11.4
5.7
6.7
7.6
8.5
9.4
11.5
12.4
13.3
14.1*
14.4*
9.6
10.5
11.5
12.4
13.3
7.6
8.6
9.5
10.4
11.3
5.6
6.5
7.4
8.3
9.2
11.3
12.2
13.1
13.8*
14.1*
9.5
10.4
11.3
12.2
13.1
7.5
8.4
9.3
10.2
11.1
5.4
6.4
7.3
8.2
9.1
11.1
12.0
13.0
13.4*
13.7*
9.3
10.2
11.1
12.0
13.0
7.3
8.2
9.1
10.0
11.0
5.3
6.2
7.1
8.0
8.9
11.0
11.9
12.8
13.1*
13.4*
9.1
10.0
11.0
11.9
12.8
7.1
8.1
9.0
9.9
10.8
5.1
6.0
6.9
7.9
8.8
10.6
11.5
12.2*
12.5*
12.7*
8.8
9.7
10.6
11.5
12.5
6.8
7.7
8.6
9.6
10.5
4.8
5.7
6.6
7.5
8.4

COMPR.
KW
3.6
3.7
3.8
4.0
3.8
3.9
4.0
4.1
3.9
4.1
4.2
4.3
4.1
4.2
4.3
4.5
4.3
4.4
4.5
4.6
4.6
4.7
4.8
4.9

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2675
X0.99
X0.95
X0.99

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 15.56 KW
AIRFLOW = 3057 CMH
COMPRESSOR POWER = 4171 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 255 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

TWA060CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
16.8
18.0
19.4
20.7
16.4
17.6
18.9
20.2
16.0
17.2
18.5
19.8
15.6
16.8
18.0
19.3
15.2
16.3
17.5
18.8
14.3
15.4
16.6
17.7

TWE5-PRC001-EN-10-15-99

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
12.8
13.7
14.6
15.6
16.5
11.0
11.9
12.9
13.8
14.7
9.0
10.0
10.9
11.8
12.7
7.0
7.9
8.8
9.8
10.7
12.6
13.6
14.5
15.4
16.3
10.8
11.8
12.7
13.6
14.5
8.8
9.8
10.7
11.6
12.5
6.8
7.7
8.6
9.6
10.5
12.5
13.4
14.3
15.2
16.1*
10.7
11.6
12.5
13.4
14.4
8.7
9.6
10.5
11.5
12.4
6.7
7.6
8.5
9.4
10.3
12.3
13.2
14.1
15.1
15.8*
10.5
11.4
12.3
13.2
14.2
8.5
9.4
10.3
11.3
12.2
6.4
7.4
8.3
9.2
10.1
12.1
13.0
13.9
14.9
15.4*
10.3
11.2
12.2
13.1
14.0
8.3
9.2
10.2
11.1
12.0
6.3
7.2
8.1
9.0
10.0
11.7
12.7
13.6
14.4*
14.8*
9.9
10.9
11.8
12.7
13.6
7.9
8.8
9.8
10.7
11.6
5.9
6.8
7.7
8.7
9.6

COMPR.
KW
4.6
4.8
4.9
5.1
4.8
5.0
5.1
5.3
5.0
5.2
5.3
5.5
5.2
5.4
5.6
5.7
5.4
5.6
5.8
5.9
5.9
6.1
6.2
6.4

15

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2675
X0.98
X0.95
X0.99

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 18.49 KW
AIRFLOW = 3057 CMH
COMPRESSOR POWER = 5326 WATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 395 WATTS
E.E.R. = 9.20 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE
VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

Performance
Data Heating

English Units

TWJ020CA WITH TWE030CA4 AT 700 CFM


O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
6.79
6.60
6.50
6.41
8.13
7.90
7.78
7.67
9.48
9.20
9.06
8.92
10.8
10.5
10.3
10.2
11.2
10.9
10.7
10.5
11.6
11.2
11.0
10.9
11.9
11.6
11.4
11.2
12.3
11.9
11.8
11.6
12.7
12.3
12.1
11.9
18.9
18.3
18.0
17.7
20.2
19.6
19.3
19.0
21.6
20.9
20.6
20.2
22.9
22.2
21.8
21.5
24.3
23.5
23.1
22.7
25.6
24.8
24.4
24.0

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.10
7.93
7.85
7.77
9.91
9.70
9.60
9.49
11.7
11.5
11.3
11.2
13.5
13.2
13.1
12.9
15.3
15.0
14.8
14.7
16.2
15.9
15.7
15.5
17.1
16.7
16.5
16.3
18.0
17.6
17.4
17.2
18.9
18.4
18.2
18.0
19.8
19.3
19.1
18.9
26.2
25.6
25.3
25.0
28.0
27.4
27.0
26.7
29.8
29.1
28.8
28.4
31.6
30.9
30.5
30.2
33.5
32.7
32.3
31.9
35.3
34.4
34.0
33.6

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
9.79
9.60
9.51
9.41
11.8
11.6
11.5
11.4
13.9
13.6
13.5
13.3
15.9
15.6
15.4
15.3
18.0
17.6
17.4
17.2
18.9
18.5
18.3
18.2
19.9
19.5
19.3
19.1
20.9
20.4
20.2
20.0
21.8
21.4
21.2
20.9
22.8
22.3
22.1
21.8
30.2
29.6
29.3
29.0
32.3
31.6
31.3
30.9
34.3
33.6
33.2
32.9
36.4
35.6
35.2
34.8
38.4
37.6
37.2
36.8
40.5
39.6
39.2
38.7

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.47
1.54
1.58
1.61
1.50
1.57
1.61
1.64
1.52
1.60
1.63
1.67
1.55
1.63
1.66
1.70
1.56
1.64
1.68
1.71
1.57
1.65
1.69
1.73
1.58
1.66
1.70
1.74
1.60
1.68
1.71
1.75
1.61
1.69
1.73
1.77
1.71
1.79
1.84
1.88
1.73
1.82
1.87
1.91
1.76
1.85
1.90
1.94
1.79
1.88
1.92
1.97
1.81
1.91
1.95
2.00
1.84
1.93
1.98
2.03

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 700 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
625
800
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.01
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 700 CFM
HEATING CAP. (HIGH TEMP.) = 18300 BTUH
HEATING CAP. (LOW TEMP.) = 10500 BTUH
COMPR. POWER (HIGH TEMP.) = 1354 WATTS
COMPR. POWER (LOW TEMP.) = 1185 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.00
COEFF. OF PERF. (LOW TEMP.) = 1.88
OUTDOOR FAN POWER = 130 WATTS
INDOOR FAN POWER = 310 WATTS
NOTE: RATED WITH 25 FEET OF 3/4
SUCTION AND 5/16 LIQUID LINE

TWJ024CA WITH TWE030CA4 AT 900 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.86
1.94
1.98
2.03
1.92
2.01
2.06
2.10
1.99
2.08
2.13
2.17
2.06
2.15
2.20
2.25
2.12
2.22
2.27
2.32
2.18
2.28
2.33
2.38
2.23
2.34
2.39
2.44
2.29
2.40
2.45
2.51
2.34
2.45
2.51
2.57
2.39
2.51
2.57
2.63
2.52
2.65
2.71
2.77
2.59
2.72
2.78
2.85
2.66
2.79
2.86
2.92
2.72
2.86
2.93
3.00
2.79
2.93
3.00
3.07
2.86
3.00
3.07
3.14

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 900 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
800
1025
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 900 CFM
HEATING CAP. (HIGH TEMP.) = 25600 BTUH
HEATING CAP. (LOW TEMP.) = 15000 BTUH
COMPR. POWER (HIGH TEMP.) = 2038 WATTS
COMPR. POWER (LOW TEMP.) = 1614 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.84
COEFF. OF PERF. (LOW TEMP.) = 1.96
OUTDOOR FAN POWER = 180 WATTS
INDOOR FAN POWER = 430 WATTS
NOTE: RATED WITH 25 FEET OF 3/4
SUCTION AND 5/16 LIQUID LINE

TWJ030CA WITH TWE030CA4 AT 1000 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.27
2.38
2.44
2.49
2.36
2.47
2.53
2.59
2.44
2.56
2.62
2.69
2.53
2.65
2.72
2.78
2.61
2.74
2.81
2.88
2.69
2.83
2.89
2.96
2.77
2.91
2.98
3.05
2.85
2.99
3.06
3.14
2.92
3.07
3.15
3.22
3.00
3.16
3.23
3.31
3.12
3.28
3.37
3.45
3.21
3.37
3.46
3.54
3.29
3.46
3.55
3.64
3.38
3.55
3.64
3.73
3.46
3.64
3.74
3.83
3.55
3.73
3.83
3.92

16

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1000 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
875
1125
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 29600 BTUH
HEATING CAP. (LOW TEMP.) = 17600 BTUH
COMPR. POWER (HIGH TEMP.) = 2649 WATTS
COMPR. POWER (LOW TEMP.) = 2109 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.64
COEFF. OF PERF. (LOW TEMP.) = 1.86
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN POWER = 440 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWE5-PRC001-EN-10-15-99

Performance
Data Heating

Metric Units

TWJ020CA WITH TWE030CA4 AT 1189 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.0
1.9
1.9
1.9
2.4
2.3
2.3
2.2
2.8
2.7
2.7
2.6
3.2
3.1
3.0
3.0
3.3
3.2
3.1
3.1
3.4
3.3
3.2
3.2
3.5
3.4
3.3
3.3
3.6
3.5
3.5
3.4
3.7
3.6
3.5
3.5
5.5
5.4
5.3
5.2
5.9
5.7
5.7
5.6
6.3
6.1
6.0
5.9
6.7
6.5
6.4
6.3
7.1
6.9
6.8
6.7
7.5
7.3
7.1
7.0

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.4
2.3
2.3
2.3
2.9
2.8
2.8
2.8
3.4
3.4
3.3
3.3
4.0
3.9
3.8
3.8
4.5
4.4
4.3
4.3
4.7
4.7
4.6
4.5
5.0
4.9
4.8
4.8
5.3
5.2
5.1
5.0
5.5
5.4
5.3
5.3
5.8
5.7
5.6
5.5
7.7
7.5
7.4
7.3
8.2
8.0
7.9
7.8
8.7
8.5
8.4
8.3
9.3
9.1
8.9
8.8
9.8
9.6
9.5
9.3
10.3
10.1
10.0
9.8

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.9
2.8
2.8
2.8
3.5
3.4
3.4
3.3
4.1
4.0
4.0
3.9
4.7
4.6
4.5
4.5
5.3
5.2
5.1
5.0
5.5
5.4
5.4
5.3
5.8
5.7
5.7
5.6
6.1
6.0
5.9
5.9
6.4
6.3
6.2
6.1
6.7
6.5
6.5
6.4
8.8
8.7
8.6
8.5
9.5
9.3
9.2
9.1
10.0
9.8
9.7
9.6
10.7
10.4
10.3
10.2
11.3
11.0
10.9
10.8
11.9
11.6
11.5
11.3

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.5
1.5
1.6
1.6
1.5
1.6
1.6
1.6
1.5
1.6
1.6
1.7
1.5
1.6
1.7
1.7
1.6
1.6
1.7
1.7
1.6
1.6
1.7
1.7
1.6
1.7
1.7
1.7
1.6
1.7
1.7
1.8
1.6
1.7
1.7
1.8
1.7
1.8
1.8
1.9
1.7
1.8
1.9
1.9
1.8
1.9
1.9
1.9
1.8
1.9
1.9
2.0
1.8
1.9
2.0
2.0
1.8
1.9
2.0
2.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1189 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1061
1358
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.01
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1189 CMH
HEATING CAP. (HIGH TEMP.) = 5.36 KW
HEATING CAP. (LOW TEMP.) = 3.08 KW
COMPR. POWER (HIGH TEMP.) = 1354 WATTS
COMPR. POWER (LOW TEMP.) = 1185 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.00
COEFF. OF PERF. (LOW TEMP.) = 1.88
OUTDOOR FAN POWER = 130 WATTS
INDOOR FAN POWER = 310 WATTS
NOTE: RATED WITH 7.62 METERS OF 19 MM
SUCTION AND 8 MM LIQUID LINE

TWJ024CA WITH TWE030CA4 AT 1528 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.9
1.9
2.0
2.0
1.9
2.0
2.1
2.1
2.0
2.1
2.1
2.2
2.1
2.2
2.2
2.3
2.1
2.2
2.3
2.3
2.2
2.3
2.3
2.4
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.6
2.5
2.7
2.7
2.8
2.6
2.7
2.8
2.8
2.7
2.8
2.9
2.9
2.7
2.9
2.9
3.0
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.1

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1528 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1358
1741
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1528 CMH
HEATING CAP. (HIGH TEMP.) = 7.50 KW
HEATING CAP. (LOW TEMP.) = 4.39 KW
COMPR. POWER (HIGH TEMP.) = 2038 WATTS
COMPR. POWER (LOW TEMP.) = 1614 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.84
COEFF. OF PERF. (LOW TEMP.) = 1.96
OUTDOOR FAN POWER = 180 WATTS
INDOOR FAN POWER = 430 WATTS
NOTE: RATED WITH 7.62 METERS OF 19 MM
SUCTION AND 8 MM LIQUID LINE

TWJ030CA WITH TWE030CA4 AT 1698 CMH

TWE5-PRC001-EN-10-15-99

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.3
2.4
2.4
2.5
2.4
2.5
2.5
2.6
2.4
2.6
2.6
2.7
2.5
2.7
2.7
2.8
2.6
2.7
2.8
2.9
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.0
2.8
3.0
3.1
3.1
2.9
3.1
3.2
3.2
3.0
3.2
3.2
3.3
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.5
3.3
3.5
3.5
3.6
3.4
3.5
3.6
3.7
3.5
3.6
3.7
3.8
3.5
3.7
3.8
3.9

17

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1698 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1486
1910
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEATING CAP. (HIGH TEMP.) = 8.67 KW
HEATING CAP. (LOW TEMP.) = 5.16 KW
COMPR. POWER (HIGH TEMP.) = 2649 WATTS
COMPR. POWER (LOW TEMP.) = 2109 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.64
COEFF. OF PERF. (LOW TEMP.) = 1.86
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN POWER = 440 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

Performance
Data Heating

English Units

TWJ030CA WITH TWE040CA4-B AT 1100 CFM


O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
9.46
9.27
9.17
9.08
11.6
11.3
11.2
11.1
13.6
13.4
13.2
13.1
15.7
15.4
15.2
15.1
17.8
17.5
17.3
17.1
18.9
18.5
18.3
18.1
19.9
19.5
19.3
19.1
21.0
20.5
20.3
20.1
22.0
21.6
21.3
21.1
23.1
22.6
22.3
22.1
30.4
29.7
29.4
29.1
32.5
31.8
31.4
31.1
34.6
33.8
33.5
33.1
36.7
35.9
35.5
35.1
38.8
37.9
37.5
37.1
40.9
40.0
39.5
39.1

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.32
8.18
8.11
8.04
10.8
10.6
10.5
10.4
13.3
13.0
12.9
12.8
15.8
15.5
15.3
15.2
18.3
17.9
17.7
17.5
20.7
20.3
20.1
19.9
21.9
21.5
21.3
21.1
23.1
22.7
22.4
22.2
24.3
23.8
23.6
23.3
25.5
25.0
24.7
24.5
26.7
26.2
25.9
25.6
35.6
34.9
34.5
34.2
38.1
37.3
36.9
36.6
40.6
39.8
39.3
38.9
43.1
42.2
41.8
41.3
45.6
44.6
44.2
43.7
48.0
47.1
46.6
46.1

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
7.73
7.59
7.52
7.45
10.3
10.1
10.0
9.94
12.9
12.7
12.5
12.4
15.5
15.2
15.1
14.9
18.1
17.7
17.6
17.4
20.7
20.3
20.1
19.9
22.0
21.6
21.3
21.1
23.3
22.8
22.6
22.4
24.6
24.1
23.9
23.6
25.9
25.4
25.1
24.9
27.2
26.7
26.4
26.1
36.3
35.5
35.1
34.8
38.9
38.1
37.7
37.2
41.5
40.6
40.2
39.7
44.1
43.1
42.7
42.2
46.6
45.7
45.2
44.7
49.2
48.2
47.7
47.2

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.12
2.24
2.30
2.36
2.19
2.31
2.37
2.44
2.26
2.39
2.45
2.52
2.33
2.47
2.53
2.60
2.40
2.54
2.61
2.68
2.47
2.61
2.68
2.76
2.54
2.69
2.76
2.83
2.61
2.76
2.83
2.91
2.67
2.83
2.91
2.99
2.74
2.90
2.98
3.06
2.83
3.00
3.08
3.17
2.91
3.08
3.16
3.25
2.98
3.15
3.24
3.33
3.05
3.23
3.32
3.41
3.12
3.31
3.40
3.49
3.19
3.38
3.48
3.57

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
975
1275
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 29800 BTUH
HEATING CAP. (LOW TEMP.) = 17500 BTUH
COMPR. POWER (HIGH TEMP.) = 2504 WATTS
COMPR. POWER (LOW TEMP.) = 2047 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.92
COEFF. OF PERF. (LOW TEMP.) = 2.00
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN POWER = 300 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWJ036CA WITH TWE030CA4 AT 1100 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.00
2.09
2.13
2.18
2.13
2.22
2.27
2.32
2.25
2.36
2.41
2.46
2.38
2.49
2.54
2.60
2.50
2.62
2.68
2.74
2.63
2.75
2.82
2.88
2.71
2.85
2.91
2.98
2.80
2.94
3.01
3.08
2.89
3.03
3.10
3.18
2.98
3.13
3.20
3.27
3.06
3.22
3.30
3.37
3.38
3.55
3.64
3.72
3.50
3.68
3.77
3.87
3.63
3.82
3.91
4.01
3.75
3.95
4.05
4.15
3.88
4.08
4.19
4.29
4.00
4.22
4.32
4.43

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
975
1275
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.02
X0.97
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 35000 BTUH
HEATING CAP. (LOW TEMP.) = 20400 BTUH
COMPR. POWER (HIGH TEMP.) = 2776 WATTS
COMPR. POWER (LOW TEMP.) = 1982 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.88
COEFF. OF PERF. (LOW TEMP.) = 2.16
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 540 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWJ036CA WITH TWE040CA4-B AT 1400 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.84
1.93
1.98
2.03
1.94
2.05
2.10
2.15
2.05
2.16
2.22
2.27
2.16
2.27
2.33
2.39
2.26
2.39
2.45
2.52
2.37
2.50
2.57
2.64
2.44
2.58
2.65
2.72
2.52
2.66
2.73
2.81
2.59
2.74
2.82
2.89
2.67
2.82
2.90
2.97
2.74
2.90
2.98
3.06
3.00
3.18
3.27
3.36
3.11
3.29
3.39
3.48
3.22
3.41
3.50
3.60
3.32
3.52
3.62
3.72
3.43
3.63
3.74
3.84
3.54
3.75
3.85
3.96

18

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1400 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1175
1525
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.03
X0.99
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1350 CFM
HEATING CAP. (HIGH TEMP.) = 35400 BTUH
HEATING CAP. (LOW TEMP.) = 20200 BTUH
COMPR. POWER (HIGH TEMP.) = 2590 WATTS
COMPR. POWER (LOW TEMP.) = 1906 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 360 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWE5-PRC001-EN-10-15-99

Performance
Data Heating

Metric Units

TWJ030CA WITH TWE040CA4-B AT 1868 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.8
2.7
2.7
2.7
3.4
3.3
3.3
3.3
4.0
3.9
3.9
3.8
4.6
4.5
4.5
4.4
5.2
5.1
5.1
5.0
5.5
5.4
5.4
5.3
5.8
5.7
5.7
5.6
6.2
6.0
5.9
5.9
6.4
6.3
6.2
6.2
6.8
6.6
6.5
6.5
8.9
8.7
8.6
8.5
9.5
9.3
9.2
9.1
10.1
9.9
9.8
9.7
10.8
10.5
10.4
10.3
11.4
11.1
11.0
10.9
12.0
11.7
11.6
11.5

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.4
2.4
2.4
2.4
3.2
3.1
3.1
3.0
3.9
3.8
3.8
3.8
4.6
4.5
4.5
4.5
5.4
5.2
5.2
5.1
6.1
5.9
5.9
5.8
6.4
6.3
6.2
6.2
6.8
6.7
6.6
6.5
7.1
7.0
6.9
6.8
7.5
7.3
7.2
7.2
7.8
7.7
7.6
7.5
10.4
10.2
10.1
10.0
11.2
10.9
10.8
10.7
11.9
11.7
11.5
11.4
12.6
12.4
12.2
12.1
13.4
13.1
13.0
12.8
14.1
13.8
13.7
13.5

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.3
2.2
2.2
2.2
3.0
3.0
2.9
2.9
3.8
3.7
3.7
3.6
4.5
4.5
4.4
4.4
5.3
5.2
5.2
5.1
6.1
5.9
5.9
5.8
6.4
6.3
6.2
6.2
6.8
6.7
6.6
6.6
7.2
7.1
7.0
6.9
7.6
7.4
7.4
7.3
8.0
7.8
7.7
7.6
10.6
10.4
10.3
10.2
11.4
11.2
11.0
10.9
12.2
11.9
11.8
11.6
12.9
12.6
12.5
12.4
13.7
13.4
13.2
13.1
14.4
14.1
14.0
13.8

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.1
2.2
2.3
2.4
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.8
2.5
2.7
2.8
2.8
2.6
2.8
2.8
2.9
2.7
2.8
2.9
3.0
2.7
2.9
3.0
3.1
2.8
3.0
3.1
3.2
2.9
3.1
3.2
3.3
3.0
3.2
3.2
3.3
3.0
3.2
3.3
3.4
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1656
2165
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 8.73 KW
HEATING CAP. (LOW TEMP.) = 5.13 KW
COMPR. POWER (HIGH TEMP.) = 2504 WATTS
COMPR. POWER (LOW TEMP.) = 2047 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.92
COEFF. OF PERF. (LOW TEMP.) = 2.00
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN POWER = 300 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

TWJ036CA WITH TWE030CA4 AT 1868 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.0
2.1
2.1
2.2
2.1
2.2
2.3
2.3
2.3
2.4
2.4
2.5
2.4
2.5
2.5
2.6
2.5
2.6
2.7
2.7
2.6
2.8
2.8
2.9
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.1
3.2
3.3
3.4
3.4
3.5
3.6
3.7
3.5
3.7
3.8
3.9
3.6
3.8
3.9
4.0
3.8
4.0
4.1
4.2
3.9
4.1
4.2
4.3
4.0
4.2
4.3
4.4

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1656
2165
HEATING CAP.
X0.99
X1.02
COMPR. KW
X1.02
X0.97
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 10.25 KW
HEATING CAP. (LOW TEMP.) = 5.98 KW
COMPR. POWER (HIGH TEMP.) = 2776 WATTS
COMPR. POWER (LOW TEMP.) = 1982 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.88
COEFF. OF PERF. (LOW TEMP.) = 2.16
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 540 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

TWJ036CA WITH TWE040CA4-B AT 2378 CMH

TWE5-PRC001-EN-10-15-99

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.8
1.9
2.0
2.0
1.9
2.0
2.1
2.2
2.0
2.2
2.2
2.3
2.2
2.3
2.3
2.4
2.3
2.4
2.5
2.5
2.4
2.5
2.6
2.6
2.4
2.6
2.7
2.7
2.5
2.7
2.7
2.8
2.6
2.7
2.8
2.9
2.7
2.8
2.9
3.0
2.7
2.9
3.0
3.1
3.0
3.2
3.3
3.4
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.7
3.4
3.6
3.7
3.8
3.5
3.8
3.8
4.0

19

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2378 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1995
2590
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.03
X0.99
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2293 CMH
HEATING CAP. (HIGH TEMP.) = 10.37 KW
HEATING CAP. (LOW TEMP.) = 5.92 KW
COMPR. POWER (HIGH TEMP.) = 2590 WATTS
COMPR. POWER (LOW TEMP.) = 1906 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN POWER = 360 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

Performance
Data Heating

English Units

TWA030CD WITH TWE030CA4 AT 1000 CFM


O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
7.48
7.28
7.18
7.08
8.81
8.57
8.45
8.33
10.1
9.86
9.72
9.59
11.4
11.1
11.0
10.8
12.8
12.4
12.3
12.1
14.1
13.7
13.5
13.4
15.4
15.0
14.8
14.6
16.7
16.3
16.1
15.9
17.7
17.3
17.0
16.8
18.7
18.2
18.0
17.7
19.7
19.2
19.0
18.7
20.7
20.2
19.9
19.6
21.7
21.2
20.9
20.6
28.8
28.0
27.6
27.2
30.8
30.0
29.5
29.1
32.8
31.9
31.5
31.0
34.8
33.9
33.4
32.9
36.8
35.8
35.3
34.8
38.8
37.8
37.2
36.7

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
7.58
7.37
7.26
7.16
8.87
8.62
8.50
8.38
10.2
9.88
9.74
9.60
11.4
11.1
11.0
10.8
12.7
12.4
12.2
12.0
14.0
13.6
13.5
13.3
15.3
14.9
14.7
14.5
16.6
16.2
15.9
15.7
17.7
17.2
16.9
16.7
18.7
18.2
18.0
17.7
19.8
19.2
19.0
18.7
20.8
20.3
20.0
19.7
21.9
21.3
21.0
20.7
29.1
28.3
27.9
27.5
31.2
30.4
29.9
29.5
33.3
32.4
31.9
31.5
35.4
34.4
33.9
33.4
37.5
36.5
35.9
35.4
39.6
38.5
37.9
37.4

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
9.52
9.31
9.20
9.10
11.1
10.9
10.8
10.6
12.8
12.5
12.3
12.2
14.4
14.1
13.9
13.7
16.0
15.6
15.5
15.3
17.6
17.2
17.0
16.9
19.2
18.8
18.6
18.4
20.8
20.4
20.2
20.0
22.2
21.7
21.5
21.3
23.6
23.1
22.8
22.6
24.9
24.4
24.1
23.9
26.3
25.7
25.4
25.2
27.7
27.1
26.8
26.5
36.6
35.8
35.4
35.0
39.2
38.4
37.9
37.5
41.9
40.9
40.5
40.0
44.5
43.5
43.0
42.5
47.1
46.1
45.5
45.0
49.7
48.6
48.1
47.5

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
1.69
1.76
1.79
1.83
1.78
1.85
1.89
1.92
1.86
1.94
1.98
2.02
1.95
2.03
2.08
2.12
2.03
2.13
2.17
2.22
2.12
2.22
2.27
2.31
2.20
2.31
2.36
2.41
2.29
2.40
2.45
2.51
2.36
2.47
2.53
2.58
2.42
2.54
2.60
2.66
2.49
2.61
2.67
2.73
2.55
2.68
2.74
2.80
2.62
2.75
2.81
2.88
2.73
2.87
2.93
3.00
2.80
2.94
3.01
3.08
2.88
3.02
3.09
3.17
2.95
3.10
3.17
3.25
3.02
3.18
3.25
3.33
3.10
3.26
3.33
3.41

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1000 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
875
1125
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 28000 BTUH
HEATING CAP. (LOW TEMP.) = 16300 BTUH
COMPR. POWER (HIGH TEMP.) = 2212 WATTS
COMPR. POWER (LOW TEMP.) = 1745 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.86
COEFF. OF PERF. (LOW TEMP.) = 1.98
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN POWER = 440 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWA030CD WITH TWE040CA4-B AT 1100 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
1.49
1.56
1.59
1.63
1.58
1.65
1.69
1.73
1.66
1.75
1.79
1.83
1.75
1.84
1.88
1.93
1.84
1.93
1.98
2.03
1.92
2.02
2.08
2.13
2.01
2.12
2.17
2.23
2.10
2.21
2.27
2.33
2.15
2.27
2.33
2.39
2.21
2.33
2.39
2.45
2.27
2.39
2.46
2.52
2.32
2.45
2.52
2.58
2.38
2.51
2.58
2.65
2.47
2.61
2.68
2.75
2.53
2.68
2.75
2.82
2.60
2.74
2.82
2.89
2.66
2.81
2.89
2.96
2.72
2.88
2.96
3.03
2.78
2.94
3.02
3.10

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
975
1275
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 28400 BTUH
HEATING CAP. (LOW TEMP.) = 16200 BTUH
COMPR. POWER (HIGH TEMP.) = 2097 WATTS
COMPR. POWER (LOW TEMP.) = 1698 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.16
COEFF. OF PERF. (LOW TEMP.) = 2.14
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN POWER = 300 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE

TWA040CD WITH TWE040CA4-B AT 1500 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
1.88
1.97
2.02
2.06
1.96
2.06
2.11
2.16
2.04
2.14
2.20
2.25
2.12
2.23
2.29
2.35
2.20
2.32
2.38
2.44
2.28
2.41
2.47
2.54
2.36
2.49
2.56
2.63
2.44
2.58
2.65
2.72
2.52
2.67
2.75
2.82
2.61
2.76
2.84
2.92
2.69
2.86
2.94
3.02
2.78
2.95
3.03
3.11
2.87
3.04
3.12
3.21
3.09
3.28
3.37
3.46
3.20
3.39
3.49
3.59
3.30
3.51
3.61
3.71
3.41
3.62
3.73
3.83
3.52
3.74
3.85
3.96
3.63
3.85
3.97
4.08

20

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1500 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1325
1700
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1500 CFM
HEATING CAP. (HIGH TEMP.) = 35800 BTUH
HEATING CAP. (LOW TEMP.) = 20400 BTUH
COMPR. POWER (HIGH TEMP.) = 2612 WATTS
COMPR. POWER (LOW TEMP.) = 1918 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.32
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN POWER = 420 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE

TWE5-PRC001-EN-10-15-99

Performance
Data Heating

Metric Units

TWA030CD WITH TWE030CA4 AT 1698 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
2.2
2.1
2.1
2.1
2.6
2.5
2.5
2.4
3.0
2.9
2.8
2.8
3.3
3.3
3.2
3.2
3.8
3.6
3.6
3.5
4.1
4.0
4.0
3.9
4.5
4.4
4.3
4.3
4.9
4.8
4.7
4.7
5.2
5.1
5.0
4.9
5.5
5.3
5.3
5.2
5.8
5.6
5.6
5.5
6.1
5.9
5.8
5.7
6.4
6.2
6.1
6.0
8.4
8.2
8.1
8.0
9.0
8.8
8.6
8.5
9.6
9.3
9.2
9.1
10.2
9.9
9.8
9.6
10.8
10.5
10.3
10.2
11.4
11.1
10.9
10.8

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
2.2
2.2
2.1
2.1
2.6
2.5
2.5
2.5
3.0
2.9
2.9
2.8
3.3
3.3
3.2
3.2
3.7
3.6
3.6
3.5
4.1
4.0
4.0
3.9
4.5
4.4
4.3
4.2
4.9
4.7
4.7
4.6
5.2
5.0
5.0
4.9
5.5
5.3
5.3
5.2
5.8
5.6
5.6
5.5
6.1
5.9
5.9
5.8
6.4
6.2
6.2
6.1
8.5
8.3
8.2
8.1
9.1
8.9
8.8
8.6
9.8
9.5
9.3
9.2
10.4
10.1
9.9
9.8
11.0
10.7
10.5
10.4
11.6
11.3
11.1
11.0

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
2.8
2.7
2.7
2.7
3.3
3.2
3.2
3.1
3.8
3.7
3.6
3.6
4.2
4.1
4.1
4.0
4.7
4.6
4.5
4.5
5.2
5.0
5.0
5.0
5.6
5.5
5.4
5.4
6.1
6.0
5.9
5.9
6.5
6.4
6.3
6.2
6.9
6.8
6.7
6.6
7.3
7.1
7.1
7.0
7.7
7.5
7.4
7.4
8.1
7.9
7.9
7.8
10.7
10.5
10.4
10.3
11.5
11.3
11.1
11.0
12.3
12.0
11.9
11.7
13.0
12.7
12.6
12.5
13.8
13.5
13.3
13.2
14.6
14.2
14.1
13.9

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
1.7
1.8
1.8
1.8
1.8
1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.0
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.5
2.4
2.5
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.7
2.5
2.7
2.7
2.8
2.6
2.8
2.8
2.9
2.7
2.9
2.9
3.0
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.0
3.2
3.3
3.3
3.1
3.3
3.3
3.4

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1698 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1486
1910
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEATING CAP. (HIGH TEMP.) = 8.20 KW
HEATING CAP. (LOW TEMP.) = 4.78 KW
COMPR. POWER (HIGH TEMP.) = 2212 WATTS
COMPR. POWER (LOW TEMP.) = 1745 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.86
COEFF. OF PERF. (LOW TEMP.) = 1.98
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN POWER = 440 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

TWA030CD WITH TWE040CA4-B AT 1868 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
1.5
1.6
1.6
1.6
1.6
1.6
1.7
1.7
1.7
1.8
1.8
1.8
1.8
1.8
1.9
1.9
1.8
1.9
2.0
2.0
1.9
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.3
2.4
2.2
2.3
2.4
2.5
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.8
2.5
2.7
2.8
2.8
2.6
2.7
2.8
2.9
2.7
2.8
2.9
3.0
2.7
2.9
3.0
3.0
2.8
2.9
3.0
3.1

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1656
2165
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 8.32 KW
HEATING CAP. (LOW TEMP.) = 4.75 KW
COMPR. POWER (HIGH TEMP.) = 2097 WATTS
COMPR. POWER (LOW TEMP.) = 1698 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.16
COEFF. OF PERF. (LOW TEMP.) = 2.14
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN POWER = 300 WATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE

TWA040CD WITH TWE040CA4-B AT 2547 CMH

TWE5-PRC001-EN-10-15-99

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
1.9
2.0
2.0
2.1
2.0
2.1
2.1
2.2
2.0
2.1
2.2
2.3
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.5
2.4
2.5
2.6
2.6
2.4
2.6
2.7
2.7
2.5
2.7
2.8
2.8
2.6
2.8
2.8
2.9
2.7
2.9
2.9
3.0
2.8
3.0
3.0
3.1
2.9
3.0
3.1
3.2
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.7
3.4
3.6
3.7
3.8
3.5
3.7
3.8
4.0
3.6
3.8
4.0
4.1

21

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2547 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2250
2887
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2547 CMH
HEATING CAP. (HIGH TEMP.) = 10.49 KW
HEATING CAP. (LOW TEMP.) = 5.98 KW
COMPR. POWER (HIGH TEMP.) = 2612 WATTS
COMPR. POWER (LOW TEMP.) = 1918 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.32
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN POWER = 420 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE

Performance
Data Heating

English Units

TWA040CD WITH TWE050CA5-C AT 1500 CFM


O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
9.68
9.46
9.36
9.25
11.3
11.1
11.0
10.8
13.0
12.7
12.6
12.4
14.6
14.3
14.2
14.0
16.3
15.9
15.8
15.6
17.9
17.6
17.4
17.2
19.6
19.2
19.0
18.8
21.2
20.8
20.6
20.4
22.6
22.1
21.8
21.6
23.9
23.4
23.1
22.8
25.2
24.6
24.4
24.1
26.5
25.9
25.6
25.3
27.8
27.2
26.9
26.6
37.2
36.4
36.0
35.6
39.9
39.0
38.6
38.1
42.5
41.6
41.1
40.7
45.2
44.2
43.7
43.2
47.9
46.8
46.3
45.7
50.5
49.4
48.8
48.3

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
12.5
12.2
12.1
12.0
14.9
14.6
14.4
14.2
17.3
16.9
16.7
16.5
19.7
19.2
19.0
18.8
22.0
21.6
21.3
21.1
24.4
23.9
23.7
23.4
26.8
26.3
26.0
25.7
29.2
28.6
28.3
28.0
30.2
29.5
29.2
28.9
31.1
30.5
30.2
29.8
32.1
31.4
31.1
30.8
33.1
32.4
32.0
31.7
34.0
33.3
33.0
32.6
48.0
47.0
46.5
46.0
51.2
50.1
49.5
49.0
54.3
53.1
52.5
52.0
57.5
56.2
55.6
54.9
60.6
59.3
58.6
57.9
63.7
62.3
61.6
60.9

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
14.0
13.8
13.7
13.5
16.9
16.6
16.4
16.3
19.7
19.4
19.2
19.1
22.6
22.2
22.0
21.8
25.4
25.0
24.8
24.6
28.3
27.8
27.6
27.3
31.1
30.6
30.3
30.1
34.0
33.4
33.1
32.8
35.7
35.1
34.8
34.5
37.4
36.8
36.5
36.2
39.1
38.5
38.2
37.8
40.9
40.2
39.8
39.5
42.6
41.9
41.5
41.2
53.9
53.0
52.5
52.1
57.2
56.3
55.8
55.3
60.6
59.5
59.0
58.5
63.9
62.8
62.3
61.7
67.2
66.1
65.5
64.9
70.5
69.3
68.7
68.1

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
1.94
2.04
2.08
2.13
2.02
2.13
2.18
2.23
2.10
2.21
2.27
2.32
2.19
2.30
2.36
2.42
2.27
2.39
2.45
2.51
2.35
2.48
2.54
2.61
2.43
2.57
2.63
2.70
2.51
2.65
2.73
2.80
2.59
2.74
2.82
2.89
2.67
2.83
2.91
2.99
2.76
2.92
3.00
3.08
2.84
3.01
3.09
3.17
2.92
3.09
3.18
3.27
3.13
3.32
3.41
3.51
3.23
3.43
3.53
3.63
3.34
3.54
3.64
3.75
3.44
3.65
3.76
3.86
3.54
3.76
3.87
3.98
3.65
3.88
3.99
4.10

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1500 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1325
1700
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1500 CFM
HEATING CAP. (HIGH TEMP.) = 36400 BTUH
HEATING CAP. (LOW TEMP.) = 20800 BTUH
COMPR. POWER (HIGH TEMP.) = 2566 WATTS
COMPR. POWER (LOW TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN POWER = 510 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE

TWA050CD WITH TWE050CA5-C AT 1800 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
2.50
2.62
2.67
2.73
2.60
2.72
2.78
2.84
2.69
2.82
2.88
2.94
2.78
2.92
2.98
3.05
2.87
3.02
3.09
3.16
2.97
3.12
3.19
3.27
3.06
3.22
3.30
3.38
3.15
3.32
3.40
3.48
3.25
3.42
3.51
3.59
3.34
3.52
3.61
3.70
3.44
3.63
3.72
3.81
3.54
3.73
3.83
3.92
3.63
3.83
3.93
4.03
4.00
4.23
4.34
4.45
4.14
4.38
4.50
4.61
4.28
4.53
4.65
4.78
4.43
4.68
4.81
4.94
4.57
4.83
4.97
5.10
4.71
4.98
5.12
5.26

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1575
2025
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 47000 BTUH
HEATING CAP. (LOW TEMP.) = 28600 BTUH
COMPR. POWER (HIGH TEMP.) = 3222 WATTS
COMPR. POWER (LOW TEMP.) = 2313 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.50
OUTDOOR FAN POWER = 255 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE

TWA060CD WITH TWE050CA5-C AT 1800 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
3.24
3.37
3.43
3.50
3.36
3.50
3.57
3.64
3.49
3.64
3.71
3.79
3.62
3.77
3.85
3.93
3.74
3.91
3.99
4.07
3.87
4.04
4.13
4.22
3.99
4.18
4.27
4.36
4.12
4.31
4.41
4.50
4.52
4.74
4.85
4.95
4.93
5.17
5.28
5.40
5.33
5.59
5.72
5.85
5.74
6.02
6.16
6.30
6.14
6.45
6.60
6.76
5.33
5.59
5.72
5.85
5.53
5.80
5.94
6.08
5.73
6.02
6.16
6.30
5.94
6.23
6.38
6.53
6.14
6.44
6.60
6.75
6.34
6.66
6.82
6.98

22

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1575
2025
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 53000 BTUH
HEATING CAP. (LOW TEMP.) = 33400 BTUH
COMPR. POWER (HIGH TEMP.) = 4446 WATTS
COMPR. POWER (LOW TEMP.) = 3166 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.76
COEFF. OF PERF. (LOW TEMP.) = 2.26
OUTDOOR FAN POWER = 395 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE

TWE5-PRC001-EN-10-15-99

Performance
Data Heating

Metric Units

TWA040CD WITH TWE050CA5-C AT 2547 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
2.8
2.8
2.7
2.7
3.3
3.3
3.2
3.2
3.8
3.7
3.7
3.6
4.3
4.2
4.2
4.1
4.8
4.7
4.6
4.6
5.2
5.2
5.1
5.0
5.7
5.6
5.6
5.5
6.2
6.1
6.0
6.0
6.6
6.5
6.4
6.3
7.0
6.9
6.8
6.7
7.4
7.2
7.1
7.1
7.8
7.6
7.5
7.4
8.1
8.0
7.9
7.8
10.9
10.7
10.5
10.4
11.7
11.4
11.3
11.2
12.5
12.2
12.0
11.9
13.2
13.0
12.8
12.7
14.0
13.7
13.6
13.4
14.8
14.5
14.3
14.2

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
3.7
3.6
3.5
3.5
4.4
4.3
4.2
4.2
5.1
5.0
4.9
4.8
5.8
5.6
5.6
5.5
6.4
6.3
6.2
6.2
7.1
7.0
6.9
6.9
7.9
7.7
7.6
7.5
8.6
8.4
8.3
8.2
8.8
8.6
8.6
8.5
9.1
8.9
8.8
8.7
9.4
9.2
9.1
9.0
9.7
9.5
9.4
9.3
10.0
9.8
9.7
9.6
14.1
13.8
13.6
13.5
15.0
14.7
14.5
14.4
15.9
15.6
15.4
15.2
16.8
16.5
16.3
16.1
17.8
17.4
17.2
17.0
18.7
18.3
18.0
17.8

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
4.1
4.0
4.0
4.0
5.0
4.9
4.8
4.8
5.8
5.7
5.6
5.6
6.6
6.5
6.4
6.4
7.4
7.3
7.3
7.2
8.3
8.1
8.1
8.0
9.1
9.0
8.9
8.8
10.0
9.8
9.7
9.6
10.5
10.3
10.2
10.1
11.0
10.8
10.7
10.6
11.5
11.3
11.2
11.1
12.0
11.8
11.7
11.6
12.5
12.3
12.2
12.1
15.8
15.5
15.4
15.3
16.8
16.5
16.3
16.2
17.8
17.4
17.3
17.1
18.7
18.4
18.3
18.1
19.7
19.4
19.2
19.0
20.7
20.3
20.1
20.0

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
1.9
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.6
2.6
2.7
2.5
2.7
2.7
2.8
2.6
2.7
2.8
2.9
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.1
2.8
3.0
3.1
3.2
2.9
3.1
3.2
3.3
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.8
3.4
3.7
3.8
3.9
3.5
3.8
3.9
4.0
3.7
3.9
4.0
4.1

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2547 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2250
2887
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2547 CMH
HEATING CAP. (HIGH TEMP.) = 10.67 KW
HEATING CAP. (LOW TEMP.) = 6.09 KW
COMPR. POWER (HIGH TEMP.) = 2566 WATTS
COMPR. POWER (LOW TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN POWER = 510 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE

TWA050CD WITH TWE050CA5-C AT 3057 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
2.5
2.6
2.7
2.7
2.6
2.7
2.8
2.8
2.7
2.8
2.9
2.9
2.8
2.9
3.0
3.0
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.1
3.2
3.3
3.4
3.2
3.3
3.4
3.5
3.3
3.4
3.5
3.6
3.3
3.5
3.6
3.7
3.4
3.6
3.7
3.8
3.5
3.7
3.8
3.9
3.6
3.8
3.9
4.0
4.0
4.2
4.3
4.4
4.1
4.4
4.5
4.6
4.3
4.5
4.7
4.8
4.4
4.7
4.8
4.9
4.6
4.8
5.0
5.1
4.7
5.0
5.1
5.3

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 3057 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2675
3439
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 3057 CMH
HEATING CAP. (HIGH TEMP.) = 13.77 KW
HEATING CAP. (LOW TEMP.) = 8.38 KW
COMPR. POWER (HIGH TEMP.) = 3222 WATTS
COMPR. POWER (LOW TEMP.) = 2313 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.50
OUTDOOR FAN POWER = 255 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE

TWA060CD WITH TWE050CA5-C AT 3057 CMH

TWE5-PRC001-EN-10-15-99

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
3.2
3.4
3.4
3.5
3.4
3.5
3.6
3.6
3.5
3.6
3.7
3.8
3.6
3.8
3.8
3.9
3.7
3.9
4.0
4.1
3.9
4.0
4.1
4.2
4.0
4.2
4.3
4.4
4.1
4.3
4.4
4.5
4.5
4.7
4.8
4.9
4.9
5.2
5.3
5.4
5.3
5.6
5.7
5.8
5.7
6.0
6.2
6.3
6.1
6.4
6.6
6.8
5.3
5.6
5.7
5.8
5.5
5.8
5.9
6.1
5.7
6.0
6.2
6.3
5.9
6.2
6.4
6.5
6.1
6.4
6.6
6.8
6.3
6.7
6.8
7.0

23

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 3057 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2675
3439
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 3057 CMH
HEATING CAP. (HIGH TEMP.) = 15.53 KW
HEATING CAP. (LOW TEMP.) = 9.79 KW
COMPR. POWER (HIGH TEMP.) = 4446 WATTS
COMPR. POWER (LOW TEMP.) = 3166 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.76
COEFF. OF PERF. (LOW TEMP.) = 2.26
OUTDOOR FAN POWER = 395 WATTS
INDOOR FAN POWER = 750 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE

Performance
Data

Evaporator Fan Performance


Blower Performance TWE030CA40B Wet Coil

CFM
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200

CMH
1018.8
1103.7
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6

0.89
0.81
0.72
0.63
0.53
0.42
0.31
0.20
0.08

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.72 (179.4)
0.71 (176.9)
0.62 (154.4)
0.61 (152.0)
0.86 (214.2)
0.51 (127.0)
0.84 (209.2)
0.50 (124.6)
0.75 (186.8)
0.40
(99.6)
0.72 (179.4)
0.39
(97.1)
(221.7)
0.65 (161.9)
0.29
(72.2)
0.87 (216.7)
0.62 (154.4)
0.28
(69.7)
(201.8)
0.54 (134.5)
0.18
(44.8)
0.79 (196.8)
0.51 (127.0)
0.17
(42.3)
(179.4)
0.43 (107.1)
0.06
(14.9)
0.69 (171.9)
0.40
(99.6)
0.08
(19.9)
(156.9)
0.32
(79.7)
0.61 (152.0)
0.30
(74.7)
(132.0)
0.21
(52.3)
0.51 (127.0)
0.17
(42.3)
(104.6)
0.10
(24.9)
0.40
(99.6)
0.02
(5.0)
(77.2)
0.31
(77.2)
(49.8)
0.22
(54.8)
(19.9)
0.10
(24.9)

NOTES:
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance TWE040CA40C Wet Coil

CFM
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500

CMH
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0

0.61
0.57
0.53
0.49
0.45
0.40
0.36
0.31
0.26
0.21
0.17
0.11
0.06
0.01
0.00

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.58 (144.5)
0.61 (152.0)
0.55 (137.0)
(152.0)
0.58 (144.5)
0.52 (129.5)
0.58 (144.5)
(142.0)
0.54 (134.5)
0.48 (119.6)
0.52 (129.5)
(132.0)
0.51 (127.0)
0.44 (109.6)
0.49 (122.1)
(122.1)
0.47 (117.1)
0.40
(99.6)
0.57 (142.0)
0.45 (112.1)
(112.1)
0.43 (107.1)
0.34
(84.7)
0.53 (132.0)
0.50 (124.6)
0.40
(99.6)
(99.6)
0.38
(94.7)
0.28
(69.7)
0.48 (119.6)
0.45 (112.1)
0.35
(87.2)
(89.7)
0.34
(84.7)
0.22
(54.8)
0.43 (107.1)
0.40
(99.6)
0.30
(74.7)
(77.2)
0.29
(72.2)
0.15
(37.4)
0.39
(97.1)
0.37
(92.2)
0.22
(54.8)
(64.8)
0.24
(59.8)
0.08
(19.9)
0.35
(87.2)
0.32
(79.7)
0.17
(42.3)
(52.3)
0.18
(44.8)
0.00
(0.0)
0.31
(77.2)
0.28
(69.7)
0.10
(24.9)
(42.3)
0.13
(32.4)
0.26
(64.8)
0.22
(54.8)
0.01
(2.5)
(27.4)
0.07
(17.4)
0.21
(52.3)
0.18
(44.8)
(14.9)
0.01
(2.5)
0.15
(37.4)
0.12
(29.9)
(2.5)
0.11
(27.4)
0.08
(19.9)
0.05
(12.5)
0.02
(5.0)

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

24

TWE5-PRC001-EN-10-15-99

Performance
Data

Evaporator Fan Performance


Blower Performance TWE050CA50D Wet Coil

CFM
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950

CMH
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0
2631.9
2716.8
2801.7
2886.6
2971.5
3056.4
3141.3
3226.2
3311.1

Hl

0.59
0.56
0.52
0.48
0.44
0.40
0.35
0.31
0.26
0.21
0.16
0.11
0.05

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
MED
LO
Hl
MED

(147.0)
(139.5)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(77.2)
(64.8)
(52.3)
(39.9)
(27.4)
(12.5)

0.61
0.57
0.53
0.49
0.45
0.40
0.35
0.30
0.25
0.20
0.14
0.08
0.02

(152.0)
(142.0)
(132.0)
(122.1)
(112.1)
(99.6)
(87.2)
(74.7)
(62.3)
(49.8)
(34.9)
(19.9)
(5.0)

0.63
0.61
0.58
0.54
0.50
0.45
0.39
0.33
0.26
0.18
0.10
0.01

(156.9)
(152.0)
(144.5)
(134.5)
(124.6)
(112.1)
(97.1)
(82.2)
(64.8)
(44.8)
(24.9)
(2.5)

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

TWE5-PRC001-EN-10-15-99

25

0.62
0.59
0.56
0.52
0.49
0.47
0.45
0.41
0.36
0.30
0.24
0.17
0.10
0.02

(154.4)
(147.0)
(139.5)
(129.5)
(122.1)
(117.1)
(112.1)
(102.1)
(89.7)
(74.7)
(59.8)
(42.3)
(24.9)
(5.0)

0.64
0.61
0.58
0.55
0.52
0.48
0.44
0.40
0.35
0.28
0.20
0.13
0.07
0.01

(159.4)
(152.0)
(144.5)
(137.0)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(69.7)
(49.8)
(32.4)
(17.4)
(2.5)

0.62
0.60
0.57
0.53
0.49
0.44
0.38
0.32
0.25
0.18
0.11
0.00

LO

(154.4)
(149.5)
(142.0)
(132.0)
(122.1)
(109.6)
(94.7)
(79.7)
(62.3)
(44.8)
(27.4)
(0.0)

Performance
Data

Air Pressure Drop (Inches) - Electric Heaters


Pressure Drop For Electric Heaters In Air Handler Models

1
AIRFLOW
CFM
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

AIRFLOW
CMH
1018.8
1188.6
1358.4
1528.2
1698.0
1867.8
2037.6
2207.4
2377.2
2547.0
2716.8
2886.6
3056.4
3226.2
3396.0

0.01
0.01
0.02
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14

(2.5)
(2.5)
(5.0)
(7.5)
(10.0)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(24.9)
(27.4)
(32.4)
(34.9)

0.02
0.02
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.15
0.17

NUMBER OF RACKS
3
AIR PRESSURE DROP
IN. W.G. (PASCALS)
(5.0)
0.02
(5.0)
(5.0)
0.02
(5.0)
(7.5)
0.03
(7.5)
(7.5)
0.04
(10.0)
(10.0)
0.05
(12.5)
(12.5)
0.06
(14.9)
(14.9)
0.07
(17.4)
(17.4)
0.08
(19.9)
(19.9)
0.10
(24.9)
(22.4)
0.11
(27.4)
(24.9)
0.12
(29.9)
(27.4)
0.14
(34.9)
(32.4)
0.16
(39.9)
(37.4)
0.18
(44.8)
(42.3)
0.20
(49.8)

0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23

(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)

0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23
0.26

(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)
(64.8)

NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.

HEATER RACKS
HEATER
NO. OF
MODEL NO.
RACKS
BAY96X1405
1
BAY96X1406
2
BAY96X1408
2
BAY96X1410
2
BAY96X1411
3
BAY96X1415
3
BAY96X1419
4
BAY96X1421
4
BAY96X1426
5
BAY96X3411
3
BAY96X3415
3

26

TWE5-PRC001-EN-10-15-99

Supplementary
Heaters

THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.
TWE030C-Heater Model Number BAY96X
Unit
Position
Vertical
Upflow
Vertical
Downflow
Horizontal
Left
Horizontal
Right

Application
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump

1405
4.0 KW
L
L
L
L
L
L
L
L

1406
4.8 KW
L
L
L
L
L
L
L
L

1408,F
6.4 KW
L
L
L
L
L
L
L
L

1410,F
8.0 KW
L
L
L
L
L
L
L
L

1410A
8.8 KW
L
L
L
L
L
L
L
L

1411
8.8 KW
L
L
L
L
L
L
L
L

1411A
8.8 KW
L
L
L
L
L
L
L
L

1415
1419
1421
12.8 KW 16.0 KW 17.6 KW
L
L
L
L
M
M
L
L
L
L
H
H
L
L
L
L
M
M
L
L
L
L
H
H

3411
8.8 KW
L
L
L
L
L
L
L
L

3415
12.8 KW
L
L
L
H
L
L
L
L

3411
8.8 KW
L
M
L
L
L
L
L
L

3415
12.8 KW
L
M
L
L
L
L
L
L

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.

TWE040C-Heater Model Number BAY96X


Unit
Position
Vertical
Upflow
Vertical
Downflow
Horizontal
Left
Horizontal
Right

Application
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump

1405
4.0 KW
L
L
L
L
L
L
L
L

1406
4.8 KW
L
L
L
L
L
L
L
L

1408,F
6.4 KW
L
L
L
L
L
L
L
L

1410,F
8.0 KW
L
L
L
L
L
L
L
L

1410A
8.8 KW
L
L
L
L
L
L
L
L

1411
8.8 KW
L
M
L
L
L
L
L
L

1411A
8.8 KW
L
M
L
L
L
L
L
L

1415
1419
1421
12.8 KW 16.0 KW 17.6 KW
L
L
L
H
H
H
L
L
L
H
H
H
L
L
L
H
H
H
L
L
L
H
H
H

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.

TWE050C-Heater Model Number BAY96X


Unit
Position
Vertical
Upflow
Vertical
Downflow
Horizontal
Left
Horizontal
Right

Application
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
Heat Pump

1405
4.0 KW

1406
4.8 KW

1408,F
6.4 KW
L
L
L
L
L
L
L
L

1410,F
8.0 KW
L
L
L
L
L
L
L
L

1410A
8.8 KW
L
L
L
L
L
L
L
L

1415
12.8 KW
L
L
L
L
L
L
L
L

1419
16.0 KW
L
M
L
H
L
H
L
M

1421
17.6 KW
L
M
L
H
L
H
L
M

(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A and 1414 not approved for this model.

TWE5-PRC001-EN-10-15-99

27

1426
21.6 KW
L
H
L
H
L
H
L
H

3415
12.8 KW
L
L
L
L
L
L
L
L

Electrical
Data

System Wiring Diagram


Legend

Symbols

NOTES:
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED
CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.

28

TWE5-PRC001-EN-10-15-99

Dimensions

TWE030-050C Outline Drawing


ALL DIMENSIONS ARE IN INCHES (MM)

SIDES
FRONT
BACK
INLET DUCT
OUTLET DUCT

MINIMUM UNIT CLEARANCE SALE


TO COMBUSTIBLE
SERVICE CLEARANCE
MATERIAL (REQUIRED)
(RECOMMENDED)
0
(0)
2
(50.8)
0
(0)
21
(533.4)
0
(0)
0
(0)
0
(0)
1
(25.4)
1
(25.4)

TWE5-PRC001-EN-10-15-99

MODEL NO.
TWE030CA4
TWE040CA4
TWE050CA5

29

A
B
43.00
15.57
(1092.2) (395.5)
51.75
24.32
(1134.5) (617.7)
57.90
30.47
(1470.7) (773.9)

C
21.50
(761.1)
23.50
(596.9)
23.50
(596.9)

D
E
F
19.50
20.28
21.63
(495.3) (515.1) (549.4)
21.50
22.28
23.63
(761.1) (565.9) (600.2)
21.50
22.28
23.63
(761.1) (565.9) (600.2)

FLOW
CONTROL

FCCV
FCCV
TXV

Dimensions

TWJ020-036CA and TWA030-060CA Outline Drawing


All dimensions are in inches (mm)

SERVICE PANEL

ELECTRICAL AND
REFRIGERANT COMPONENTS
CLEARANCES PER PREVAILING

67/8
93/4 (175)
(248)

TOP DISCHARGE AREA SHOULD BE


UNRESTRICTED FOR AT LEAST FIVE (5)
FEET ABOVE UNIT. UNIT SHOULD BE
PLACED SO ROOF RUN-OFF WATER
DOES NOT POUR DIRECTLY ON UNIT,
AND SHOULD BE AT LEAST 12" (305)
FROM WALL AND ALL SURROUNDING
SHRUBBERY ON TWO SIDES. OTHER
TWO SIDES UNRESTRICTED.

11/4
(32)

11/8 (28.6) DIA. K.O. WITH


7/8 (22.2) DIA. HOLE

ELECTRICAL POWER
7/8 (22.2) DIA. HOLE
LOW VOLTAGE

81/4
(210)

43/4
(121)
GAS LINE SERVICE VALVE, "D" O.D.
FEMALE BRAZED CONNECTION WITH
1/4" SAE FLARE PRESSURE TAP
FITTING.

2 (51)

LIQUID LINE SERVICE VALVE, "E" O.D.


FEMALE BRAZED CONNECTION WITH
1/4" SAE FLARE PRESSURE TAP
FITTING.

FIG. 1

9
(229)

GAS LINE BALL SERVICE VALVE, BALL


1/4 TURN "D" O.D. FEMALE BRAZED
CONNECTION WITH 1/4" SAE FLARE
PRESSURE TAP FITTING.

5
(127)
15/8 (41)
23/8 (60)

LIQUID LINE SERVICE VALVE, "E" O.D.


FEMALE BRAZED CONNECTION WITH
1/4" SAE FLARE PRESSURE TAP
FITTING.

FIG. 2

MODEL
TWJ020CA00A

Figure
1

TWJ024CA00A

TWJ030CA00A

TWJ036CA00A

TWA030CD00A

TWA040CD00A

TWA050CD00A

TWA060CD00A

A
243/8
(619)
323/4
(832)
323/4
(832)
37
(940)
323/4
(832)
323/4
(832)
37
(940)
443/4
(1137)

B
281/4
(718)
281/4
(718)
281/4
(718)
327/8
(835)
281/4
(718)
327/8
(835)
387/8
(987)
387/8
(987)

C
245/8
(625)
245/8
(625)
245/8
(625)
283/4
(730)
245/8
(625)
283/4
(730)
343/4
(883)
343/4
(883)

D
/4
(19)
3
/4
(19)
7
/8
(22.2)
7
/8
(22.2)
7
/8
(22.2)
11/8
(28.6)
11/8
(28.6)
11/8
(28.6)
3

E
/16
(8)
5
/16
(8)
3
/8
(9.53)
3
/8
(9.53)
3
/8
(9.53)
3
/8
(9.53)
3
/8
(9.53)
3
/8
(9.53)
5

From Dwg. 21D147562 Rev. 6


30

TWE5-PRC001-EN-10-15-99

Convertibility

TWE030 Through 050 Convertibility


Six (6) Way Convertibility

One Unit - 4 Applications

TWE5-PRC001-EN-10-15-99

Easy Conversion to Opposite Side Access

31

Mechanical
Specification Options

General
Blower coil units shall be completely
factory assembled including coil, condensate drain pan, fan, motor, filters and
controls in an insulated casing that can
be applied in horizontal or vertical
configuration.
This new line of TWE-C air handlers
provides exclusive compact size combined with simple four-way convertibility
in three sizes. The unit ships in the right
hand horizontal configuration and
converts to vertical upflow just by
standing the unit on end. No tools
required. Simple coil rotation provides
downflow and horizontal left applications.
The four-way convertibility provides you
inventory benefits and service/installation
flexibility. The simple conversion provides
opposite side access for installation and
service.
Casing
Units shall have rugged sheet metal and
steel frame construction and shall be
painted with an enamel finish. Casing
shall be insulated and knockouts shall be
provided for electrical power and control
wiring.

The Trane Company


Trane International Unitary Systems
1789 Chausse de Wavre
1160 Brussels
Belgium
www.trane.com

An American Standard Company

Refrigerant Circuits
The TWE units shall have a single
refrigerant circuit. TWE03-040C refrigerant circuit shall be controlled by a flow
control check valve (FCCV). The
TWE050C refrigerant circuit shall be
controlled by a factory-installed thermal
expansion valve.
Coil
Aluminum fin surface shall be mechanically bonded to 3/8-inch OD copper
tubing. Coils shall be factory pressure
and leak tested.
Fan
Forward curved, dynamically and
statically balanced with three-speed
direct drive shall be standard, fan motor
bearing shall be permanently lubricated.
Controls
Fan contactor, and plug-in module for
accessory electric heat control shall be
included. TWE models shall also include
check valves.
Filters
Filters shall be included as standard.
Accessories
Electric Heaters Shall be available in
a wide range of capacities and voltages
with various staging options and plug in
control wiring. Heaters shall fit inside
internal compartment.

File Number

TWE5-PRC001-EN-10-15-99

Supersedes

TWE5-PRC000-EN

Stocking Location

P.I.-L

Since The Trane Company has a policy of continuous product improvement, it reserves the right to change